Professional Documents
Culture Documents
Tank Foundations
GP 04-08-01
Scope
[I] This Global Practice (GP) covers the design and construction of foundations for atmospheric storage
tanks, refrigerated storage tanks, and carbon steel tanks in sulfuric acid service.
[I] An asterisk (*) indicates that additional information is required. If a job is contracted, this information
is furnished in the Job Specification.
Table of Contents
Table of Figures
1. Required References
1) [I] This Section lists the Practice that is referenced and assumed to be a part of this document. Unless
otherwise specified herein, use the latest edition.
2) * [I] Local codes and standards may be substituted for the ones referenced herein provided the
following provisions are met:
a) The resultant design meets the safety and serviceability criteria attained through this practice.
b) Substitution is accepted by the authorities where the facility is to be located and by the Owner's
Engineer.
2. Additional References
1) * [I] The following Practices and Standards shall be used with this Practice as applicable.
2) * [I] Local codes and standards may be substituted for the ones referenced herein provided the
following provisions are met:
a) The resultant design meets the safety and serviceability criteria attained through this GP.
b) Substitution is accepted by the authorities where the facility is to be located and by the Owner's
Engineer.
3. General
1) [R] Earth subgrade preparation, placement of fill, and compaction requirements shall be per GP 04-
09-01.
2) [R] Where concrete ringwalls are provided under the shell, they shall be designed in accordance with
API STD 650, Appendix B, and ACI 318/318R, taking into consideration predicted settlements.
b) The membrane shall be High Density Polyethylene sheet, 80 mil thickness, unless the stored
product necessitates the use of another material.
c) The membrane shall be furnished with factory sealed seams if practical. If field seams are used,
these shall be made using the extrusion welding or hot wedge methods. Seams shall be 100
percent tested using the vacuum box method and any leaks shall be repaired.
d) Where permitted, a concrete pad may be used under small tanks instead of a synthetic membrane
for leak detection subject to the following:
i) A continuous slab may be used for closely spaced tanks.
ii) The concrete pad or slab shall be structurally designed to prevent concrete cracking.
iii) The concrete pad or slab shall have no joints under the tank. If a joint cannot be avoided,
then a waterstop shall be provided to permanently seal the joint.
iv) The pad or slab shall be provided with groves or slots in the top of the slab/pad or
equivalent means to allow a leak to flow quickly out from under the tank and be detected.
A sump shall not be placed under the tank.
11) [R] Permanent zinc reference electrode: All tanks shall be provided with a permanent zinc reference
electrode installed per Figure 4. The zinc anode shall be per ASTM B 418, Type II composition.
Where an impermeable membrane is used per Item (10) above, the electrode shall be installed above
the membrane.
RINGWALL
SUBGRADE
NOTES:
(1) For tanks not requiring ringwalls, all other details remain the same, except general fill replaces the ringwall material and
starts at pit grade level.
(2) For tanks less than 30 ft diameter and 30 ft high, the berm width shall be decreased to 2 ft.
(3) The crushed stone or gravel (2 in. Legend) should extend outward past the annular ring through water test.
The necessary amount may be removed to apply the impermeable sand-asphalt mix after the water test.
(4) 1/2 in. (13 mm) thick (min.) asphalt-impregnated board required when oiled sand or permeable asphalt subbase is used.
LEGEND:
1 With cathodic protection, one of the following subbases should be specified (listed in order of preference). The
subbase thickness requirement is dependent on the anode configuration.
• Dry Clean Sand: 4 in. minimum thickness below the tank bottom if used in conjunction with a galvanic (sacrificial) anode
cathodic protection system. 8 in. minimum thickness if used in conjunction with an impressed current cathodic
protection system.
• Fine Crushed Stone (gravel/limestone): Size number 9 (ASTM D448 Table 1) crushed stone shall be used. The
thickness requirements are similar to those required of the dry clean sand.
Without cathodic protection, one of the following subbases should be specified (listed in order of preference).
• Oiled Sand: The sand shall entirely pass the 3/8 in. (9.5 mm) sieve, almost entirely pass the No. 4
(4.75 mm) sieve, and have no more than 10% passing the No. 200 (0.074 mm) sieve. The oil used shall be a low
corrosivity oil such as 18 gravity railroad fuel oil or 11.5 minimum gravity Bunker C. A satisfactory mix of oil and
sand shall maintain its shape when pressed into a vertical plane. In general, 5 to 10% oil by weight should suffice.
The oiled sand shall be compacted by rolling or tamping. Low viscosity asphalt may be substituted for the oil;
however, care should be taken to ensure that the resulting mix is suitable for cold placement. Oil may also be
spray-applied to the sand, provided oil penetration through the full depth of the sand is demonstrated with a test
application. The minimum thickness shall be 2 inches.
• Permeable Asphalt: Aggregate shall have gradation No. 8 or 89 (ASTM D448) or equivalent, asphalt cement type AC-20
or equivalent at 2 to 4% by weight. Compact using light, walk-behind equipment if the pad is equipped with a leak
detection membrane. AASHTO T166 should be used to assess the permeability of the asphalt.
The minimum air void percentage should be 8% for a 9.5 mm mix, 6% for a 12.5 mm mix, and 5% for a 19 mm mix.
The minimum thickness shall be 2 inches.
2 4 in. of well graded crushed stone or crushed gravel, size number 7 (ASTM D448 Table 1). Size numbers 6, 56, or
67 are also acceptable, provided that tank pad elevation differences can be met.
3 1 in. minimum thickness impermeable sand-asphalt mix. Terminate at the outer edge of the annular plate.
4 Cohesive or Cohesionless compacted fill.
5 12 in. minimum after settlement.
6 Leak Detection Membrane in accordance with Section 4, Item (10).
3 1 5 1
3 in. 4
1.5 2 ft MIN. 1.5 6
GENERAL FILL 8 in. MIN.
GRADE
AS REQUIRED (MIN. = 0) 7
RINGWALL SUBGRADE
NOTES:
(1) For tanks not requiring ringwalls, all other details remain the same, except general fill replaces the ringwall material and
starts at pit grade level.
(2) For tanks less than 30 ft diameter and 30 ft high, the berm width shall be decreased to 2 ft.
(3) Specified bottom plate slope (1:48) does not apply for tanks less than 20 ft in diameter.
(4) The crushed stone or gravel (2 in Legend of Figure 1) should extend outward past the annular ring through water test.
The necessary amount may be removed to apply the impermeable sand-asphalt mix after the water test.
(5) 1/2 in. (13 mm) thick (min.) asphalt-impregnated board required when oiled sand or permeable asphalt subbase is used.
LEGEND:
1 For Legend Notes 1 through 5, see Figure 1 - Legend
6 8 in. minimum, increased by predicted differential settlement between the center and the shell of the tank. Increase
this dimension as required when a leak detection system is specified, to ensure that the drain pipe slopes for drainage.
7 Leak Detection Membrane in accordance with Section 4, Item (10).
5 4
3 1
REINFORCED 1
CONCRETE 1.5
RINGWALL
NATURAL SOIL
OR GENERAL FILL
LEGEND:
1 and 2 Materials and bottom slopes per Figures 1 and 2 as applicable.
3 Leak detection membrane. Attached to ringw all. Cushion top and bottom w ith non-w oven
geotextile w here in contact w ith materials that could cause punctures.
4 Compacted crushed stone 1 in. (25 mm) maximum size, gravel, or clean sand backfill.
5 3 in. (75 mm) chamfer at 45 degrees. Chamfer may be reduced if there is satisfactory site
specific experience w ith smaller chamfers.
5 2
3
6 in. MIN. COMPACTED
(150 mm) 1
6 in. MIN. 4
(150 mm) SAND FILL
GRADE 7
COMPACTED
CRUSHED STONE
1 in. (25 mm)
MAXIMUM SIZE
OR GRAVEL
BACKFILL 1
1.5
BOTTOM FACE
BELOW FROSTLINE NATURAL SOIL
OR GENERAL FILL
REINFORCED CONCRETE RINGWALL
LEGEND:
1 Clean, dry, sand layer, 1 in. (25 mm).
2 Insulation, foam glass block.
3 Vapor Barrier, polyethylene sheet 0.015 in. (.375 mm) thick, factory sealed joints or 6 in. (150 mm) min overlap.
4 Galvanized carbon steel conduit for Electric Heating Elements and Sensors, with sleeved opening through
concrete walls.
5 Hardwood block: kiln dried, < 10% moisture, coated all sides with elastomeric vapor barrier. Alternatively,
a load bearing insulating concrete block, similarly coated is acceptable.
6 Metal jacket insulation covering shall be extended to lap over the top of the Ringwall, with joints lapped and
sealed against entrance of water.
7 Layer of non-woven geotextile.
4 2
3
PILE CAP 1
GRADE
LEGEND:
1 Clean, dry, sand layer, 1 in. (25 mm).
2 Insulation, foam glass block.
3 Vapor Barrier, polyethylene sheet 0.015 in. (.375 mm) thick, factory sealed joints or 6 in. (150 mm) min overlap.
4 Hardwood block: kiln dried, < 10% moisture, coated all sides with elastomeric vapor barrier. Alternatively, a load
bearing insulating concrete block, similarly coated is acceptable.
5 Metal jacket insulation covering shall be extended to lap over the top of the Ringwall, with joints lapped and
sealed against entrance of water.
6 in.
A A
SLOPE
1:50
DRAINAGE
GUTTER DRAIN
PLAN
ACID TANK
CURB
8 in.
FIN.
6 in. AT
PROTECTIVE COATING GRADE
FOUNDATION HIGH PT.
SECTION A-A OF SLAB
in. mm
1 25
2 50
3 75
4 100
6 150
8 200
12 300
24 600
28 700
30 750
36 900
42 1050
Tank Diameter
20 ft 6m
30 ft 9m
Record of Change
Version 1.0.0 Date: 02/02
Location Action Description
Initial Publish.