ANNEX 01 - Technical specifications

1. 220kV Circuit Breaker:

Item
Description Warranty
No.

1 Manufacturer/Country of Origin GE T&D INDIA LTD/ INDIA


2 Ordering number GL314
3 Applicable standard IEC 62271-100
Outdoor, three single-pole and
4 Type 1
three-pole operation

Outdoor, three single-pole


5 Type 2
operation
6 Insulating medium SF6
7 Rated voltage 245 kV
8 Rated frequency 50 Hz
9 Rated current (In) for type 3150 A
Rated three phase symmetrical short-circuit
10 50 kA rms
breaking current
Rated three phase symmetrical short circuit
11 125 kAp
making current
12 Rated duration of short-circuits 3s
13 Rated Operating Sequence O-0.3s-CO-3min-CO
Lightning impulse voltage (1.2/50ms) withstand
14 1050 kV peak
to earth
One minute power frequency voltage withstand to
15 460 kV rms
earth 50 Hz

16 First-pole-to-clear factor 1.3

17 Minimum creepage distance 25 mm/kV

18 Operating mechanism Three-pole/single pole


19 Operating mechanism drive type Spring
20 Minimum clearance between phases 3640 mm
21 Minimum clearance from phase to earth 2490 mm
22 Operating times: (*)
-Maximum opening time ≤ 50 ms
-Maximum closing time ≤ 72 ms

23 Rated out-of phase breaking current 12,5 kA

24 Rated line charging breaking current 125 A


Page 1 of 4
Item
Description Warranty
No.

25 Rated cable charging breaking current 250 A

26 Rated small inductive breaking current 100 A


Rated transient recovery voltage for terminal
27 364 kVp
faults (T100)
28 Transient recovery voltage (TRV) 364 kVp
29 Rate of rise recovery voltage (RRRV) 2 kV/μs
30 Auxiliary power supply
- Voltage for heating and spring charged motor 220 V AC
- Control, tripping voltage 220Vdc ~ (70%-110%) *220Vdc

- Control, closing voltage 220Vdc ~ (85%-110%) *220Vdc


-Total burden of tripping and closing coils for
345 W per coil
three phase
31 Number of tripping coil for type 1 Total 6
Number of tripping coil for type 2 6
32 Number of closing coil for type 1 Total 3
Number of closing coil for type 2 3
> 10,000 cycles (closing-
33 Mechanical operation duration(In- class M2)
opening)
Type test for Mechanical operation duration
34 (The contractor must provide type tests to Yes
demonstrate the parameters offered.)
Times tripping of 50kA short circuit current
35 10
without repair
Times tripping of 25kA short circuit current
36 40
without repair
Major inspection and maintenance (interrupter
37 and mechanism unit) shall not be required at less yes
than 25-year intervals
38 SF6-loss-rate / year < 0,5%

Wiring in control cubicle including :


+ Anti-pumping device
+ Pole discrepancy device
+ Local/remote control switch
39 + SF6 density meter with alarm/trip contact Yes
+ Auxiliary contact: 12NO & 12NC (minium)
+ Auxiliary contacts for charged spring signal and
motor control
+ Heating and lighting device

Page 2 of 4
Item
Description Warranty
No.
Common local control cabinet :- For type of
single-pole circuit breaker, the common local
control cabinet (combined from local control
cubicles of three single - pole circuit breaker)
must be equipped. The common local control
shall allow operating independently
closing/opening on each phase and operating
40 Yes
simultaneously closing/opening on three phases
of circuit breaker. Common control cabinet with
connecting cables for electrical coupling of
control cabinet with operating mechanism cubicle
on each phase. Separate cables for power supply
of motor&heating,lighting from common local
cabinet to each phase.
Aluminium IP55
41 Control cubicle of Circuit Breaker
protection level
42 Insulating bushing Ceramic, brown
43 Rated capacitive breaking current 400 A
44 Number of spare auxiliary contact
Normally opened 12
Normally closed 12
45 Materials of terminals
HV Aluminium
46 Steel structure
Type Yes
Materials Yes
47 Rated times quantities of circuit breaker
Opening time (no-load) ≤27
Closing time (no-load) ≤72
Open-close time (no-load) ≤300
Reclosing time (no-load) ≤350
Close-open time (no-load) <70
48 SF6 gas
SF6 mass for one three-pole circuit breaker 18.1 kgs per CB
0.75 MPa (abs) at
Rated SF6 density
20deg.C
0.64 MPa (abs) at
First threshold of SF6 density
20deg.C
0.61 MPa (abs) at
Second threshold of SF6 density
20deg.C
SF6 gas pressure density gauss Yes
Max. noise level at 3 meters distance due to
49 <140dB
operation of circuit breaker
3957 daN upwards & 4415 daN
50 Max. impact load due to circuit breaker operation
downwards
Page 3 of 4
Item
Description Warranty
No.
51 Rated mechanical terminal load kN Please refer OGA drg.
52 Total weight of complete circuit breaker 3000kg (approx)
Terminals (Dimensions : Holes - No. , size and 125 mm x 125 mm; 4 holes;
53
spacing) 14mm dia; 50 mm spacing
HV Al.
54 Drawings of steel structure Yes

Page 4 of 4