You are on page 1of 191

I-Line™ Circuit Breaker

Panelboards
Catalog
2110CT9701R02/16
2016
Class 2110

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
General and Application Information . . . . . . . . . . . . . . . . . . . . . . . Page 8
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13


I-Line™ Circuit Breaker Panelboards
Product Description

Product Description

Square D™-brand I-Line™ circuit breaker power distribution panelboards


are for use on AC or DC systems. The panels, labeled cULus (compliance
to UL and CSA standards certified by UL) are also Underwriters
Laboratories® (UL®) Listed under File E33139. The following are suitable for
use as service entrance equipment:
• All main circuit breaker panelboards.
• All main lugs panelboards with branch-mounted, back-fed main
circuit breaker. (For Canadian MLO service entrance, use HCP-SU and
HCR-U only).
• All main lugs panelboards with six disconnects or less.
• A solid neutral that is insulated, but may be bonded to the box with a
grounding strap.
• Service entrance panelboards meeting the requirements of CSA are
available in Canada factory-assembled only.
I-Line circuit breaker panelboards are available as 400–1200 A main lugs
only and 100–1200 A main circuit breakers. I-Line panelboards are
designed to accept the following circuit breakers: FA, FH, BD, BG, BJ, BK,
HD, HG, HJ, HL, HR, QB, QD, QG, QJ, JD, JG, JJ, JL, JR, LA, LD, LG, LJ,
LH, LL, LR, MG, MJ, PG, PJ, PK, PL, RG, RJ, RK, and RL.

Standards

I-Line circuit breaker panelboards are designed, manufactured, and tested


Type HCR-U—1200 A Main Circuit Beaker to comply with the following standards:

Standard Description
UL 50 Standard for enclosures for electrical equipment
UL 67 Standard for panelboards
CSA C22.2, Nos. 29 and 94—1989 Standard for panelboards and enclosed panelboards
NFPA 70 National Electrical Code (NEC)
NEMA PB 1 Standard for panelboards
W–P 115C Type 1 Class 1 Specification for circuit breaker panelboards
2000 IBC US standard for seismic requirements
1995 NBCC Canadian standard for seismic requirements

Service

I-Line circuit breaker panelboards can be used on the following


system voltages:
• 120/240 VAC; 1-phase, 3-wire
• 240 VAC; 1-phase, 2-wire
• 240 VAC; 3-phase, 3-wire
• 240 VAC Ground, B-phase; 3-phase, 3-wire
• 208Y/120 VAC; 3-phase, 4-wire
• 480Y/277 VAC; 3-phase, 4-wire
• 480 VAC; 3-phase, 3-wire
• 600Y/347 VAC; 3-phase, 4-wire
Type HCR-U—1200 A Main Circuit Beaker • 600 VAC; 3-phase, 3-wire
• 125/250 VDC; 3-wire
• 250 VDC; 2-wire
2
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Product Description

Panelboard Types

Maximum
Maximum Mains Branch Circuit Enclosure
Ampacity Breaker Frame Dimensions b
Panelboard Size a
Type
Main
Width Depth
Main Lugs Circuit Left Right
IN (mm) IN (mm)
Breakers
8.25 (210)/
HCM 800 A 800 A JD JD 32 (813)
9.50 (241)
HCP-SU 800 A 800 A c MG, PG None 26 (600) 9.50 (241)
HCP 1200 A 800 A c MG, PG JD 42 (1067) 9.50 (241)
HCR-U 1200 A 1200 A c RG JD 44 (1118) 9.50 (241)
a For a complete listing of applicable circuit breaker types, refer to the dimensions section.
b Refer to the Dimensions section for standard panelboard heights.
c Available as a main circuit breaker panelboard when provided with a branch mounted back-fed
main circuit breaker.

Type HCP—600 A Main Circuit Breaker

Type HCP-SU
800 A Main Circuit Beaker Type HCM—400 A Main Lugs

3
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Product Description

Enclosure Types

Types Environments Provides Protection Against


Type 1 Indoor Contact with the enclosed equipment
Type 2 Indoor Falling water and dirt
Type 3R Outdoor Falling rain, sleet; undamaged by ice
Type 4/4X Stainless Indoor/Outdoor Corrosion, hose-directed water, dust
Type 5 Indoor Settling dust, falling dirt, dripping liquids
Type 12 Indoor Circulating dust, falling dirt, dripping liquids

HCM, HCP, HCP-SU, and HCR-U surface and flush trims available as
four-piece construction, standard (door not included). An optional four-
piece trim with door is also available.
Fronts:
Finished with gray-baked enamel electrodeposited over cleaned
Type 1 phosphatized steel (ANSI 49).
Enclosures
Directory card holders provided with all fronts.
Types 1 and 2 Enclosure with Optional Door Galvanized steel in 26, 32, 42, and 44-inch (660, 813, 1067, and 1118
Boxes: mm) widths.
Removable endwalls without knockouts.
Gasketed door with vault handle and directory card holder.
Three-point latching.

Type 3R, 5, End and side gutter trim.


and 12 No knockouts.
Enclosures
Removable drain screw for Type 3R.
Finished with gray-baked enamel electrodeposited over cleaned phosphatized
steel (ANSI 49).
Flush Lock used on Sliding Vault Lock used on
HCM, and HCP-SU Types HCP, and HCR-U Types 1 Corrosion-resistant, stainless steel.
Type 4X
1 and 2 Fronts and 2 Fronts Enclosures Watertight and dusttight.
(Catalog No. PK4FL) (Catalog No. PK5FL) (Factory-
Assembled Gasketed door.
Only)
Directory card located on inside of door.

Vault Handle used on all


Type 3R, 5, and 12 Enclosures
Type 3R, 5, and 12 Enclosures (Catalog No. PK4NVL)

Type 3R, 5, and 12 Enclosures

4
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Product Description

Main Breaker Panelboards

• Accept a maximum 1200 A, 80% or 100% rated main breaker.


• Available factory-assembled or merchandised.*
• Factory-assembled main circuit breaker interiors are available
bottom-feed or top-feed.
• Suitable for use as service entrance equipment with appropriate
barriers, US and Canada.
• Accepts mechanically restrained I-Line circuit breakers.
• Available with a short circuit current rating (SCCR) up to 200 kA
maximum (100 kA @ 600 VAC) when supplied by an I-Limiter™
circuit breaker.
• Available with a silver-plated or tin-plated copper bus, or tin-plated
Main Circuit Breaker and Solid Neutral Compartment aluminum bus.
(Canada service entrance not shown)
• Solid neutral is mounted in the mains compartment with the main
circuit breaker.
• Merchandised panelboards are provided as bottom-feed.

Main Lugs Only Panelboards

• Available with main lug only interiors rated up to 1200 A.


• Available factory-assembled or merchandised.
• Suitable for use as service entrance equipment when provided with a
main circuit breaker, US and Canada.
• Accepts mechanically restrained I-Line circuit breakers.
• Available with a short circuit current rating (SCCR) up to 200 kA
Main Lug and Solid Neutral Compartment
maximum (100 kA @ 600 VAC) when supplied by an I-Limiter circuit
breaker.
• Available with a silver-plated or tin-plated copper bus, or tin-plated
aluminum bus.
• Solid neutral is mounted in the mains compartment with the main lugs.
• Hinged cover, isolated main lugs compartment.
Main neutral lug • Main lug interiors are available as top-feed or bottom-feed.

Solid Neutral

Full capacity bonding • Mounts in main lug or main circuit breaker compartment.
strap for use on service
entrance applications • Does not take up interior circuit breaker mounting space.
• UL/CSA Listed for use with Al or Cu conductors.
• Copper or aluminum neutral available.
Typical Solid Neutral
• 200% rated neutral available as a factory-assembled option.

Neutral with C/T for Use on HCR-U When Ground-Fault


Protection is Required (Catalog No. HCR12SNCT)

5
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Features and Benefits

Features and Benefits

Featured below are just a few of the many features and benefits of
Square D™-brand I-Line™ circuit breaker panelboards.

Circuit Breakers

I-Line circuit breakers, with their exclusive bus connection design, provide
superior reliability and performance advantages.

Circuit Breaker Mounting

• 15–1200 A frame circuit breakers require only a screwdriver and are


firmly attached to the bus stack and mechanically attached to the interior
assembly.
• The connectors are an integral part of the I-Line circuit breaker—
eliminating the assembly of connectors to the bus bar.
• Pre-assembled hardware means reduced installation time.
• The unique line side connection requires no routine maintenance.
Bus phase insulators interlock
with the circuit breaker
Steel channels provide insulating shroud and provide
additional support for insulator high dielectric strength
bracing structure. between the bus bars.
Circuit breakers on right-
hand side of the bus
structure are completely
Ratchet-Type Mounting independent of position
and frame size of those
on left-hand side.

Circuit breaker
mounting
bracket—an
integral part of
each circuit
breaker; securely
supports and
aligns load end of
circuit breaker.

Insulating shroud keys Glass-reinforced


Circuit breaker connectors are
into slots in bus polyester insulators
shrouded and braced in molded
support base. Aligns provide continuous
protective insulator. Circuit breaker
and supports line end bus bar support.
jaws are lubricated and pre-set at the
of circuit breaker.
factory and require no adjustment.

I-Line Bus Structure and Circuit Breaker Mounting

Push-to-Trip

Push-to-trip is a standard feature on all I-Line circuit breakers. It is useful for


checking circuit breaker operation and for testing auxiliary devices. The
circuit breaker is mechanically tripped by pressing the push-to-trip button in
the circuit breaker case.

Blow-On Connections

All circuit breaker connections are “blow-on” type. Under high-level short
Blow-On Connections circuit conditions, the magnetic forces developed tend to draw the connector
jaws together, gripping the I-Line bus bar more firmly.

6
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Accessories

Short Circuit Current Rating (SCCR)

• SCCR is equal to the lowest interrupting capacity of a branch or main


circuit breaker installed in the panelboard.
• I-Line panelboards, with branch circuit breakers installed, are
short-circuit tested as complete units.
• All tests are conducted in accordance with UL 67 and CSA C22.2
(Standards for Panelboards).
With I-Limiter main circuit breaker, I-Line main circuit breaker panelboards
are UL/CSA Listed for use on systems with up to a 200,000 maximum RMS
symmetrical amperes available fault current (100 kA @ 600 VAC).

I-Line Plug-on Unit with Surgelogic™ SPD

• SPD requires no wiring or conduit, saving labor time and materials.


• Bus-connected design enhances performance.
• Meets the requirements of UL and CSA for retrofit applications in
existing I-Line panelboards and switchboards.
• Integrated and circuit breaker disconnects feature compact design,
requiring only 13.50 inches (343 mm) of branch mounting space.
• SCCR up to 200 kA rating (100 kA @ 600 VAC) meets a wide variety of
customer applications.

Accessories
I-Line Plug-On Unit with Surgelogic TVSS
A wide variety of accessories are available for field or factory installation of
I-Line panelboards.

Equipment Ground Bars

Equipment ground bars mount in the panelboard box to provide convenient


termination of equipment grounding conductors. They are available in
Equipment Ground Bar (Catalog No. PK32DGTA) copper or aluminum.

Box Extensions

Box extensions provide additional end gutter for feeding cables into the end
of the cabinet; they are UL/CSA Listed.

Blank Fillers

Typical Box Extensions Blank fillers are required to cover unused mounting space in I-Line
panelboards.

Backfed Main Breaker Barriers

Primarily for use in Canada, these barriers provide additional protection for
backfed main breakers.

Blank Fillers (Catalog Nos. HNM4BL and HNM1BL)

7
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
General and Application Information

General and Application Information

Please refer to Digest Section 9 for circuit breaker ratings information.

UL/CSA Interrupting Rating—RMS Amperes (Symmetrical)


Maximum Cont.
Circuit Breaker Number of
Voltage Ampere AC Volts, 50/60 Hz DC Volts
Frame Type Poles
Rating Rating
120 240 480 600 125 250
2
FA 240 V 240 15–100 10 K 25 K — — — 5K
3
277 1 35–100
FA 480 V 2 25 K 25 K 18 K — 10 K 10 K
480 15–100
3
277 1 15–30 65 K c
65 K 25 K — 10 K —
FH a 35–100 25 K c
600 2, 3
15–100 — — — 18 K — 50 K
BD 600 Y 1, 2, 3 15–125 25 K 25 K 18 K 14 K — —
BG 600 Y 1, 2, 3 15–125 65 K 65 K 35 K 18 K — —
BJ 600 Y 1, 2, 3 15–125 100 K 100 K 65 K 25 K — —
BK 600 Y 1, 2 15–30 100 K 100 K 65 K 65 K — —
HD 600 2, 3 15–150 25 K 25 K 18 K 14 K 20 K 20 K
HG 600 2, 3 15–150 65 K 65 K 35 K 18 K 20 K 20 K
HJ 600 2, 3 15–150 100 K 100 K 65 K 25 K 20 K 20 K
HL 600 2, 3 15–150 125 K 125 K 100 K 50 K 20 K 20 K
HR 600 3 15–150 200 K 200 K 200 K 100 K — —
QB 240 2, 3 70–225 10 K 10 K — — — —
QD 240 2, 3 70–225 25 K 25 K — — — —
QG 240 2, 3 70–225 65 K 65 K — — — —
QJ e 240 2, 3 70–225 100 K 100 K — — — —
JD 600 2, 3 150–250 25 K 25 K 18 K 14 K 20 K 20 K
JG 600 2, 3 150–250 65 K 65 K 35 K 18 K 20 K 20 K
JJ 600 2, 3 150–250 100 K 100 K 65 K 25 K 20 K 20 K
JL 600 2, 3 150–250 125 K 125 K 100 K 50 K 20 K 20 K
JR 600 2, 3 150–250 200 K 200 K 200 K 100 K — —
LA 600 2, 3 125–400 42 K 42 K 30 K 22 K 10 K 10 K
LH a 600 2, 3 125–400 65 K 65 K 35 K 25 K — 50 K
LD 600 2, 3 250–600 25 K 25 K 18 K 14 K — —
LG 600 2, 3 250–600 65 K 65 K 35 K 18 K — 20 K
LJ 600 2, 3 250–600 100 K 100 K 65 K 25 K — —
LL 600 2, 3 250–600 125 K 125 K 100 K 50 K — 20 K
LR 600 2, 3 250–600 200 K 200 K 200 K 100 K — —
MG 600 2, 3 300–800 65 K 65 K 35 K 18 K — —
MJ 600 2, 3 300–800 100 K 100 K 65 K 25 K — —
PG 600 2, 3 600–1200 65 K 65 K 35 K 18 K — —
PJ 600 2, 3 600–1200 100 K 100 K 65 K 25 K — —
PK d 600 2, 3 600–1200 65 K 65 K 50 K 50 K — —
PL 480 2, 3 600–1200 125 K 125 K 100 K 25 K — —
Continued on next page

8
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
General and Application Information

UL/CSA Interrupting Rating—RMS Amperes (Symmetrical)


Maximum Cont.
Circuit Breaker Number of
Voltage Ampere AC Volts, 50/60 Hz DC Volts
Frame Type Poles
Rating Rating
120 240 480 600 125 250
RG 600 2, 3 1000–1200 65 K 65 K 35 K 18 K — —
RJ 600 2, 3 1000–1200 100 K 100 K 65 K 25 K — —
RK d 600 2, 3 1000–1200 65 K 65 K 65 K 65 K — —
RL 600 2, 3 1000–1200 125 K 125 K 100 K 50 K — —
‡ 15 and 20 A are Switching Duty rated (SWD).
c 277 VAC rated.
a Separate UL rating available for 240 V and 480 V grounded B phase systems. Circuit breakers must be ordered with 5861 suffix.
c FG and FJ 600Y/347 VAC @ 15–30 A only.
d Canada Only.
e QJ 3-pole is rated 100 KA@208Y/120 VAC.

Circuit Breaker Terminal Data

Circuit Breaker Frame Size Ampere Rating Terminal Lug Wire Size
FA 100 A 15–30 #14-#4 Cu or #12-#4 Al
FA 100 A 35–100 #14-1/0 Cu or #12-1/0 Al
FH 100 A 15–30 #14-#4 Cu or #12-#4 Al
FH 100 A 35–100 #14-1/0 Cu or #12-1/0 Al
BD, BG, BJ 125 A 15–125 #14–2/0 Al/Cu
BK 125 A 15–30 #14–2/0 Al/Cu
HD, HG, HJ, HL, HR 150 A 15–150 #14-3/0 Al/Cu
QB, QB, QG, QJ 225 A 70–225 #4-300 kcmil Al/Cu
JD, JG, JJ, JL 250 A 150–175 #4/0 Al/Cu
JD, JG, JJ, JL, JR 250 A 200–250 #3/0-350 kcmil Al/Cu
(1) #1-600 kcmil or
LA, LH 400 A 125–400
(2) #1-250 kcmil Al/Cu
LD, LG, LJ, LL, LR 400 A 250 (1) #2-600 kcmil CU or (1) #2-500 kcmil AL
LD, LG, LJ, LL, LR 600 A 400–600 (2) #2-500kcmil AL/CU
MG, MJ 800 A 300–800 (3) 3/0-500 kcmil Al/Cu
PG, PJ, PKd, PL 1200 A 250–800 (3) 3/0-500 kcmil Al/Cu
PG, PJ, PKd, PL 1200 A 1000–1200 (4) 3/0-500 kcmil Al/Cu
RG, RJ, RKd, RL 1200 A 1000–1200 (4) 3/0-600 kcmil Al/Cu
NOTE: Lugs are rated for 75 °C wire, except FA (15–30 A) and FI (20–30 A), which are rated for 60/75 °C. Torque values are listed
on the circuit breaker faceplate tables.
d Canada only.

Circuit Breaker Accessories

• Shunt trip
• Undervoltage trip
• Alarm switch
• Auxiliary contacts
• Ground-fault shunt trip

9
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
General and Application Information
NOTE: All accessories, except for the Ground-fault shunt trip are
field-installable for LA, LH circuit breakers.
For detailed information on circuit breakers and accessories, refer to the
Digest.

Circuit Breaker Class


HD, HG, HJ, HL 611
QB, QD, QG, QJ 734
JD, JG, JJ, JL 611
LA, LH 660
MG, MJ 612
A PG, PJ, PKd, PL 612
00
12
RG, RJ, RKd, RL 612
d Canada only.
0A
80
Plug-On Lugs Terminal Data
0A
40
5A Catalog
22
Amperage Rating Frame Size Terminal Lug Wire Size
No.

Plug-On Lugs 250 A 250 A SL250 (1) #4-300 kcmil Al/Cu


(1) #1-600 kcmil Al/Cu or
400 A 400 A SL400
(2) #1-250 kcmil Al/Cu
800 A 800 A SL800M5 (3) 3/0 AWG-500 kcmil
1200 A 1200 A SL1200P5 (4) 3/0 AWG-500 kcmil
1200 A 1200 A SL1200P6 (3) 350-600 kcmil
(3) 3/0 AWG-750 kcmil
1200 A 1200 A SL1200P7
(750 kcmil: Compact Al only)
1200 A ‡ 1200 A S33930 (4) 3/0-600 kcmil Al/Cu
‡ For 100% rated applications (“R” frame breakers).

Plug-On QO™ Distribution Panel (Catalog No. HQO306)

• Six-pole, 240 VAC maximum


• Use with QO, QO-H, QO-VH, QH, and Qwik-Gard™ plug-on circuit
breakers through 30 A. For detailed information, refer to DP Catalog
Class 730 and 910.
1-Pole 2-Pole 3-Pole • Mounts in all I-Line panelboards.
QO with Visi-Trip™ Indicator
QO Distribution Panel Branch Circuit Breakers

Distribution Channel Type Number of Poles & Amperages


1-Pole 10–30 A
10 k AIR, QO 2-Pole 10–30 A
3-Pole 10–30 A
1-Pole 15–30 A ‡
10 k AIR, QO-GFI
2-Pole 15–30 A ‡
1-Pole 15–30 A
Qwik-Gard Circuit Breaker with Ground Fault 22 k AIR, QO-VH 2-Pole 15–30 A
Circuit Interrupter
3-Pole 15–30 A
22 k AIR, QO-VHGFI 1-Pole 15–30 A ‡
1-Pole 15–30 A
65 k AIR, QH 2-Pole 15–30 A
3-Pole 15–30 A
‡ Maximum of three GFI-suffix circuit breakers can be installed.

10
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
General and Application Information

Circuit Breaker Types

BD, BG, BJ, BK


1-, 2-, and 3-Pole; 15–125 A(BK is 15–30 A)

QB, QD, QG, QJ HD, HG, HJ, HL JD, JG, JJ, JL


2- and 3-Pole; 70–225 A 2- and 3-Pole; 15–150 A 2- and 3-Pole; 150–250 A

MG, MJ
2- and 3-Pole; 300–800 A

PG, PJ, PK, PL RG, RJ, RK, RL


2- and 3-Pole; 250–1200 A 2- and 3-Pole; 1000–1200 A

11
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
General and Application Information

Main Lugs and Main Circuit Breaker Ratings and Lug Sizes

Mains Main Lugs Main Circuit Breaker


Ampere Cable Size Per UL/CSA Wire Cable Size Per UL/CSA Wire
Rating Actual Lug Size Actual Lug Size
Bending Space Bending Space

Mechanical Lug Sizes


100 — — (1) #14-1/0 Al/Cu (1) #14-#1 Al/Cu
225 (1) #6-300 kcmil Al/Cu (1) #6-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu
(1) #2-600 kcmil Cu or (1) #1-600 kcmil Al/Cu (1) #1-600 kcmil Cu or
400 (2) #2-600 kcmil Al/Cu
(2) #2-500 kcmil Al/Cu (2) #1-250 kcmil Al/Cu (2) #1-250 kcmil Al/Cu
600 (2) #2-600 kcmil Al/Cu (2) #2-500 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu
800 (4) 3/0-750 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu (4) 3/0-500 kcmil Al/Cu (3) 3/0-500 kcmil Al/Cu
1200 (4) 3/0-750 kcmil Al/Cu (4) 3/0-500 kcmil Al/Cu (4) 3/0-600 kcmil Al/Cu (4) 3/0-500 kcmil Al/Cu

VCEL Lug Sizes c


100 — — (1) #8-1/0 Al/Cu (1) #8-#1 Al/Cu
225 (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu (1) #4-300 kcmil Al/Cu
(1) 2/0-500 kcmil Al/Cu or (1) 2/0-500 kcmil Al/Cu or
(1) 500 kcmil Cu or (1) 500 kcmil Cu or
400 (1) 500-750 kcmil Al or (1) 500-750 kcmil Al or
(1) 500-750 kcmil Al (1) 500-750 kcmil Al
(2) #4-300 kcmil Al/Cu (2) #4-250 kcmil Al/Cu
600 (2) 2/0-500 kcmil Al/Cu (2) 2/0-500 kcmil Al/Cu (2) 2/0-500 kcmil Al/Cu (2) 2/0-500 kcmil Al/Cu
(2) 500 kcmil Cu or (2) 500 kcmil Cu or
800 (3) 2/0-500 kcmil Al/Cu (3) 2/0-500 kcmil Al/Cu
(2) 500-750 kcmil Al (2) 500-750 kcmil Al
(4) 500 kcmil Cu or (4) 500 kcmil Cu or
1200 — —
(4) 500-750 kcmil Al (4) 600 kcmil Al
c Compression lugs vary depending on interior type used; contact your local Schneider Electric sales office for assistance.
NOTE: All lugs are suitable for 75 °C wire. Torque values are included on the neutral diagram.

12
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Dimensions

Type HCM—800 A Maximum Main Lugs


32.00
1.75 813
44 26.38 2.00
51
670

3/8 Dia.

Flush Mounting H + 2.00


51
Surface Mounting H
B H Flush
A Lock

Solid Neutral
When
Required

C
End of
Main Lugs D

E
22.00 8.25 Typical 4-Piece Trim
559 210
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall

Flush Mounting 34.25 S/


870
N
Surface Mounting 32.25 A B C
819 Front Center Rear
Bus Bus Bus

5.00 5.00
127 127 Af
Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, QB, QD, QG, QJ Typical Wiring Diagram
Circuit Breakers
Branch connection phasing is
determined by circuit breaker Typical 4-Piece Trim
INCHES selection. without Optional Door
Dual Dimensions: Millimeters

Catalog Number H A B C D E
Main
Lugs 4-Piece
Ampere Trim 4-Piece Trim
Interior Box in. mm in. mm in. mm in. mm in. mm in. mm
Rating without with Door ‡
Door ‡
HCM14482N b HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 14.43 367 9.30 236
HCM23642N HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 17.93 455 12.80 325
225
HCM32732N HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 17.93 455 12.80 325
HCM50912N HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 17.93 455 12.80 325
HCM14484 b HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 14.90 378 9.30 236
HCM23644 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 18.40 467 12.80 325
400
HCM32734 b HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 18.40 467 12.80 325
HCM50914 HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 18.40 467 12.80 325
Continued on next page

13
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Catalog Number H A B C D E
Main
Lugs 4-Piece
Ampere Trim 4-Piece Trim
Interior Box in. mm in. mm in. mm in. mm in. mm in. mm
Rating without with Door ‡
Door ‡
HCM14486 b HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 16.50 419 9.30 236
HCM23646 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 20.00 508 12.80 325
600
HCM32736 b HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 20.00 508 12.80 325
HCM50916 HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 20.00 508 12.80 325
HCM14488 HC3248B HCM48T( ) HCM48T( )D 48.00 1219 13.50 343 30.00 762 21.85 555 15.32 389 9.30 236
HCM23648 HC3264B HCM64T( ) HCM64T( )D 64.00 1626 22.50 572 39.00 991 29.85 758 18.82 478 12.80 325
800
HCM32738 HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 31.50 800 48.00 1219 22.90 582 18.82 478 12.80 325
HCM50918 HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 49.50 1257 66.00 1676 28.90 734 18.82 478 12.80 325
‡ Replace parentheses with “F” for flush or “S” for surface.
a Two flush locks are supplied.
b Add Cu to suffix for copper bus.

14
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCM—400 A Maximum Main Circuit Breaker


32.00
1.75 813
44 26.38 2.00
51
670

3/8 Dia.

C
A

Flush Mounting H + 2.00


51
Surface Mounting H
B H Flush
Lock
Solid Neutral
When
Required
Service Entrance
Barrier
(Canada only)
End of C
Main Circuit
Breaker Lugs

D
E
22.00 8.25 Typical 4-Piece Trim
559 210
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall

Flush Mounting 34.25 S/


870
N
Surface Mounting 32.25 A B C
819 Front Center Rear
Bus Bus Bus

5.00 5.00
127 127 Af
Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, HR, JD, JG, JJ, JL, JR, QB, QD, QG, QJ Typical Wiring Diagram
KA, KH, QB, QD, QG, QJ, or QO
Circuit Breakers Branch connection phasing is
determined by circuit breaker Typical 4-Piece Trim
selection. without Optional Door
Dual Dimensions: INCHES
Millimeters

Main Catalog Number H A B C D E


Circuit 4-Piece
Breaker Trim 4-Piece Trim
Ampere Interior Box in. mm in. mm in. mm in. mm in. mm in. mm
without with Door ‡
Rating Door ‡
225 HCM18642MN HC3264B HCM64T( ) HCM64T( )D 64.00 1626 18.00 457 39.00 991 29.85 758 15.50 394 12.80 325
225 HCM27732MN b HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 27.00 686 48.00 1219 22.90 582 15.50 394 12.80 325
400 HCM14644M HC3264B HCM64T( ) HCM64T( )D 64.00 1626 13.50 343 39.00 991 29.85 758 16.96 431 12.80 325
400 HCM23734M HC3273B HCM73T( ) HCM73T( )D a 73.00 1854 22.50 572 48.00 1219 22.90 582 16.96 431 12.80 325
400 HCM41914M b HC3291B HCM91T( ) HCM91T( )D a 91.00 2311 40.50 1029 66.00 1676 28.90 734 16.96 431 12.80 325
‡ Replace parentheses with “F” for flush or “S” for surface.
a Two flush locks are supplied.
b Add Cu to suffix for copper bus.

15
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCM—800 A Maximum Main Circuit Breaker


32.00
1.75 813
44 26.38 2.00
51
670

3/8 Dia.

A Flush

Flush Mounting H + 2.00


Lock

51
Surface Mounting H
B H
Solid Neutral
When
Required
Service Entrance
Barrier
(Canada only)
End of C
Main Circuit
Breaker Lugs

D
E
22.00 9.50 Typical 4-Piece Trim
559 241
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall

Flush Mounting 34.25 S/


870
N
Surface Mounting 32.25 A B C
819 Front Center Rear
Bus Bus Bus

5.00 5.00
127 127 Af
Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, HR, , JD, JG, JJ, JL, JR, QB, QD, QG, QJ Typical Wiring Diagram
Circuit Breakers
Branch connection phasing is
determined by circuit breaker
selection.
Dual Dimensions: INCHES
Millimeters
Typical 4-Piece Trim
without Optional Door

Main Catalog Number H A B C D E


Circuit 4-Piece
Breaker 4-Piece
Trim
Ampere Interior Box Trim with in. mm in. mm in. mm in. mm in. mm in. mm
without
Rating Door ‡ a
Door ‡
HCM18736MP HC3273DB9 HCM73T( ) HCM73T( )D 73.00 1854 18.00 457 48.00 1219 22.90 582 18.68 474 12.80 325
600
HCM36916MP HC3291DB9 HCM91T( ) HCM91T( )D 91.00 2311 36.00 914 66.00 1676 28.90 734 18.68 474 12.80 325
HCM18738MP HC3273DB9 HCM73T( ) HCM73T( )D 73.00 1854 18.00 457 48.00 1219 22.90 582 18.68 474 12.80 325
800
HCM36918MP HC3291DB9 HCM91T( ) HCM91T( )D 91.00 2311 36.00 914 66.00 1676 28.90 734 18.68 474 12.80 325
‡ Replace parentheses with “F” for flush or “S” for surface.
a Two flush locks are supplied.

16
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCP—800 A Maximum Main Lugs


42.00
2.00 1067
51 34.38 2.13
54
873
27/64
Dia.
Vault
Lock
C

Flush Mounting H + 2.00


51
Surface Mounting H
A H
Solid
Neutral B
When
Required

End of
Main Lugs
C
D
10.30
262

30.00 9.50 Typical 4-Piece Trim


762 241
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall

Flush Mounting 44.25 S/


N
1124
A B C
Surface Mounting 42.25 Front Center Rear
1073 Bus Bus Bus

8.00 8.00 Af
203 203 Bf
Cf
Typical Mounting of BD, BG, BJ, BK, FA, FH,
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, MG, MJ, Typical Wiring Diagram
PG, PJ, PK, PL, QB, QD, QG, QJ Branch connection phasing is
Circuit Breakers determined by circuit breaker
selection. Typical 4-Piece Trim
without Optional Door
INCHES
Dual Dimensions: Millimeters

Main Catalog Number H A B C D


Lugs 4-Piece Trim 4-Piece
Ampere Interior Box without Door Trim with in. mm in. mm in. mm in. mm in. mm
Rating ‡ Door ‡
HCP14504 HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 17.50 445
HCP23594 HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.35 695 17.50 445
400
HCP32684 HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 17.50 445
HCP50864 HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 17.50 445
HCP14506 HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 17.50 445
HCP23596 HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.35 695 17.50 445
600
HCP32686 HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 17.50 445
HCP50866 HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 17.50 445
HCP14508 HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 16.32 415
HCP23598 HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.35 695 16.32 415
800
HCP32688 HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 16.32 415
HCP50868 HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 16.32 415
‡ Replace parentheses with “F” for flush or “S” for surface.

17
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCP—1200 A Maximum Main Lugs


42.00
2.00 1067
2.13
51 35.47 54
901

27/64 Dia.
Vault
Lock
C

Flush Mounting H + 2.00


51
Surface Mounting H
A
H
Solid
Neutral B
When
Required

End of
Main Lugs
C

D
10.30
262

30.00 9.50 Typical 4-Piece Trim


762 241
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall

Flush Mounting 44.25 S/


N
1124
A B C
Surface Mounting 42.25 Front Center Rear
1073 Bus Bus Bus

10.35 5.41 Af
263 137 Bf
Cf

Typical Mounting of BD, BG, BJ, BK, FA, FH,


HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Typical Wiring Diagram
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ Branch connection phasing is
Circuit Breakers determined by circuit breaker
selection.
Typical 4-Piece Trim
without Optional Door

Dual Dimensions: INCHES


Millimeters

Main Catalog Number H A B C D


Lugs 4-Piece Trim 4-Piece
Ampere Interior Box without Door Trim with in. mm in. mm in. mm in. mm in. mm
Rating ‡ Door ‡
HCP145012N HC4250DB HCW50T( ) HCW50T( )D 50.00 1270 13.50 343 30.00 762 22.85 580 16.32 415
HCP235912N HC4259DB HCW59T( ) HCW59T( )D 59.00 1499 22.50 572 39.00 991 27.23 692 16.32 415
1200
HCP326812N HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 31.50 800 48.00 1219 31.85 809 16.32 415
HCP508612N HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 49.50 1257 66.00 1676 27.23 692 16.32 415
‡ Replace parentheses with “F” for flush or “S” for surface.

18
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCP—800 A Maximum Main Circuit Breaker


42.00
2.00 1067
2.13
51 34.38 54
873
27/64 Dia.

Vault
C Lock

Flush Mounting H + 2.00


A

51
Surface Mounting H
Solid H
Neutral
When B
Required
Service Entrance
Barrier
(Canada only)
End of
Main Circuit
Breaker Lugs
C

10.30 D
262

30.00 9.50
762
241
Typical 4-Piece Trim
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall

Flush Mounting 44.25 S/


N
1124
A B C
Surface Mounting 42.25 Front Center Rear
1073 Bus Bus Bus

8.00 8.30 Af
203 211 Bf
Cf

Typical Mounting of BD, BG, BJ, BK, FA, FH, Typical Wiring Diagram
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Branch connection phasing is
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ
determined by circuit breaker
Circuit Breakers selection.

INCHES
Dual Dimensions: Millimeters Typical 4-Piece Trim
without Optional Door

Main Catalog Number H A B C D


Circuit
Breaker 4-Piece Trim 4-Piece
Ampere Interior Box without Door Trim with in. mm in. mm in. mm in. mm in. mm
Rating ‡ Door ‡
HCP18686M HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 18.00 457 48.00 1219 31.85 809 18.68 474
600
HCP36866M HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 36.00 914 66.00 1676 27.23 692 18.68 474
HCP18688M HC4268DB HCW68T( ) HCW68T( )D 68.00 1727 18.00 457 48.00 1219 31.85 809 18.68 474
800
HCP36868M HC4286DB HCW86T( ) HCW86T( )D 86.00 2184 36.00 914 66.00 1676 27.23 692 18.68 474
‡Replace parentheses with “F” for flush or “S” for surface.

19
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCP-SU—800 A Maximum Main Circuit Breaker

2.00 .42 Surface


11 2.07 Mounting 26.16
51 53 665

Service Entrance
Barrier
(Canada only) C

Directory
B

A
85.75
Flush 2178
H Lock Surface
Mounting

.25
(6)

1.86 1.86 8.25


210
47 47 2.07 Typical 2-Piece Trim
53
26.16 with Optional Door
665

Typical Box with Interior Typical Box Side View

S/
N
Typical Mounting of BD, BG, BJ, BK, FA, FH, A B C
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Front Center Rear
Bus Bus Bus
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ
Circuit Breakers
Af
Bf
Cf

Dual Dimensions: INCHES


Branch connection phasing is
Millimeters determined by circuit breaker selection.

Typical 2-Piece Trim


without Optional Door

Main Catalog Number H A B C


Circuit
Breaker 2-Piece Trim without 2-Piece Trim with
Ampere Interior Box in. mm in. mm in. mm in. mm
Door ‡ a Door ‡ a
Rating
800 HCP54868SU HC2686DB HC2686T( ) HC2686T( )D 86.00 2184 54.00 1372 65.40 1661 27.23 692
‡ Replace parentheses with “F” for flush or “S” for surface.
a Flush trims are 4-piece.
20
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards
Dimensions

Type HCR-U—1200 A Main Lugs or Main Circuit Breaker


44.25
2.00 1124
2.13
51 40.40 54
1026

Service Entrance C Vault


Barrier Lock
(Cananda only)

Flush Mounting H + 2.00


51
Surface Mounting H
A
27/64 Dia. H
B
Solid
Neutral
When
Required

10.30
262

30.00 9.50 Typical 4-Piece Trim


762 241
with Optional Door
Typical Box with Interior Typical Box Side View

Typical Endwall
S/
Flush Mounting 46.25 N
1175 A B C
Front Center Rear
Surface Mounting 44.25 Bus Bus Bus
1124

Af
11.04 5.25 Bf
280 133 Cf

Typical Mounting of BD, BG, BJ, BK, FA, FH, Typical Wiring Diagram
HD, HG, HJ, HL, JD, JG, JJ, JL, LA, LD, LG, LJ, LL, LR, Branch connection phasing is
MG, MJ, PG, PJ, PK, PL, QB, QD, QG, QJ, RG, RJ, RK, RL determined by circuit breaker
Circuit Breakers selection.

Back-fed PG, PJ, PL, RG


RJ, and RL Main Circuit Typical 4-Piece Trim
Breaker or Main Lugs without Optional Door
Kit S33930
(see Note:)
INCHES
Dual Dimensions: Millimeters

Main Lugs or Catalog Number H A B C


Main Circuit Breaker 4-Piece Trim 4-Piece Trim
Ampere Rating Interior Box in. mm in. mm in. mm in. mm
without Door ‡ with Door ‡
1200 HCR548612U HC4486DB HCR86T( ) HCR86T( )D 86.00 2184 54.00 1372 65.10 1654 18.00 457
‡ Replace parentheses with “F” for flush or “S” for surface.

NOTE: The back-fed RG, RJ, and RL Main Circuit Breaker or Main Lugs Kit takes up 15 in. (381 mm) of mounting space, leaving 93 in. (2362 mm) of branch circuit
breaker mounting space. The back-fed PG, PJ, PL Main Circuit Breaker takes up 9 in. (229 mm) of mounting spaces, leaving 99 in. (2515 mm) of branch circuit
breaker mounting space.

21
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

I-Line™ Circuit Breaker Panelboards

22
02/2016 © 1998–2016 Schneider Electric
All Rights Reserved

I-Line™ Circuit Breaker Panelboards

23
© 1998–2016 Schneider Electric 02/2016
All Rights Reserved

Schneider Electric USA, Inc.
800 Federal Street Schneider Electric and Square D are trademarks owned by Schneider Electric Industries SAS or its
Andover, MA 01810 USA affiliated companies. All other trademarks are the property of their respective owners.
888-778-2733 2110CT9701R02/16 Replaces 2110CT9701R10/04
www.schneider-electric.us © 1998–2016 Schneider Electric All Rights Reserved

02/2016
NF Circuit Breaker Panelboards
Catalog
1670CT0701

2008
Class 1670

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Standards and Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Main Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Branch Circuit Breakers (Bolt-on). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Interiors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Neutrals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ground Bar Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Surge Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Single Row (Column-Width) Panelboards . . . . . . . . . . . . . . . . . . . . . . . . 16
Terminal Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Typical Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NF Circuit Breaker Panelboards
Standards and Ratings

Standards and Ratings


NF circuit breaker panelboards are for use on ac systems. They are
UL® Listed under File E33139 and marked cULus. NF circuit breaker
Voltage System System Diagram
panelboards accept EDB, EGB, and EJB branch circuit breakers.

120/240 Vac 1φ3W

Standards
208Y/120 Vac 3φ4W
NF circuit breaker panelboards are designed, manufactured, and tested to
comply with the following standards:
• UL 67—Standard for Panelboards
• UL 50—Enclosures for Electrical Equipment
3φ4W
240/120 Vac • UL Listed Class CTL panelboard
Delta
• CSA C22.2, No. 29-M1989—Panelboards and Enclosed Panelboards
• CSA C22.2, No. 94-M91—Special Purpose Enclosures
• NEMA PB 1—Panelboards
3φ3W
240 Vac
Delta
• NFPA 70—National Electrical Code® (NEC®)
• Federal Specification W-P-115C Type I Class 1—Circuit
Breaker Panelboards
3φ3W • 2003 IBC, NFPA 5000, ASCE/SE17—Seismic Qualification
240 Vac Grounded Bφ
Delta

480Y/277 Vac 3φ4W

Ratings
600Y/347 Vac 3φ4W
• Main lugs: 125–800 A
• Main circuit breaker: 125–600 A

3
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Main Circuit Breakers
Main Circuit Breakers

• 125 A maximum field-installable EDB, EGB, or EJB (110 A max at 600Y/347 Vac)
• 100 A maximum field-installable FI
• 125 A maximum field-installable HDL, HGL, HJL, or HLL
• 250 A maximum field-installable JDL, JGL, JJL, or JLL
• 400 A maximum field-installable LAL or LHL
• 400 A or 600 A maximum factory-installed LCL or LIL (LCL is 480Y/277 Vac maximum)

HDL
Factory-Installed Circuit Breaker Accessories

FIL, HDL, HGL, HJL, HLL, JDL, JGL, JJL, JLL, and KIL circuit breakers are available with shunt trip,
ground fault shunt trip, undervoltage trip, time delay, auxiliary switches, and alarm switches.

Table 1: Main Circuit Breaker Adapter Kits (Circuit Breaker Not Included)

Adapter Kit Catalog Number Ampere Rating Main Circuit Breaker1


N100MFI 20–100 A FIL
N150MH2 15–125 A3 HDL, HGL, HJL, HLL
N250MJ 150–250 A JDL, JGL, JJL, JLL
N250MKC 110–250 A KIL
N400M 125–400 A LAL, LHL
1
Main circuit breakers are not included in the adapter kits. Order them separately.
2
For single phase applications of HDL and HGL, select a 3-pole main circuit breaker. For
single-phase applications of HJL and HLL, select a 2-pole main circuit breaker.
3
RTI kit accepts maximum 125 A H-frame circuit breaker.

JDL
NOTE: See “Main Circuit Breaker Terminal Data” on page 18.

Field-Installable Circuit Breaker Accessories

Field-installable undervoltage release, alarm switch, shunt trip, and auxiliary contacts are available for
LAL, LHL, LCL, and LIL 400 A main circuit breaker interiors.
NOTE: See Supplemental Digest for additional accessories.

LAL

N250MJ Main Circuit Breaker Kit N400M Main Circuit Breaker Kit

4
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Branch Circuit Breakers (Bolt-on)

Branch Circuit Breakers (Bolt-on)

Table 2: Standard Branches, 600Y/347 Vac Maximum

Branch Availability Short Circuit Current Rating1

Prefix 1-Pole 2-Pole 3-Pole at 480Y/277 Vac at 600Y/347 Vac


EDB 15-70 A 15-125 A2 15-125 A2 18,000 A 14,000 A
EGB 15-70 A 15-125 A2 15-125 A2 35,000 A 18,000 A
EJB 15-70 A 15-125 A2 15-125 A2 65,000 A 25,000 A
1
Series ratings are also available.
In Canada: See Series Rating Guide (Data Bulletin #S1600PD0302EP).
In USA: See Switchboard/Panelboard Short Circuit Current Ratings (Data Bulletin #2700DB9901) or the Digest.
2
600Y/347 Vac is 110 A maximum.

Table 3: EPD Branches – 30 mA Ground Fault Equipment Protection Devices,


277 Vac Maximum

Availability Short Circuit Current Rating2


Branch Prefix
1-Pole1 at 277 Vac
EDB-EPD 15-70A 18,000 A
EGB-EPD 15-70A 35,000 A
EJB-EPD 15-70A 65,000 A
1
EPD branches are single-pole only, and require two pole spaces in the panelboard.
2
Also available with series ratings.

Table 4: Standard and EPD Branches – Terminal Lug Data

Branch Circuit Wire Size


Ampere Rating
Breaker Prefix Aluminum Copper

EDB, EGB, EJB, 15-30 A #12 - #6 #14 - #6


EDB-EPD, EGB-EPD, EJB-EPD 35-125 A #12 - 2/0 #14 – 2/0

EDB Branch Circuit


Breakers

5
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Interiors

Interiors
Main Lug Interiors

• Will accept bolt-on branch circuit breakers


• Top or bottom feed
• 65,000 A Short Circuit Current Rating (SCCR) maximum branch circuit breakers at 480Y/277 Vac
• 25,000 A SCCR maximum branch circuit breakers at 600Y/347 Vac
• Series rated to 200,000 A SCCR maximum when supplied by remote I-Limiter® circuit breaker
at 480Y/277 Vac
• Series rated to 65,000 A SCCR maximum when supplied by remote I-Limiter circuit breaker
at 600Y/347 Vac
• 125 A and 250 A interiors are suitable for use as cULus service entrance with back-fed EDB, EGB,
or EJB circuit breakers
• Factory-installed main lugs on all interiors
• 125–400 A main lug interiors are convertible to main circuit breaker interiors by adding a main
circuit breaker adapter kit and a main circuit breaker
• Several bus options:
— Silver-plated copper or tin-plated aluminum bus (aluminum is standard)
— Tin-plated copper bus is available as an option
250 A Maximum — 600 A and 800 A only available with copper
Main Lugs Interior
(Deadfronts Installed) • Branch connector fingers are tin-plated copper
— Silver-plated branch connector fingers are optional
• Line lugs are suitable for 75o C copper or aluminum wire

Factory-Installed Options for Main Lugs and Main Breaker Interiors

• Sub-Feed Lugs (on the Main)


NOTE: Only available on 1φ or 3φ, 125–800 A main lug interiors
• Feed-Through Lugs
NOTE: Available on 1φ or 3φ, 125–800 A main lug or 100–600 A main circuit breaker interiors
• Sub-Feed Circuit Breakers
NOTE: Available on 1φ or 3φ, 125–800 A main lug or 100–600 A main circuit breaker interiors
— One sub-feed HDL, HGL, HJL, HLL, JDL, JGL, JJL, or JLL circuit breaker per 250 A panelboard
— Two sub-feed HDL, HGL, HJL, HLL, JDL, JGL, JJL, or JLL circuit breakers per 400 A panelboard
— One sub-feed LA, LH, LC, or LI circuit breaker (400 A maximum) and one HDL, HGL, HJL, HLL,
JDL, JGL, JJL, or JLL circuit breaker, or two sub-feed HDL, HGL, HJL, HLL, JDL, JGL, JJL, or
JLL circuit breakers per 600 A or 800 A panelboard
NOTE: LC/LI circuit breakers cannot be combined with JJL or JLL circuit breakers
• Split bus
• Lighting contactors
• Compression lugs

6
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Interiors
Main Circuit Breaker Interiors

• Will accept bolt-on branch circuit breakers


• Suitable for use as UL service entrance (statement found on wiring label on back of deadfront);
meets local electrical codes (CSA type service entrance available factory-assembled)
• Top or bottom feed
• 65 k AIR maximum branch circuit breakers at 480Y/277 Vac
• 25 K AIR maximum branch circuit breakers at 600Y/347 Vac
• Series rated to 200 k AIR maximum when supplied by remote I-Limiter circuit breaker at
480Y/277 Vac
• Series rated to 65 k AIR maximum when supplied by remote I-Limiter circuit breaker at
600Y/347 Vac
• Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard). Tin-plated
copper bus is available as an option; 600 A only available with copper
• Branch connector fingers are tin-plated copper; silver-plated branch connector fingers are optional
• 125 A at 480Y/277 Vac (110 A at 600Y/347 Vac) main circuit breaker interiors contain back-fed
EDB, EGB, or EJB main circuit breakers
• 100–250 A main circuit breaker panelboards consist of:
— Standard main lug interiors
— Main circuit breaker adapter kit (N150MH, N100MFI, N250MKC, N250MJ)
— Appropriate FIL, HDL, HGL, HJL, HLL, JDL, JGL, JJL, JLL, or KIL circuit breakers
— Line lugs are suitable for 75o C copper or aluminum wire
• 400 A main circuit breaker panelboard consists of:
400 A LAL — Standard main lug interior
Main Circuit — Main circuit breaker adapter kit (N400M)
Breaker Interior
— Appropriate LAL or LHL circuit breaker
— Factory-installed LCL or LIL main circuit breaker with 8 in. (203 mm) deep enclosure (Type 1 only)
• 600 A main circuit breaker panelboard:
— Factory-assembled only
— Use LCL, LIL main circuit breakers
— 8.75 in. (223 mm) deep enclosure (Type 1 only)

400 A Main Lugs Interior

400 A LAL Main Circuit Breaker and Adapter Kit

400 A Main Lugs Interior with 400 A Main Circuit Breaker and Adapter Kit
7
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Interiors

Field-Installable Options
• Feed-Through Lug Kits
— NF125FTL, NF250FTL, NF400FTL available for 125–400 A,
1φ or 3φ interiors
• Sub-Feed Circuit Breaker Kits
— NF250SFBH allows a single sub-feed HDL, HGL, HJL, or HLL circuit
breaker on 250 A interiors
— NF250SFBJ allows a single sub-feed JDL, JGL, JJL, or JLL circuit
breaker on 250 A interiors
— NF600SFBH allows twin sub-feed HDL, HGL, HJL OR HLL circuit
breaker on 400 A main lug or main circuit breaker interiors and 600A
main lug interiors
— N600SFBJ allows twin sub-feed JDL, JGL, JJL, or JLL circuit
breakers on 400 A main lug or main circuit breaker interiors and
600 A main lug interiors
• Sub-Feed Lug Kits

Amperes Catalog Number


125 A NF125SFL
250 A NF250SFL
400 A NF400SFL

• 200% Neutral Kits

Amperes Catalog Number


100 A NFNL1
125 A NFNL1
250 A NFNL2
400 A NFNL41

1
400 A Main Lug Interior with Sub-Feed Lugs 200% neutrals not available with FTL, SFL, or SFB.

• Copper 100% Kits

Copper 100% Amperes Copper Neutral Kits Catalog Number


125 A NFN1CU
250 A NFN2CU
400 A NFN6CU
600 A NFN6CU1
1
Not to be used with SFL, FTL, or SFB. These combinations are factory-assembled only.

400 A Sub-Feed Main Lug Kits

Compression Lugs

Compression lugs are available for 125–600 A main lug interiors and
100–400 A main circuit breaker interiors.

Compression Lugs
8
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Neutrals

Neutrals

Neutral Assembly

• All lugs are suitable for copper or aluminum wire


• 125–250 A interiors have a split neutral located on the same end as the mains
• 400–800 A interior neutrals can be located on either end depending on the configuration
• Neutral may be bonded for use as a UL service entrance
• Branch terminals are suitable for #14-2/0 copper or aluminum and #14-#6 copper or aluminum
• Provisions for larger branch terminal lug kits are available as options
• Suitable lug provided on neutrals for termination of the grounding conductor
• All unused neutral terminals may be used to terminate equipment grounding conductors when the
panelboard is used as UL service equipment
• 100% rated neutrals are standard; one neutral termination provided per circuit in the panelboard
• 200% rated neutrals are optional see, “200% Neutral Kits” below

Neutral Bonding Provisions

The bonding strap may be field installed for UL service equipment requirements on 125–800 A
interiors. Not applicable for CSA service entrance panels in Canada.

Table 5: Copper 100% Neutral Kits for Use with Single or Three Phase 125-600 A Interiors

Amperage 125 A 250 A 400 A 600 A 800 A


Kit not available,
Catalog Number NFN1CU NFN2CU NFN6CU NFN6CU1
Factory-assembled only
1
125–250 A Neutral Not to be used with SFL, FTL or SFB. These combinations are factory-assembled only.
Bonding Provisions

200% Neutral Kits

Table 6: 200% Neutral Kits for Use with Single or Three Phase 125-400 A Interiors

Amperage 125 A 250 A 400 A 600 A 800 A


Kit not available,
Catalog Number NFNL1 NFNL2 NFNL41
Factory-assembled only
1
Not to be used with SFL, FTL or SFB. These combinations are factory-assembled only.

NFNL2

9
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Ground Bar Kits

Ground Bar Kits


• Field installable in all panelboards
• Wire size of terminals (refer to the technical information below)

Table 7: Ground Bar Kits

Catalog Number Terminals Material


PK23GTAL 23 AL
PK27GTA 251 CU
PK27GTACU 27 AL
1
24 small terminals and 1 large terminal

• Order enough ground bar kits to accommodate all the ground


conductors used in the panel

Ground Bar Kit


Ground Bar Insulator Kits (Catalog No. PKGTAB)

• The insulator kit isolates the standard panelboard ground bar from
the panelboard
• The insulator kit is field installable, and panelboard enclosures have
ground bar mounting provisions in all four corners

Ground Bar with Insulator Kit


Technical Information

All PK equipment grounding kits are supplied with mounting screws,


installation instructions, and an “Equipment Grounding Terminal”
self-adhesive label.

Table 8: Technical Information

Terminals
Approximate Distance Between
Catalog
Number of Quantity Available for Each Size Overall Length Mounting Holes
Number
Terminals Inches (mm) Inches (mm)
Material I / II1
PK23GTAL 24 AL 23 / 1 9.125 (232) 3.125 (79)
PK27GTA 27 AL 24 / 1 9.125 (232) 3.125 (79)
PK27GTACU 27 CU 27 / 0 9.125 (232) 3.125 (79)
1
See wire range table below.

Table 9: Wire Range

Size Cu Al
I (1) #14 to #4 or (2) #14 or #12 (1) #12 to #4 or (2) #12 or #10
II (1) #1 to 4/0 (1) #1 to 4/0

10
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Surge Protection

Surge Protection
The Surgelogic® IMA series surge protective device is a modular parallel
transient voltage surge suppressor (TVSS). The IMA device is a multi-stage
suppression circuit consisting of field-proven, fast-acting, 34 mm metal oxide
varistors (MOVs).

A surge suppression path is provided for each mode, line-to-neutral (L-N),


line-to-line (L-L), line-to-ground (L-G), and neutral-to-ground (N-G). Each surge
suppression mode is individually fused and uses circuitry with thermal cutouts
to isolate the TVSS and ensure shutdown in the event of MOV damage during
severe overvoltages, even when operated on high fault current power systems.

The suppression elements are encapsulated in a UL recognized potting


material—another performance element that provides additional protection. A
filter provides a high level of EMI/RFI noise attenuation. On-line diagnostics
continuously monitor the device status, and LEDs signal loss of a suppression
circuit. An audible alarm with an enable/disable feature and dry contacts are
included in the standard diagnostic package.

NF Main Lugs Panelboard with Integral TVSS

Table 10: NF Interiors with TVSS1

Max Circuit TVSS Rating Components for Adding a Vertical Main Circuit Breaker
Mains Interior Catalog
Breaker
Rating Voltage Surge Rating Number2 Main Circuit Breaker Kit Main Circuit Breaker Frames
Spaces
120 NF442L2TVS412 N150MH3 HD, HG, HJ or HL
480Y/277 Vac
250 A 42 160 NF442L2TVS416 N250MJ JD, JG, JJ or, JL
600Y/347 Vac 120 NF442L2TVS812 N250MKC KI
120 NF442L4TVS412
480Y/277 Vac LAL/LHL
400 A 42 160 NF442L4TVS416 N400M
(LC and LI F/A only)
600Y/347 Vac 120 NF442L4TVS812
1 These interiors are available as catalog numbered devices. TVSS is not available as a field-installable kit.
2
To order an interior with copper bus, add a “C” to the end of the catalog number (example: NR442L2TVS412C).
3
RTI kit accepts maximum 125 A H-frame circuit breaker.

Table 11: IMA Series Voltage Specifications

UL Suppression Voltage Rating (SVR)


Service Voltage
L–N L–G N–G L–L MCOV 1
120/240 Vac, 1-phase 400 400 400 800 150
208Y/120 Vac, 3-phase, 4-wire 400 400 400 800 150
240/120 Vac, 3-phase, high-leg delta 800/400 800/400 400 1500/800 275/150
480Y/277 Vac, 3-phase, 4-wire 800 800 800 1600 320
600Y/347 Vac, 3-phase, 4-wire 1200 1200 1200 2000 420
1 MCOV: maximum continuous operating voltage.

11
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Surge Protection

Table 12: Performance Features

Surge Capacity L–N L–G N–G (3-Phase Rating)


100 kA / phase 50 kA 50 kA 100 kA
120 kA / phase 60 kA 60 kA 120 kA
200 kA / phase 100 kA 100 kA 200 kA
160 kA / phase 80 kA 80 kA 120 kA
240 kA / phase 120 kA 120 kA 120 kA

Table 13: Specifications


Relative Humidity 0 to 95% non-condensing
Operating Frequency 47–63 Hz
Storage Temperature -40 to +65 °C (-40 to +149 °F)
Operating Temperature -40 to +65 °C (-40 to +149 °F)
Display Operating Temperature -10 to +50 °C (+14 to +122 °F)
C-UL, UL 1449 Second Edition
Standards
UL Category Section 37.3 (200 kA short-circuit current module rating)
Fusing Individually fused suppression modules
Audible Alarm Provides audible indication that there is a loss of protection
Provides remote indication of the TVSS device’s operating status to a computer interface
Dry Contacts
board or emergency management system

Table 14: Other Options

Option Description
Displays the combined total number of transient voltage surges detected from L–G, L–L, L–N,
Surge Counter
and N–G since the counter was last reset.
Displays the alarm status of the surge protective device up to 1,000 ft. (305 m) away from the
Remote Monitor
unit. This option uses the dry contacts.

Design Features

• Individually fused suppression modules


• Thermal cutout
• Inline, copper bus bar connection
• Solid state bi-directional
• Push-to-Test on-line diagnostic display
• Audible alarm with enable/disable switch
• LED indicators indicate loss of protection, or fully operational circuit
• High-energy parallel design for IEEE C62.41 category A, B, and C3 applications
• Available in main circuit breaker and main lug only panelboards with sub-feed circuit breakers,
feed-through lugs, or sub-feed lugs
• AC tracking filter with EMI/RFI filtering up to -50 dB from 100 kHz to 100 MHz

12
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Enclosures

Enclosures
Enclosure Types

Type Environment Protects Against


Type 1 Indoor Contact with the enclosed equipment, falling dirt
Type 1, plus
Type 2 Indoor
• Dripping and light splashing of non-corrosive liquids
Type 2, plus
Type 3R Outdoor
• Rain, snow, and sleet
Type 3R, plus
• Circulating dust, lint, fibers and flyings
Type 4 Indoor/outdoor • Settling airborne dust, lint, fibers and flyings
• Windblown dust
Mono-Flat Type 1 • Hosedown and splashing water
Enclosure for Type 4, plus
100–250 A Interiors Type 4X Indoor/outdoor
• Corrosive agents
Type 2, plus
Type 5 Indoor
• Settling airborne dust, lint, fibers, and flyings
Type 2, plus
Type 12 Indoor • Circulating dust, lint, fibers, and flyings
• Settling airborne dust, lint, fibers, and flyings
• Oil and coolant seepage

Indoor Enclosures (Types 1 and 2)

MH type Box

• Standard boxes are 20 in. (508 mm) wide by 5.75 in. (223 mm) deep
• NF interiors with an LC or LI main circuit breaker or with an 800 A MLO interior require an
8.75 in. (223 mm) deep box — therefore, they are available factory-assembled and
fully-assembled only
• Boxes are galvanized steel with removable endwalls. On standard 5 3/4 inch depth boxes, one
endwall is provided with knockouts, and the other endwall is blank. On deeper boxes, both are
blank. Endwalls are removable and interchangeable
• Box and interior mounting instructions are included in the documentation shipped with the interior
• Keyhole slots are located in the box backwall to ease installation
NOTE: Interiors mount directly to studs in MH boxes. No interior mounting brackets are required.
NOTE: 800 A interiors and interiors that have LC/LI main circuit breakers require elevating
brackets, due to the requirement of an 8.75 in. (223 mm) deep box.
• Type 2 boxes include a drip hood (available with surface mounted trim only)

Type 1 Enclosure for


400–800 A Interiors

13
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Enclosures

Type 1 and 2 Trim Fronts

• Finished with gray-baked enamel electrodeposited over cleaned, phosphatized steel (ANSI 49)
• Order flush or surface mounted
• Door with flush lock; uses NSR-251 key
• Directory card located on the inside of the door
• Mono-Flat® fronts on 100–250 A interiors mount to the interior trim with trim screws. Both trim
mounting screws and door hinges are concealed; fronts are not removable with the door closed
and locked
• Fronts for 400–800 A interiors are ventilated and mount to the enclosure with trim screws; door
hinges are concealed
• Fronts 56 in. (1422 mm) high or more on 250 A interiors or 74 in. (1880 mm) high or more on 600 A
and 800 A interiors have two flush locks
• Fronts 68 in. (1727 mm) high or more on interiors with LC/LI main circuit breakers or LC sub-feed
circuit breakers use a sliding vault lock with 3-point latching

Key NSR-251 Concealed Hinge for 100–800 A Trim Fronts Interiors Mount Directly to Enclosure Studs
(Catalog No. LP9618)

Standard Flush Lock Optional Sliding Vault Lock (Catalog No. PK5FL) MH Box
(Catalog No. PK4FL)

14
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Enclosures
Rainproof (Type 3R) Dust tight (Type 5 and 12)

• Finished with gray-baked enamel electrodeposited over cleaned,


phosphatized galvanized steel (ANSI 49)
• Gasketed door with lockable vault handle (PK4NVL); uses NSR-251 key
• Directory card located on the inside of the door
• No knockouts in endwalls
• Trim kit included for end and side gutters
• Provisions for two ground bars
• 125 A, 250 A, 400 A main lug and main circuit breaker interiors
• 600 A and 800 A main lug only

Type 3R, 5, and 12 Enclosures

Vault Handle with Lock


(Catalog No. PK4NLV)

Corrosion-Resistant Fiberglass-Reinforced Polyester (Type 4X)

• Watertight and dust-tight


• Gasketed door with trunk latches
• Directory card located on the inside of the door

Stainless Steel (Type 4 and 4x)

• Water and dust tight


• Gasketed door
Type 4X Enclosure • Directory card located on inside of door

15
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Single Row (Column-Width) Panelboards

Single Row (Column-Width) Panelboards


Application Data

Ratings

• Main lugs: 125 A, 225 A


• Main circuit breaker: 100 A, 225 A

Interiors

• 60 A maximum branch circuit breaker


• Bolt-on EDB/EGB/EJB circuit breakers
• Solid neutral opposite mains

Column-Width Enclosures
Panelboard
• 8-5/8 in. (219 mm) wide by 5-5/8 in. (143 mm) deep for 10 in. (254 mm) H- or I-beam
• Galvanized steel
• Removable endwalls

Trim Fronts

• Screw mounted
• Door with two flush latches
• Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel

Line Lugs

• All lugs are suitable for 75° C copper or aluminum wire

Table 15: Branch Circuit Breaker Short-Circuit Current Ratings

Branch Breaker Prefix Short Circuit Current Rating1


1, 2 and 3 pole 15 to 60A @ 480Y/277 Vac @ 600Y/347 Vac
EDB 18,000 A 14,000 A
EGB 35,000 A 18,000 A
EJB 65,000 A 25,000 A
1 Series ratings are also available.
Canada: See the Series Rating Guide (data bulletin S1600PD0302EP R__).
USA: See Switchboard/Panelboard Short-Circuit Ratings (data bulletin 2700DB9901), or the Digest
(http://ecatalog.squared.com/category.cfm).

16
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Single Row (Column-Width) Panelboards
Cable Trough

Pull Box • Cable trough is stackable


(Cover Removed) • 8-5/8 in. (219 mm) wide by 5-5/8 in. (143 mm) deep for 10 in. (254 mm)
I-beam or H-beam
• Galvanized steel trough uses enclosure endwall
Solid Neutral
• Screw-mounted two-piece front
— 15 in. (381 mm) long top piece of front removable for
Cable Trough pull box mounting
— Finish: gray-baked enamel electrodeposited over cleaned,
phosphatized steel

Table 16: Column-Width Cable Trough

Length of Cable Trough Catalog No.

Single Row (Column-Width) Panelboard 36 in. (914 mm) NTX836


48 in. (1219 mm) NTX848
56 in. (1422 mm) NTX856
66 in. (1676 mm) NTX866
84 in. (2134 mm) NTX884
96 in. (2438 mm) NTX896
104 in. (2642 mm) NTX8104
112 in. (2845 mm) NTX8112

Cable Trough Top View with I-Beam

Pull Box
(catalog number MPX81542)

• Mounts on cable trough


• 20 in. (508 mm) wide by 5-3/4 in. (146 mm) deep by
15 in. (381 mm) high
• Screw-mounted front
• Finish: gray-baked enamel electrodeposited over cleaned,
phosphatized steel
• Removable top endwall with knockouts
• Solid neutral included

17
© 2008 Schneider Electric 08/2008
All Rights Reserved
NF Circuit Breaker Panelboards
Terminal Data

Terminal Data

Main Lugs Terminal Data

Table 17: Standard Aluminum and Copper Lugs

Aluminum Copper

Aluminum
Aluminum Mechanical Copper Mechanical Copper Compression
Amperes Compression

Lug Wire Lug Wire Lug Wire


Cat. # Lug Wire Range Cat. # Cat. # Cat. #
Range Range Range
(1) #6 - 350 NFCUV
125 NFALM1 (1) #6 - 2/0l1 NFALV1 (1) #4-300 kcmil NFCUM1 (1) #6 - 1/0
kcmil 1
(1) 250-350 (1) #6 - 350 NFCUV (1) 2/0 - 300
250 NFAML2 (1) #6 - 350 kcmil NFALV2 NFCUM2
kcmil kcmil 2 kcmil
(1) 1/0-750 kcmil
(1) 1/0-750 kcmil or NFCUV (1) 400-750
400 NFALM4 NFALV4 (2) 2/0-500 kcmil NFCUM4 or
(2) 1/0-350 kcmil 4 kcmil
(2) 1/0-350 kcmil
NFCUV (2) 250-750
600 NFALM6 (2) 1/0-600 kcmil NFALV6 (2) 2/0-500 kcmil NFCUM6 (2) 1/0-750 kcmil
6 kcmil
800 Contact the Technical Applications Group (TAG)
1
Neutral accepts #6-2/0 Al/Cu.

Main Circuit Breaker Terminal Data

See Digest section 7 for copper lugs.

Table 18: Standard Aluminum Mechanical Lugs

Panelboard Ampere
Circuit Breaker Type Lug Wire Range
Type Rating
100 A FIL (1) #14-1/0 Cu or (1) #12-1/0 Al
125 A1 EDB, EGB, EJB (1) #14-2/0 Al/Cu
150 A HDL, HGL, HJL, HLL (1) #14-3/0 Al/Cu
NF 250 A JDL, JGL, JJL, JLL, KI (1) 3/0-350 kcmil Al/Cu
400 A LAL, LHL (1) #1-600 kcmil Al/Cu or (2) #1-250 kcmil Al/Cu
600 A LCL, LIL, LEL, LXL LXIL (2) 4/0-500 kcmil Al/Cu
800 A 800 A main breaker panelboard not available.
1
110 A maximum at 600Y/347 Vac.

Table 19: Aluminum Compression Lugs

Panelboard Ampere
Circuit Breaker Type Catalog No. Lug Wire Range
Type Rating
100 A FC, FI VC100FA (1) #8-1/0 Al/Cu
125 A1 ED, EG, EJ VC100FD (1) #8-1/0 Al/Cu
150 A HDL, HGL, HJL, HLL YA150HD (1) #1–4/0 Al/Cu
250 A JDL, JGL, JJL, JLL YA250J35 (1) 3/0–350 kcmil Al/Cu
NF
250 A KI VC250KA3 (1) #4-300 kcmil Al/Cu
400 A LA, LH VC400LA52 (1) 2/0-500 kcmil Al/Cu
600 A LC, LI, LE, LX, LXI — —
800 A 800 A main breaker panelboard not available.
1
110 A maximum at 600Y/347 Vac.
2
Other lug sizes available.

18
08/2008 © 2008 Schneider Electric
All Rights Reserved
NF Circuit Breaker Panelboards
Typical Wiring Diagrams

Typical Wiring Diagrams

S S
S S S S N N
N N N N

125–250 A Main Lugs 125 A EDB Main Circuit Breaker 100–250 A Main Circuit Breaker
(110 A max. at 600/347 Vac) Types FIL, HDL, HGL, HJL, HLL,
JDL, JGL, JJL, JLL, KIL
S/N
S/N

400–800 A Main Lugs 400–600 A Main Circuit Breaker


Types LAL, LHL, LCL, LIL

1-Phase, 3-Wire

S S
S S S S
N N
N N N N

125–250 A Main Lugs 125 A EDB Main Circuit Breaker 100–250 A Main Circuit Breaker
(110 A max. at 600/347 Vac) Types FIL, HDL, HGL, HJL, HLL,
JDL, JGL, JJL, JLL, KIL
S/N
S/N

400–800 A Main Lugs 400–600 A Main Circuit Breaker


Types LAL, LHL, LCL, LIL

3-Phase, 4-Wire

19
© 2008 Schneider Electric 08/2008
All Rights Reserved
Schneider Electric USA Schneider Electric Canada "Surgelogic", "Mono-Flat", and "I-Limiter" are trademarks or registered trademarks of
252 North Tippecanoe 19 Waterman Avenue, Schneider Electric and/or its affiliates in the United States and/or other countries. Other
Peru, IN 46970 USA M4B 1 Y2 marks used herein may be the property of their respective owners.
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 1670CT0701 © 2008 Schneider Electric All Rights Reserved
www.us.SquareD.com www.schneider-electric.ca Replaces 1670CT0701 dated 03/2008
08/2008
NQ Circuit Breaker Panelboards

Catalog
1640CT0801
2008
Class 1640

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Standards and Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Interiors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
Branch Circuit Breakers (Bolt-On) . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
Neutrals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
Ground Bar Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
Surge Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
Single Row (Column-Width) Panelboards . . . . . . . . . . . . . . . . . . . . Page 17
Typical Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
NQ Circuit Breaker Panelboards
Standards and Ratings

Standards and Ratings

NQ circuit breaker panelboards meet US and Canadian standards, and are


Voltage System System Diagram marked cULus. NQ circuit breaker panelboards accept QO® and QOB
branch circuit breakers.

120/240 Vac 1φ3W

208Y/120 Vac 3φ4W


Standards

NQ circuit breaker panelboards are designed, manufactured, and tested to


comply with the following standards:
3φ4W
240/120 Vac
Delta • UL 67—Standard for Panelboards
• UL 50—Enclosures for Electrical Equipment
• CSA C22.2, No. 29-M1989—Panelboards and Enclosed Panelboards
3φ3W
240 Vac • CSA C22.2, No. 94-M91—Special Purpose Enclosures
Delta
• NEMA PB 1—Panelboards
• NFPA 70—National Electrical Code® (NEC®)
3φ3W • Federal Specification W-P-115C Type I Class 1—Circuit Breaker
240 Vac Grd. Bφ Panelboards
Delta
• 2003 IBC, NFPA 5000, ASCE/SE17 Seismic Qualification

Ratings

• Main Lugs 100–600 A


• Main Circuit Breaker 100–600 A

3
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors

Interiors

225 A Main Lugs Interior


(Catalog No. NQ442L2)

225 A QBL Main


Circuit Breaker Interior
(Catalog No. QBL32225)

and Adapter Kit


(Catalog No. NQMB2Q)

Deadfront Removed Deadfront Installed

Main Circuit Breaker Interiors


• Will accept plug-on or bolt-on branch circuit breakers.
• Merchandised main circuit breaker interiors are suitable for use as service entrance (US only).
• Service entrance barriers are required and available in Canada (factory-assembled only).
• Top- or bottom-feed.
• 65k AIR maximum branch circuit breakers (fully-rated).
• 200k AIR maximum when supplied by I-Limiter circuit breaker (series rated).
• Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard). Tin-plated
copper bus is available as an option. Branch connector fingers are all tin-plated copper; silver-
plated branch connector fingers are optional.
• 100 A main circuit breaker interiors use a standard main lug interior and an appropriate QOB or
100 A QOB Interior QOB-VH main circuit breaker in a branch space; vertical main breaker main breaker interiors are
also available.
• 110-225 A main circuit breaker interior consists of:
— Standard main lug interior.
— Main circuit breaker adaptor kit (NQMB2Q, NQMB2HJ or NQMB2KI).
— Appropriate QBL, QDL, QGL, QJL, HDL, HGL, HJL, HLL, JDL, JGL, JJL, JLL, or KIL
circuit breaker.
• 250 A main circuit breaker interiors are factory-assembled only.
• 400 A main circuit breaker interiors consist of:
— Standard main lug interior
— Main circuit breaker adapter kit (Catalog No. NQMB4LA)
225 A QBL Interior
— Appropriate LAL or LHL circuit breaker
• 600 A main circuit breaker interiors (factory-assembled only) consist of:
— Appropriate LCL or LIL circuit breaker

4
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors

Main Circuit Breaker Adapter Kits Table 1: Main Circuit Breaker Adapter Kits
(Order Circuit Breaker Separately)
Catalog No. Ampere Rating Main Circuit Breaker
A B
C
NQMB2Q 100–225 A QBL, QDL, QGL, QJL
NQMB2HJ 100–225 A HDL, HGL, HJL, HLL, JDL, JGL, JJL, JLL
NQMB2KI 110–225 A KIL
NQMB4LA 125–400 A LAL, LHL

MAIN
Main circuit breakers are not included in the adapter kits, order separately.
PRINCIPAL

H 80
80
11
G
E
8
0
1
2
8
0
1
1
0
11
0-
32
0-
32
7-
03
Table 2: Main Circuit Breakers
F 2
-1
2
-3
2
7
7-
03
5 -0
-0
1 3

Max. Amperes Circuit Breaker Type


100 A QOB1, QOB-VHa, or FIL
Hardware not shown to scale 150 A HDL, HGL, HJL, or HLL
225 A QBL, QDL, QGL, QJL, JDL, JGL, JJL, JLL, or KIL
NQMB2Q
250 A2 JDL, JGL, JJL, JLL, or KIL
Kit Contents
A. Main circuit breaker deadfront cover (1) LAL or LHL
400 A
B. Main circuit breaker mounting pan (1) LC/LI/LX/LXI/LEb
600 A LC/LI/LX/LXI/LEb
C. Deadfront support brackets (2)
1
D. “Main” circuit breaker label (1) Backfed main circuit breaker
2
E. 10-32 x 7/16-inch tapping screws (2) Factory assembled only
F. 10-32 x 5/16-inch tapping screws (6)
G. 8-32 x 2 ¼-inch tapping screws (2)
H. 8-32 x 3 ¼-inch tapping screws (2)
I. Main lug wires (4) Table 3: Additional Main Circuit Breaker Information
Ampere Rating Circuit Breaker Type Circuit Breaker Catalog Section Class
QOB 730
100
FIL 820
150 HDL, HGL, HJL, HLL 611
QBL, QDL, QGL, QJL 734
225/250 JDL, JGL, JJL, JLL 611
KIL 825
400 LAL, LHL 660

Field-Installable Circuit Breaker Accessories

Field-installable shunt trip, alarm switch, and auxiliary contacts are available
for LAL 400 A main circuit breaker interiors. Refer to the Square D Digest
for additional information.

5
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors

Main Lug Interiors


• Will accept plug-on or bolt-on branch circuit breakers.
• Top- or bottom-feed.
• 65k AIR maximum branch circuit breakers (fully-rated).
• 200k AIR maximum when supplied by remote I-Limiter® circuit breaker
(series rated).
• 100 A and 225 A interiors are suitable for use as service entrance with
back-fed QOB circuit breaker (USA only).
• Field-installable sub-feed lug kits for 100–400 A interiors.
• Factory installed main lugs on all interiors.
• 225–400 A main lug interiors are convertible to main circuit breaker by
adding a main circuit breaker and adapter kit.
• Available with silver-plated copper or tin-plated aluminum bus
(aluminum is standard). Tin-plated copper bus is available as an option.
Branch connector fingers are all tin-plated copper; silver-plated branch
connector fingers are optional.

225 A Maximum Main Lug Interior


and Deadfront
Main lugs for MLO Interiors

Table 4: Aluminum Main lugs for MLO Interiors


Amperes Catalog Number Lug Wire Range for wire bending space
Aluminum Mechanical
100 standard (1) #6-350 kcmil
225 standard (1) #6-350 kcmil
(1) 1/0-750 kcmil, or
400 standard
(2) 1/0-350 kcmil
600 standard (2) 1/0-750 kcmil
6001 NQALM6A (3) 1/0-250 kcmil
Aluminum Compression
100 NQALV1 (1) #4-300 kcmil
225 NQALV2 (1) 250-350 kcmil
100–225 A Maximum 600 A Maximum 400 NQALV4 (2) 2/0-500 kcmil
600 NQALV6 (2) 2/0-500 kcmil
Main Lug Interiors 1
Optional lug for 600 A. Can also be used for 400 A.

Table 5: Copper Main lugs for MLO Interiors


Amperes Catalog Number Lug Wire Range for wire bending space
Copper Mechanical
100 NQCUM1 (1) #6-350 kcmil
225 NQCUM2 (1) #6-350 kcmil
(1) 1/0-750 kcmil, or
400 NQCUM4
(2) 1/0-350 kcmil
600 NQCUM6 (2) 1/0-750 kcmil
Copper Compression
100 NQCUV1 (1) #6-350 kcmil
225 NQCUV2 (1) #6-350 kcmil
400 NQCUV4 (1) 400-750 kcmil
600 NQCUV6 (2) 250-500 kcmil
Type VCEL VERSAtile™ Compression
Equipment Terminals
6
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Interiors

Interior Accessories

Branch Mounted Sub-Feed Lug Kits, 240 Vac

Table 6: Branch Mounted Sub-Feed Lugs


Rating Amperes Number of Poles Type of Connection Catalog No. Main Wire Size
2 QOB2125SL
125 Bolt-On #4-2/0 Al or Cu
3 QOB3125SL

Field-Installable Sub-Feed Main Lugs

• 100 A (NQSFL1)
• 225 A (NQSFL2)
• 400 A (NQSFL4)
NOTE: Refer to the Digest for the correct box size.

225 A Main Lug Interior Field installable Through-Feed Lugs


with Sub-Feed Lugs
• 225 A (NQFLT2L) for 30 or 42 circuit interiors
• 225 A (NQFLT2H) for 54, 72 or 84 circuit interiors
• 400 A (NQFLT4H) for 30 or 42 circuit interiors or less
• 400 A (NQFLT4L) for 54, 72 or 84 circuit interiors
NOTE: Refer to the Digest for the correct box size.

Field Installable Sub-Feed Circuit Breaker Kits

Table 7: Field Installable Sub-Feed Circuit Breaker Catalog Numbers


Number of Sub-Feed Circuit
Field Ampere Rating Catalog Number
Breakers and Type
225 NQSFB2Q 1 Q-frame
225 NQSFB2HJ 1 H or J-frame
400 NQSFB4Q 2 Q-frame
400 NQSFB4HJ 2 H or J-frame

Factory-Installed Options

• Sub-Feed Lugs are available on 1φ or 3φ, 100–400 A main lug interiors only.
• Feed-Through Lugs are available on 1φ or 3φ 225–600 A main lug, or 225–600 A main circuit breaker
interiors.
• Sub-Feed Circuit Breakers
— Available on 1φ or 3φ main lugs 225–600 A, or main circuit breaker interiors 225–600 A.
— One sub-feed circuit breaker for each 225 A panelboard.
— Two sub-feed circuit breakers for each 400–600 A panelboard.
— Sub-feed circuit breakers may be type HDL, HGL, HJL, HLL, QBL, QDL, QGL, QJL, JDL, JGL,
JJL, OR JLL circuit breakers.

225 A Main Lug


Other Accessories Available:
Interior with
Feed-Through Lugs • Split bus
• Lighting contactors
• Compression lugs
• Copper bus
• Phenolic nameplates

7
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Branch Circuit Breakers (Bolt-on)

Branch Circuit Breakers (Bolt-on)

Table 8: Branch Circuit Breakers (Plug-on or Bolt-on) 1


10 k AIR 22 k AIR 65 k AIR 10 k AIR (240 Vac) 42 k AIR
QO, QOB QO-VH, QOB-VH QH, QHB QO-H, QOB-H QOH
1-Pole 10–70 A 1-Pole 15–30 A 1-Pole 15–30 A
2-Pole 10–125 A 2-Pole 15–150 A 2-Pole 15–30 A 2-Pole 15–100 A 2-Pole 35–125 A
3-Pole 10–100 A 3-Pole 15–150 A 3-Pole 15–30 A
1
Series ratings are also available. Canada: See the Series Rating Guide (data bulletin #S1600PD0302EP) USA: See
Switchboard/Panelboard Short-Circuit Current Ratings (data bulletin #2700DB9901), or the Digest

QOB Branch Circuit Breakers QO Branch Circuit Breakers

Table 9: Branch Circuit Breaker Interrupting Data


Interrupting Rating—
RMS Symmetrical Amperes
Circuit Breaker Number of
Max. Vac Rating Ampere Rating
Catalog Prefix Poles Vac
120 120/240 240
120/240 1 10-70 — 10k —
QO, QOB 120/240 2 10-125 — 10k —
240 3 10-100 — — 10k
QO-H, QOB-H 240 2 15–125 — — 10k
120/240 1 15–30 — 22k —
QO-VH 120/240 2 15–125 — 22k —
240 3 15–100 — — 22k
120/240 1 15–30 — 22k —
QOB-VH 120/240 2 15–150 — 22k —
240 3 15–150 — — 22k
QOH-QOHB 120/240 2 35–125 — 42k —
120/240 1 15–30 — 65k —
QH
120/240 2 15–30 — 65k —
QHB
240 3 15–30 — — 65k

Table 10: Additional Branch Circuit Breaker Information


Circuit Breaker Type Circuit Breaker Catalog Class
QO, QOB 730
QO-AFCI 760
QO-GFI, QOB-GFI 910

8
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Branch Circuit Breakers (Bolt-on)

QO® Arc-Fault Circuit Breakers1

QO arc-fault circuit breakers provide branch feeder protection (i.e., QO115AFI) or combination
protection (i.e. QO115CAFI) as required by the NEC and local code adoption, and comply with
UL 1699.

Table 11: QO Arc-Fault Circuit Breaker Catalog Numbers


1P 120 Vac 10 kAIR 1P 120 Vac 22 kAIR
Ampere 1 Space Required 1 Space Required
Circuit Breaker Type
Rating
Catalog Number Catalog Number
Branch Feeder 15 QO115AFI QO115VHAFI
Arc-Fault Interrupter 20 QO120AFI QO120VHAFI
Combination 15 QO115CAFI QO115VCAFI
Arc-Fault Interrupter 20 QO120CAFI QO120VHCAFI

Table 12: Branch Circuit Breaker Lug Data


Wire Size
Ampere Rating Circuit Breaker Type
Aluminum Copper
10–30 QO, QOB (2) #12-#8 (2) #14-#8
35–50 QO, QOB (1) #8-#4 (1) #8-#4
60–70 QO, QOB (1) #6-#2 (2) #6-#2
80–125 QO, QOB (1) #4-2/0 (1) #4-2/0
150 QOB-VH (1) #4-300 kcmil (1) #4-300 kcmil

NOTE:
• Lugs suitable for 75° C wire.
• Torque QOB connector mounting screws to 18–21 lb-in.
• Torque labels are included on the circuit breakers with load side lug torque requirements.

1
HACR type for use with air conditioning, heating and refrigeration equipment having motor group combinations and marked for
use with HACR type circuit breakers.

9
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Neutrals

Neutrals
• All lugs suitable for copper or aluminum wire.100–600 A interiors have split neutral located on
same end as mains.
• Bondable for use as service entrance (in Canada, available as factory-assembled only).
• Branch terminals suitable for #12-#4 aluminum and #14-#4 copper.
• Provisions for larger branch terminal lugs with use of auxiliary neutral lugs.
• Suitable lug provided on neutrals for termination of grounding conductor.
• All unused neutral terminals may be used to terminate equipment grounding conductors when
panelboard is used as service entrance.
• 100% rated neutrals. One neutral termination provided per circuit in panelboard.
• 200% rated neutrals are available as factory-assembled options or as kits.

Table 13: Field Installable Copper 100% Neutral Kits

Amperes Catalog Number


100 NQN1CU
225 NQN2CU
400/6001 NQN6CU
100–225 A 1
Not for use with 600 sub-feed lugs, feed-through lugs, or sub-feed circuit breaker
Neutral Assembly

Table 14: Field Installable 200% Neutral Kits

Amperes Catalog Number


100 NQNL1
225 NQNL21
400 NQNL42
1 Use NQNL2ACCY when installing on a 225A panel with SFL, SFB, or TFL.
2
Not to be used with SFL, FTL, or SFB. These combinations are factory-assembled only.

10
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Neutrals

200% Neutral Restrictions


225 A, 200% Neutral

• Integral lighting contactors are not available.


• Crimp neutral line lugs are not available.
• If sub-feed lugs, feed-through lugs, or sub-feed circuit breakers are
required, order the following 200% neutral kit: NQNL2ACCY

400 A, 200% Neutral

• Type 3R, 5, and 12 enclosures require copper-bussed interiors.


• Sub-feed circuit breakers are available with main lug interiors in Type 1
enclosures only. Sub-feed circuit breakers are not available in Type 3R,
4, 4X, 5, and 12 enclosures.
• Using a sub-feed circuit breaker restricts standard QO and QOB
225 A Interior with Sub-Feed Lugs branches to a maximum of 125 A.
• Integral lighting contactors are not available.
• Crimp neutral line lugs are not available.
• 400 A panelboards equipped with 200% neutrals and sub-feed lugs,
feed-through lugs, or sub-feed circuit breakers are only available
factory-assembled.

Auxiliary Neutral Lugs

Lugs are suitable for copper or aluminum wire and are field-installable on
neutral assembly.

#10–#4 AWG #1–4/0 AWG


(Catalog No. QO70AN) (Catalog No. Q1150AN)

Auxiliary Neutral Lugs


Neutral Bonding Provisions

Bonding strap may be field-installed for UL service equipment requirements


on 100–400 A interiors (in Canada, available as factory-assembled only).

400 A 600 A

Typical Neutral Assemblies 100–225 A Provision 400 A Provision

Neutral Bonding Provisions

11
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Ground Bar Kits

Ground Bar Kits


• Field-installable in all panelboards.
• Suitable for copper or aluminum wire.
• Provisions for mounting up to four ground bar kits per panel.

Equipment Ground Bar

Ground Bar Insulator Kit (Catalog No. PKGTAB)

The insulator kit is field installable and may be used with equipment ground
bar kits. NQ panelboard enclosures have equipment ground bar mounting
provisions in all four corners.

Ground Bar with Insulator Kit


Technical Information

All PK equipment grounding kits are supplied with mounting screws,


necessary installation instructions, and an “Equipment Grounding Terminal”
self-adhesive label.
Table 15: Ground Bar Kit Technical Information

Terminals
Distance Between
Qty Each Size (For Wire Range Approximate Overall Length
Catalog Number Total Qty Mounting Holes
see Table 16:) in (mm)
in (mm)
I II
PK23GTAL 24 23 1 9.125 (232) 3.125 (79)
PK27GTA 27 27 — 9.125 (232) 3.125 (79)
PK27GTACU 27 27 — 9.125 (232) 3.125 (79)

Table 16: Ground Bar Kit Wire Ranges

Size Cu Al
I (1) #14 to #4 or (2) #14 or #12 (1) #12 to #4 or (2) #12 or #10
II (1) #1 to 4/0 (1) #1 to 4/0

12
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Surge Protection

Surge Protection
The Surgelogic™ IMA series surge protective device is a modular parallel transient voltage surge
suppressor (TVSS). The IMA device is a multi-stage suppression circuit consisting of field-proven, fast-
acting, 34 mm metal oxide varistors (MOVs). A surge suppression path is provided for each mode,
line-to-neutral (L-N), line-to-line (L-L), line-to-ground (L-G), and neutral-to-ground (N-G). Each surge
suppression mode is individually fused and uses circuitry with thermal cutouts to isolate the TVSS and
ensure shutdown in the event of MOV damage during severe overvoltages, even when operated on
high fault current power systems. The suppression elements are encapsulated in a UL recognized
potting material—another performance element that provides additional protection. A filter provides a
high level of EMI/RFI noise attenuation. On-line diagnostics continuously monitor the device status,
and LEDs signal loss of a suppression circuit. An audible alarm with an enable/disable feature and dry
contacts are included in the standard diagnostic package.

Table 17: Surge Protection Ratings

IMA Series Voltage Specifications UL Suppression Voltage Rating (SVR)

Service Voltage L–N L–G N–G L–L MCOV 1


120/240 Vac, 1-phase 400 400 400 800 150
208Y/120 Vac, 3-phase, 4-wire 400 400 400 800 150
240/120 Vac, 3-phase, high-leg delta 800/400 800/400 400 1500/800 275/150
NQ Main Lug interior 1
MCOV: maximum continuous operating voltage
with integral TVSS

Table 18: Surge Protection Performance Features

Surge Capacity L–N L–G N–G (3-phase rating)


100 kA / phase 50 kA 50 kA 100 kA
120 kA / phase 60 kA 60 kA 120 kA
160 kA / phase 80 kA 80 kA 120 kA
200 kA / phase 100 kA 100 kA 200 kA
240 kA / phase 120 kA 120 kA 120 kA

13
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Surge Protection

Table 19: Surge Protection Specifications


Relative Humidity 0 to 95% non-condensing
Operating Frequency 47–63 Hz
Storage Temperature -40° to +65° C (-40° to +149° F)
Operating Temperature -40° to +65° C (-40° to +149° F)
Display Operating Temperature -10° to +50° C (+14° to +122° F)
Standards UL 1449 Second Edition: UL Category Section 37.3 (200 kA short-circuit current module rating)
Fusing Individually fused suppression modules
Audible Alarm Provides audible indication that there is a loss of protection
Provides remote indication of the TVSS device’s operating status to a computer interface
Dry Contacts
board or emergency management system

Table 20: Other Surge Protection Options

Option Description
Displays the combined total number of transient voltage surges detected from
Surge Counter
L–G, L–L, L–N, and N–G since the counter was last reset.
Displays the alarm status of the surge protective device up to 1,000 ft (305 m) away from the unit.
Remote Monitor
This option uses the dry contacts.

Design Features

• Individually fused suppression modules


• Thermal cutout
• Inline, copper bus bar connection
• Solid state bi-directional
• Push-to-Test on-line diagnostic display
• Audible alarm with enable/disable switch
• LED indicators indicate loss of protection, or fully-operational circuit
• High-energy parallel design for IEEE C62.41 category A, B, and C3 applications
• Available in main circuit breaker and main lug only panelboards with sub-feed circuit breakers,
feed-through lugs, or sub-feed lugs.
• AC tracking filter with EMI/RFI filtering up to -30 dB from 100 kHz to 100 MHz

14
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Enclosures

Enclosures

Table 21: Enclosure Types

Type Environment Protects Against


Type 1 Indoor Contact with the enclosed equipment, falling dirt
Type 1, plus
Type 2 Indoor • Dripping and light splashing of
non-corrosive liquids
Interior Mounts to Box Studs Type 2, plus
Type 3R Outdoor
• Rain, snow, and sleet
Type 3R, plus
• Circulating dust, lint, fibers and flyings
Type 4 Indoor/outdoor • Settling airborne dust, lint, fibers and flyings
• Windblown dust
• Hosedown and splashing water
Type 4, plus
Type 4X Indoor/outdoor
MH Box • Corrosive agents
Type 2, plus
Type 5 Indoor
• Settling airborne dust, lint, fibers, and flyings
Type 2, plus
Type 12 Indoor • Circulating dust, lint, fibers, and flyings
• Settling airborne dust, lint, fibers, and flyings
• Oil and coolant seepage

Indoor Enclosures (Types 1 and 2)

Boxes (MH):
• Galvanized steel with removable endwalls. One is provided with
knockouts and the other is blank.
• Standard box sizes:
— 20 in. (508 mm) wide x 5.75 in. (146 mm) deep,
600 A main lug interior max. or 400 A main circuit breaker max
— 20 in. (508 mm) wide x 8.75 in. (223 mm) deep,
600 A main circuit breaker interior, factory-assembled only
• Box and interior mounting instructions are found in the information
Mono-Flat Front
Front (Type 1) Enclosure (Type 1 Enclosure)
manual shipped with the interior.
for 400–600 A Interiors for 100–250 A Interiors • Interiors mount directly to studs in the MH box. Interior mounting
Indoor Enclosures brackets are not required.
• Type 2 enclosure includes a driphood.
— Surface-mounted trim only.
NOTE: Also available with knockouts / blank endwalls both ends.
Trims:
Flush Lock (standard)
(Catalog No. PK4FL) • Finished with gray baked enamel electrodeposited over cleaned
phosphatized steel (ANSI 49).
• Flush or surface mounted (Type 2 surface only).
Key NSR-251 • Door has flush lock. Uses NSR-251 key.
(Catalog No. LP9618)
• Directory card located on the inside of the door.
• Mono-Flat® trims on 100–225 A interiors mount to the interior trim with
Sliding Vault Lock (optional) trim screws. Both trim screws and door hinges are concealed. Trims are
(Catalog No. PK5FL) not removable with the door closed and locked.
• Trims for 400–600 A interiors are vented and mount to the enclosure
Concealed Hinge
with trim screws. Door hinges are concealed.
Used on 100–600 A Fronts • Optional hinged trims are available. These meet door-in-door specs.
Indoor Enclosure Accessories
15
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Enclosures
Rainproof (Type 3R) and
Dusttight (Type 5 and 12) Enclosures

• Finished with gray-baked enamel electrodeposited over cleaned


phosphatized galvanized steel (ANSI 49).
• Gasketed door has vault handle with lock (uses NSR-251 key).
• Directory card holder on inside of door.
• No knockouts.
• Removable drain screw for Type 3R enclosure rating.
• Trim kit (ordered separately) is required for end and side gutters.
• Provisions for two ground bars.

Type 3R, 5, and 12 Enclosure Vault Handle with Lock


(Catalog No. PK4NVL)

Rainproof and Dusttight Enclosure

Corrosion-Resistant Fiberglass-Reinforced
Polyester Enclosures (Type 4X)

• Watertight and dusttight.


• Gasketed door with optional locking handle.
• Directory card holder on inside of door.

Corrosion-Resistant Fiberglass-Reinforced
Polyester Enclosure
Stainless Steel Enclosures (Type 4 and 4X)

• Watertight and dust tight.


• Gasketed door with optional locking handle.
• Directory card holder on inside of door.

Stainless Steel Enclosure


16
12/2008 © 2008 Schneider Electric
All Rights Reserved
NQ Circuit Breaker Panelboards
Single Row (Column-Width) Panelboards

Single Row (Column-Width) Panelboards


Ratings
• Main lugs: 100–225 A
• Main circuit breaker: 100–225 A
Enclosures
• 8.625 in. (219 mm) wide by 5.00 in. (126.95) deep for 10” WF Beams
• Galvanized Steel
• Removable endwalls
• Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel
Miscellaneous
• All lugs are suitable for 75° C copper or aluminum wire
• 60 A maximum branch circuit breaker
• Bolt-on QOB/QOB-VH/QHB circuit breakers
• Solid neutral opposite mains, second neutral in pull box

Table 22: Branch Circuit Breakers (Bolt-on) 240 Vac


10 k AIR QOB 22 k AIR QOB-VH 65 k AIR QHB
NQ Column Width 1 pole, 10-60 A 1 pole, 10-30 A 1 pole, 10-30 A
Panelboard with 2 pole, 10-60 A 2 pole, 10-60 A 2 pole, 10-30 A
Cable Trough and 3 pole, 10-60 A 3 pole, 10-60 A 3 pole, 10-30 A
Pull Box

Cable Trough

• Stackable
• 8.625 in. (219 mm) wide by 5.00 in. (127 mm) deep for 10” WF Beams
• Galvanized steel trough uses enclosure end wall
• Two-piece front trim
— 15 in. (381mm) long top piece of front trim removable for pull box mounting
• Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel
• Cable troughs are standard with a trough barrier

Table 23: Cable Troughs


Length of Cable Trough Catalog Number
36 inch (9914 mm) MTX836
48 inch (1219 mm) MTX848
56 inch (1422 mm) MTX856
66 inch (1676 mm) MTX866

Pull Box

• Mounts on cable trough


• 20 in. (508 mm) wide by 5.00 in. (127.00 mm) deep by 15 in. (381 mm) high
• Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel
• Removable end walls with knockouts
• Solid neutral included with 42 circuits
• Pull Box catalog number MPX81542

17
© 2008 Schneider Electric 12/2008
All Rights Reserved
NQ Circuit Breaker Panelboards
Typical Wiring Diagrams

Typical Wiring Diagrams

S S
N N
S S S S
N N N N

100–225 A Main Lugs 100 A QOB Main Circuit Breaker 70–225 A Main Circuit Breaker
Types QBL, JDL, HDL

S/N S/N

400–600 A Main Lugs 400 A Main Circuit Breaker


Type LAL

1-Phase, 3-Wire

S S
N N
S S S S
N N N N

100–225 A Main Lugs 100 A QOB Main Circuit Breaker 70–225 A Main Circuit Breaker
Types QBL, JDL, HDL

S/N S/N

400 A Main Circuit Breaker


400–600 A Main Lugs Type LAL

3-Phase, 4-Wire

18
12/2008 © 2008 Schneider Electric
All Rights Reserved
Notes
Notes
Notes
Notes
Schneider Electric USA Schneider Electric Canada
252 North Tippecanoe 19 Waterman Avenue,
Peru, IN 46970 USA M4B 1 Y2
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 1640CT0801 © 2008 Schneider Electric. All Rights Reserved.
www.schneider-electric.us www.schneider-electric.ca

12/2008
Surgelogic SurgeLoc
Advanced power and equipment protection
For Square D NQ panelboards
Surgelogic SurgeLoc

Utility industry experts estimate that power quality problems, including those
resulting from transient voltage surges, cost North American companies a
stunning $80 billion annually. That figure not only includes the high price of
direct damage to electrical distribution systems, electronic equipment, software,
and tools, but also the crippling cost of lost productivity. Facility downtime, lost
data, lost orders, and the disruption of critical processes can seriously reduce
productivity. Minimizing the risk of damage from electrical surges is an absolute
priority for companies of all types.
The Square D Surgelogic brand is a 30-year pioneer in the surge protective
device industry. Building on a history and reputation for reliability, Surgelogic
SurgeLoc surge protective devices exceed competitor brands with outstanding
specifications in a compact device.

billion
annually
The estimated cost of power quality problems
for North American companies
Easy installation, space-saving,
money-saving design
Setting a new standard for commercial internal surge
mounted devices, the Square D Surgelogic™ product line
from Schneider Electric™ has revolutionized commercial
surge protection with the new SurgeLoc product.
Engineered with input from contractors and specifiers, the innovative
SurgeLoc device saves time and money normally required when SPDs
are factory-installed on any project.
Installs in two minutes or less, a significant reduction from the
typical 20 minutes.

• Uses standard-sized panels, requiring only 0 to 6 inches of increased panel


size based on the number of breaker slots needed
• Unique design for easy field mounting and retrofitting
• Custom bus bar, rails, dead front, and fasteners not required
• Eliminates the need for specialized hardware at the bottom of the panel
• Reduces the overall cost of adding internal surge protection to any panelboard
• Wider range of Surge Current Ratings (80 kA – 240 kA)
• Advanced diagnostics for improved SPD status information
Installation
time reduction
Standard features: Better performance
• Enhanced EFI/RFI Filtering • Short phase wires
• Engineered to UL 1449 3rd Edition, Type 1
®
• Direct bus connection
SPD and complies with UL96A for Lightning
Protection Systems
Space savings
• Requires only six breaker spaces on each side
(12 spaces total) • Eliminates need for additional enclosure or longer
wire leads for mounting external SPD
• 24 – 30% height reduction by using standard
panel sizes
Cost savings
• Factory- or field-installable
• Does not require additional wire, conduit,
• Diagnostic interface with audible alarm, dry connectors, or circuit breakers
contacts surge counter, and phase testing

Specifications:
Surge Modes of
Model Number Voltage Protection Type I(n) SCCR VPR
Current
SSP01BIA08PBQ1 120 / 240 V 80 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA08PBQ1 208 Y / 120 V 80 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA08PBQ1 240 / 120 HLD 80 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA10PBQ1 120 / 240 V 100 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA10PBQ1 208 Y / 120 V 100 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA10PBQ1 240 / 120 HLD 100 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA12PBQ1 120 / 240 V 120 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA12PBQ1 208 Y / 120 V 120 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA12PBQ1 240 / 120 HLD 120 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA16PBQ1 120 / 240 V 160 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA16PBQ1 208 Y / 120 V 160 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA16PBQ1 240 / 120 HLD 160 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA20PBQ1 120 / 240 V 200 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA20PBQ1 208 Y / 120 V 200 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA20PBQ1 240 / 120 HLD 200 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
SSP01BIA24PBQ1 120 / 240 V 240 kA 6 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP02BIA24PBQ1 208 Y / 120 V 240 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L
SSP03BIA24PBQ1 240 / 120 HLD 240 kA 10 1 20 kA 200 kA 700 L-N, L-G, N-G / 1200 L-L, H-N, H-L, H-G
Unmatched surge suppression.
Unequaled experience.
With the rapid growth of the internet and web-hosting facilities,
and an explosion in the use of sensitive electronic equipment
and controls in manufacturing plants, offices, hospitals, and
water/wastewater facilities, there is a universal demand for
reliable power. Schneider Electric is the world’s leader in power
protection. From residential surge circuit breakers to large
commercial surge protection, Square D Surgelogic brand
products are dedicated to advancing technology to safely
deliver and control electrical power for all of our customers
around the world.
Take the next step to dependable power and equipment security with SurgeLoc surge protective

©2013 Schneider Electric. All Rights Reserved. Schneider Electric, Square D, and Surgelogic are trademarks owned by Schneider Electric
devices. Whatever your requirements for products are, Schneider Electric has a solution to meet
your needs. For more information, call us at 1-800-577-7353.

Industries SAS or its affiliated companies. All other trademarks are property of their respective owners. 998-1218717_US
Snap this QR code to access
the Surgelogic website.

Schneider Electric USA Schneider Electric Canada, Inc. Schneider Electric México, S.A. de C.V.
1751 South 4800 West 5985 McClaughlin Road Calz. J. Rojo Gómez 1121-A
Salt Lake City, UT 84104 Mississauga, Col. Gpe. del Moral
Tel: 801-977-9009 Ontario L5R 1B8 09300 México, D.F.
Fax: 801-977-0200 Tel: 1-800-565-6699 Tel. 55-5804-5000
www.schneider-electric.com/us www.schneider-electric.com/ca www.schneider-electric.com/mx

Document Number 1300BR1302 September 2013


Surgelogic® Surge Protective Device
I-Line® Plug-On Unit Series

Catalog
1310CT0201R05/09
2009
Class 1310

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Selection and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Product Description

Product Description

Surge protective device (SPD) units protect electronic equipment from


transients. The I-Line® Plug-On Unit with Surgelogic® Surge Protective
Device (SPD) is a modular parallel surge protective device designed for
service entrance, distribution, or branch panel applications. The device is a
multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm
metal oxide varistors (MOVs). Each MOV is thermally protected for low
current faults, and each module is fused.
The I-Line plug-on unit with a Surgelogic surge protective device is a high
performance surge suppressor package incorporating individual modules
for each phase. Modes of protection include:
• Line-to-Neutral (L–N)
• Line-to-Ground (L–G)
• Neutral-to-Ground (N–G)
• Line-to-Line (L–L)
A filter provides EMI/RFI noise filtering. The suppression elements are
encapsulated in a UL® Recognized thermosetting epoxy material—another
I-Line Plug-On Unit with Surgelogic SPD performance element that provides additional protection.
Each surge suppression module is individually fused and uses circuitry with
thermal cutouts to isolate the SPD and ensure shutdown in the event of
MOV damage during severe overvoltages—even when operated on high
fault current power systems. Online diagnostics continuously monitor the
unit status, and LEDs signal a loss of a suppression circuit. An audible
alarm with an enable/disable feature and dry contacts are included in the
standard diagnostic package.

Design Features

• Same easy installation as I-Line circuit breakers


• Requires 13.50 in. (343 mm) of mounting space
• FC units mount in the same mounting slots as FA circuit breakers. FI units
mount in the same mounting slots as KA circuit breakers
• Can be applied in a six-disconnect panel or switchboard (SPD counts as
one disconnect)
• High-energy parallel design for ANSI/IEEE C62.41 and C62.45
category B and C3 applications.

2
06/2009 © 2009 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Application Information

Application Information

The effects of lightning and the damage caused by lightning-generated transients are well known. The
failure of electronic equipment in a facility located in a high lightning area can easily be attributed
directly to lightning-generated transients. Transient protection can be installed on the power
distribution system to protect this equipment from these externally generated transients. Lower
magnitude transients generated within a facility and their effect on microprocessor-based equipment
are less obvious than the transients induced by lightning. Transient voltage generated from inductive
motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they
can cause equipment to malfunction.
A damaging transient voltage can enter a facility from several locations. The highest level of protection
should be provided at the service entrance. A second level of protection should be provided at
distribution points serving critical areas, for example, computer rooms, accounting areas, and
laboratories. Other facility entry points that should be protected include panels serving outdoor lights,
or outdoor equipment such as motors. Protection should also be provided for critical areas with
equipment essential to the company.
Square D® brand SPD products offered by Schneider Electric provide protection at every level of the
electrical distribution system. Typical applications include:

• Banking • Transportation • Retail


• Education • Wastewater/Sanitation • Utility
• Government • Medical • Insurance
• Petrochemical • Financial • Data Processing
• Military • Telecommunications
• Publishing • Automated Manufacturing

3
© 2009 Schneider Electric 06/2009
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Selection and Specifications

Selection and Specifications

Model Number Format

The model number format consists of: Device Type, Voltage Code, SPD
FC 4 IMA 16 C
Model, Surge Current Rating Code, and Option Code. The possible device
types and codes are shown in the tables below.

Option Code
In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac
Surge Current Rating Code
3-phase 4-wire 160 kA surge capacity with surge counter.
SPD Model (IMA only)
Voltage Code Specifications
Device Type

Device Types, Interrupting Ratings, and Continuous Current Ratings

Interrupting Rating
Device Continuous
Type at 240 Vac at 480 Vac at 600Y/347 Vac Current Rating

FC 100 kA 65 kA — 60 A
FI 200 kA 200 kA 100 kA 60 A

Voltage Codes and Systems

Voltage Code Voltage System


1 120/240 Vac 1-phase, 3-wire
2 208Y/120 Vac 3-phase, 3- or 4-wire
3 240/120 Vac 3-phase, 4-wire (high leg Delta)
4 480Y/277 Vac, 3-phase, 3- or 4-wire
7 380Y/220 or 415Y/240 Vac, 3-phase, 3- or 4-wire
8 600Y/347 Vac, 3-phase, 3- or 4-wire

Surge Current Rating Codes and Surge Capacities

Per Mode
Surge Current Rating Code Per Phase
L–N L–G N–G
12 120 kA 60 kA 60 kA 120 kA
16 160 kA 80 kA 80 kA 120 kA
24 240 kA 120 kA 120 kA 120 kA

Descriptions and Option Codes

Option Description Option Code


Displays the combined total number of transient
Surge counter voltage surges detected from L–N, L–G, N–G, and C
L–L since the counter was last reset.
Displays the alarm status of the surge protective Order catalog
Remote monitor device up to 1000 ft (305 m) away from the unit. This number
option uses the dry contacts. TVS12RMU
Dry contacts Provides available Form C type contacts. Standard
Audible alarm with Provides audible indication that there is a loss of
Standard
enable/disable switch protection.

4
06/2009 © 2009 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Selection and Specifications

UL Suppression Voltage Ratings

IMA Series Voltage Specifications UL Suppression Voltage Rating (SVR)

Partial
Catalog Voltage Service L–N L–G N–G L–L MCOV▲
Number
FC1IMA 120/240 Vac,
400 400 400 800 150
FI1IMA 1-phase, 3-wire
FC2IMA 208Y/120 Vac,
400 400 400 800 150
FI2IMA 3-phase, 3- or 4-wire
240/120 Vac,
FC3IMA
3-phase, 4-wire 800/400 800/400 400 1500/800 275/150
FI3IMA
(high leg Delta)
FC4IMA 480Y/277 Vac,
800 800 800 1600 320
FI4IMA 3-phase, 3- or 4-wire
FC7IMA 380Y/220 Vac
800 800 800 1600 320
FI7IMA 3-phase, 3- or 4-wire
600Y/347 Vac,
FI8IMA ■ 1200 1200 1200 2000 420
3-phase, 3- or 4-wire

Surgelogic® I-Line® Plug-on SPD Unit ▲ MCOV = Maximum Continuous Operating Voltage.
■ Not available as FC device.

Standard Features and Descriptions

Feature Description
Relative humidity: 0 to 95% non condensing
Operating frequency: 47–63 Hz
Environmental
Surge suppression operating temperature: -40–+65 °C (-40–+149 °F) ✪
Storage temperature: -40–+65 °C (-40–+149 °F)
UL 1449, Second Edition, UL 1283
Compliance
standards cULus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5
(SPD unit only)
Meets 2002 NEC® Article 285.6
Fused
suppression Fused with individual surge-rated fuses (200 kAIR)
paths
Thermal
Thermal cutout for low current faults
protection
On-line test functions
Diagnostics Indication per phase
Service indicator shown on the front panel of each SPD unit

Replaceable Separate, replaceable modules for each phase


modules Self-contained suppression circuits and filtering for each module
LED indicators Indication of loss of protection
Suppression
Individually-fused
modules
Solid state Bi-directional
Front panel alarm Includes an enable/disable switch
High-energy
Category A, B, and C3 applications
parallel design
EMI/RFI Filtering Up to -50 dB (100 kHz to 100 MHz)
Short-circuit
200 kA (SPD modules only)
current rating
Duty cycle tested
ANSI C62.41 C3, Minimum 5000 impulses
10 kA 20 kV
Warranty Ten years
✪ Surge counter liquid crystal display may not indicate at temperatures less than -20 °C (-4 °F).

5
© 2009 Schneider Electric 06/2009
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Replacement Parts

Replacement Parts

MA Module Replacements

Peak Surge Catalog Number


Voltage System ●
Current Rating Phase A Phase B Phase C
120 kA MA1IMA12 Empty MA1IMA12
120/240 Vac, 1-phase, 3-wire 160 kA MA1IMA16 Empty MA1IMA16
240 kA MA1IMA24 Empty MA1IMA24
120 kA MA1IMA12 MA1IMA12 MA1IMA12
208Y/120 Vac, 3-phase,
160 kA MA1IMA16 MA1IMA16 MA1IMA16
3- or 4-wire
240 kA MA1IMA24 MA1IMA24 MA1IMA24
120 kA MA1IMA12 MA3IMA12 MA1IMA12
240/120 Vac, 3-phase,
160 kA MA1IMA16 MA3IMA16 MA1IMA16
4-wire (high leg Delta) ▼
240 kA MA1IMA24 MA3IMA24 MA1IMA24
120 kA MA4IMA12 MA4IMA12 MA4IMA12
480Y/277 Vac, 3-phase,
160 kA MA4IMA16 MA4IMA16 MA4IMA16
3- or 4-wire
240 kA MA4IMA24 MA4IMA24 MA4IMA24
120 kA MA7IMA12 MA7IMA12 MA7IMA12
380Y/ 220 or 415Y/240 Vac,
160 kA MA7IMA16 MA7IMA16 MA7IMA16
3-phase, 3- or 4-wire
240 kA MA7IMA24 MA7IMA24 MA7IMA24
120 kA MA8IMA12 MA8IMA12 MA8IMA12
600Y/347 Vac, 3-phase,
160 kA MA8IMA16 MA8IMA16 MA8IMA16
3- or 4-wire
240 kA MA8IMA24 MA8IMA24 MA8IMA24
● With all system voltages, SPD devices must be grounded in accordance with all
applicable standards.
▼ Phase B modules are different than Phase A and Phase C modules.

Surgelogic® Device
Mounted in Panel with
4-Piece Trim Installed

6
06/2009 © 2009 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Surgelogic® Surge Protective Device
Dimensions and Weights

Dimensions and Weights

FC I-Line® Plug-On Unit (Front View)

FI I-Line Plug-On Unit (Front View)

7
© 2009 Schneider Electric 06/2009
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Schneider Electric USA Schneider Electric Canada
1601 Mercer Road 19 Waterman Avenue,
Lexington, KY 40511 USA M4B 1 Y2
1-888-SquareD Toronto, Ontario
(1-888-778-2733) 1-800-565-6699 1310CT0201R05/09 © 2009 Schneider Electric All Rights Reserved
www.schneider-electric.us www.schneider-electric.ca Replaces 1310CT0201R5/07 dated May 2007.

06/2009

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Product data sheet SSP02EBA24
Characteristics Surge Protect - EBA - 240kA - 208Y/120VAC -
3P4W - T1
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Surge protection device
Device Short Name EBA

Complementary
Surge Current 240 kA
System Voltage 208Y/120 V AC
Phase 3 phases
Wiring Configuration 4-wire
Connection Wire AWG 10 copper
MCOV 150 V
SCCR 200 kA
Local Signalling Status LED, green = normal operation per phase
Status LED, red = fault per phase
Provided Equipment Surge counter
Alarm enable/disable switch
Dry contacts
Device Mounting Surface
Height 13.32 in (338.3 mm)
Width 5.74 in (145.8 mm)
Depth 4.42 in (112.3 mm)

Environment
Enclosure Rating NEMA 1
Enclosure Material Painted sheet steel, colour : grey
Standards UL 1283
UL 96A ed. 12
UL 1449 ed. 4
CSA C22.2 No 8
Ambient Operating 104 °F (40 °C)

Ordering and shipping details


Category 08464 - SURGE PROTECTION EMA
Sep 17, 2018
1
Discount Schedule DE1B
GTIN 00785901627517
Nbr. of units in pkg. 1
Package weight(Lbs) 8
Returnability Y
Country of origin MX

Offer Sustainability
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP which is known to the State of California to cause cancer and
- - - - - - - Substance 2 DIDP which is known to the State of California to cause birth defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

2
2D Drawing Index 09/19/2018 22:19:54
Project #97321: 3ER PUENTE NEMA4X 304
Item# Designation Material Qty Description Drawing(s)
1 TUPSW,TU NQ ML 2 NQ Panelboard O97321-0001-01-1.PDF
PSE PNLB
(INT,ENCL)
2 TPSA, NQ ML 2 NQ Panelboard O97321-0002-01-1.PDF
TPSB PNLB
(INT,ENCL)
3 TAB 4CH NF ML 1 NF Panelboard O97321-0003-01-1.PDF
PNLB
(INT,ENCL)
4 TAB 4D NF ML 1 NF Panelboard O97321-0004-01-1.PDF
PNLB
(INT,ENCL)
5 TAB 4AB NF ML 1 NF Panelboard O97321-0005-01-1.PDF
PNLB
(INT,ENCL)
6 TAB C NQ MB 1 NQ Panelboard O97321-0006-01-1.PDF
PNLB
(INT,BOX,F
RT)
7 TAB A, B NQ MB 2 NQ Panelboard O97321-0007-01-1.PDF
PNLB
(INT,ENCL)
8 4PLC0 NF MB 1 NF Panelboard O97321-0008-01-1.PDF
PNLB
(INT,ENCL)
9 4PLCE NF MB 1 NF Panelboard O97321-0009-01-1.PDF
PNLB
(INT,ENCL)
10 4TL NF MB 1 NF Panelboard O97321-0010-01-1.PDF
PNLB
(INT,BOX,F
RT)
11 4MDPB NF MB 1 NF Panelboard O97321-0011-01-1.PDF
PNLB
(INT,ENCL)
12 4MDPA ILINE MB 1 I-Line Panelboard O97321-0012-01-1.PDF
PNLB
(INT,ENCL)
13 4MDP ILINE MB 1 I-Line Panelboard O97321-0013-01-1.PDF
PNLB
(INT,BOX,F O97321-0013-01-2.PDF
RT)
Product data sheet HC4286WP
Characteristics HCP 42 INCH WIDE by 86 INCH HIGH
TYPE3R/12 I-LINE PANELBOARD ENCLOSURE
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product I-Line
Product or component type Enclosure
Device application Panelboard
Device short name HCP

Complementary
Line Rated Current 800 A
1200 A
400 A
600 A
Enclosure nominal width 1067 mm
Enclosure nominal height 2184 mm
Enclosure nominal depth 241 mm

Environment
NEMA degree of protection NEMA 3R/12
Standards CSA
UL

Ordering and shipping details


Category 00110 - RTA PANELBOARD BOXES - SPECIAL, 3R, ETC.
Discount Schedule PE1A
GTIN 00785901077220
Nbr. of units in pkg. 1
Package weight(Lbs) 419
Returnability Y

Sep 20, 2018


Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE

INTERIOR MOUNTING STUDS

,----\ ~

\ 0
8

H +1.20

~
[J1] A

~ I I ___i_
8

I ~ w :.8. ~ I
~ [2>]~
JYP!CAI FRONT VIEW

rtpiCAI ENDWAII

REFER TO DP CATALOG CLASS 2110 FOR ADDITlONAl INFORMATlON

1-UNE PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA.

BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED PHOSPHATIZED STEEL
INCLUDES HINGED COVER. MOUNTS TO WALL WITH MOUNTING CHANNEL AND SWINGABLE
MOUNTING BRACKET.
LOCK: CHROME-PLATED HANDLE LOCK. NSR-251 KEY CHANGE. NO PROVISIONS FOR PADLOCK. DUAL DIMENSIONS: INCHES
MIWMETERS

NOTE: NEMA TYPE JR/12 ENCLOSURE FOR HCN, HCM, AND HCP 1-UNE PANELBOARDS.

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: I-LINE HCN,HCM,HCP TYPE 3R 12
DRAWN BY: DRAWl NG TYPE:
ENGR: r;:::;J Sl"jjl IAFIE D
DATE: JULY 2007 l!::::::!J Schneider Electric
DWG PG OF REV-
Product data sheet HCW68TSD
Characteristics Trim - I-Line PNLBRD - hcp - surface - 4 pcs - w/
door - 42x68 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range I-Line
Product or Component Type Trim
Parts Quantity 4

Complementary
Product Destination Panelboard HCP 42 in 68 in
Device Mounting Surface
Number of Door 1

Environment
Standards CE
cULus

Ordering and shipping details


Category 00112 - I-LINE PB RTA TRIMS
Discount Schedule PE1A
GTIN 00785901089490
Nbr. of units in pkg. 1
Package weight(Lbs) 92
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 19, 2018


Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
Product data sheet HC4268DB
Characteristics HCP 42 INCH WIDE by 68 INCH HIGH TYPE1 I-
LINE PANELBOARD ENCLOSURE
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product I-Line
Product or component type Enclosure
Device application Panelboard
Device short name HCP

Complementary
Line Rated Current 1200 A
400 A
600 A
800 A
Enclosure nominal width 1067 mm
Enclosure nominal height 1727 mm
Enclosure nominal depth 241 mm

Environment
NEMA degree of protection NEMA 1
Standards CSA
UL

Ordering and shipping details


Category 07979 - I-LINE RTA N1 PB BOX - STD
Discount Schedule PE1A
GTIN 00785901792048
Nbr. of units in pkg. 1
Package weight(Lbs) 136.27000000000001
Returnability Y

Sep 19, 2018


Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE ----
---- -- -- ----

.42 DIA FLUSH


MOUNTING 4[1124] 4 ~
[11]
2.00 SURFACE 42.25
[51] MOUNTING [1073]

0 • • •
• • •
s s DIRECTORY • •
0 [DJ [DJ 0
LOCK
[DJ [DJ
L - ...J

[DJ [DJ +2.00


A H [51]

H (!)
[DJ [DJ

• z
:r:F
LJ.I (!) ~ '5
0 0
CJ~-'o
< I- u...::::;;
u.:z
a,:::,
:::,0
V)::::;;

• - -• - •
0 0
• • • • •
2.00
1.701
[43]
• 42.00
[1067] •
11.70
[43] [51]
~ 9.50
[241] ~ lYPICAL FRQNT
( 4 PIECE TRIM - WITH DOOR)

1~
JYPICAL BQX WITH INIERIQR

'.Id
lYPICAL BQX
SIPE VIEW


-== -== -==
s

s


I [DJ [DJ

lYPICAL MQIJNIING QE BP, BG, Bi.I, BK, PG,


[)J, PL,EA- EC, ED, EG, El:::I, El, EJ, EK, El'., [DJ [DJ

l::IP, l::IG, l::IJ, l::IL, JP, JG, JJ, JL,


KA, KC, Kl::I, Kl, LA LC, LE, Ll::I, U, [DJ [DJ

LX, LXI, MG, MJ, eG, PJ. eK, eL. Q2,


Q2l::I, Q2-l::I, QB, QP, QG, OJ. QR QQ, BREAKERS [DJ [DJ
FRONT CENTER
BUS BUS

s s

BRANCH CONNECTION PHASING IS


DETERMINED BY CIRCUIT BREAKER SELECTION

• -- -- --
iiiiiiiiiiiiiii

lYelCAL SIJREACE ERQNT


iiiiiiiiiiiiiii


( 4 PIECE TRIM - NO DOOR)
iiiiiiiiiiiiiii


REFER TO DP CATALOG CLASS 2110 FOR ADDITIONAL INFORMATION

I-LINE HCP PANELBOARDS MEET THE APPLICABLE REQUIREMENTS


OF UL AND CSA. INCHES
DUAL DIMENSIONS:
MILLIMETERS
BOX: CODE GAUGE GALVANIZED STEEL WITH REMOVABLE
BLANK ENDWALLS.
MAXIMUM MLO BRANCH BREAKER H A
FRONT: CODE GAUGE STEEL. GRAY BAKED ENAMEL FISHISH ELECTRODEPOSITED OR BF-MCB MOUNTING SPACE
OVER CLEANED PHOSPHATIZED STEEL. AMPERE RATING (INCHES)
IN MM IN MM
LOCK: (COVERS WITH DOORS) HAVE 3 POINT ESCUTCHEON FLUSH 27 50.00 1270 20.40 518
225A
LOCK WITH NSR-251 KEY. 45 59.00 1499 38.40 975
THRU
63 68.00 1727 47.40 1204
800A
FOR NEMA TYPE 3R APPLICATIONS USE IN CONJUNCTION WITH PBA412. 99 86.00 2184 65.10 1654

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: I-LINE HCP MLO OR BF-MCB
DRAWN BY: DRAWING TYPE:
ENGR:
DATE: MARCH 2018
DWG PBA418
....................E:]
SC)UARE

PG 01 OF 01 REV -
DRAWING STATUS:
Product data sheet M800S
Characteristics TYPE 1 300 to 800A SURFACE MOUNT
MOULDED CASE CIRCUIT BREAKER
ENCLOSURE
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Circuit breaker type MGL
MJL
PGL
PJL
PKL
PLL

Complementary
Enclosure material Steel
Width 533.4 mm
Height 1025.52 mm
Depth 247.65 mm
Line Rated Current 300...800 A
Device mounting Surface
Poles description 2P
3P

Environment
NEMA degree of protection NEMA 1
Product certifications CSA
UL

Ordering and shipping details


Category 00030 - IND CB ENCL NEMA 1,3R
Discount Schedule DE1
GTIN 00785901430438

Sep 19, 2018


Nbr. of units in pkg. 1
Package weight(Lbs) 95.460000000000008
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1434  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
Product data sheet AL800SN
Characteristics NEUTRAL ASSEMBLY 1000A
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Circuit breaker type Standard

Complementary
AWG gauge AWG 6...250 kcmil 1 aluminium
AWG 3/0...500 kcmil 6 aluminium/copper

Ordering and shipping details


Category 00030 - IND CB ENCL NEMA 1,3R
Discount Schedule DE1
GTIN 00785901239826
Nbr. of units in pkg. 1
Package weight(Lbs) 5.5800000000000001
Returnability Y
Country of origin US

Offer Sustainability
RoHS (date code: YYWW) Will be compliant  on  3Q2014
Will be compliant  on  3Q2014
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Sep 20, 2018


Contractual warranty
Warranty period 18 months
WIRING DIAGRAM

21.00
[533] 1/~ASHED LINE
NOICATES HOOD A
I:~: r))r B
.un
:~:
)))
------------------------- ---------
,, -r bb 'J.'Ul
\.44 = DIA
[11] I CIRCUIT
CIRCUIT BREAKER lERMINAL LUG DATA
WIRE SIZE
BREAKER AMPERE CONDUCTORS (AWG/KCt.tiL) lYPE
(4 HOLES) COVER HANDLESJ CATALOG NO. RATING PER PHASE
PREFIX MAX MIN
(2) PLACES

[Q
MGL,t.1JL J00-800A AL
PGL.PJL.PKL.PLL 250-800A 3 500 3/0 OR
40.38 40.38 cu
[1026]
35.16 [1026]
[893]
FIELD INSTALLABLE NEUTRAL ASSEMBUES AND GROUND KIT
WIRE SIZE
CATALOG t.IAXIMUM NUMBER OF CONDUCTORS
AMPERE PER
(AWG/KCMIL) lYPE
NUMBER RATING TERt.tiNALS lERMINAL MAX MIN

ALBOOSN BOOA '


(3 IN-3 OUT)
1


500 3/0

I
= ' l 2.00
[51] • SNBOOSNI AND
(2) SN1200 BOOA
16
(B IN 8 OUT)
2
1


250
500 '
3/0 AL
,, ,,
•• S33576 AND B
2
1
350
500 '
3/0
OR
cu
2.0~j
[5l] 2.16
j _16.0?,- L2.16
1-- ::jT
9.75
[248]
SJ3576MK
PKOGTA4 ...
BOOA (4 IN-4 OUT)
4
2
1
• 300
300
4
6
[55] [406] [55] . INCHES
DUAL DIMENSIONS. MILUMETERS

FIELD INSTAL!ABLE CIRCUIT BREAKER DATA


UL LISTED INTERRUPTING RATING
I
'I CIRCUIT
BREAKER
CATALOG NO.
WIRING
0~
AMPERE
RATING
RMS SYMMETRICAL At.IPERES
AC VOLTAGE DC VOLTAGE
FEDERAL
SPECS
W-C-375B/
I 9.75 PREFIX
240 4BOY/277 480 600 125 250 600
GEN
_18]
M800S
A - - -
I w w
NEMA/EEMAC 1YPE 1
MGL
B
300-800 65K 35K 35K 1BK
- - - X

MJL
A 300-800 100K 65K 65K 25K
- - - X
20.32 NO KNOCKOUTS B - - -
[516]
PGL
• A
B
250-800 65K 35K 35K 1BK
- - - X

NOlES:
FINISH - GRAY BAKED ENAt.tEL ELECTRODEPOSITED OVER CLEANED PHOSPHATIZED STEEL.
PJL
• A
B
250-800 100K 65K 65K 25K
-
-
-
-
-
- X

cULus - FILE E136861 CE MARKED.


SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT WHEN NEUTRAL ASSEMBLY IS INSTALLED.
PKL
• A
B
250-800 65K 50K 50K 50K
-
-
-
-
-
- X

NEUTRAL - INSULAlED GROUNDABLE.


THE SHORT CIRCUIT CURRENT RATING OF THIS ENCLOSED CIRCUIT BREAKER, INDICAlED ON CHART
ABOVE, MAY BE LESS THAN THE AIR RATING INDICAlED ON THE INSTALLED CIRCUIT BREAKER.
PLL
• A
B
250-800 125K 100K 100K 25K
- - - X

* FOR 200" NEUTRAL APPUCATION.


** NEUTRAL AND NEUTRAL CT FOR USE ON INTEGRAL GROUND FAULT PROlECTION APPUCATION. APPLICABLE ONLY TO
""" 01 11ARED
P-FRAME, 400-800A
• NUMBER OF TERMINALS FOR SERVICE GROUND CONDUCTORS.
.&. GROUND KIT.
• STANDARD OR 1OOX RAlED, BOOA MAX.
CIRCUIT BREAKER ENCLOSURES
250-800 AMPERE
NEMA/EEMAC TYPE 1 GENERAL PURPOSE ENCLOSURE
IIJI Schneider Electric

~~ 3432
DECEMBER 2014
Product data sheet MH26WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 26 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure

Complementary
Material Steel
Width 20 in
Height 26 in
Depth 6.5 in
Device mounting Surface

Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus

Ordering and shipping details


Category 00110 - RTA PANELBOARD BOXES - SPECIAL, 3R, ETC.
Discount Schedule PE1A
GTIN 00785901798040
Nbr. of units in pkg. 1
Package weight(Lbs) 50
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 20, 2018


Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds which is known to the State of California to cause cancer and
- - - - - - - Substance 2 Bisphenol A (BPA) which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE

'-INTERIOR
MOUNTING STUDS

H+1.46 H+.86
A
~
H [37] [22]

X
SEE
NOTE
BELOW

1.00
0 0
[25]

0 0

L....:.......J
II II L....:.......J

~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]

TYPICAL BOX SIDE VIEW TYPICAL FRONT VIEW


20.98
[533]
!!,
I I

I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS

INCHES
DUAL DIMENSIONS: MILLIMITERS

BOX HEIGHT MOUNTING INTERIOR HEIGHT


CATALOG NUMBER H A
IN MM IN MM
NOTE: FOR "X" DIMENSION, SUBTRACT 6.60/[168] FROM THE BOX HEIGHT.
MH26WP 26.00 660 21.00 533
REFER TO DP CATALOG CLASS 1640 FOR ADDITIONAL INFORMATION MH32WP 32.00 813 27.00 686
NQ PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA. MH38WP 38.00 965 33.00 838
MH44WP 44.00 1118 39.00 991
BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED MH50WP 50.00 1270 45.00 1143
PHOSPHATIZED STEEL. INCLUDES HINGED COVER. MOUNTS TO WALL MH56WP 56.00 1422 51.00 1295
MH62WP 62.00 1575 57.00 1448
WITH MOUNTING BRACKETS.
MH68WP 68.00 1727 63.00 1600
LOCK: CHROME-PLATED HANDLE LOCK. NSR 251 KEY. MH74WP 74.00 1880 69.00 1753
NOT PROVISIONS FOR PADLOCK. MH80WP 80.00 2032 75.00 1905
MH86WP 86.00 2184 81.00 2057
UNLESS OTHERWISE NOTED ALL DIMENSIONS ARE NOMINAL.

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: NQ NEMA 3R 5 12 ENCLOSURES
DRAWN BY: DRAWING TYPE:
ENGR: SQUARE E:)
DATE: AUGUST 2017 _, ..................
DRAWING STATUS: DWG MH26WP PG 01 OF 01 REV -
Product data sheet MH32WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 32 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure

Complementary
Material Steel
Width 20 in
Height 32 in
Depth 6.5 in
Device mounting Surface

Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus

Ordering and shipping details


Category 00110 - RTA PANELBOARD BOXES - SPECIAL, 3R, ETC.
Discount Schedule PE1A
GTIN 00785901056782
Nbr. of units in pkg. 1
Package weight(Lbs) 58
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 20, 2018


Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds which is known to the State of California to cause cancer and
- - - - - - - Substance 2 Bisphenol A (BPA) which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE

'-INTERIOR
MOUNTING STUDS

H+1.46 H+.86
A
~
H [37] [22]

X
SEE
NOTE
BELOW

1.00
0 0
[25]

0 0

L....:.......J
II II L....:.......J

~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]

TYPICAL BOX SIDE VIEW TYPICAL FRONT VIEW


20.98
[533]
!!,
I I

I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS

INCHES
DUAL DIMENSIONS: MILLIMITERS

BOX HEIGHT MOUNTING INTERIOR HEIGHT


CATALOG NUMBER H A
IN MM IN MM
NOTE: FOR "X" DIMENSION, SUBTRACT 6.60/[168] FROM THE BOX HEIGHT.
MH26WP 26.00 660 21.00 533
REFER TO DP CATALOG CLASS 1640 FOR ADDITIONAL INFORMATION MH32WP 32.00 813 27.00 686
NQ PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA. MH38WP 38.00 965 33.00 838
MH44WP 44.00 1118 39.00 991
BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED MH50WP 50.00 1270 45.00 1143
PHOSPHATIZED STEEL. INCLUDES HINGED COVER. MOUNTS TO WALL MH56WP 56.00 1422 51.00 1295
MH62WP 62.00 1575 57.00 1448
WITH MOUNTING BRACKETS.
MH68WP 68.00 1727 63.00 1600
LOCK: CHROME-PLATED HANDLE LOCK. NSR 251 KEY. MH74WP 74.00 1880 69.00 1753
NOT PROVISIONS FOR PADLOCK. MH80WP 80.00 2032 75.00 1905
MH86WP 86.00 2184 81.00 2057
UNLESS OTHERWISE NOTED ALL DIMENSIONS ARE NOMINAL.

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: NQ NEMA 3R 5 12 ENCLOSURES
DRAWN BY: DRAWING TYPE:
ENGR: SQUARE E:)
DATE: AUGUST 2017 _, ..................
DRAWING STATUS: DWG MH26WP PG 01 OF 01 REV -
Product data sheet MH38
Characteristics NQNF Panelboard Enclosure Box, Type 1, 20 x
38 x 5.75 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure

Complementary
Material Steel
Width 20 in
Height 38 in
Depth 5.75 in

Environment
Enclosure Rating NEMA 1
Product certifications CULus

Ordering and shipping details


Category 07969 - RTA PANELBOARD BOX - STD NEMA 1
Discount Schedule PE1A
GTIN 00785901378884
Nbr. of units in pkg. 1
Package weight(Lbs) 27.800000000000001
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
Sep 20, 2018
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE - ---- -- -- --
- ---- -- -- -- - ---- -- -- --

19.12 KNOCKOUTS
2.50
[ 486]
±.20 __J [64]
TYP
SYMBOL
CONDUIT SIZE
IN MM
KNOCKOUT DIA
IN MM
A .50 13 .88 22
O® G) ®
B .75 19 1.12 28
c:=::J D 1.25 32 1.75 44
E 1.50 38 2.00 51
• •
F 2.00 51 2.50 64
G 2.50 64 3.00 76
H 3.00 76 3.62 92
3.50 89 4.12 105
L

M • • s

• •

0 ® G) ® ---Ft---~

3.00
[76]
TYP
L- 10.44
[265]
20.12
[511] --
4.78
[121]

DUAL DIMENSIONS. MILLIMETERS


. INCHES
DIMPLES ARE
.30/[8] DEEP
REFERENCE L s M
CATALOG
NO IN MM IN MM IN MM
MH26 26.00 660 21.00 533 20.00 508
MH32 32.00 813 27.00 686 26.00 660
D,E,F,G,H,1
MH38 38.00 965 33.00 838 32.00 813
MH44 44.00 1118 39.00 991 38.00 965
MH50 50.00 1270 45.00 1143 44.00 1118
MH56 56.00 1422 51.00 1295 50.00 1270
MH62 62.00 1575 57.00 1448 56.00 1422
MH68 68.00 1727 63.00 1600 62.00 1575
MH74 74.00 1880 69.00 1753 68.00 1727
MH80 80.00 2032 75.00 1905 74.00 1880
MH86 86.00 2184 81.00 2057 80.00 2032
MH92 92.00 2337 87.00 2210 86.00 2184

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: NEMA 1 BOXES
DRAWN BY: DRAWING TYPE:
ENGR:
DATE: JULY 2018
DWG PBA600
....................E:]
SQUARE

PG 1 OF 1 REV -
DRAWING STATUS:
Product data sheet MH38WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 38 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure

Complementary
Material Steel
Width 20 in
Height 38 in
Depth 6.5 in
Device mounting Surface

Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus

Ordering and shipping details


Category 00110 - RTA PANELBOARD BOXES - SPECIAL, 3R, ETC.
Discount Schedule PE1A
GTIN 00785901798071
Nbr. of units in pkg. 1
Package weight(Lbs) 69
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 19, 2018


Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds which is known to the State of California to cause cancer and
- - - - - - - Substance 2 Bisphenol A (BPA) which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE

'-INTERIOR
MOUNTING STUDS

H+1.46 H+.86
A
~
H [37] [22]

X
SEE
NOTE
BELOW

1.00
0 0
[25]

0 0

L....:.......J
II II L....:.......J

~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]

TYPICAL BOX SIDE VIEW TYPICAL FRONT VIEW


20.98
[533]
!!,
I I

I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS

INCHES
DUAL DIMENSIONS: MILLIMITERS

BOX HEIGHT MOUNTING INTERIOR HEIGHT


CATALOG NUMBER H A
IN MM IN MM
NOTE: FOR "X" DIMENSION, SUBTRACT 6.60/[168] FROM THE BOX HEIGHT.
MH26WP 26.00 660 21.00 533
REFER TO DP CATALOG CLASS 1640 FOR ADDITIONAL INFORMATION MH32WP 32.00 813 27.00 686
NQ PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA. MH38WP 38.00 965 33.00 838
MH44WP 44.00 1118 39.00 991
BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED MH50WP 50.00 1270 45.00 1143
PHOSPHATIZED STEEL. INCLUDES HINGED COVER. MOUNTS TO WALL MH56WP 56.00 1422 51.00 1295
MH62WP 62.00 1575 57.00 1448
WITH MOUNTING BRACKETS.
MH68WP 68.00 1727 63.00 1600
LOCK: CHROME-PLATED HANDLE LOCK. NSR 251 KEY. MH74WP 74.00 1880 69.00 1753
NOT PROVISIONS FOR PADLOCK. MH80WP 80.00 2032 75.00 1905
MH86WP 86.00 2184 81.00 2057
UNLESS OTHERWISE NOTED ALL DIMENSIONS ARE NOMINAL.

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: NQ NEMA 3R 5 12 ENCLOSURES
DRAWN BY: DRAWING TYPE:
ENGR: SQUARE E:)
DATE: AUGUST 2017 _, ..................
DRAWING STATUS: DWG MH26WP PG 01 OF 01 REV -
Product data sheet MH50WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 50 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure

Complementary
Material Steel
Width 20 in
Height 50 in
Depth 6.5 in
Device mounting Surface

Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus

Ordering and shipping details


Category 00110 - RTA PANELBOARD BOXES - SPECIAL, 3R, ETC.
Discount Schedule PE1A
GTIN 00785901798095
Nbr. of units in pkg. 1
Package weight(Lbs) 89
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 19, 2018


Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds which is known to the State of California to cause cancer and
- - - - - - - Substance 2 Bisphenol A (BPA) which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE

'-INTERIOR
MOUNTING STUDS

H+1.46 H+.86
A
~
H [37] [22]

X
SEE
NOTE
BELOW

1.00
0 0
[25]

0 0

L....:.......J
II II L....:.......J

~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]

TYPICAL BOX SIDE VIEW TYPICAL FRONT VIEW


20.98
[533]
!!,
I I

I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS

INCHES
DUAL DIMENSIONS: MILLIMITERS

BOX HEIGHT MOUNTING INTERIOR HEIGHT


CATALOG NUMBER H A
IN MM IN MM
NOTE: FOR "X" DIMENSION, SUBTRACT 6.60/[168] FROM THE BOX HEIGHT.
MH26WP 26.00 660 21.00 533
REFER TO DP CATALOG CLASS 1640 FOR ADDITIONAL INFORMATION MH32WP 32.00 813 27.00 686
NQ PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA. MH38WP 38.00 965 33.00 838
MH44WP 44.00 1118 39.00 991
BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED MH50WP 50.00 1270 45.00 1143
PHOSPHATIZED STEEL. INCLUDES HINGED COVER. MOUNTS TO WALL MH56WP 56.00 1422 51.00 1295
MH62WP 62.00 1575 57.00 1448
WITH MOUNTING BRACKETS.
MH68WP 68.00 1727 63.00 1600
LOCK: CHROME-PLATED HANDLE LOCK. NSR 251 KEY. MH74WP 74.00 1880 69.00 1753
NOT PROVISIONS FOR PADLOCK. MH80WP 80.00 2032 75.00 1905
MH86WP 86.00 2184 81.00 2057
UNLESS OTHERWISE NOTED ALL DIMENSIONS ARE NOMINAL.

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: NQ NEMA 3R 5 12 ENCLOSURES
DRAWN BY: DRAWING TYPE:
ENGR: SQUARE E:)
DATE: AUGUST 2017 _, ..................
DRAWING STATUS: DWG MH26WP PG 01 OF 01 REV -
Product data sheet MH74WP
Characteristics NQNF Panelboard Enclosure Box, Type 3R/5/12,
20 x 74 x 6.5 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Enclosure

Complementary
Material Steel
Width 20 in
Height 74 in
Depth 6.5 in
Device mounting Surface

Environment
Enclosure Rating NEMA 3R/5/12
Product certifications CULus

Ordering and shipping details


Category 00110 - RTA PANELBOARD BOXES - SPECIAL, 3R, ETC.
Discount Schedule PE1A
GTIN 00785901083276
Nbr. of units in pkg. 1
Package weight(Lbs) 123
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 20, 2018


1
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds which is known to the State of California to cause cancer and
- - - - - - - Substance 2 Bisphenol A (BPA) which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
REV DESCRIPTION BY DATE

'-INTERIOR
MOUNTING STUDS

H+1.46 H+.86
A
~
H [37] [22]

X
SEE
NOTE
BELOW

1.00
0 0
[25]

0 0

L....:.......J
II II L....:.......J

~n1~~;~j 6.88
[175]
1 0.44=-J
[265]
15.44
[392]

TYPICAL BOX SIDE VIEW TYPICAL FRONT VIEW


20.98
[533]
!!,
I I

I I
20.34
[517]
TYPICAL MOUNTING OF TYPICAL ENDWALL
QO, QOB BREAKERS

INCHES
DUAL DIMENSIONS: MILLIMITERS

BOX HEIGHT MOUNTING INTERIOR HEIGHT


CATALOG NUMBER H A
IN MM IN MM
NOTE: FOR "X" DIMENSION, SUBTRACT 6.60/[168] FROM THE BOX HEIGHT.
MH26WP 26.00 660 21.00 533
REFER TO DP CATALOG CLASS 1640 FOR ADDITIONAL INFORMATION MH32WP 32.00 813 27.00 686
NQ PANELBOARDS MEET THE APPLICABLE REQUIREMENTS OF UL AND CSA. MH38WP 38.00 965 33.00 838
MH44WP 44.00 1118 39.00 991
BOX: GRAY BAKED ENAMEL FINISH ELECTRODEPOSITED OVER CLEANED MH50WP 50.00 1270 45.00 1143
PHOSPHATIZED STEEL. INCLUDES HINGED COVER. MOUNTS TO WALL MH56WP 56.00 1422 51.00 1295
MH62WP 62.00 1575 57.00 1448
WITH MOUNTING BRACKETS.
MH68WP 68.00 1727 63.00 1600
LOCK: CHROME-PLATED HANDLE LOCK. NSR 251 KEY. MH74WP 74.00 1880 69.00 1753
NOT PROVISIONS FOR PADLOCK. MH80WP 80.00 2032 75.00 1905
MH86WP 86.00 2184 81.00 2057
UNLESS OTHERWISE NOTED ALL DIMENSIONS ARE NOMINAL.

JOB NAME: EQUIPMENT DESIGNATION:


JOB LOCATION: EQUIPMENT TYPE: NQ NEMA 3R 5 12 ENCLOSURES
DRAWN BY: DRAWING TYPE:
ENGR: SQUARE E:)
DATE: AUGUST 2017 _, ..................
DRAWING STATUS: DWG MH26WP PG 01 OF 01 REV -
Product data sheet NC38S
Characteristics NQNF Panelboard Enclosure Surface Cover,
Type 1, 20 x 38 in
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Surface cover
Color Grey
Cover type Surface cover

Complementary
Material Steel
Width 20 in
Height 38 in

Environment
Enclosure Rating NEMA 1
Product certifications CULus

Ordering and shipping details


Category 08352 - NF / NQ TRIMS RTA
Discount Schedule PE1A
GTIN 00785901798866
Nbr. of units in pkg. 1
Package weight(Lbs) 19.800000000000001
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1419  -  Schneider Electric declaration of conformity

Sep 20, 2018


Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Nickel compounds which is known to the State of California to cause cancer and
- - - - - - - Substance 2 Bisphenol A (BPA) which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
CATALOG A B C
NUMBER IN MM IN MM IN MM
NC26S 26.12 663 17.70 436 6.16 156
NC32S 32.12 816 23.70 602 9.16 233
NC38S 38.12 968 29.70 754 12.16 309
NC44S 44.12 1121 35.70 907 15.16 385
NC50S 50.12 1273 41.70 1059 18.16 461
NC56S 56.12 1425 47.70 1212 21.16 537
NC62S 62.12 1578 53.70 1364 24.16 614
NC68S 68.12 1730 59.70 1516 27.16 690
NC74S 74.12 1883 65.70 1669 30.16 766
NC80S 80.12 2035 71.70 1821 33.16 842
NC26F 27.52 699 17.70 436 6.16 156
NC32F 33.52 851 23.70 602 9.16 233
NC38F 39.52 1004 29.70 754 12.16 309
NC44F 45.52 1156 35.70 907 15.16 385
NC50F 51.52 1309 41.70 1059 18.16 461
NC56F 57.52 1461 47.70 1212 21.16 537
NC62F 63.52 1613 53.70 1364 24.16 614
NC68F 69.52 1766 59.70 1516 27.16 690
NC74F 75.52 1918 65.70 1669 30.16 766
NC80F 81.52 2071 71.70 1821 33.16 842
B REF NC86S 86.12 2187 77.70 1974 36.16 918
NC86F 87.52 2071 77.70 1974 36.16 918
C REF
.05 NC35S 35.12 892 26.70 678 10.66 271
2.00
[1] [51] NC35F 36.52 928 26.70 678 10.66 271
TYP
NC41S 41.12 1044 32.70 831 13.66 347
NC41F 42.52 1080 32.70 831 13.66 347
NC92S 92.12 2340 83.70 2126 39.16 995
= .. = = c:::::::::)c.=)c.=) •• c:::::::::)
= = c:::::::::) •• c:::::::::)c:::::::::)c:::::::::)
= = .. = 20.12
[511]
(.'.)
12.93 w 21.52
2.77 u<( z
3.44
[87] D [70]
[328]
REF LL z
Ct'.
=:)
U)
f-
=:)
0
2
[547]

:r: z
U)
(.'.)

f-
=:) z
= = = === = = = = === = = = _J =:)
LL 0
2

l
=
-----------------------A REF------------------------
= =
DUAL DIMENSIONS: INCHES
MILLIMETERS

,.
PANELBOARD COVER SQUARE E:]
TRIM TYPE 1 by Schnelder Electric
SURFACE/FLUSH
DWG#
NO. PWFDS-SYTl-0164
OCTOBER 2017 NC26S
Product data sheet EDB14020
Characteristics E-Frame Brkr 20A, 1P, 277V, 18/25kA, Bolt-on
Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EDB
Module type E-Frame
Trip unit rating 875 A

Complementary
Line Rated Current 20 A
System Voltage 277 V AC
AWG gauge AWG 14...AWG 6 copper
AWG 12...AWG 6 aluminium
Breaking capacity 18 kA 277 V AC
18 kA 240 V AC
25 kA 120 V AC
18 kA 120/240 V AC
Circuit breaker application HACR rated
Switching Duty rated
HID rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 270 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 1
Number of spaces 1
Number of spaces required 1
Product destination Panelboard NF
Sep 19, 2018
Product weight 2 lb(US)
Protection type Short-circuit
Overload
Width 0.98 in
Trip unit technology Thermal-magnetic
Breaking capacity code D

Environment
Product certifications CULus
IEC
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00931 - EDB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901878902
Nbr. of units in pkg. 12
Package weight(Lbs) 1.3200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet QOB120
Characteristics QO Mini CB 20 A 1P 120/240 V 10 kA Bolt-on
Mount
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Miniature circuit-breaker
Range QO
Line Rated Current 20 A
System Voltage 120 V AC
120/240 V AC
48 V DC
Mounting Type Bolt-on
Number of Poles 1P
Circuit Breaker Type Standard
Ratings HACR and Switching Duty rated
Electrical Connection Pressure plate

Complementary
Inturrupt Rating 10 kA at: 120/240 V AC
5 kA at: 48 V DC
10 kA at: 120 V AC
Number of Panel Spaces 1
Wire Size AWG 14...AWG 8 (copper or aluminium)
Height 3 in
Depth 2.91 in
Width 0.75 in

Environment
Certifications CSA
UL listed
Ambient Rating 104 °F (40 °C)

Sep 20, 2018


Ordering and shipping details
Category 00015 - QOB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901416722
Nbr. of units in pkg. 10
Package weight(Lbs) 0.27000000000000002
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0701  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet QOB220H
Characteristics QO Mini CB 20 A 2P 120/240 V 10 kA Bolt-on
Mount
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Miniature circuit-breaker
Range QO
Line Rated Current 20 A
System Voltage 120 V AC
120/240 V AC
240 V AC
Mounting Type Bolt-on
Number of Poles 2P
Circuit Breaker Type Standard
Ratings HACR rated
Electrical Connection Pressure plate

Complementary
Inturrupt Rating 10 kA at: 120/240 V AC
10 kA at: 120 V AC
10 kA at: 240 V AC
Number of Panel Spaces 2
Wire Size AWG 14...AWG 8 (copper or aluminium)
Height 3 in
Depth 2.91 in
Width 1.5 in

Environment
Certifications UL listed
CSA
Ambient Rating 104 °F (40 °C)

Sep 20, 2018


Ordering and shipping details
Category 00015 - QOB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901368274
Nbr. of units in pkg. 1
Package weight(Lbs) 0.55000000000000004
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1323  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet EJB34020
Characteristics E-Frame Brkr 20A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 875 A

Complementary
Line Rated Current 20 A
System Voltage 480Y/277 V AC
AWG gauge AWG 14...AWG 6 copper
AWG 12...AWG 6 aluminium
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HID rated
HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 270 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Sep 20, 2018
Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J

Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00937 - EJB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901326380
Nbr. of units in pkg. 1
Package weight(Lbs) 3.6200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet QOB230H
Characteristics QO Mini CB, 30A, 2P, 120/240V, 10kA, Bolt-on
Mount
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product Miniature circuit-breaker
Range QO
Line Rated Current 30 A
System Voltage 120 V AC
120/240 V AC
240 V AC
Mounting Type Bolt-on
Number of Poles 2P
Circuit Breaker Type Standard
Ratings HACR rated
Electrical Connection Pressure plate

Complementary
Inturrupt Rating 10 kA at: 120/240 V AC
10 kA at: 120 V AC
10 kA at: 240 V AC
Number of Panel Spaces 2
Wire Size AWG 14...AWG 8 (copper or aluminium)
Height 3 in
Depth 2.91 in
Width 1.5 in

Environment
Certifications CSA
UL listed
Ambient Rating 104 °F (40 °C)

Sep 20, 2018


Ordering and shipping details
Category 00015 - QOB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901341802
Nbr. of units in pkg. 1
Package weight(Lbs) 0.55000000000000004
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1323  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet BJL36030LU
Characteristics PowerPact-circuit breaker-30A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 030
Product or component type Circuit breaker
Device application Distribution

Complementary
[In] rated current 30 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2

Sep 20, 2018


10 kA : at 690 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV according to IEC 60947-2
[Ui] rated insulation voltage 800 V according to IEC 60947-2
Trip unit technology Thermal-magnetic
Trip unit name TM-D
Trip unit protection functions LI
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Trip unit rating 30 A at 40 °C
Magnetic hold current 400 A
Magnetic tripping current 600 A
Suitability for isolation Yes according to IEC 60947-2
Utilisation category Category A
Mechanical durability 15000 cycles IEC 947-1 Annex K ed 5.2
Electrical durability 10000 cycles according to IEC 947-1 Annex K ed 5.2 for In at 440 V
Connection pitch 27 mm
Local signalling Green flag for presence of auxiliary contacts
Toggle padlocking (with accessories) Padlock in OFF or ON position
Connections - terminals Upside 1 EverLink lug with voltage tap-off wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded
copper
Downside 1 Everlink lug wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded copper
Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or
stranded aluminium/copper
Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/
copper
Control wire terminal 10 A for 0.5...6 mm² ( AWG 20...AWG 10) , (stranded or fine stranded)
10 A for 1.5...6 mm² ( AWG 20...AWG 10) , (rigid)
Tightening torque 5 N.m for 2.5...16 mm² (AWG 14...AWG 4)
9 N.m for 25...95 mm² (AWG 3...AWG 3/0)
Number of slots 1 slot(s) for auxiliary switch OF (plug-in)
1 slot(s) for voltage release MN or MX (plug-in)
1 slot(s) for alarm switch SD (plug-in)
Power wire stripping length 20 mm
Quality labels CE
Standards EN/IEC 60947-2
EN/IEC 60947-5-1
GB 14048.2
NEMA AB1
UL 489
CSA C22.2 No 5
NMX J-266
Colour Grey (RAL 7016)
9 mm pitches 9
Height 137 mm
Width 81 mm
Depth 80 mm
Product weight 1.074 kg
Quantity per set Set of 1

Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1644  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34030
Characteristics E-Frame Brkr 30A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 875 A

Complementary
Line Rated Current 30 A
System Voltage 480Y/277 V AC
AWG gauge AWG 14...AWG 6 copper
AWG 12...AWG 6 aluminium
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
HID rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 270 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Sep 20, 2018
Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J

Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00937 - EJB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901435327
Nbr. of units in pkg. 6
Package weight(Lbs) 3.6200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet HDL36030SA
Characteristics PowerPact H Circuit
Breaker,ThermMagn,30A,3P,600V,14kA, Shunt
Trip
Product availability : Non-Stock - Not normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code D
Options Shunt trip 120 V AC

Complementary
Line Rated Current 30 A
Number of Poles 3P
Interrupt Rating 18 kA at 480 V AC
25 kA at 240 V AC
14 kA at 600 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 80 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 350 A
Magnetic tripping current 750 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in

Sep 20, 2018


Environment
Product certifications CCC
CE
CSA
IEC
UL listed
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 01110 - HD,JD UNIT MT BREAKER/SWITCH
Discount Schedule DE2
GTIN 00785901654865
Nbr. of units in pkg. 1
Package weight(Lbs) 5
Returnability N
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0832  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
Product data sheet HJL36030T
Characteristics PowerPact H Circuit
Breaker,ThermMagn,30A,3P,600V,25kA,
Removable TU
Product availability : Non-Stock - Not normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code J

Complementary
Line Rated Current 30 A
Number of Poles 3P
Interrupt Rating 65 kA at 480 V AC
25 kA at 600 V AC
100 kA at 240 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 80 %
Trip Unit Field installable trip unit
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 350 A
Magnetic tripping current 750 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in

Sep 20, 2018


Environment
Product certifications UL listed
IEC
CCC
CSA
CE
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 01115 - HG,HJ,JG,JJ UNIT MT BREAKER/SWITCH
Discount Schedule DE2
Nbr. of units in pkg. 1
Package weight(Lbs) 4
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0832  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
Product data sheet BJL36040LU
Characteristics PowerPact-circuit breaker-40A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 040
Product or component type Circuit breaker
Device application Distribution

Complementary
[In] rated current 40 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2

Sep 20, 2018


10 kA : at 690 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV according to IEC 60947-2
[Ui] rated insulation voltage 800 V according to IEC 60947-2
Trip unit technology Thermal-magnetic
Trip unit name TM-D
Trip unit protection functions LI
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Trip unit rating 40 A at 40 °C
Magnetic hold current 400 A
Magnetic tripping current 600 A
Suitability for isolation Yes according to IEC 60947-2
Utilisation category Category A
Mechanical durability 15000 cycles IEC 947-1 Annex K ed 5.2
Electrical durability 10000 cycles according to IEC 947-1 Annex K ed 5.2 for In at 440 V
Connection pitch 27 mm
Local signalling Green flag for presence of auxiliary contacts
Toggle padlocking (with accessories) Padlock in OFF or ON position
Connections - terminals Upside 1 EverLink lug with voltage tap-off wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded
copper
Downside 1 Everlink lug wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded copper
Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or
stranded aluminium/copper
Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/
copper
Control wire terminal 10 A for 0.5...6 mm² ( AWG 20...AWG 10) , (stranded or fine stranded)
10 A for 1.5...6 mm² ( AWG 20...AWG 10) , (rigid)
Tightening torque 5 N.m for 2.5...16 mm² (AWG 14...AWG 4)
9 N.m for 25...95 mm² (AWG 3...AWG 3/0)
Number of slots 1 slot(s) for auxiliary switch OF (plug-in)
1 slot(s) for voltage release MN or MX (plug-in)
1 slot(s) for alarm switch SD (plug-in)
Power wire stripping length 20 mm
Quality labels CE
Standards EN/IEC 60947-2
EN/IEC 60947-5-1
GB 14048.2
NEMA AB1
UL 489
CSA C22.2 No 5
NMX J-266
Colour Grey (RAL 7016)
9 mm pitches 9
Height 137 mm
Width 81 mm
Depth 80 mm
Product weight 1.074 kg
Quantity per set Set of 1

Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1644  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34050
Characteristics E-Frame Brkr 50A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 1800 A

Complementary
Line Rated Current 50 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HID rated
HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 630 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF
Sep 19, 2018
Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J

Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00937 - EJB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901335238
Nbr. of units in pkg. 1
Package weight(Lbs) 3.6200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet BJL36060LU
Characteristics PowerPact-circuit breaker-60A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 060
Product or component type Circuit breaker
Device application Distribution

Complementary
[In] rated current 60 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2

Sep 20, 2018


10 kA : at 690 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV according to IEC 60947-2
[Ui] rated insulation voltage 800 V according to IEC 60947-2
Trip unit technology Thermal-magnetic
Trip unit name TM-D
Trip unit protection functions LI
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Trip unit rating 60 A at 40 °C
Magnetic hold current 640 A
Magnetic tripping current 960 A
Suitability for isolation Yes according to IEC 60947-2
Utilisation category Category A
Mechanical durability 15000 cycles IEC 947-1 Annex K ed 5.2
Electrical durability 10000 cycles according to IEC 947-1 Annex K ed 5.2 for In at 440 V
Connection pitch 27 mm
Local signalling Green flag for presence of auxiliary contacts
Toggle padlocking (with accessories) Padlock in OFF or ON position
Connections - terminals Upside 1 EverLink lug with voltage tap-off wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded
copper
Downside 1 Everlink lug wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded copper
Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or
stranded aluminium/copper
Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/
copper
Control wire terminal 10 A for 0.5...6 mm² ( AWG 20...AWG 10) , (stranded or fine stranded)
10 A for 1.5...6 mm² ( AWG 20...AWG 10) , (rigid)
Tightening torque 5 N.m for 2.5...16 mm² (AWG 14...AWG 4)
9 N.m for 25...95 mm² (AWG 3...AWG 3/0)
Number of slots 1 slot(s) for auxiliary switch OF (plug-in)
1 slot(s) for voltage release MN or MX (plug-in)
1 slot(s) for alarm switch SD (plug-in)
Power wire stripping length 20 mm
Quality labels CE
Standards EN/IEC 60947-2
EN/IEC 60947-5-1
GB 14048.2
NEMA AB1
UL 489
CSA C22.2 No 5
NMX J-266
Colour Grey (RAL 7016)
9 mm pitches 9
Height 137 mm
Width 81 mm
Depth 80 mm
Product weight 1.074 kg
Quantity per set Set of 1

Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1644  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34060
Characteristics E-Frame Brkr 60A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 1800 A

Complementary
Line Rated Current 60 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 630 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF

Sep 20, 2018


Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J

Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00937 - EJB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901335245
Nbr. of units in pkg. 1
Package weight(Lbs) 3.6200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet HDL36060SA
Characteristics PowerPact H Circuit
Breaker,ThermMagn,60A,3P,600V,14kA, Shunt
Trip
Product availability : Non-Stock - Not normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code D
Options Shunt trip 120 V AC

Complementary
Line Rated Current 60 A
Number of Poles 3P
Interrupt Rating 18 kA at 480 V AC
25 kA at 240 V AC
14 kA at 600 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 80 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 800 A
Magnetic tripping current 1450 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in

Sep 20, 2018


Environment
Product certifications CCC
CE
CSA
IEC
UL listed
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 01110 - HD,JD UNIT MT BREAKER/SWITCH
Discount Schedule DE2
GTIN 00785901590972
Nbr. of units in pkg. 1
Package weight(Lbs) 5
Returnability N
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0832  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
~-6.40
[162,6]
¢.20
~-5.66
[5,1]
[143,8] (MOUNTING HOLE}
.74
[18,8]
1.38
1.38 [35,0]
[35,0]

2.06 f
[52,4] + - - - - - + - - - 4.12
[104,7]

.44
1.38 [11,3]
[35,0] 1.37
1.20 [34,8]
[30,5]
2.04
[51,9]
4.99 ISOMETRIC VIEW
[126,7] SCALE 1:2
5.20
[132,1]
~-5.96
[151,3]

l~ r~~O]
.43
19.5° [10,8]
ON

SEEDETAIL A
t
'
"
4.36
3.44 3.74 [110,8]
[87,4] 1.91 [95,1] .62
[15,9]
[48,5]

~3.69 DETAIL A
[93,8] SCALE 1:1

t-CA:_:r_M.OG
__ N_UM_B_ER_:_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _--t~ E3 THIRD
DESCRIPTION: H-Frame 15A- 150A 3P Toggle Lug-Lug ~ ANGLE
"THE SQUARE D COMPANY HAS PROPRIETARY RIGHTS TO THE INFORMATION
CONTAINED HEREON. THIS INFORMATION REMAINS THE PROPERTY OF
BA'IARE D
DRAWN BY: LRG DATE: 12AUG2003
SQUARED COMPANY AND MAY BE USED ONLY IN CONFORMANCE WITH
INSTRUCTlONS ISSUED BY SQUARE D CO. DO NOT SCALE DRAWING Schneider Electric
USER SHOULD VERIFY DRAWINGS ARE TO THE LATEST/CURRENT CHECKED BY: RLS DATE: 11 MAR2004 UNLESS OTHERWISE SPECIFIED
REVISION PRIOR TO INCORPORATlNG IN A DESIGN FILE: DIMENSIONS ARE
DRAWING FILE: 48996-012-01 .DRW _Hi_ DRAWING NUMBER _ _ REVISION
ECN: J582 mm 48996 012 0 1 0
Product data sheet HJL36060C
Characteristics PowerPact H Circuit
Breaker,ThermMagn,60A,3P,600V,25kA
Product availability : Non-Stock - Not normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code J

Complementary
Line Rated Current 60 A
Number of Poles 3P
Interrupt Rating 65 kA at 480 V AC
25 kA at 600 V AC
100 kA at 240 V AC
20 kA at 250 V DC
System Voltage 250 V DC
600 V AC
Continuous current rating 100 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 800 A
Magnetic tripping current 1450 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in

Environment
Product certifications CE

Sep 20, 2018


CSA
IEC
UL listed
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 01115 - HG,HJ,JG,JJ UNIT MT BREAKER/SWITCH
Discount Schedule DE2
GTIN 00785901636632
Nbr. of units in pkg. 1
Package weight(Lbs) 4
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0832  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet EJB34070
Characteristics E-Frame Brkr 70A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 1800 A

Complementary
Line Rated Current 70 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 630 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF

Sep 20, 2018


Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J

Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00937 - EJB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901130635
Nbr. of units in pkg. 1
Package weight(Lbs) 3.6200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet BJL36080LU
Characteristics PowerPact-circuit breaker-80A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 080
Product or component type Circuit breaker
Device application Distribution

Complementary
[In] rated current 80 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2

Sep 20, 2018


10 kA : at 690 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV according to IEC 60947-2
[Ui] rated insulation voltage 800 V according to IEC 60947-2
Trip unit technology Thermal-magnetic
Trip unit name TM-D
Trip unit protection functions LI
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Trip unit rating 80 A at 40 °C
Magnetic hold current 800 A
Magnetic tripping current 1200 A
Suitability for isolation Yes according to IEC 60947-2
Utilisation category Category A
Mechanical durability 15000 cycles IEC 947-1 Annex K ed 5.2
Electrical durability 10000 cycles according to IEC 947-1 Annex K ed 5.2 for In at 440 V
Connection pitch 27 mm
Local signalling Green flag for presence of auxiliary contacts
Toggle padlocking (with accessories) Padlock in OFF or ON position
Connections - terminals Upside 1 EverLink lug with voltage tap-off wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded
copper
Downside 1 Everlink lug wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded copper
Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or
stranded aluminium/copper
Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/
copper
Control wire terminal 10 A for 0.5...6 mm² ( AWG 20...AWG 10) , (stranded or fine stranded)
10 A for 1.5...6 mm² ( AWG 20...AWG 10) , (rigid)
Tightening torque 5 N.m for 2.5...16 mm² (AWG 14...AWG 4)
9 N.m for 25...95 mm² (AWG 3...AWG 3/0)
Number of slots 1 slot(s) for auxiliary switch OF (plug-in)
1 slot(s) for voltage release MN or MX (plug-in)
1 slot(s) for alarm switch SD (plug-in)
Power wire stripping length 20 mm
Quality labels CE
Standards EN/IEC 60947-2
EN/IEC 60947-5-1
GB 14048.2
NEMA AB1
UL 489
CSA C22.2 No 5
NMX J-266
Colour Grey (RAL 7016)
9 mm pitches 9
Height 137 mm
Width 81 mm
Depth 80 mm
Product weight 1.074 kg
Quantity per set Set of 1

Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1644  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

3
Product data sheet BJL36090LU
Characteristics PowerPact-circuit breaker-90A 3P AC 65kA at
480/440V(UL/IEC)-TMD-EverLink lug

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerPact
Product name PowerPact B
Device short name BJ 090
Product or component type Circuit breaker
Device application Distribution

Complementary
[In] rated current 90 A
Poles description 3P
Protected poles description 3t
Control type Toggle
Mounting mode By screws for plate
Clip-on for 35 mm symmetrical DIN rail
Network type AC
Network frequency 50/60 Hz
Breaking capacity code J
Breaking capacity 100 kA at 240 V AC 50/60 Hz according to UL 489
65 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 100 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
Icu : 65 kA at 440 V AC 50/60 Hz according to IEC 60947-2
Icu : 25 kA at 500...525 V AC 50/60 Hz according to IEC 60947-2
Icu : 10 kA at 690 V AC 50/60 Hz according to IEC 60947-2
65 kA at 480Y/277 V AC 50/60 Hz according to UL 489
25 kA at 600Y/347 V AC 50/60 Hz according to UL 489
100 kA at 208Y/120 V AC 50/60 Hz according to UL 489
[Ue] rated operational voltage 690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity 100 kA : at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA : at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA : at 500...525 V AC 50/60 Hz according to IEC 60947-2

Sep 20, 2018


10 kA : at 690 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV according to IEC 60947-2
[Ui] rated insulation voltage 800 V according to IEC 60947-2
Trip unit technology Thermal-magnetic
Trip unit name TM-D
Trip unit protection functions LI
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Trip unit rating 90 A at 40 °C
Magnetic hold current 1000 A
Magnetic tripping current 1500 A
Suitability for isolation Yes according to IEC 60947-2
Utilisation category Category A
Mechanical durability 15000 cycles IEC 947-1 Annex K ed 5.2
Electrical durability 10000 cycles according to IEC 947-1 Annex K ed 5.2 for In at 440 V
Connection pitch 27 mm
Local signalling Green flag for presence of auxiliary contacts
Toggle padlocking (with accessories) Padlock in OFF or ON position
Connections - terminals Upside 1 EverLink lug with voltage tap-off wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded
copper
Downside 1 Everlink lug wire size 2.5...70 mm² (AWG 14...AWG 2/0) , fine stranded copper
Upside 1 EverLink lug with voltage tap-off wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or
stranded aluminium/copper
Downside 1 Everlink lug wire size 2.5...95 mm² (AWG 14...AWG 3/0) , rigid or stranded aluminium/
copper
Control wire terminal 10 A for 0.5...6 mm² ( AWG 20...AWG 10) , (stranded or fine stranded)
10 A for 1.5...6 mm² ( AWG 20...AWG 10) , (rigid)
Tightening torque 5 N.m for 2.5...16 mm² (AWG 14...AWG 4)
9 N.m for 25...95 mm² (AWG 3...AWG 3/0)
Number of slots 1 slot(s) for auxiliary switch OF (plug-in)
1 slot(s) for voltage release MN or MX (plug-in)
1 slot(s) for alarm switch SD (plug-in)
Power wire stripping length 20 mm
Quality labels CE
Standards EN/IEC 60947-2
EN/IEC 60947-5-1
GB 14048.2
NEMA AB1
UL 489
CSA C22.2 No 5
NMX J-266
Colour Grey (RAL 7016)
9 mm pitches 9
Height 137 mm
Width 81 mm
Depth 80 mm
Product weight 1.074 kg
Quantity per set Set of 1

Environment
Product certifications UL
CSA
CCC
EAC
NOM
IEC
IP degree of protection IP40 (front cover) according to IEC 60529
IK degree of protection IK07 according to IEC 62262
Pollution degree 3 according to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Operating altitude 5000 m with derating
2000 m without derating

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1644  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
Product data sheet EJB34090
Characteristics E-Frame Brkr 90A, 3P, 480Y/277V, 65/100kA,
Bolt-on Mnt
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product 125 A Frame EDB-EGB-EJB
Product or component type Miniature circuit-breaker
Device short name EJB
Module type E-Frame
Trip unit rating 2300 A

Complementary
Line Rated Current 90 A
System Voltage 480Y/277 V AC
AWG gauge AWG 12...AWG 2/0 aluminium
AWG 14...AWG 2/0 copper
Breaking capacity 65 kA 277 V AC
65 kA 480Y/277 V AC
100 kA 120 V AC
100 kA 120/240 V AC
100 kA 240 V AC
Circuit breaker application HACR rated
Depth 4.05 in
Electrical connection Lugs
Height 5.66 in
Holding current 1000 A
Local signalling Trip indicator
Mounting mode Bolt-on
Number of poles 3
Number of spaces 3
Number of spaces required 3
Product destination Panelboard NF

Sep 20, 2018


Product weight 4 lb(US)
Protection type Short-circuit
Overload
Width 2.94 in
Trip unit technology Thermal-magnetic
Breaking capacity code J

Environment
Product certifications CULus
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 00937 - EJB CIRCUIT BREAKERS
Discount Schedule DE2
GTIN 00785901723783
Nbr. of units in pkg. 1
Package weight(Lbs) 3.6200000000000001
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1423  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
Product data sheet LA36400
Characteristics 3P 400A 600V, LA FA/LA MOLDED CASE
CIRCUIT BREAKER
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product I-Line
Trip Unit Type Thermal-magnetic
Rating Code A

Complementary
Line Rated Current 400 A
Number of Poles 3P
Interrupt Rating 25 kA at 600 V AC
42 kA at 240 V AC
30 kA at 480 V AC
System Voltage 250 V DC
600 V AC
Mounting mode I-Line
Electrical connection I-Line connection line
Lugs load
Wire Gauge AWG 1...600 kcmil (aluminium/copper) 1 cable(s)
AWG 1...250 kcmil (aluminium/copper) 2 cable(s)
Terminal Type AL400LA
Magnetic hold current 2000 A
Magnetic tripping current 4000 A
Wiring configuration 3-wire
Phase connection ABC
Height 11 in
Width 6 in
Depth 5.84 in

Sep 19, 2018


Environment
Product certifications CSA
UL listed

Ordering and shipping details


Category 01040 - LA/LH BRKR, SW, MAG-GARD
Discount Schedule DE2
GTIN 00785901426325
Nbr. of units in pkg. 1
Package weight(Lbs) 18.34
Returnability Y
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1304  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months
CATALOG NUMBERING

A, H, OR c __.J
260R36
I
-
.I
L (•) L (••) (***)

SEE CHART BELOW


-26=2POLE
_!;l,.tJ:!!;q[_CJ<o[!!Ol[O. i!<OJllOJL'ii>.O«

36 = 3 POLE Wire bendin s ace is based u on the maximum


wire size af t~e ~ermlnal, and Nfrc article 430-10.
Wire bending sftace for the bottom Is the '"("""'
125 - -400 AMP - 125- 250 AMP: some os he top wire bending space. _
INCREMENT BY 25 14 00
250 - -400 AMP:
INCREMENT BY 50 5.9B
~387~
-
2.B1
86 1.58 I-
LAL (Standard Interrupting)
Ratings: BOOVAC/250VDC, 125 - 400 AMPERE
LHL (High Interrupting)
,.J _f
I

... l4.27

) ~-----1~,
Ratings: BOOVAC/250VDC, 125 - 400 AMPERE ON
LCL (Extra High Interrupting)
Ratings: BOOVAC, 300 - -400 AMPERE 11.00
~ 7'1RIPPE01
9.25
If" II-- lj®

l£E'~··-
---..: ~
l)._ 3r

LAL lie LHL (125 - 400 AMP)


11'
'RESET
. OFF

r l
OFF
Wire Size: (1) f1 BOO kcmil
Terminal Torque: -
=<!:"1
LCL (300 - -400 AMP)
Wire Size: (2) 14/0
Terminal Torque: -
- 500 kcrnn

5.81-
.88

D - 2.00-
1.98 f--

200t[ff
'h ~
.3.~J
Catalog Number: SEE CHART
Ratings: SEE CHART 't { ~
UL File/Guide: E10027 .34- I-
CSA File/Guide: LR7551 - l-1.26
Meets Standards: IEC 157-1
Weight: 8.50 lbs.
Wire Size: SEE CHART
Terminal torque:
Mounting Hwd.:
-
8-32 SCREWS

--$--a- CIRCUIT BREAKERS )JOOA FRAMEt


~
"THE SQUARE D COIIF'NIY HAS PRII'RIETARY RIGHTS TO THE IN'tllt.tATlON CONTAit£D 111111 -..E
HERE!Iol. THS IN'tllt.tATlON REMAINS TI£ PROPERTY OF SQUARE D COMPANY ANl MAY ~"" (THERMAL MAGNETIC OLDED CAS ) 513LJARE D CCJVIR<>.NY
BE USED ONLY IN CONFORMANCE WTH INSTRUCliONS ISSUED BY SWARE D COWPANY. !01 FRANCES
SEE CHART
USER SIOllD 'o'ERIFY DRA'MNGS ARE TO THE L.ATEST/DJIHNT REVISION PRIOR
DO NOT SCALE DRAWING UNLESS CTlER\IISE SPECF1m
TO INCORI"<mllNG IN A DESIGN AlE." INE9S cntEJit&: SI'ECFED IIIIEMSUIS N£ .. ~IHS 2 PL.O.CE CECI.IIILS :t .D1 :"' LA-LC-LH_3P _400A_OUTLINE_001
DECEMBER 2000 E1001501
Product data sheet MJL36400
Characteristics PowerPact M Molded CASE CIRCUIT BREAKER
600V 400A 3P
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact M
Breaking capacity code J
Trip unit technology Electronic basic ET 1.0 LI

Complementary
Current sensor rating range 400 A
Line Rated Current 400 A
System Voltage 600 V AC
Mounting mode Unit mount
Poles description 3P
Breaking capacity 100 kA 240 V AC
65 kA 480 V AC
25 kA 600 V AC
Continuous current rating 80 %
Electrical connection Lugs load
Lugs line
AWG gauge AWG 3/0...500 kcmil aluminium/copper 3(cables(s))

Environment
Product certifications CSA
IEC
UL listed

Ordering and shipping details


Category 01205 - MG, MJ UNIT MOUNT BREAKER
Discount Schedule DE2
Sep 19, 2018
GTIN 00785901701828
Nbr. of units in pkg. 1
Package weight(Lbs) 28.890000000000001
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1323  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
Product data sheet MJA36600
Characteristics PowerPact M Molded CASE CIRCUIT BREAKER
600V 600A 3P
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact M
Breaking capacity code J
Trip unit technology Electronic basic ET 1.0 LI

Complementary
Current sensor rating range 600 A
Line Rated Current 600 A
System Voltage 600 V AC
Mounting mode Plug-in
Poles description 3P
Breaking capacity 100 kA 240 V AC
65 kA 480 V AC
25 kA 600 V AC
Continuous current rating 80 %
Electrical connection I-Line connection line
Lugs load
AWG gauge AWG 3/0...500 kcmil aluminium/copper 3(cables(s))
Magnetic tripping current 1200...6000 A

Environment
Product certifications CSA
IEC
UL listed

Ordering and shipping details


Category 01200 - MG, MJ I-LINE BREAKER
Sep 19, 2018
Discount Schedule DE2
GTIN 00785901504757
Nbr. of units in pkg. 1
Package weight(Lbs) 29.190000000000001
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1323  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months
Product data sheet MJL36800
Characteristics PowerPact M Molded CASE CIRCUIT BREAKER
600V 800A 3P
Product availability : Stock - Normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact M
Breaking capacity code J
Trip unit technology Electronic basic ET 1.0 LI

Complementary
Current sensor rating range 800 A
Line Rated Current 800 A
System Voltage 600 V AC
Mounting mode Unit mount
Poles description 3P
Breaking capacity 100 kA 240 V AC
65 kA 480 V AC
25 kA 600 V AC
Continuous current rating 80 %
Electrical connection Lugs load
Lugs line
AWG gauge AWG 3/0...500 kcmil aluminium/copper 3(cables(s))

Environment
Product certifications CSA
IEC
UL listed

Ordering and shipping details


Category 01205 - MG, MJ UNIT MOUNT BREAKER
Discount Schedule DE2
Sep 19, 2018
GTIN 00785901655398
Nbr. of units in pkg. 1
Package weight(Lbs) 29.080000000000002
Returnability Y
Country of origin US

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  1323  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available

Contractual warranty
Warranty period 18 months
7.87

-
[200,0] f.22
- [5,5]
~ 1/-
' •
0 0
r---1 h
~ li:
•• c 3.92
[9~,5~
~

....~
.,-
~
~
~-
==---
r-
......,
r--
r-··-
~
~
.83
[199,0]
0

Cl

- c
ID

:i '" 1111
aD I'(
~
•~
!;=;
.
1-4------- 8.27
.30 [210,0]
[7,51.49
[12,5] ~--7.40
[188,0]
2.56
[64,9]

l
~---.26
[6,5]
1-4------ .43
6] [11 ,0]

5.78
[146,8]
3.84
[97,6]
t
~-5.00
[126,9]
~---12.86
t-----8.27
[326,6] [210,0]
_ _N_u_M_BE_R_:
t-CA:_:r_M.OG
DESCRIPTION:
-----------------------t~
C4RUUIEC 3P SODA ~
E3 THIRD
ANGLE
"THE SQUARE D COMPANY HAS PROPRIETARY RIGHTS TO THE INFORMATION
CONTAINED HEREON. THIS INFORMATION REMAINS THE PROPERTY OF
BA'IARE D
SQUARED COMPANY AND MAY BE USED ONLY IN CONFORMANCE WITH DRAWN BY: wre DATE: 25MAR2004
DO NOT SCALE DRAWING Schneider Electric
INSTRUCTlONS ISSUED BY SQUARE D CO.
USER SHOULD VERIFY DRAWINGS ARE TO THE LATEST/CURRENT CHECKED BY: DATE: UNLESS OTHERWISE SPECIFIED
REVISION PRIOR TO INCORPORATlNG IN A DESIGN FILE: DIMENSIONS ARE
DRAWING FILE: 48096-445-01 .DRW _Hi_ DRAWING NUMBER -4 _ REVISION
ECN: K026 mm 48096 45 0 1
Product data sheet HLL36060LV
Characteristics PowerPact H Circuit
Breaker,ThermMagn,60A,3P,600V,50kA,Control
Wire
Product availability : Non-Stock - Not normally stocked in distribution facility

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product or component type Circuit breaker
Range of product PowerPact H
Trip Unit Type Thermal-magnetic
Breaking capacity code L
Options Control wire at OFF end

Complementary
Line Rated Current 60 A
Number of Poles 3P
Interrupt Rating 125 kA at 240 V AC
100 kA at 480 V AC
50 kA at 600 V AC
20 kA at 250 V DC
50 kA at 500 V DC
System Voltage 250 V DC
500 V DC
600 V AC
Continuous current rating 80 %
Mounting mode Unit mount
Electrical connection Lugs load
Lugs line
Wire Gauge AWG 14...AWG 3/0 (aluminium/copper)
Magnetic hold current 800 A
Magnetic tripping current 1450 A
Height 6.4 in
Width 4.12 in
Depth 4.36 in
Sep 20, 2018
Environment
Product certifications CCC
CE
CSA
IEC
UL listed
Ambient air temperature for operation 104 °F (40 °C)

Ordering and shipping details


Category 01120 - HL,JL UNIT MT BREAKER/SWITCH
Discount Schedule DE2
Nbr. of units in pkg. 1
Package weight(Lbs) 4.1600000000000001
Returnability N
Country of origin MX

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0832  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 DINP, which is known to the State of California to cause cancer, and
- - - - - - - Substance 2 DIDP, which is known to the State of California to cause Birth Defects or other reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov

Contractual warranty
Warranty period 18 months

You might also like