Professional Documents
Culture Documents
Manual
ou 00
Transfer
Switches
962-0504
SPEC E, F
12-88
Printed in U.S.A
OT2- UG-3
Redistribution or publication of this document
by any means, is strictly prohibited.
Table of Contents
TITLE PAGE
TThTT
b TT T I T
-1 i2 3 5 '6 7 8 1.0
3
Redistribution or publication of this document
by any means, is strictly prohibited.
SOURCE 2
TRANSFORMER
ASSEMBLY
ENCLOSURE
LIGHT ARRAY
CONNECTORS
ASSEMBLY
CAPACITOR
CONTACTOR
t
5
Redistribution or publication of this document
by any means, is strictly prohibited.
TABLE 1
Power Sentry Control Light Array
Light ON Indicates
Source 2 OK Source 2 voltage is available and within the voltage and frequency
settings of the voltage/frequency sensor.
Timing for Stop Control is timing out for generator stop signal. At the end of the
timing period, the 2 Wire Run lamp and the Timing for Stop light will V
go out.
Transfer Command Control is signaling for transfer to Source 2 power source. The
Source 2 OK lamp and the 2 Wire Run lamp will also be on.
Timing f.or Over-voltage Source 2 Control is timing out for overvoltage condition on Source 2.
Overvoltage time delay is adjustable from 0 to 120 seconds; factory
setting is 5 seconds. Source 2 OK light will stay on during timing out
period. Does-notoperate if no overvoltage sensor.
Retransfer Command Control is signaling for retransfer to Source 1 power source. The
Source 1 OK light will also be on.
Timing f.w Overvoltage Source 1 Control is timing out for overvoltage condition on Source 1.
Overvoltage time delay is adjustable from 0 to 120 seconds; factory
setting is 5 seconds. Source 1 OK light will stay on during timing out
period. Does not operate if no overvoltage sensor.
Source 1 0.K Source 1 voltage is available and within the voltage and frequency
settings of the voltage/frequency sensor. .
Timing, far Retransfer Control is timing out for retransfer to Source 1 power source. At end
of timing period, light will go out. Delay is adjustable from 0 to 32
minutes; factory setting is 15 minutes.
Timing: for Transfer Control is timing out for transfer to Source 2 power source. At end of
timing period, light will go out. Delay is adustable from 0 to 120
seconds; factory setting is 2 seconds.
i"
;-
, --
a
zi
$.
I
I
The start time delay, adjustable from zero t o six Refer to the Time Delay Adjustments section for the
seconds, begins timing if the input signal from the time delay adjustment procedures.
Source 1 voltage sensor is interrupted. If the signal
returns during the timing out period, the timer will K12 Reversing Contactor
reset. If the signal does not return by the end of the The K12 reversing contactor (also called interposing
delay period, the timer will signal for the generator set relay - see Figure 1) consists of two separate relay
to start. The purpose of the delay is to prevent genera- coils (designated as K1 and K2 relays) and an inter-
tor set start up when power interruptions of very short locking set of relay contacts. The K1 and K2 relay
duration occur. The factory delay setting is for two contacts are used to connect line voltage to the linear
seconds. actuator motor. If the transfer switch is connected to
the Source 2 side and the Source 1 power source is
The transfer time delay, adjustable from zero to two available, closing the K1 contacts will energize the
minutes, begins timing as soon as the Source 2 vol- linear actuator motor and cause the load to transfer to
tage sensor signals that power is available. At the end the Source 1 side. If the transfer switch is connected
of the delay, the timer will signal for the load to to the Source 1side and theSource2 powersource is
transfer to the generator set. The purpose of the delay available, closing the K2 contacts will energize the
is to allow the generator set to stabilze before the load linear actuator and cause the load to transfer to the
is applied. The factory delay setting is for two Source 2 side. A mechanical interlock prevents the
seconds. K1 and K2 contactsfrom closing at the same time. An
electrical interlock prevents the K1 and K2 relay coils
When the Source 1 power source returns and Source from being energized at the same time. The K1 and K2
OK signals are received from both voltage sensors, relay coils are driven by DC output voltage from the
the time delay module will respond to the preferred mother board rectifier bridges.
source. In utility-to-generator installations, Source 1
(normal) is recognized as the preferred source. In C1 Storage Capacitor
utility-to-utility o r generator-to-generator The C1 capacitor functions as an energy storage
installations, the preferred source is selected by set- element. During power outages, the C1 capacitor
ting an externally mounted selector switch. holds the K3Two-Wire Run relay energized while the
start time delay times out. This avoids nuisance start-
The retransfer time delay, adjustable from zero to ing during short duration power outages.
thirty-two minutes, begins timing as s o m as the input
signal from the Source 1 voltage sensor returns. At C12 Filter Capacitor
the end of the delay, the timer will signal for the load
to transfer to the normal source. The purpose of the The C12 capacitor functions as a filter capacitor to
delay is to allow the normal power source to stabilize smooth out the output voltage from the mother board
before the load is applied. The factory delay setting is rectifier bridges. The integrated circuit design pro-
for fifteen minutes. vides a rectified output voltage if either power source
is available.
Source 7 Voltage Sensor: The Source 1 voltage sen- A separate voltage sensor (see Figure 3) is used for
sor monitors the normal power source. When the each power source. The voltage sensor above the
voltage and frequency rise above the pickup settings, time delay module is for the emergency power source
the sensor will signal that Source 1 voltage is avail- (source 2) and the sensor below the time delay
able. The Source 1 OK lamp will light and stay on as module is for the normal power source (source 1).
long as the normal source voltage is within the volt-
age and frequency settings of the voltage sensor. Undervoltage Sensor: The standard voltage sensor
modules monitor the Normal and Emergency power
Retransfer Time Delay: The retransfer time delay will source for an undervoltage condition. The under-
begin timing as soon as the voltage sensor signals voltage range of adjustment is shown below. If other
that Source 1 voltage is available. The retransfer time than factory setting is desired, align the slot on the
delay isadjustable from 0 to30 minutesand is factory potentiometer to the desired markings on the module
'
EMERGENCY
SOURCESENSOR
QXAX
J ,6 SEC 10 MIN 30MIN 2MIN
PICKUP%
OF NOMINAL
DROPOUT%
OF PICKUP
PICKUP BAND TIME DELAY LIMIT%
C OFNOMINALISSECONDS OFNOMINAL
NORMAL
TIME DELAY
2 MINUTES
-
SOURCE SENSOR 'Esl408.2
SOURCE 2 0 K
TRANSFER COMMAND
RETRANSFER COMMAND
2 WIRE RUN
SOURCE ONE OK
TIMING FORTRANSFER
After calibration, reset the Pickup and Dropout If other than factory setting is desired, align the slot
potentiometers t o the factory settings or to desired on the potentiometer to the desired markings on the
setting. module panel. See Figure 3. Range of adjustments
and factory settings are shown below.
OvervolfageSensor: The optional overvoltage sensor
detects when the source voltage has exceeded the ADJUSTMENT FACTORY
overvoltage Iimit. FUNCTlON RANGE SETTlNG
Pickup Band +4 to +20% +lo%
If other than factory setting is desired, align the slot Time Delay 0 to 15 Seconds 5 Seconds
on the potentiometer to the desired markings on the
module panel. See Figure 3. Range of adjustments The dropout bandwidth is always 2.5% wider (on
and factory settings are shown below. each end) than the pickup bandwidth.
ADJUSTMENT FACTORY The adjustable dropout Time Delay allows the control to
FUNCTION RANGE SETTING ignore momentary dips or rises in frequency.
Limit 105 to 135% 110%
Time Delay 0 to 2 minutes 5 seconds Time Delay Module
The overvoltage pickup point is fixed at 5 percent below The time delay module controls the following
the Limit setting. The adjustable dropout Time Delay f u nctions:
allows the control to ignore momentary overshoots in
vo I tage. Start time delay
Stop time delay
If necessary, the Overvoltage sensor may be cali- Transfer time delay
brated as follows: 0 Retransfer time delay
If the Undervoltage sensor has not been calibrated, do so before
proceeding. If other than factory setting is desired, align the slot
on the potentiometer to the desired markings on the
1. Ensure that nominal voltage is present on all module panel. See Figure 3. Range of adjustments
phases of the source being calibrated (Normal or and factory settings are as follows:
Emergency). On voltage sensors with the fre-
quency sensing option, the source frequency ADJUSTMENT FACTORY
must be within the limits set by the Frequency FUNCTION RANGE SETTl NG
Pickup Band potentiometer. Start 0-6 seconds 2 seconds
2. Turn the overvoltage Limit and Time Delay poten- Transfer 0-1 20 seconds 2 seconds
tiometers fully counterclockwise. Retransf er 0-30 minutes 15 minutes
3. Turn the Overvoltage Cal potentiometer fully stop 0-10 minutes 5 minutes
clockwise. The Source OK lamp for the selected
source should light (Figure 4).
4. Turn the Cal potentiometer counterclockwise
until the Source OK lamp turns off.
5. Slowly turn the Cal potentiometer clockwise until
the Source OK lamp just turns on again.
generator set. Adjustable start and retransfer time the emergency side and the normal power source is
delays and non-adjustable stop and transfer time available, closing the K1 contacts will energize the
delays are also available. linear actuator motor and cause the load to transfer to
the normal side. If the transfer switch is connectd to
All components for the relay control are mounted the normal side and the emergency power source is
within a separate enclosure. A wiring' harness with available, closing the K2 contacts will energize the
plug-in connectors connects the control with the linear actuator and cause the load to transfer to the
transfer switch. emergency side.
A l l TRANSFER
TIMEDELAY 1
- A10 STOP
TIME DELAY
K5 LINE
VOLTAGE 1
RELAY
-
c
- K6 GENERATOR
VOLTAGE RELAY
0 0
KlfK2
-
-
REVERSING
CONTACTOR
-TRANSFORMER
T1 LINE SIDE
0
K1 0
RELAY \
COIL
T2 GENERATOR
'SIDE TRANSFORMER
/
RELAY
K2 /
COIL
/
SC-1161
Energizing the K4 relay closes the normally open K4 Energizing the K2 relay closes the normally open K2
contacts (1 set). However, the closed K6 contacts paral- contacts (2 sets) and opens the normally closed K2
lel the K4 contacts so that the circuit is already complete contacts (1 set). Opening the normally closed K2
(assuming that the generator set is not running). contacts opens the K1 relay circuit. Since the normal
power source is not available, the K1 relay is already
de-energized. However, opening the K2 contacts
Energizing the K3 relay opens the normally closed K3 provides an electrical interlock that prevents the K1
contacts. This holds the start circuit open (two-wire and K2 relays from energizing at the same time.
start) so that the generator set does not start.
Closing the normally open K2 contacts connects
Energizing the K1 relay closes the normally open K1 line-to-line voltage from the emergency side to the
contacts (3 sets) and opens the normally closed K1 linear actuator motor. This energizes the linear actua-
contacts (1 set). Closing the normally open K1 con- tor and causes it to open the transfer switch on the
tacts does not complete any circuits so that no addi- normal side and close the transfer switch to the
tional components are energized. Opening the nor- emergency side. When the transfer switch closes to
mally closed K1 contacts (1 set) opens the circuit the emergency side, the S6 auxiliary switch opens the
between the K2 relay and the emergency power linear actuator circuit which de-energizes the linear
source. Since the generator set is not operating, the actuator motor, the T2 transformer, and the K2 relay.
K2 relay is already de-energized. However, opening The K2 relay contacts return to their de-energized
the K1 contacts provides an electrical interlock that position, The transfer switch remains closed to the
prevents the K2 and K1 relays from energizing at the emergency side and the load is now powered by the
same time. generator set.
Normal Power Source Interrupted
If any phase of the normal power source is inter- Emergency Power Source
rupted, either the K5 Line Voltage relay or theT1 Line
Side transformer w i l l de-energize. When t h i s Connected to Load
happens, the output voltage from the T1 transformer Under emergency power conditions, the transfer
immediately terminates causing the K4 Retransfer switch will be closed to the emergency side and the
Time Delay, K3 Start Time Delay relay, and K1 load will be powered by the generator set. Line-to-
Reversing Contactor relay to de-energize. Both the line voltage from the emergency side energizes the
K4 and K1 relay contacts immediately return t o their K6 Generator Voltage relay and opens the normally
de-energized positions. However, the K3 relay holds closed K6 contacts. Holding the normally closed K6
the normally closed K3 contacts open until the start contacts open prevents the load from immediately
time delay has timed out. At the end of the time delay, retransferring to the normal side when the normal
the K3 contacts close and a start signal is sent to the power source returns.
generator set.
1
I n-I ff P
T82
TRANSFER
SWITCH
1.
-1
' I
I
0-
@- I
I
TBZ
0-
c " I
A
B LOAD
1
I II I
& 4 B C
EMERGENCY
19
Redistribution or publication of this document
by any means, is strictly prohibited.
Options and Accessories
INTRODUCTION EXERCISER CLOCK
This section covers the adjustment and service The exerciser clock is set by the factory to provide
procedures for the options and accessories that are one-half hour of exercise each week. Onan recom-
available with the OTll transfer switch. Separate mends that the generator set be operated under load
installation instructions are furnished with each for 30 minutes each week to remove moisture and to
option. Refer to the appropriate instruction sheet for keep a film of lubricating oil on the engine parts.
wiring connections and installation procedures. The Exercising for one long period is better than several
location of each option is shown in Fiaure 7.
1
short periods. The normal exercise period is from ?
PROGRAMMED
TRANSITION
THREE WIRE
STARTING CONTROL
OVERCRANK RELAY
I BATTERY CHARGER
ES-1093
20
Redistribution or publication of this document
by any means, is strictly prohibited.
Disconnect both the normal and the emergency 3. To set the time of day you want the generator set
power source from the transfer switch before servic- to stop, use the outside row of holes on the large
ing. Turn the operation selector switch for the gener- dial. Install a trip pin in the hole that corresponds
ator set to STOP; and disconnect the negative battery to the desired set stop time.
cable from the set starting battery. The selector 4. Install a trip pin in the small spoked wheel for
switch is located on the generator set control panel each day that no exercise is desired.
on two wire start systems and on the transfer switch
control panel on three wire start systems. 5. Rotate the large dial clockwise until the correct
time of day aligns with the pointer.
High voltages within the cabinet 6. Rotate the small spoked wheel counterclockwise
@!%!@%I present an electrical shock hazard
that can cause severe personal injury or death. Dis-
until the correct day aligns with the pointer.
connect all sources of AC power from the transfer Sixteen trip pins are supplied. Store any unused pins on the
1 time pointer bracket.
switch before servicing.
7 . Set the exerciser switch so that the generator set
1. Open the transfer switch cabinet door. will exercise with or without load as desired.
2. To set the time of aay you want the generator set to 8. Close the cabinet and reconnect the normal
start, use the inside row of holes on the large dial power source and emergency power source.
(see Figure 8A). Install a trip pin (left-hand thread) in Connect the negative battery cable to the starting
the hole that corresponds to the desired set starting battery and place the set operation selector
time. switch in automatic or remote position.
@+CUDl OlIO I
stop time.
2. Press the h button (3) to set the stop hour. PROGRAMMED TRANSITION
3. Press the m button (4) to set the stop minute. Three programmed transition time delays are available
4. Press the 1-7 button (5) to advance the indicator bar with OT II transfer switches. The delay period is adjusta-
(14) from 1 to 7 and back to 1. For each start time ble from 0.5 to 5 seconds, 1.5 to 15 seconds, or 5 to 50
(selected in step 5 above), there must be a corres- seconds, depending on the option selected. The time
ponding stop time. A program can start on day 2, delay is set by the factory for two seconds. If this delay is
pass through midnight,and stop on day 3 (for exam- not safisfactory, the timer can be adjusted using the
ple); but there must be a stop time for every start following procedure.
time. Press the Q button (7) when the indicator is
under the desired day number. Disconnect both the normal and the emergency power
5. To enter the complete start/stop program, press the source from the transfer switch before servicing. If a
Pr button (8). If all program requirements have been generator set provides standby emergency power, furn
satisfied, the display returns to the time of day. If the the operation selector switch to STOP, and disconnect
program requirements are not met, the display of the the negative battery cable from the set starting battery.
section that needs correction flashes on and off. The selector switch is located on the generator set
control panel on two wire start systems and on the
To enter more programs, repeat the two 5-step proce- transfer switch control panel on three wire start
dures. A maximumof ten programs can be entered. (The systems.
same programs can be repeated each day.)
TABLE 1
Lead-Acid Batteries
Battery Voltage Float Voltage
12 13.3
SC-1139 24 26.6
5. When adjustments are complete, close the TWO TO THREE WIRE CONVERTER
transfer switch cabinet door. A two to three wire converter is available for convert-
6. Disconnect the voltmeter from the battery termi- ing a two wire start transfer switch to a three wire start
nals and disconnect the test battery from the system. The converter includes a Start-Disconnect
- generator set.. relay, Overcrank relay, and might include a Preheat
7. Reconnect the generator set starting battery and Time Delay depending on the options selected. Refer
place the operation selector switch in automatic to Figure 11 for the location of each component. The
or remote position. time delays can be adjusted using the following
procedures.
24
Redistribution or publication of this document
by any means, is strictly prohibited.
Preheat Time Delay
SC-1140
40-70-100 amperes, 150-260 amperes, 400 amperes, (with flat washers) that secure the red plastic
and 600-800-1000 amperes. switch cover to the switch base; and lift off the
cover.
3. Separate the actuator lead wires from the rest of
For servicing purposes; each transfer switch assem- the wiring harness; remove wire ties as required.
bly can be separated into the following components: 4. Remove the red and white actuator leads from the
capacitor and the black lead from circuit breaker.
Linear Actuator Notethe leadconnectionsto the capacitor terminals.
Transfer Switch 5. Remove the socket head capscrews, flat washers,
0 Auxiliary Switches lock washers, and nuts that secure the actuator to
the switch assemblies (see Figure 12). Note the
A separate section covers the removal and replace- ground wire connection to lower left capscrew.
ment procedures for each major component within a
particular amp range. 6. Disengage actuator rod from switch handle and
remove actuator from switch assembly.
7. Remove one of the hexhead capscrews and lock
LINEAR ACTUATOR REMOVAL washers that secure the rod end assembly to the
AND REPLACEMENT actuator rod.
(40-70-1 00 Amperes) 8. Remove rod end assembly from actuator rod (see
Disconnect both the normal and the emergency Figure 13)and slide rod out of the actuator.
power source from the transfer switch before servic-
ing. If a generator set provides standby emergency Replacing Actuator
power, turn the operation selector switch to STOP;
. and disconect the negative battery cable from the set 1. Insert the actuator rod into the replacement actu-
starting battery. The selector switch is located on the ator motor from the side opposite the ground
generator set control panel on two wire start systems brush (see Figure 13). Install the rod end assem-
and on the transfer switch control panel on three wire blyand tightencapscrewto130to135 in-lbs(14.7
start systems. to 15.3 Nom).
2. Position actuator motor on switch assemblies so
High voltages within the cabinet
1-1 present an electrical shock hazard
that can cause severe personal injury or death. Dis-
the load wires are at the bottom; and fit the rod '
assembly into the handle of the closed switch
assembly.
connect all sources of AC power from the transfer
switch before servicing.
The following procedures cover the removal and
replacement of the linear actuator for 40 to 100
Ampere switches.
WIRING
HARNESS
PLUGS
SECTION A-A
SECTION B-B
FIGURE 12. TRANSFER SWITCH FRONT COVER
ACTUATOR
WITH LOCK
WASHER
3. Secure actuator motor to switch assemblies 7. Place red plastic switch cover in position and
using socket head capscrews (4), flat washers ( 8 ) , secure with machine screws (4).and flat washers
lock washers (4), and nuts (4). Be sure to recon- (4). Tighten to 25 to 30 in-lbs (2.8to 3.4 Nom)
nect ground wire to lower left screw (see Figure torque.
12).Tighten capscrews to 25 to 30 in-lbs (2.8to 8. Plug in the threecontrol wiring harness plugs (Jl,
3.4 Nom) torque. J2,and J3);and reconnect normal power source
and emergency power source. If a generator set is
k@%@@Do not overtighten screws or the
switch assembly can be damaged.
the emergency power source, connect the nega-
tive battery cable to the starting battery and place
operation selector switch in automatic or remote
4. Connect the black actuator lead wire to the circuit position.
breaker; and the red and whiteactuator lead wires
to the following capacitor terminals: 9. Test switch for proper operation and close
cabinet.
Red Lead Wire - Connect to capacitor terminal
with S3 lead wire. SWITCH ASSEMBLY REMOVAL
AND REPLACEMENT
White Lead Wire - Connect to capacitor terminal (40-70-1 00 Amperes)
with S7 lead wire. Disconnect both the normal and the emergency
power source from the transfer switch before servic-
Transfer switches for voltage ranges 347, 3801416, 4401480
and 480 use two capacitors (C1 and C2) wired together in
ing. If a generator set provides standby emergency
series. A single jumper wire is placed between one of the power, turn the operation selector switch to STOP;
terminals on C1 and one of the terminals on C2. Connect red and disconnect the negative battery cable from the
and white leads as described in previous section. set starting battery. The selector switch is located on
the generator set control panel for two wire start
5. Use wire ties to hold actuator lead wires in place systems and on the transfer switch control panel for
with rest of wiring harness. three wire start systems.
6. Check operation of transfer switch and alignment
of actuator rod by manually opening and closing High voltages within the cabinet
both the normal and emergency switch
assemblies.
@@@%%I present an electrical shock hazard
that can cause severe personal injury or death. Dis-
connect all sources of AC power from the transfer
switch before servicing.
10. Remove the pan head screws that secure the left
and right phase barriers and retainer barriers (see
Figure 17) to the switch assembly; and lift out the
phase barriers, retainer barriers, arc chutes, and
arc chute barriers. Discard arc chutes and arc
chute barriers.
29
Redistribution or publication of this document
by any means, is strictly prohibited.
40-70-100 AMP MODEL
3 INTERLOCK BAR !
-4
HANDLE
ASSEMBLY
v,
-+ -
I
I P
/
-t
I
I
-4
I
-+-I - +-
I
I I' I
---,
3I 5 - - . l
JUMPER BUS
JUMPER: BUS: ta
La
BAR BUS BAR
1. 2
JUMPER BUSBAR
VIEW A-A
AUXILIARY SWITCH
LEVER POSITION WHEN
TRANSFER SWITCH IS CLOSED I
3 5 5 3
AUXILIARY SWITCH
LEVER POSITION WHEN
TRANSFER SWITCH IS CLOSED
1. 2
LOAD-BUS BAR I
- - -
I
VIEW D-D
MAIN CONTACTS CLOSED
SECTION A-A
- -
2 TORQUE TO 20 32 IN. LBS.
STRAP
5. On front connect switches, install the power 9. Secure the jumper bus bars t o each load bus bar
source supply wires and securely tighten the lug using a hex ,head machine screw, ring terminal,
terminals. flat washer, lockwasher, and nut. Tighten to 25 to
On rear connect switches, apply a thin coat of 30 in-lbs (2.8to 3.4 N om) torque.
'
electric joint compound between the current car- 10. Connect the control wiring leads to the corres-
. rying surIdces of the contact strap and rear con- ponding jumper bus bar terminal. Control wires
- nect strap (see Figure 16). Secure with hex head are marked LOAD A,B,C, for identification.
machine screw, spring washer, flat washer, lock 11. Place the handle assembly in position on the
washer, and nut. Tighten to 70 to75 in-lbs (7.9 to switch assembly and secure with pan head
8.5 Nom) torque. screws (2), locking washers (2), and flat washers
6. Connect the control wiring leads to the corres- (2).
ponding power source terminals. Control wires 12. Install the interlock bar and secure to each inter-
are marked NORM A,B,C or EMER A,B,C for lock arm with a round head machine screw, lock-
identification. ing washer, small flat washer, and large flat
7. Apply a thin coat of electric joint compound washer.Tighten to 15 to20 in-lbs(l.7 to2.3 Nom)
between the mating surfaces of the jumper bus torque.
bars, braided strap connector, and load bus bars.
8. Install the jumper bus bars and secure to the
switch assemblies with hex head machine screws
and spring washers. Tighten to70 to75 in-lbs (7.9
to 8.5 Nom) torque.
RETAINER
BARRIER
LEFT PHASE
BARRIER
LUG TERMINAL
13. Replace the linearactuatorasdescribed in Linear The following procedures cover the removal and
Actuator Removal And Replacement section for replacement of the auxiliary switch for 40 to 100
40 to 100 Ampere switches. ,Follow steps 2 ampere switches.
through 8 in the Replacing Actuator section.
14. Test switch for proper operation and close Removing Auxiliary Switch Assembly
cabinet.
1. Open the transfer switch cabinet door and unplug
the three control wiring harness plugs ( J l , J2, &
J3 - Refer to Figure 12) from the front cover.
AUXILIARY SWITCH REMOVAL 2. Loosen and remove the four machine screws
AND REPLACEMENT (with flat washers) that secure the red plastic
switch cover to the switch base; and lift off the
(40-70-1 00 Amperes) cover.
Disconnect both the normal and the emergency 3. Remove the control wiring leads from the auxil-
power source from the transfer switch before servic- iary switch terminals (see Figure 18).
ing. If a generator set provides standby emergency
power, turn the operation selector switch to STOP; 4. Remove the round head machine screws that
and disconnect the negative battery cable from the secure the auxiliary switch assembly bracket to
set starting battery. The selector switch is located on the base.
the generator set control panel on two wire start sys- 5. Disengage the auxiliary switch lever from the
tems and on the transfer switch control panel on transfer switch crossbar and lift out the auxiliary
three wire start systems. switch assembly.
33
Redistribution or publication of this document
by any means, is strictly prohibited.
40-70-100 AMP MODEL
1
It
1
1.
I 1
II c
d s3
55
OC s9
6. Remove the round head machine screws and nuts 2. Install the auxiliary switches (4) and insulating .
that secure the auxiliary switches to the bracket barriers (5) in the bracket; and secure with round
(see Figure 18); arid lift out the four auxiliary head machine screws (2) and nuts (2). Note that
switches, insulating barriers, and switch lever. each switch must be assembled so the side with
two terminals (see Figure 18) is facing the open
end of the bracket.
3. Manually close the transfer switch that will be
coupled to the auxiliary switch lever.
4. Hold the auxiliary switch assembly in position on
the base (open end of bracket must face inward)
and check alignment of the auxiliary switch lever.
Replacing Auxiliary Switch Assembly When the transfer switch assembly is closed, the
auxiliary switch must be aligned as shown in Fig-
1. Place the auxiliary switch lever in the bracket as ure 18. Move auxiliary lever as required to get
shown in Figure 18. Note that the end of the lever correct alignment.
with the octagonal hole must engage the transfer
switch cross bar when the auxiliary switch
assembly is installed.
I 1
FRONT
COVER +
D
8
CAPACITORS
,SWITCH -z
_--_
,
r
F:
I /
GROUND
WIRE
.. PLASTIC
1
BARRIER
2?
-- SPACER - .'
t
- D- 1
I
I
JUMPER WIRE
I I
HEX HELD
CAPSCREW i
GROUND BRUSH
2. Hold actuator motor in position over the switch Transfer switches for voltage ranges 347, 3801416, 4401480
assemblies so the lead wires are at the bottom; and 480 use two capacitors (C1 and C2) wired together in
series. A single jumper wire is placed between terminal 1 on
and fit the rod assembly into the handle of the C1 and terminal 1 on C2.
closed switch assembly.
3. Secure the actuator motor to the switch assem- 5. Replace the capacitor end cap(s) and install the
blies using hex head capscrews (4), lock washers capacitor(s) in the bracket(s).
(4), flat washers (4),
barriers (2), and spacers (4). 6. Connect the ground wire to the end of the actua-
Tighten capscrews to 70 to 75 in-lbs (7.9 to 8.5 tor. Use wire ties to hold actuator lead wires in
Nom). place with rest of wiring harness.
4. Connect the black actuator lead wire to the circuit 7. Place the red plastic barrier in position and
breaker; and the red and white actuator lead wires secure to the switch base with machine screws
to the following capacitor terminals: (2) and flat washers (2). Tighten to 25 to 30 in-lbs
(2.8 to 3.4 Nom) torque.
Red Lead Wire- Connect to capacitor C1 -Termi-
nal 2.
JUMPER'BUS BAR ._
HANDLE
ASSEMBLY
1 - PLACE THIN COAT OF ELECTRIC JOINT COMPOUND BETWEEN CURRENT CARRYING SURFACES
SECTION B-B
. -
BUS BAR
4
/
/
4-
HANDLE
J U M ~ E RBUS BAR
ASSEMBLY
4- + JI J2 J8 +
& + +
1 - PLACE THIN COAT OF ELECTRIC JOINT COMPOUND BETWEEN
CURRENT CARRYING SURFACES.
THREADED HEX
SPACER 2 -TORQUE SHALL BE 15-20 IN-LBS FOR 118-32 SCREWS.
,/
1:
ARC CHUTE
BARRIER
ARC CHUTE
INSULATOR ARC
FRONT CONNECT
4
\ \ CHuY
LUG
I
' 1
t
CONTACT
STRAP ARC CHUTE
BARRIER
FLAT WASHERS
MACHINE SCREW
INSULATING BARRIER
SWITCH LEVER
AUXILIARY SWITCH LEVER IN CLOSED POSITION
1 - ORIENTATE TERMINALS ON S3 AND S6 AS SHOWN
N/O
EMERGENCY
WITH
WITCH
LINEAR ACTUATOR
REMOVAL AND REPLACEMENT
7. Test switch for proper operation and close
-
(400 Amperes Spec E) -
cabinet. Disconnect both the normal and the emergency
power source from the transfer switch before servic-
ing. If a generator set provides standby emergency
power, turn the operation selector switch to STOP;
and disconnect the negative battery cable from the
set starting battery. The selector switch is located on
the generator set control panel for two wire start
systems and on the transfer switch control panel for
three wire start systems.
FRONT COVER
+- I
4
i
w3 SW'TC
k;;l TE?R
1'
CAPSCREWS
GROUI
\ SPACER
f
0
HEX HEAD
CAPSCREW
WASHER
-qF7
WITH LOCK
-- I
GROUND BRUSH
8. Place red plastic switch cover in position and SWITCH ASSEMBLY REMOVAL
secure with machine screws (4) and flat washers AND REPLACEMENT
(4). Tighten to 25 to 30 in-lbs (2.8 to 3.4 Nom)
toraue.
-- -
-I
(400 Amperes Spec E) -
?
9. Plug in the three control wiring harness plugs ( J l , Disconnect both the normal and the emergency
J2,and J3); and reconnect normal power source power source from the transfer switch before servic-
and emergency power source. If a generator set is ing. If a generator set provides standby emergency
the emergency power source, connect the nega- power, turn the operation selector switch to STOP;
and disconnect the negative battery cable from the
tive battery cable to the starting battery and place
set starting battery. The selector switch is located on
operation selector switch in automatic or remote
the generator set control panel on two wire start sys-
position.
tems and on the transfer switch control panel on
10. Test switch for proper operation and close three wire start systems.
cabinet.
47
Redistribution or publication of this document
by any means, is strictly prohibited.
High voltages within the cabinet Use care when removing the
present an electrical shock hazard block and cross-bar assembly
that can cause severe personal injury or death. Dis- from the base. Carefully disengage the crossbar
connect all sources of AC power from the transfer from the auxiliary switch lever to avoid cracking
switch before servicing. the switch lever.
-
1 PLACE THIN COAT OF ELECTRIC JOINT COMPOUND BETWEEN CURRENT CARRYING SURFACES
6 - PLACE A THIN COAT OF THREAD SEALANT TO THREADS OF SCREW THEN TORQUE AS NOTED
1
INSULATOR
49
Redistribution or publication of this document
by any means, is strictly prohibited.
HANDLE ' JUMPER BUS
ASSEMBLY , BAR
-
5 PLACE A THIN COAT OFTHREAD SEALANTTO THREADS OF SCREW THEN TORQUE.AS NOTED
REAR CONNECT
STRAP
50
Redistribution or publication of this document
by any means, is strictly prohibited.
400 AMP MODEL (SPEC E)
FRONT CONNECT
REAR CONNECT
ARC CHUTE I , oi
LUG
TERMINAL
-
SECTION B-B
2'
51
Redistribution or publication of this document
by any means, is strictly prohibited.
Replacing Switch Assembly 8. On fronf connect switches, install the power
source supply wires and securely tighten the lug
(Normal or Emergency) terminals. On rear connect switches, apply a thin
coat of electric joint compound between the cur-
1. Apply a thin coat of electric joint compound rent carrying surfaces of the contact strap and
between the mating surfaces of the switch rear connect strap (see Figure 28). Secure with
assembly and the lug terminal (front connect) or hex head capscrew, spring washer, flat washer,
the switch assembly and contact strap (rear locking washer, and nut. Tighten to 70to 75 in-lbs
connect). (7.9 to 8.5 Nom) torque.
9. Connect the control wiring leads to the corres- t
On fronf connect switches, install the lug terminal ponding power source terminals. Control wires
and secure with the hex head capscrews, ring are marked NORM A,B,C or EMER A,B,C for
terminal, and spring washer. Tighten to 70 to 75 identification.
in-lbs (7.9 to 8.5 Nom) torque. 10. Apply a thin coat of electric joint compound
between the current carrying surfaces of the
On rear connect switches, install the contact jumper bus bars, the braided strap connectors,
strap and secure with hex head capscrew, ring and load bus bars.
terminal, and spring washer. Tighten to 70 to 75 11. Install the jumper bus bars and secure to the
in-lbs (7.9 to 8.5 Nom) torque. switch assemblies with hex head capscrews and
spring washers. Tighten to 10 to 12ft-lbs (13.6 to .
2. Install the hex head machine screws (used to
secure arcchute barrier), locking washers (2),flat 16.3 Nom).
washers (2), and nuts in the switch assembly 12. Secure the jumper bus bars to each load bus bar
base. Tighten to 15 to 20 in-lbs (1.7 to 2.3 Nom) using a hex head capscrew, ring terminal (lower
torque. row only), spring washer, and nut. Tighten to 70
3. Place the handle assembly in position on the to 75 in-lbs (7.9 to 8.5 Nom) torque.
switch assembly and secure with shoulder 13. Connect the control wiring leads t o the corres-
screws (2) and locking washers (2). ponding jumper bus bar terminal. Control wires
are marked LOAD A,B,C for identification.
4. Install the arc chute insulators (new). arc chutes
(new), and arc chute barrier; and secure with nuts
(2), locking washers (2) and flat washers (2).
Tighten nuts to 15 to 20 in-lbs (1.7 to 2.3 Nom)
torque.
5. Apply thread sealant to the threads of the inter-
lock arm capscrew. Install the interlock arm to the
switch assembly and secure with capscrew and
spring washer. Tighten to 70 to 75 in. Ibs. (7.9 to
8.5 Nom) torque. .
6. Install the hex head capscrews (used to secure
the jumper bus bars), locking washers, flat
washers, spacer bushings, and jam nuts in the
switch assembly base.Tighten to 10 to 12 ft-lbs
(13.6 to 16.3 Nom) torque.
7. Secure switch assembly to base with hex head
capscrews (4), locking washers (4), and fiat
washers (4). Tighten to 70 to 75 in-lbs (7.9 t o 8.5
N*m) torque.
52
Redistribution or publication of this document
by any means, is strictly prohibited.
400 AMP MODEL (SPEC E)
INSULATINGBARRIER
BRACKET
SWITCH LEVER
IN CLOSED POSITION
/
-
1 ORIENTATE TERMINALS ON S3 AND S6 AS SHOWN
N/O
1 L
NORMAL
SIDE WITH
TWO SWITCH
TERMINALS
EMERGENCY
0 0
14. Install the interlock bar and secure to each inter- AUXlLIARY SWITCH
lock arm with a hex head capscrew, locking REMOVAL AND REPLACEMENT
washer, and flat washer. Tighten to 70 to 75 in-lbs.
(7.9 to 8.5 Nom) torque. (400 Amperes Spec E) -
15. Replace the linear actuator as clescribed in Linear Disconnect both the normal and emergency power
Actuator Removal and Replacement section for source from the transfer switch before servicing. If a
400 Ampere switches. Follow steps 2 through 9 in generator set provides standby emergency power,
the Replacing Actuator section. turn the operation selector switch to STOP: and dis-
16. Test switch for proper operation and close cabinet. connect the negative battery cable from the set start-
ing battery. The selector switch is located on the
generator set control panel for two wire start systems
and on the transferswitch control panel forthree wire
start systems.
53
Redistribution or publication of this document
by any means, is strictly prohibited.
High voltages within the cabinet Replacing Auxiliary Switch Assembly
present an electrical shock hazard
that can cause severe personal injury or death. Dis- 1. Place the auxiliary switch lever in the bracket as
connect all sources oi AC power irom the transier shown in Figure 30.
switch beiore servicing. 2. Install the flat washers (4),insulating barriers (4),
and auxiliary switches (3) in the bracket; and
The following procedures cover the removal and secure with round head machine screws (2)and
n u t s (2). N o t e that each switch must be
replacement of the linear actuator for the 400 Ampere
assembled so the side with two terminals faces
(Spec E) switches.
inward (see Figure 30)when the auxiliary switch
assembly is installed. I
Removing Auxiliary Switch Assembly 3. Hold the auxiliary switch assembly in position on
base (side with two terminals must face inward)
1. Open the transfer switch cabinet door and unplug and secure bracket to base with round head
the three control wiring harness plugs (Jl,J2 & J3 machine screws. Tighten to 25 to 30 in-lbs (2.8to
- Refer to Figure 25)from the front cover. 3.4 Nom) torque.
2. Loosen and remove the four machine screws 4. Install control wiring leads on the corresponding
(with flat washers) that secure the red plastic switch terminals. Leads are marked with the ter-
switch cover to the switch base; and lift off the minal numbers (S2/NO, S5/NC, S7/C, etc.) for
cover. identification. Refer to Figure 30 for identification
3. Remove the round head machine screws that of auxiliary switch terminals.
secure the plug bracket to the base. Push the plug 5. Place the plug bracket in position on the base and
bracket to the side toallow access to theauxiliary secure with round head machine screws (4).
switches. Tighten to 25 to 30 in-lbs (2.8to 3.4 Nom) torque.
4. Remove the control wiring leads from the auxil- 6. Place red plastic switch cover in position and
iary switch terminals (see Figure 30). secure with machine screws (4) and flat washers
5. Remove the round head machine screws that (4).Tighten t o 25 to 30 in-lbs (2.8to 3.4 Nom)
secure the auxiliary switch assembly bracket to torque.
the base. 7. Plug in the three control wiring harness plugs (JI,
J2,J3,);and reconnect the normal power source
6. Disengage the auxiliary switch lever from the and emergency power source. If a generator set is
transfer switch crossbar and lift out the auxiliary the emergency power source, connect the nega-
switch assembly. tive battery cable to the starting battery and place
operation selector switch in automatic or remote
Use care when disengaging position.
1 avoid
- cracking theswitch lever irom crossbar to
switch lever.
8. Test switch for proper operation and close
cabinet.
54
Redistribution or publication of this document
by any means, is strictly prohibited.
LINEAR ACTUATOR 7. Remove the hex head capscrews, lock washers,
and flat washers that secure the actuator to the
REMOVAL AND REPLACEMENT switch assemblies (see Figure31); and lift out the
(600 (Spec E)-800-1000 Amperes) spacers (4) and actuator motor.
extreme caution when making adjustments to avoid Red Lead Wire - Connect to capacitor C1- Termi-
touching high-voltage components. nal 2.
1. Open the transfer switch cabinet door and unplug 4. Replace the capacitor end cap and install the
the three control wiring harness plugs ( J I ,J2 & J3 capacitor in the bracket.
- Refer to Figure 31) from the front cover. 5. Connect the ground wire to the end of the actua-
2. Remove the hex head capscrews, lock washers, tor. Use wire ties to hold actuator lead wires in
and rod assemblies from the end of the actuator place with rest of wiring harness.
rod (see Figure 32); and slide rod out of the actua- 6. Place red plastic switch cover in position and
tor motor. secure with machine screws (4) and flat washers
3. Loosen and remove the four machine screws (4). Tighten to 25 to 30 in-lbs (2.8 to 3.4 Nom)
'(with flat washers) that secure the red plastic torque.
switch cover to the switch base; and lift off the 7. Insert the actuator rod into the replacement actu-
switch cover. ator motor (see Figure 32). Hold the actuator
4. Separate the actuator lead wires from the rest of ground brush up slightly to allow passage of the
the wiring harness; remove wire ties as required. actuator rod.
5. Pry the capacitor(s) loose from the bracket.
Remove the end cap and disconnect the red and
white actuator lead wires from the capacitor .
terminals.
6. Disconnect the black actuator lead wire from the
circuit breaker and the ground wire from the end
of the actuator.
55
Redistribution or publication of this document
by any means, is strictly prohibited.
600 (Spec E)-800-1000 AMP SWITCH
FRONT COVER
SPACE^ '
CONTAM 4
COVERS
56
Redistribution or publication of this document
by any means, is strictly prohibited.
600 (SPEC E)-800-1000 AMP MODEL
ACTUATOR
- . YD
.
HEX HEAD
CAPSCREW
WITH LOCK
WASHER
GROUNDBRUSH
8 . Secure the rod end assemblies to the actuator rod SWITCH ASSEMBLY REMOVAL
with hex head capscrews (2)and lock washers AND 'REPLACEMENT
(2).Tighten capscrews to 1030 12 ft-lbs (13.6to
16.3Nom) torque. (600 (Spec E)-800-1000 Amperes)
9. Check operation of transfer switch and alignment Disconnect both the normal and the emergency
of actuator rod b y manually opening and closing power source from the transfer switch before servic-
b o t h t h e n o r m a l and e m e r g e n c y s w i t c h ing. If a generator set provides standby emergency
assemblies. power, turn the operation selector switch to STOP;
and disconnect the negative battery cable from the
10. Plug in the three control wiring harness plugs (JI, set starting battery. The selector switch is located on
J2,and J3);and reconnect normal power source the generator set control panel for two wire start
and emergency power source..lf a generator set is systems and on the transfer switch control panel for
the emergency power source, connect the nega- three wire start systems.
tive battery cable to the starting battery and place
operation selector switch in automatic or remote High voltages within the cabinet pre-
position. (BWARNINGI sent an electrical shock hazard that
11. Test switch for proper operation and close can cause severe personal injury or death. Disconnect
cabinet. all sources of AC power from the transfer switch before
servicing.
57
Redistribution or publication of this document
by any means, is strictly prohibited.
600 (SPEC E)-800-1000 AMP MODEL
INTERLOCK
.I
BLOCK ASSEMBLY
..
JUMPER
BUS BAR
CROSS-BAR
ASSEMBLY
"
SPACERS BAR
-
1 PLACE THIN COAT OF ELECTRIC JOINT COMPOUND BETWEEN CURRENT CARRYING SURFACES
, 4 -APPLY THIN COAT (.010APPROX.) OF GLYPTOL BETWEEN ARC CHUTE SPACER AND ARC CHUTE
PAPER BARRIER
5 -TORQUE SHALL BE 10-12 FT-LBS FOR 5/16-18 SCREWS
58
Redistribution or publication of this document
by any means, is strictly prohibited.
4
INTERLOCK 600 (SPEC E)-800-1000 AMP MODEL
ARC CHUTES
1 - PLACE A THIN COAT OF ELECTRIC JOINT COMPOUND BETWEEN CURRENT CARRYING SURFACES
5 -APPLY THIN COAT OF GLYPTOL BETYWEEN ARC CHUTE SPACER AND ARC CHUTE PAPER BARRIER
59
Redistribution or publication of this document
by any means, is strictly prohibited.
600 (Spec E)-800-1000 AMP MODEL
-
1 PLACE A THIN COAT OF ELECTRIC JOINT COMPOUND BETWEEN
CURRENT CARRYING SURFACES
SHOULDER SCREW
CROSS-BAR
ASSEMBLY
LUG TERMINAL
REAR
CONNECT-
STRAP
ARC CHUTE
! / BARRIER
61
Redistribution or publication of this document
by any means, is strictly prohibited.
4. Apply a thin coat of insulating varnish (such as 13. Install the interlock bar and secure to each inter-
Glyptal'" 1201 or Dolf" ER41) between arc chute lock arm with a hex head capscrew, locking
spacer and arc chute barrier. Place the arc chute washer, and flat washer. Tighten to 70-75 in-lbs
spacers (2), arc chute barrier, and arc chute in posi- (7.9 to 8.5 Nom) torque.
tion on each block assembly; and secure with round 14. Place the arc chute covers in position over the arc
head machine screws (2), lock washers (2) and flat chutes and replace the red plastic contact covers.
washers (2). Tighten to 15 to 20 in-lbs (1.7 to 2.3
15. Replace the linear actuator as described in Linear
Nom) torque.
Actuator Removaland Replacementsection for 600
5. Apply a thin coat of electric joint compound (Spec E)-800-1000Ampere switches. Follow steps
between the mating surfaces of the block assem- 1 through 10 in the Replacing Actuator section.
bly and the lug terminal (front connect) or block 16. Test switch for proper operation and close
assembly and rear connect strap (rear connect). cabinet.
On fronf connect switches, install the lug termi-
nals on the block assemblies and secure with hex
head capscrew and spring washer. Tighten to 28
to 33 ft-lbs (40.0 to 44.7 Nom) torque.
AUXILIARY SWITCH REMOVAL
On rearconnect switches, install the rear connect
straps on the block assemblies and secure with
AND REPLACEMENT
hex head capcrew and spring washer. Tighten to (600 (Spec E)-800-1000 Amperes)
28 t o 33 ft-lbs (40.0 to 44.7 Nom) torque. Disconnect both the normal and the emergency
6. Place each block assembly in position on the power source from the transfer switch before servic-
base and secure with hex head capscrews (8), ing. If a generator set provides standby emergency
lock washers (8),and flat washers (8). Refer to power, turn the operation selector switch to STOP;
(Figures 33 and 34) to determine where the spac- and disconnect the negative battery cable from the
ers are required and where the short capscrews set starting battery. The selector switch is located on
should be installed. Tighten capscrews to 70to 75 the generator set control panel for two wire start
in-lbs (7.9 to 8.5 Nom) torque. systems and on the transfer switch control panel for
three wire start systems.
7. On fronf connect switches, install the power
source supply wires and securely tighten the lug
terminals. On rear connect switches, apply a thin
coat of electric joint compound between the
mating surfaces of the contact strap and rear
connect strap (see Figure 34). Secure with hex
head capscrew, flat washers, spring washers, ring
terminaland nut.Tighten tolOto12ft-lbs (13.6to
16.3 N*m) torque.
8. Connect the control wiring leads to the corres-
ponding poLver source terminals. Control wires
are marked NORM A,B,C or EMER A,B, C for
identification.
9. Apply a thin coat of electric joint compound
between the mating surfaces of the jumper bus
bars, the braided strap connectors, and load bus
bars.
10. Install the jumper bus bars and secure to the
switch assemblies with hex head capscrews,
spring washers, and bushings. Tighten to 18to 20
ft-lbs (24.4 to 27.1 Nom) torque.
11. Secure the jumper bus bars to each load bus bar
with a hex head capscrew, ring terminal (lower
row only), flat washer, spring washer and nut.
Tighten to 10 to 12 ft-lbs (13.6 to 16.3 Nom)
torque.
12. Connect the control wiring leads to the corres-
ponding jumper bus bar terminal. Control wires
are marked LOAD A,B,C for identification.
62
Redistribution or publication of this document
by any means, is strictly prohibited.
600-800-1000 AMP MODEL
LAT WASHERS
INSULATING
BARRIER
SWITCH LEVER
IN CLOSED POSITION
-
1 ORIENTATE TERMINALS ON S3 AND S6 AS SHOWN
& f
N/CC-@ ’’ @jF%Wl
NORMAL
#
SIDE WITH
TWO SWITCH
TERMINA
d /
40
FIGURE 36. AUXILIARY SWITCHES
1 .
High voltages within the cabinet pre- 2. Remove the hex head capscrews, lock washers,
[BWARNINGI sent an electrical shock hazard that and rod assemblies from the end of the actuator
can cause severe personal injury or death. Disconnect rod (see Figure 32);and slide rod out of theactua-
all sources of AC power from the transfer switch tor motor.
before servicing. 3. Loosen and remove the four machine screws
(with flat washers) that secure the red plastic
The following procedures cover the removal and switch cover to the base: and lift off the switch
replacement of the auxiliary switch assembly for 600 cover.
(Spec E)-800-1000Ampere switches. 4. Remove the round head machine screws that
secure the plug bracket to the base. Push the plug
Removing Auxiliary Switch Assembly bracket to the side to allow access to the auxiliary
switches.
1. Open the transfer switch cabinet door and unplug 5. Remove the control wiring leads from the auxil-
the three control wiring harness plugs (Jl,J2,& iary switch terminals (see Figure 36).
J3 - Refer to Figure 31)from the front cover.
63 Redistribution or publication of this document
by any means, is strictly prohibited.
6. Remove the round head machine screws that 4. Install control wiring leads on the corresponding
secure the auxiliary switch assembly bracket to switch terminals. Leads are marked with the ter-
the base. minals numbers (S2/NO, SWNC, S7/C, etc.) for
7. Disengage the auxiliary switch lever from the identification. Refer to Figure 36 for identification
transfer switch crossbar and lift out the auxiliary of auxiliary switch terminals.
switch assembly. 5. Place the plug bracket in position on the base and
secure with round head machine screws (4).
Use care when disengaging Tighten to 25 to 30 in-lbs (2.8 t o 3.4 Nom) torque.
swifch lever from crossbar to 6. Place red plastic switch cover in position and
avoid cracking fhe swifch lever. secure with machine screws (4) and flat washers
4
8. Remove the round head machine screws, flat (4). Tighten to 25 to 30 in-lbs (2.8 to 3.4 Nom)
washers, and nuts that secure the auxiliary torque.
switches to the bracket (see Figure 36); and lift 7. Insert the actuator rod into the replacement actu-
out the three auxiliary switches, insulating barri- ator motor (see Figure 32). Hold the actuator
ers, and switch lever. ground brush up slightly to allow passage of the
actuator rod.
Replacing Auxiliary Switch Assembly 8. Secure the rod end assemblies to theactuator rod
with hex head capscrews (2) and lock washers
(2). Tighten capscrews to 10 t o 12 ft-lbs (13.6 to
1. Place the auxiliary switch lever in the brfcket as 16.3 Nom) torque.
shown in Figure 36. , '..
4
64
Redistribution or publication of this document
by any means, is strictly prohibited.
LINEAR ACTUATOR 5. Pry the capacitor(s) loose from the bracket. Remove
REMOVAL AND REPLACEMENT the end cap and disconnect the red and white actu-
(400-600 Amperes Spec F)- ator lead wires from the capacitor terminals.
6. Disconnect the black actuator lead from the circuit
breaker and the ground wire from the end of the
Disconnect both the normal and the emergency power actuator.
source from the transfer switch before servicing. If a 7. Removethe hex head capscrews,flat washers, lock
generator provides standby emergency power, turn the washers, and nuts that secure the actuator to the
+ operation selector switch to STOP, and disconnect the switch assemblies (see Figure 37).
negative battery cable from the starting battery. The
selector switch is located on the generator set control 8. Disengagethe actuator rod from the switch handle
panel for two-wire start systems and on the transfer and remove actuator from switch assembly.
switch control for three-wire start systems. 9. Remove one of the hex head capscrews and lock
washers that secure the rod end assemblies to the
High voltages within the cabinet end of the actuator rod.
present an electrical shock hazard 10. Remove rod end assembly (Figure 38) and slide
that can cause severe personal injury or death. Dis- actuator rod out of the actuator motor.
connect all sources of AC power from fhe transfer
switch before servicing. Replacing Actuator
The following procedures cover the removal and 1. Insert the actuator rod into the replacement actuator
replacement of the linear actuator. motor (see Figure. 38). Hold the actuator ground
brush up slightly to allow passage of the actuator
Removing Actuator rod. Install the rod end assembly and tighten caps-
crew 10 to 12 ft. Ib. (13.6 to 16.3 Nom).
1. Open the transfer switch cabinet door and unplug
2. Hold actuator motor in position over the switch
the three control wiring harness plugs (Jl, J2, and
assemblies so the lead wires are at the bottom; and
J3 - refer to Figure 37) from the front cover.
fit the rod assembly into the handle of the closed
2. Loosen and remove the ET machine screws that switch assembly.
' secure the red plastic switch cover to the transfer
switch; and lift off cover. 3. Secure the actuator motor to the switch assemblies
using hex head capscrews (4), lock washers (4),flat
3. Separate the actuator lead wiresfrom the rest of the washers (4), and spacers (4). Tighten capscrews 70
wiring harness; remove wire ties as required. to 75 in. Ib. (7.9 to 8.5 Nom).
4. Remove the four ET screws (two on top and two on
bottom) from the plug bracket. Do not pull bracket
from transfer switch, but allow to hang loose. See
Figure 37.
LOAD COVER
ET SCREW
AND LOCK @ ET SCREW
WASHER AND FLAT WASHER
/ @ ET
+
r-
CREW.
CAPACITOR +
0
5/16 SCREW
AND LOCK WASHER
TOGGLE
SWITCH
@
A
r 1
- ACTUATOR
BARRIER
-
PCUG
BRACKET
BASE GND
I
ET SCREW
FLLT 0
WASHER
TORQUES
s1
p?) M1
GND
*
@ 10-15 IN. LB (1.1-1.7 Nom)
xsc 1473
II
I ACTUATOR
ROD
I
7;
WHITE
\
\
HEX'HEAD
CAPSCREW
WITH LOCK
WASHER
BLACK
\
RED
xsc 1474
4. Connect the black actuator lead wire to the circuit emergency power sources. If a generator set is
breaker; and the red and white actuator lead wires the emergency power source, connect the nega-
to the following capacitor terminals: tive battery cable to the starting battery, and
place the operation selector switch in automatic
White Lead Wire - Connect to capacitor C1-I for or remote position.
switch with One capacitors Or 11. Test switch for proper operation and close
connect to capacitor C2-2 for cabinet.
switch with two capacitors.
I I
AUXILIARY SWITCH JUMPER ACTUATOR
XSC 1475
TORQUES
@ 25-30 IN. LB (2.8-3.4 N m )
I
LINE
\
INSULATOR
STANDOFF
XSC 1476
STRAP .^
PLACE A THIN COAT OF ELECTRICAL
JOINT COMPOUND BETWEEN CURRENT
CARRYING SURFACES
L Q
N ~ C s7 ~ ~COM
A SEALANT
PLACE A THIN COAT OF THREAD
TOTHREADSOF SCREW.THEN
TYPICAL TERMINAL TYPICAL TERMINAL TIGHTEN TO GIVEN TORQUE
IDENTIFICATION IDENTIFICATION
VIEW A-A VIEW B - B
69
Redistribution or publication of this document
by any means, is strictly prohibited.
400-600 AMP MODEL (SPEC F)
--I&
SECTION 0-0
xsc 1477
Removing Switch Assembly 8. Remove the hex head capscrews, lock washers,
(Normal or Emergency) and flat washers that secure the jumper straps to
the switch assemblies; and lift off the jumper
1. Remove the linear actuator as described in Linear straps.
Actuator Removal and Replacement section of 9. Remove the four screws, lock washers, and flat
this supplement. Follow steps 1 through 10 in the washers that secure the switch assembly to the
Removing Actuator Section. base; and lift off the switch assembly.
2. Remove the hex head capscrews, lock washers, Use care when removing the
and flat washers that secure the interlock bar to the
interlock arm (Figures 39 and 40); and remove the
kirom
%%! the
l! base. Careiully
block and cross-bar assembly
disengage the crossbar
interlock bar. irom the'auxiliary switch lever to avoid cracking
3. Disconnect the control wiring from the jumper the switch lever.
bus bars. 10. Remove the hex head capscrew and lock washer
4. Remove the round head shoulder screws and that secures the interlock arm assembly to the
lock washers that secure the handle assembly to switch.
theswitch assembly; and lift off handle assembly. 11. Remove the four screws and arc chute cover from
5. Remove the control wiring leads from the power the switch assembly (Figure 41). Then remove the
source terminals (Figures 39 and 40). arc chutes.
6. On front connect switches, loosen the lug termi-
nal screws and remove the power supply wires
from the lug terminals. Then remove the solder-
less lugs from the switch assemblies.
On rear connect switches, Remove the hex head Replacing Switch Assembly
capscrews, lock washers, and flat washers which (Normal or Emergency)
secure the line straps to the switch assemblies.
You can loosen the line strap.from the insulator 1. Install the arc chutes in the switch assembly, put
standoff to enable switch removal without com- on the arc chute cover, and secure with the pan
plete removal of the line strap if you want; or you head screws. Tighten 10 t o 15 in. Ib (1.1 to 1.7
can remove the line strap completely. Nom).
7. Remove the hex head capscrews, ring terminals; 2. Apply thread sealant to the threads of the interlock
spring washers, flat washers, lock washers, and arm capscrews. Mount the interlock arm on the
nuts that secure the jumper strap to the load switch assembly using torques as shown in Figure
strap. 39 or 40.
INSULATING BARRIER
AUXILIARY
SWITCH LEVER
IN CLOSED POSITION
______- --------
-
1 ORIENTATE TERMINALS ON S3 AND S6 AS SHOWN
N/O
NORMAL
m
a I
/\A A
B B
xsc 1478
FIGURE 42. AUXILIARY SWITCHES
All reference points in the Power Sentry control are preceded by “P.S.” For example, “P.S. TB2-3” refers to terminal 3 Of
terminal block 2 on the (Al) Power Sentry control.
1- Improper operation oithe generator set presents a hazard that can cause severepersonal injury or
death. Observe all saiety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
Improper operation of the generator set presents a hazard that can cause severe personal injury or
@%@!@I
death. Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
Improper operation of the generator set presents a hazard that can cause severe personal injury or
1- death. Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side ofthe cabinet doorpresent a shock hazard that
[AWARNINGI can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
Improper operationof the generator set presents a hazard that can cause severe personal injury or
laWAR"Gl death. Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
a
@ @ can!@ &I
cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
Improper operationof the generator set presents a hazard that can cause severepersonalinjury or
@!@!@
death.IObserve all safety precautions in your generafor set manuals.
[AWARNINGI High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
.
Section II: 3-Phase Transfer Switch (Continued) ,
Generator Set Starts During a Power Failure
But Transfer Doesn’t Take Place
Yes No
. .
Improper operationofthe generator set presents a hazard that can cause severe personalinjury or
@@!!!&death. I Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet doorpresent a shock hazard that
@ !@ !& I
can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
Improper operation of the generator set presents a hazard that can cause severepersonalinjury or
death. Observe all saiety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
2 X
4 3
3. Check leads between generator set and transfer siwtch. X X
~ 4. Will engine crank if TBl-3 is grounded? 6 5'
5. A. Check K l l - 1 and 7; contact should be closed. X X
B. Check jumper on TB10-5 to 6 or operation of preheat relay K12. X X
C. Check K10-3 and 6; contact must be closed. . x- X
6. Will the engine crank if TB1-3 and 4 are jumpered? 8 7
7. Check for continuity to ground from TB1-4 through S13-1 and 2. X X
8. Is P.S. K3 de-energized? 9 10
9. A. Check for continuity from TB1-3 through P.S. J5, P5-1
through P.S. J6, P 6-9 to P.S. K3 socket position 1 and 2. X X
B. Check for continuity from TB1-4 through P.S. J5, P5-2 X X
through J6, P6-3 to P.S. K3 socket positions 9 and 10. X X
10. Is 12 VDC available at P.S. J2-13 to ground? 12 11
11. Replace mother board. X X
12. Is 12 VDC available at P.S. 52-5 to ground? 14 13
13. Try new time delay card. -X X
14. Is 40 VAC available at P.S. TB1 - 3x1 to LS? 15 16
15. Check operation of S12-5 and 6 contacts using key switch. X X
16. Is 40 VDC (single phase) 50 VDC (three phase) available at P.S. J1-14? 18 17
17. Try new line side voltage sensor. X X
18. Replace mother board. X X
Improper operation of the generator set presents a hazard that can cause severepersonalinjury or
@!%@%I
death. Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
Improper operation of the generator setpresents a hazard that can cause severepersonalinjury or
death. Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
lcontacts
aWAR"G1 can cause severe personal injury or death. Use extreme caution to avoid touching electrical
when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No
30. Check diodes CR10, CRl 1, and CR12 on mother board 300-21 09. X X
Check diodes CR2, CR3, and CR6 on mother board 300-2936. X X
31. Check T2 transformer. X X
32. Is approximately 30 VDC available at P.S. K2 - 4 to 5? 49 33
33. Is diode across coil shorted? X 34
34. Is approximately 30 VDC available at P.S.K2 - 4 to ground? 40 35
35. Is approximately 40 VDC available at P.S. TB2 - 1x1 to 1x2? 26 36
36. Is line to line voltage available at P.S. TB4 - 2 to 3? 48 37
37. A. Check connections at P.S. K12-9 and P.S.K12-3. X X
B. Check pins 11 and 13 in P.S. J4, P4 and J3, P3. X X
C. Check switch S6 (40,70,100 amp) I S 5 (above 100 amp) and connection at TB2-9. X - x
38. Check transformer T3. X X
39. Check pins 10 and 13 in P.S. J4, P4. X X
40. Is approximately 24 VDC available at P.S. K1-2 to ground? 42 41
41. Check lead from P.S.K2-5 to P.S. K1-2. X X
42. Is approximately 24 VDC available at P.S. K1-1 to ground? 44 43
43. Check P.S.'Kl auxiliary switch. X X
44. Is approximately 12 VDC available at P.S. J2-12 to ground? 26 45
45. Try new time delay board. X X
46. Calibrate and/or try new generator side voltage sensor. X X
47. A. Check pins 10 and 13 in P.S. J4, P4. X X
B. Check for proper jumpers on P.S. TB4. X X
48. Check T1 transformer. X X
49. Is K2 energized? 51 50
50. Try new K1, K2 reversing contactor. x X
Improper operation of the generator setpresents a hazard that can cause severe personalinjury or
1- death. Observe all safety precautions in your generator set manuals.
High voltages within the cabinet and the rear side of the cabinet door present a shock hazard that
c
k%@%l can cause severe personal injury or death. Use extreme caution to avoid touching electrical
contacts when the cabinet door is open. Remove all power sources before removing and replacing components.
Yes No