Room Dimensions
Width (ft) = 52
Length (ft) = 120
Heigth (ft) = 10
Pen Information Duct Design
Number of pen rows = 4 Pen Ventilation Rate (CFM) =
Number of pens per row = 30 Number of Ducts =
Total Number of Pens = 120 Number Duct Fans =
Pen Length (ft) = 8 Fan Capacity (CFM/Fan) =
Alley Width (ft) = 10 Minimum Duct Area (sq ft) =
Number of Rows of Holes ( 1 or 2) = 2 Minimum Duct Diameter (Inches) =
Ventilation Rate per Pen (15 CFM/pen Minimum) = 15 Number Holes/Tube =
Desired Hole Discharge Velocity (600-1,200 ft/min) = 700 Individual Hole Area (sq ft) =
Hole Diameter (Inches) =
Hole Rows Orientation
Height of Duct Bottom (ft) = 9.2
Horizontal Distance to Pen Center (ft) = 9
Length of Air Trajectory (ft) = 12.9
Angle of Each Air Trajectory(degrees) = 44.2
Hole Angle (degrees) = 88.5
*
Select Hole Discharge Velocity (Cell D23) so Throw Distance is
less than or equal to Length of Air Trajectory (Cell D28)
sheet will size mechanical ventilation components for 4x8 floor level pen barns
concept of a positive pressure ventilation tube to introduce fresh air into the pens using
n tube/duct. The barn is presumed to be adequately ventilated with a natural ventilation system.
ria based on MWPS-7 and "Practical Considerations for Ventilating Calf Barns in Winter" by
dlund, UW-Madison, School of Veterinary Medicine.
Trajectory of
Air Stream
Calf Pen
Pen
Length 8 ft