You are on page 1of 69

Zelio Control

Monitoring &
Control Relays
Catalog
December 2016
Quick access to Product information
Select your Catalogue, your Training

With just 3 clicks, you can reach the 7,000 pages


of the Automation & Industrial Control catalogue,
in both English and French.
–– Digi-Cat is available on a USB key (for PC). To get your Digi-Cat, please
contact your local center
–– Download Digi-Cat from this address:

http://digi-cat.schneider-electric.com/download.html

Find your training


–– Find the right training for your needs
–– Locate the training center with the selector tool, using this address:
http://www.schneider-electric.com/b2b/en/services/training/technical-training.jsp

then click on
General contents

Zelio Control – Monitoring & Control Relays


bb General Presentation ............................................................................... page 2
Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4

bb RM17TG 3-phase supply control relays................................................. page 12


bb R
 M22TA, RM22TU, RM22TR, and RM22TG
Multifunction 3-phase supply control relays......................................... page 14
bb RM17Tp00 Multifunction 3-phase supply control relays...................... page 18
bb RM35TF Multifunction 3-phase supply control relays.......................... page 22
bb RM17UB3 and RM35UB3 3-phase voltage control relays..................... page 24
bb RM35TM 3-phase supply and motor temperature control relays......... page 28
bb RM17UAS and RM17UBE 1-phase voltage control relays.................... page 32
bb RM35UA Multifunction 1-phase voltage control relays........................ page 36
bb RM22UA and RM22UB 1-phase voltage control relays......................... page 38
bb R
 M17JC 1-phase current control relays with
integrated current transformer................................................................ page 42
bb RM22JA and RM35JA 1-phase current control relays.......................... page 44
bb RM35JA 1-phase current control relays................................................. page 48
bb RM22LA and RM22LG Liquid level control relays................................. page 50
bb RM35L Level control relays.................................................................... page 54
bb RM35BA 3-phase and 1-phase pump control relays............................. page 58
bb RM35HZ Frequency control relay........................................................... page 60
bb RM35S Speed control relay..................................................................... page 62
bb R
 M35ATp Temperature control relays for elevator machine rooms
and 3-phase supplies.............................................................................. page 66
bb Electrode holders and probes................................................................ page 68
bb Product reference index . ....................................................................... page 70

1
General presentation Zelio Control – Monitoring &
Control Relays

Zelio Control – Monitoring & Zelio Control relays monitor and detect abnormal operating conditions concerning
phase, current, voltage, frequency, speed, or temperature. The relays inform users
Control Relays of abnormal conditions, and allow them to initiate the necessary corrective actions
before serious and costly breakdowns can occur. By monitoring energy network
statuses, they enable both electrical and mechanical load control.

RM17T, RM35L, RM17J Zelio Control Relays

They are suitable for a wide range of applications:


bb Hoisting: construction cranes, harbor cranes
bb Packaging: motor voltage, current overload
bb Lifts: construction lifts, passenger lifts, escalators
bb Textile: motor voltage, current overload
bb Water: liquid level on water tank at water and waste water recycling plant

Depending on the product model, control relays are categorized into 8 product
families:
bb 3-phase control
bb Current control
bb Voltage control
bb Frequency control
bb Speed control
bb Lift temperature control
bb Level control
bb Pump control

Zelio Control relay functions


Monitoring
Control relays monitor physical and electrical values. They measure variable signals
such as phase (presence, sequence and symmetry), voltage, current, and
frequency. They also control liquid levels and process operating rates.

Informing
Control device outputs provide users with electrical information. In addition, setting
faults are signaled by simultaneous flashing of all LEDs.

Protecting
Integrated in the control circuits of automated systems, they enable automatic
shutdown management and provide fault information, thus protecting the equipment.

Managing
When the power is switched on, the control relays are inhibited to enable correct
measurement circuit setting. The outputs operate with positive logic, the contact or
contacts being closed under normal conditions and opening as soon as a fault or
power supply loss is detected.

Commissioning
When the diagnostic button is used, the downstream circuit can be closed
immediately without sending a fault input signal to the relays. This shortens the
testing time during commissioning and troubleshooting.

Zelio Control A simple approach to monitoring your equipment


2
General presentation Zelio Control – Monitoring &
(continued) Control Relays

Zelio Control relays with unique design and features


>> Compact modular sizes: 17.5 mm/0.69 in., 22.5 mm/0.88 in., 35 mm/1.38 in.
>> Adapted for industrial and building control panels
>> True RMS measurement that minimizes the possibility of unexpected trips from
highly polluted networks
>> Diagnostic button to check the downstream circuit immediately and reduce
commissioning and troubleshooting time (1)
>> IP50 lead-sealable settings protection cover helps prevent dust and unintended
human intervention
>> Status indication by LEDs, additional dial pointer LED for easy setup in dark
conditions (1), and power “On” status indication when relay is ready to perform

Dial pointer LED indicator

Diagnostic button

>> Optimization of power supplies


>> Worldwide certification:
®

(1) Available in RM35JA32MR, RM35JA32MT, and all RM22 references.

Zelio Control To control your machines and processes of the future


3
Selection guide Zelio Control - Monitoring &
Control Relays

Application 3-phase control 3-phase control

Functions - Phase sequence - Phase sequence - Phase sequence - Phase sequence - Phase sequence - Phase sequence - Phase sequence - Overvoltage and - Phase sequence
- Phase loss - Phase loss - Phase loss - Phase loss - Phase loss - Phase loss - Phase loss undervoltage between - Phase loss
- Overvoltage and - Undervoltage - Asymmetry - Asymmetry - Asymmetry phases - Motor temperature
undervoltage - Overvoltage and - Overvoltage and
undervoltage undervoltage between
phases and neutral
- Absence of neutral/
phase

Values controlled 208…480 V a 183…528 V a 208…480 V a 200…240 V a 208…480 V a 200…240 V a 208…480 V a 200…240 V a 208…480 V a 220…480 V a 208…480 V a
208…440 V a 380…480 V a 380…480 V a 380…480 V a 220…480 V a 208…480 V a Motor temperature:
120…277 V a PTC probe resistance
15 Ω to 3100 Ω
Output contact rating 1 or 2 CO 5 A 2 CO 8 A 1 CO 5 A 2 CO 8 A 1 CO 5 A 2 CO 8 A 1 CO 5 A 2 CO 8 A 1 or 2 CO 5 A 1 CO or 2 CO 5A 2 NO 5 A

Supply voltage Self-powered Self-powered

Time delay – 0.1…30 s 0.1…10 s – 0.1…10 s 0.1…30 s 0.1…10 s 0.3…30 s –

Size (mm/in.) 17.5/0.69 22.5/0.885 17.5/0.69 22.5/0.885 17.5/0.69 22.5/0.885 17.5/0.69 22.5/0.885 17.5/0.69 or 35/1.377 17.5/0.69 or 35/1.377
35/1.377

Modular relay type RM17TGp0 RM22TG20 RM17TT00 RM22TR31 RM17TU00 RM22TU21 RM17TA00 RM22TA31 RM17TE00 RM17UB310 RM35TMp50MW
RM22TR33 RM22TU23 RM22TA33 RM35TF30 RM35UB3ppp

Pages 12 14 18 14 18 14 18 14 18, 22 24 28

4 5
Selection guide (continued) Zelio Control - Monitoring &
Control Relays

Application 1-phase voltage control 1- phase voltage control

Functions - Overvoltage or undervoltage with/without memory - Overvoltage (without memory) - Overvoltage (with/without memory) - Overvoltage and undervoltage in window mode
- Undervoltage (with/without memory)
- Overvoltage or undervoltage in
window mode (with/without memory)

Values controlled 9…15 V c 0.05…5 V z 0.05…5 V z 0.05…5 V z 20…80 V z 80…300 V z


20…80 V z 1…100 V z 1…100 V z 1…100 V z 65…260 V z
65…260 V z 15…600 V z 15…500 V z 15…500 V z

Output contact rating 1 CO 5 A 2 CO 5 A 2 CO 8 A 2 CO 8 A 1 CO 5 A 2 CO 8 A

Supply voltage Self-powered 24…240 V z 24…240 V z 24…240 V z Self-powered 110…240 V z


380…415 V a

Time delay 0.1…10 s 0.3…30 s – 0.1…30 s 0.1…10 s 0.1…30 s

Size (mm/in.) 17.5/0.69 35/1.377 22.5/0.885 22.5/0.885 17.5/0.69 22.5/0.885

Modular relay type RM17UAS1p RM35UA1pMW RM22UA21MR RM22UA31MR RM17UBE1p RM22UB34


RM22UA22MR RM22UA32MR
RM22UA23MR RM22UA33MR
RM22UA33MT

Pages 32 36 38 38 32 38

4
6 5
7
Selection guide (continued) Zelio Control - Monitoring &
Control Relays

Application 1-phase current control 1- phase current control

Functions Integrated current transformer No integrated current transformer No integrated current transformer
- Overcurrent without memory - Overcurrent with/without memory - Overcurrent with/without memory
- Undercurrent with/without memory - Undercurrent with/without memory
- Overcurrent and undercurrent with/without memory and window mode

Values controlled 2…20 A 4…100 mA 2…500 mA 4…100 mA


0.15…15 A 150...15,000 mA

Output contact rating 1 CO 5 A 2 CO 8 A 2 CO 5 A 2 CO 8 A

Supply voltage 24…240 V z 24…240 V z 24…240 V z 24…240 V z


380…415 V a

Time delay – Inhibition time delay upon startup 1…20 s 0.1…30 s


Time delay 0.3…30 s

Size (mm/in.) 17.5/0.69 22.5/0.885 35/1.377 22.5/0.885, 35/1.377

Modular relay type RM17JC00MW RM22JA21MR RM35JA31MW RM22JA31MR


RM35JA32MW RM35JA32MR
RM35JA32MT

Pages 42 44 48 44

6
8 7
9
Selection guide (continued) Zelio Control - Monitoring &
Control Relays

Application Level control Pump control Frequency control Speed control Temperature control for elevator machine rooms and
3-phase supplies

Functions By resistive probes By resistive probes By resistive probes By discrete sensor 3-phase and 1-phase - Over-frequency and - Over or under operating rate/ - Elevator Machine room - Elevator Machine room
- Level 1/Level 2 - Level 1/Level 2 - Level 1/Level 2 - Empty or fill - Overcurrent and undercurrent under-frequency (with/without speed (with/without memory) temperature temperature
- Fill operation - Fill operation - Fill operation - Input for discrete - Phase sequence on 3-phase memory) -Over temperature and under -Over temperature and
- Empty operation - Empty operation - Empty operation sensor AON: Contact/ supply temperature under temperature
- Standard sensitivity - Low sensitivity - Low sensitivity PNP/NPN - Phase loss on 3-phase supply - Phase loss and phase
- Standard sensitivity - Standard sensitivity sequence
- High sensitivity - High sensitivity

Values controlled 5…100 kΩ 0.25…5 kW 0.25…5 kΩ – Current: 1…10 A Mains supply: 50 or 60 Hz Time controlled between Temperature Temperature
5…100 kW 5…100 kΩ 3-phase 208…480 V a High threshold: - 2…+ 10 Hz pulses: Low threshold: - 1…11 °C Low threshold: - 1…11 °C
0.05…1 MW 0.05…1 MΩ 1-phase 230 V a Low threshold: - 10…+ 2 Hz 0.05…0.5 s, 0.1…1 s, High threshold: 34…46 °C High threshold: 34…46 °C
0.5…5 s, 1…10 s 3-phase supplies
0.1…1 min, 0.5…5 min, 208…480 V a
1…10 min

Output control rating 1 CO 8 A 2 CO 5 A 2 CO 8 A 1 CO 5 A 1 CO 5 A 2 CO 5 A 1 CO 5 A 1 CO 5 A or 2 NO 5 A


2 NO 5 A

Supply voltage 24…240 V z 24…240 V z 24…240 V z 24…240 V z 208…480 V a , 3-phase 120…277 V a 24…240 V z 24…240 V z 24…240 V z
380…415 V a 380…415 V a 230 V a, 1-phase

Time delay – 0.1…5 s 0.1…30 s 0.1…5 s Inhibition time delay upon 0.1…10 s Inhibition time delay upon 1…10 s
startup 1…60 s startup 0.6…60 s
Time delay 0.1…10 s

Size (mm/in.) 22.5/0.885 35/1.377 22.5/0.885 35/1.377 35/1.377 35/1.377 35/1.377 35/1.377 35/1.377

Modular relay type RM22LG11MR RM35LM33MW RM22LA32MR RM35LV14MW RM35BA10 RM35HZ21FM RM35S0MW RM35ATL0MW RM35ATW5MW
RM22LG11MT RM22LA32MT RM35ATR5MW

Pages 50 54 50 54 58 60 62 66 66

10
8 11
9
Presentation, Zelio Control - Monitoring &
description Control Relays
3-phase supply control relays
RM17TG

Presentation
RM17TGp0 measurement and control relays for 3-phase supplies monitor the
correct sequencing of phases L1, L2, and L3 and the total loss of one or more of
these phases.

Functions RM17TG
Sequence of phases L1, L2, and L3
Phase loss
Function performed
Function not performed

Depending on the model, RM17TG control relays:


bb Accept different nominal 3-phase voltage values
RM17TG00
vv 208…480 V a for RM17TG00
vv 208…440 V a for RM17TG20
bb Monitor their own power supply measured as a true rms value
bb Are designed for clip-on mounting on a 5 rail

The control status is indicated by an LED.

Applications
bb Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
bb Control against reverse motor operation (lifting, handling, elevators,
escalators, etc.)
bb Control of sensitive 3-phase supplies
bb Emergency power supply switching in abnormal conditions

Description
L1 L2 L3 L1 L2 L3
RM17TG00 , RM17TG20
24 21 22
1  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail

R R

12 11 14 12 11 14

1 1
RM17TG00 RM17TG20
R Yellow LED: indicates relay output status

12
Operation, Zelio Control - Monitoring &
references Control Relays
3-phase supply control relays
RM17TG

Operating principle
3-phase supply control relays monitor: Function Diagram
bb Correct sequencing of phases L1, L2, and L3
Output 11-14, 21-24 open
bb Fault signaling by LEDs
bb Total loss of one or more of the phases Output 11-14, 21-24 closed

RM17TGp0
Phase control
vv Sequence of phases L1, L2, and L3 The relays monitor:
vv Phase loss bb That the phase sequence and voltages are correct (> 183 V), the output relay(s)
Phase L1
100%
is/are closed and the yellow LED is on.
0%
L3 bb If a sequencing fault or total loss of one or more phases is detected (detected as
Phase L2
100%
soon as one of the voltages drops below 100 V), the relay opens instantly and the
0%
L2
LED goes off.
100%
Phase L3 bb On energization of the device with a detected measured fault, the relay stays
0%
open.
Relays R
Tr Tr Tr Tr

Note: Tr: response time on detection of a fault

References
Function Rated 3-phase Output Reference Weight
PF153401A
PF153400B

supply voltage
V kg/lb
bb Phase sequence 208…480 a 1 CO 5 A RM17TG00 0.080/
bb Phase loss 0.176

208…440 a 2 CO 5 A RM17TG20 0.085/


0.187

RM17TG00 RM17TG20

13
Presentation, description, Zelio Control - Monitoring &
operation Control Relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Presentation
RM22 multifunction Zelio control relays monitor the following functions on 3-phase
supplies:
Functions RM22TA RM22TU RM22TR RM22TG
Sequence of phases L1, L2, and L3
Phase loss
Asymmetry
Undervoltage
Overvoltage and undervoltage
Function performed
Function not performed
RM22T●●●
Depending on the model, RM22T●●● control relays:
b Accept different nominal 3-phase voltages: up to 480 Va
b Monitor their own power supply measured as a true rms value
b Are designed for clip-on mounting on a 5 rail

They feature a:
b Sealable cover to help protect the settings
b Diagnostic button for load circuit testing
b Relay output status LED
b Fault detection indication LED
b Dial pointer LED indicator for relay power ON status
b Relay output On-delay or Off-delay

Applications
b Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
b Control against reverse motor operation (lifting, handling, elevators, escalators, etc.)
b Control of sensitive 3-phase supplies
b Emergency power supply switching in abnormal conditions

Description
RM22TA, RM22TU, RM22TR, RM22TG
L1 L2 L3 L1 L2 L3 1a  Voltage range selector switch
1b  Voltage range/On-Off delay selector
2  Time delay adjustment potentiometer Tt
3a  Asymmetry threshold setting potentiometer Asym
RM22TA31 RM22TU23
200 400
208 380 415

1a 1a
440
220

3b  Undervoltage setting potentiometer <U


240 480

10 20 -8 -14

3b
-6 -16

2
<U
Tt 5 25 -4 -18

3c  Overvoltage setting potentiometer >U


-2 -20%
0,1 30s
10
8

3a
12

Asym
Def

4  Diagnostic button
Def
5 15%
R R

DIAGNOSTIC
4 DIAGNOSTIC
4
Operating principle
12 11 14 12 11 14 Multifunction 3-phase supply control relays Function Diagram
monitor: Output 11-14, 21-24 open
22 21 24 22 21 24
bb Product being powered by L1 and L3
RM22TA RM22TU bb Correct sequencing of phases Output 11-14, 21-24 closed
L1 L2 L3
L1, L2, and L3
L1 L2 L3
bb LED indication for relay output status and
fault detection (except phase disconnection)
bb Phase loss, including in the case of voltage
RM22TR31
200 200
RM22TG20
regeneration
1b
ON DELAY

bb Undervoltage from - 2…- 20% of the supply


DELAY

208 208
OFF

220 220
240 240

voltage Un
10 20
5 25
Tt
0,1 30s

8 14
bb Overvoltage from 2…20% of the supply
3c
6 16
>U
4 18 Un

voltage Un
Def
2 20%
R
-8 -14 R

3b
-6 -16

bb Asymmetry from 5…15% of the supply


<U
-4 -18

4
-2

4
-20%
DIAGNOSTIC

voltage Un
DIAGNOSTIC

12 11 14 12 11 14
Voltage switch operation:
22 21 24 22 21 24 vv Set the switch to 3-phase supply voltage Un.
vv The position of this switch is taken into account on energization of the device.
RM22TR RM22TG
vv If the switch position is changed while the device is operating, all the LEDs flash
Un Green LED: indicates that supply to the product is on but the product continues to operate normally with the voltage selected at the time of
R Yellow LED: indicates relay output status energization preceding the change of position.
DEF Yellow LED: indicates fault detection vv If the switch is returned to the original position selected prior to the last
energization, the LEDs return to their normal state.

14
Operation (continued) Zelio Control - Monitoring &
Control Relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Operating principle (continued)


RM22TA
Phase + Asymmetry
vv Sequence of phases L1, L2, and L3 The relay monitors its own supply voltage Un:
vv Phase loss vv correct sequence of three phases
vv Asymmetry Asy vv phase loss of at least one of the three phases (U measured < 150 V
150 V (RM22TA31) (RM22TA31) and < 250 V (RM22TA33))
250 V (RM22TA33) vv asymmetry adjustable from 5…15% of Un
Phase L1 bb If a sequencing or phase loss fault is detected, the relay opens instantly.
L3
Phase L2 bb If an asymmetry fault is detected, the relay opens at the end of the time
L2
Phase L3 delay set by the user.
bb On energization of the device with a detected measured fault, the relay
Asymmetry stays open.
Hysteresis
0%
Relay R
Note: Tt: time delay after crossing of the threshold (adjustable on the front panel)
outputs
Tt Tt

RM22TU
Phase + Undervoltage
v Sequence of phases L1, L2, and L3 The relay monitors its own supply voltage Un:
v Phase loss vv correct sequence of the three phases
150 V (RM22TU21) vv phase loss of at least one of the three phases (U measured < 150 V
250 V (RM22TU23) (RM22TU21) and < 250 V (RM22TU23))
Phase L1 vv undervoltage adjustable from - 2…- 20% of Un
L3 bb If a sequencing or phase loss fault is detected, the relay opens instantly.
Phase L2
L2 bb If a voltage fault is detected, the relay opens instantly.
Phase L3
bb On energization of the device with a detected measured fault, the relay
Relay
outputs R
stays open.

vv Undervoltage control <U


L1 L3
L2 L2
L3 L1
Hysteresis
Threshold <U
Phases L1/L2/L3
Relay Note: Tt: time delay after crossing of the threshold
R
outputs
Tt Tt

15
Operation (continued) Zelio Control - Monitoring &
Control Relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

Operating principle (continued)


RM22TR
Phase + Undervoltage/overvoltage
vv Sequence of phases L1, L2, and L3 The relay monitors its own supply voltage Un:
vv Phase loss vv phase loss (U measured <150 V (RM22TR31) and
150 V (RM22TR31)
< 250 V(RM22TR33))
250 V (RM22TR33) vv undervoltage and overvoltage
bb An adjustable time delay on threshold crossing provides immunity to
Phase L1 L3 transients, and helps prevent spurious triggering of the output relay.
Phase L2 L2 bb If a voltage fault is detected, the relay opens at the end of the time delay
Phase L3 set as On-delay or Off-delay by the user.
Relay bb On energization of the device with a detected measured fault, the relay
R
outputs stays open.
bb In the event of phase loss, the relay opens instantly.
vv Overvoltage and undervoltage (Off-delay)

Threshold >U
Hysteresis
L1
L2

Hysteresis L3
Threshold <U
Phases L1/L2/L3
Relay R
outputs Tt Tt
Note: Tt: time delay after crossing of the threshold (adjustable on the front panel)

RM22TG
Phase control
vv Sequence of phases L1, L2, and L3 The RM22TG relay monitors:
vv Phase loss vv correct sequencing of the three phases
vv total loss of one or more of the three phases
100%
Phase L1 bb When the phase sequence and voltages are correct (> 183 Va), the
0%
L3
output relays are closed and the R LED is on.
100% bb When there is a sequencing fault or total loss of one or more phases
Phase L2
0%
(detected as soon as one of the voltages drops below 100 V) the relay
100%
L2 opens instantly and the R LED goes off.
Phase L3 bb On energization of the device with a detected measured fault, the relay
0%
stays open.
Relay R
outputs Tr Tr Tr Tr
Note: Tr: response time on appearance of a fault

16
References Zelio Control - Monitoring &
Control Relays
Multifunction 3-phase control relays
RM22TA, RM22TU, RM22TR, and RM22TG

References
Function Measurement Time delay Output Reference Weight
PF143402

PF143405
range

V kg/lb
b Phase 200…240 a Off delay 2 CO RM22TA31 0.090/
sequence (0.1...30 s) 8A 0.198
b Phase loss
b Asymmetry

380…480 a Off delay 2 CO RM22TA33 0.090/


(0.1...30 s) 8A 0.198

RM22TA31 b Phase 200…240 a On/Off delay 2 CO RM22TR31 0.090/


RM22TR31
sequence (0.1...30 s) 8A 0.198
b Phase loss
b Undervoltage
and
overvoltage 380…480 a On/Off delay 2 CO RM22TR33 0.090/
PF143400

PF143403

(0.1...30 s) 8A 0.198

b Phase 200…240 a No 2 CO RM22TU21 0.090/


sequence 8A 0.198
b Phase loss
b Undervoltage

380…480 a No 2 CO RM22TU23 0.090/


8A 0.198

RM22TG20 RM22TU21
b Phase 183…528 a No 2 CO RM22TG20 0.090/
sequence 8A 0.198
b Phase loss

17
Presentation, Zelio Control - Monitoring &
description Control Relays
Multifunction 3-phase supply control relays
RM17TT, RM17TA, RM17TU, and RM17TE

Presentation
RM17TT, RM17TA, RM17TU and RM17TE multifunction control relays monitor the
following on 3-phase supplies:

Functions RM17TT RM17TA RM17TU RM17TE


Sequence of phases L1, L2, and L3
Phase loss (1)
Asymmetry
Undervoltage
Overvoltage and undervoltage
RM17Tp00
Function performed
Function not performed

Depending on the model, RM17T●00 control relays:


bb Accept different nominal 3-phase voltages: 208...480 V a
bb Monitor their own power supply measured as a true rms value
bb Are designed for clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
bb Control against reverse motor operation (lifting, handling, elevators,
escalators, etc.)
bb Control of sensitive 3-phase supplies
bb Emergency power supply switching in abnormal conditions

Description
L1 L2 L3 L1 L2 L3
RM17TT00, RM17TA00, RM17TU00, RM17TE00
1  Voltage range selector switch (208, 220, 380, 400, 415, 440, and 480 V a)
2  Time delay adjustment potentiometer Tt
1 1
2 3a  Asymmetry threshold setting potentiometer Asy
3a 3b  Undervoltage setting potentiometer < U
Un
R
Un
R 3c  Undervoltage/overvoltage setting potentiometer ∆U
MWG

12 11 14 12 11 14
4  Asymmetry threshold setting potentiometer Asy
5  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
5 5
RM17TT00 RM17TA00

L1 L2 L3 L1 L2 L3

1 1
2 2
3b 3c
Un Un 4
R R

12 11 14 12 11 14

5 5
RM17TU00 RM17TE00
(1) Phase loss with regeneration.
Un  Green LED: indicates that supply to the product is on
R  Yellow LED: indicates relay output status

18
Operation Zelio Control - Monitoring &
Control Relays
Multifunction 3-phase supply control relays
RM17TT, RM17TA, RM17TU, and RM17TE

Operating principle
3-phase supply control relays monitor:
Function Diagram
bb Correct sequence of phases L1, L2, and L3
bb Phase loss, including voltage regeneration Output 11-14, 21-24 open
bb Undervoltage from - 2…- 20% of the supply voltage Un Output 11-14, 21-24 closed
bb Overvoltage from 2…20% of the supply voltage Un
bb Asymmetry from 5…15% of the supply voltage Un
bb Fault signaling is by LED

Voltage switch operation:


bb Set the switch to the 3-phase supply voltage Un.
bb The position of this switch is taken into account on energization of the device.
bb If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the
voltage selected at the time of energization preceding the change of position.
bb If the selector switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

RM17TT00
Phase + Voltage regeneration
vv Sequence of phases L1, L2, and L3 The relay monitors:
vv Phase loss vv correct sequence of the three phases
30% Un 30% Un 30% Un vv phase loss of at least one of the three phases (U measured < 0.7 x
Un)
Phase L1
bb If a sequencing or phase loss fault is detected, the relay opens
L3 instantly.
Phase L2 L2 bb On energization of the device with a detected measured fault, the
Phase L3 relay stays open.
Relays R

RM17TA00
Phase + Asymmetry
vv Sequence of phases L1, L2, and L3 The relay monitors:
vv Phase loss vv correct sequence of the three phases
vv Asymmetry Asy vv phase loss of at least one of the three phases
(U measured < 150 V)
Phase L1 L3 vv asymmetry adjustable from 5…15% of Un
Phase L2 L2 bb If a sequencing or phase loss fault is detected, the relay opens
Phase L3 instantly.
Asymmetry bb If an asymmetry fault is detected, the relay opens at the end of the
Hysteresis
time delay set by the user.
0%
bb On energization of the device with a detected measured fault, the
Relays R relay stays open.
Tt Tt

Note: Tt: time delay after crossing of the threshold (adjustable on front panel).

19
Operation (continued) Zelio Control - Monitoring &
Control Relays
Multifunction 3-phase supply control relays
RM17TT, RM17TA, RM17TU, and RM17TE

Operating principle (continued)


RM17TU00
Phase + Undervoltage
vv Sequence of phases L1, L2, and L3 The relay monitors:
vv Phase loss vv correct sequence of the three phases
150 V 150 V 150 V vv phase loss of at least one of the three phases
(U measured < 150 V)
Phase L1 vv undervoltage adjustable from - 2…- 20% of Un (- 2… - 12% in the
L3
Phase L2
range 3 x 208 V a and - 2%…- 17% in the range 3 x 220 V a due to
L2 the minimum voltage 183 V a)
Phase L3
bb If a sequencing or phase loss fault is detected, the relay opens
Relays R instantly.
bb If a voltage fault is detected, the relay opens at the end of the time
delay set by the user.
vv Undervoltage control U <
bb On energization of the device with a detected measured fault, the
L1 L3 relay stays open.
L2 L2
L3 L1
Hysteresis
Threshold U <

Phases L1/L2/L3

Relays R
Tt Tt

Tt: time delay after crossing of the threshold (adjustable on front panel)

RM17TE00
Phase + Asymmetry + Undervoltage/overvoltage
vv Sequence of phases L1, L2, and L3 The relay monitors:
vv Phase loss vv correct sequence of the three phases
vv Asymmetry Asy vv phase loss of at least one of the three phases
150 V 150 V 150 V (U measured < 150 V)
vv asymmetry adjustable from 5…15% of Un
Phase L1 vv the overvoltage and undervoltage difference in window mode,
L3
adjustable from 2…20% of Un
Phase L2 L2
Phase L3 Un 208 V 220 V 380, 400, 415, 440 V 480 V
Voltage < - 12…- 2 - 17…- 2 - 20…- 2 - 20…- 2
Asymmetry
Hysteresis
threshold (%) > + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 10
0%
bb If a sequencing or phase loss fault is detected, the relay opens
Relays R instantly.
Tt Tt
bb If an asymmetry or voltage fault is detected, the relay opens at the
end of the time delay set by the user.
Tt: time delay after crossing of the threshold (adjustable on front panel)
bb On energization of the device with a detected measured fault, the
relay stays open.
vv Control of overvoltage and undervoltage in window mode U> / U<
L1
Threshold U>
Hysteresis
L2

Hysteresis L3
Threshold U <
Phases L1/L2/L3
Relays R
Tt Tt Tt

Tt: time delay after crossing of the threshold (adjustable on front panel)

20
References Zelio Control - Monitoring &
Control Relays
Multifunction 3-phase supply control relays
RM17TT, RM17TA, RM17TU, and RM17TE

References
PF153402A

PF153404A
Function Measurement Output Reference Weight
range
V kg/lb
bb Phase sequence 208…480 a 1 CO RM17TT00 0.080/
bb Phase loss with voltage 5A 0.176
regeneration

bb Phase sequence 208…480 a 1 CO RM17TA00 0.080/


bb Phase loss 5A 0.176
RM17TA00 bb Asymmetry
RM17TT00
PF153404A

PF153405A

bb Phase sequence 208…480 a 1 CO RM17TU00 0.080/


bb Phase loss 5A 0.176
bb Undervoltage

bb Phase sequence 208…480 a 1 CO RM17TE00 0.080/


bb Phase loss 5A 0.176
bb Asymmetry
bb Undervoltage and
overvoltage in
RM17TU00 RM17TE00 window mode

21
Presentation, description, Zelio Control – Monitoring &
operation Control Relays
Multifunction 3-phase supply control relays
RM35TF

Presentation
The RM35TF30 control relay monitors the following on 3-phase supplies:

Functions RM35TF30
Sequence of phases L1, L2, and L3
Phase loss
Overvoltage and undervoltage in window mode
Asymmetry

Function performed
RM35TF30 Function not performed

These control relays:


bb Accept different nominal 3-phase voltages: 220... 480 V a
bb Monitor their own power supply measured as a true rms value
bb Are designed for clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
bb Control against reverse motor operation (lifting, handling, elevators,
escalators, etc.)
bb Control of sensitive 3-phase supplies
bb Emergency power supply switching in abnormal conditions

L1 L2 L3
Description
RM35TF
1  Voltage range selector switch (220, 380, 400, 415, 440, and 480 V a)
1
2 2  Overvoltage setting potentiometer >U

Def.
3 3  Undervoltage setting potentiometer <U
Un 4 4  Asymmetry threshold setting potentiometer Asy
R
5 5  Time delay adjustment potentiometer Tt
6  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
12 11 14 22 21 24

6
RM35TF

Def. Yellow LED: indicates fault present status (on for


asymmetry, flashing for overvoltage, and undervoltage)
Un  Green LED: indicates that supply to the product is on Operating principle
R   Yellow LED: indicates relay output status 3-phase supply control relay RM35TF30 Function Diagram
monitors: Output 11-14, 21-24 open
vv Correct sequence of phases L1, L2, and L3
vv Phase loss Output 11-14, 21-24 closed
vv Undervoltage and overvoltage in
window mode
Un 220 V 380, 400, 415, 440 V 480 V
Voltage threshold (%) < - 12…- 2 - 20…- 2 - 20…- 2
> + 2…+ 20 + 2…+ 20 + 2…+ 10
vv Asymmetry from 5…15% of the supply voltage Un
vv LED indication for relay output status and fault detection (except phase
disconnection)
bb Voltage switch operation:
vv Set the switch to the 3-phase supply voltage Un.
vv The position of this switch is only taken into account on energization of the
device.
vv If the switch position is changed while the device is operating, all the LEDs
flash, but the product continues to operate normally with the voltage selected at the
time of energization preceding the change of position.
vv If the switch is returned to the original position selected prior to the last
energization, the LEDs return to their normal state.

22
Operation (continued), Zelio Control – Monitoring &
references Control Relays
Multifunction 3-phase supply control relays
RM35TF

Operating principle (continued)


RM35TF
Phase + Overvoltage + Undervoltage in window mode
vv Sequence of phases L1, L2, and L3 The relay monitors:
vv Phase loss vv correct sequence of the three phases
vv Asymmetry vv phase loss of at least one of the three phases
150 V 150 V 150 V (U measured < 150 V)
vv asymmetry, adjustable from 5 to 15% of Un
Phase L1 L3 vv the undervoltage, adjustable from - 2…- 20% of Un (- 2…- 12% in
Phase L2 the range 3 x 220 V a)
Phase L3 vv the overvoltage, adjustable from + 2…+ 20% of Un (+ 2…+ 10% in
the range 3 x 480 V a due to the maximum voltage 528 V a)
Asymmetry
Hysteresis bb If a sequencing or phase loss fault is detected, the relay opens
0% instantly.
Relay R bb If an asymmetry or voltage fault is detected, the relay opens at the
Tt Tt end of the time delay set by the user.
bb On energization of the device with a detected measured fault, the
vv Control of overvoltage and undervoltage in window mode <U< relay stays open.
L1
Threshold U >
Hysteresis
L2

Hysteresis L3
Threshold U <
Phase L1/L2/L3

Relay R
Tt Tt Tt Note: Tt: time delay after crossing of the threshold (adjustable on front panel)

Reference
Function Rated 3-phase supply Output Reference Weight
PF153428A

voltage
V kg/lb
b Phase sequence 220…480 a 2 CO 5 A RM35TF30 0.130/
b Phase loss 0.287
b Asymmetry
b Undervoltage and
overvoltage in
window mode

RM35TF30

23
Presentation, Zelio Control – Monitoring &
description Control Relays
3-phase voltage control relays
RM17UB3 and RM35UB3

Presentation
Voltage measurement and control relays RM35UB330, RM17UB310 and
RM35UB3N30 monitor the following, on 3-phase supplies:
Functions RM35UB330 RM17UB310 RM35UB3N30
Phase loss
Absence of neutral
Overvoltage and undervoltage
Voltage between phases 220…480 V a 208…480 V a
Voltage between phases 120…277 V a
RM35UB3ppp RM17UB310 and neutral

Function performed
Function not performed

Depending on the model, control relays:


bb Monitor their own power supply measured as a true rms value
bb Are designed for clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
bb Control against reverse motor operation (lifting, handling, elevators,
escalators, etc.)
bb Control of sensitive 3-phase supplies
bb Emergency power supply switching in abnormal conditions

L1 L2 L3 L1 L2 L3 N Description
RM35UB330, RM35UB3N30
1a  Voltage range selector switch (220, 380, 400, 415, 440, and 480 V a)
1a 1b
1b  Voltage range selector switch (120, 127, 220, 230, 240, 260, and 277 V a)
2 2
2  Overvoltage setting potentiometer >U
3 3
3  Undervoltage setting potentiometer <U
R1 R1
Un 4 Un 4
R2 R2
5 5 4  Undervoltage threshold delay setting potentiometer Tt2
5  Overvoltage threshold delay setting potentiometer Tt1
12 11 14 22 21 24 12 11 14 22 21 24 6  Spring for clip-on mounting on 35 mm/1.38 in.  5 rail
6 6
RM35UB330 RM35UB3N30
Un Green LED: indicates that supply to the product is on
R1 Yellow LED: indicates relay output status. Overvoltage threshold
R2 Yellow LED: indicates relay output status. Undervoltage threshold

L1 L2 L3 RM17UB310
1  Voltage range selector switch (208, 220, 380, 400, 415, 440, and 480 V a)
2  Time delay adjustment potentiometer Tt
1
3  Overvoltage setting potentiometer >U
2
3 4  Undervoltage setting potentiometer <U
4 5  Spring for clip-on mounting on 35 mm/1.38 in.  5 rail

12 11 14

5
RM17UB310
Un Green LED: indicates that supply to the product is on
R Yellow LED: indicates relay output status

24
Operation Zelio Control – Monitoring &
Control Relays
3-phase voltage control relays
RM17UB3 and RM35UB3

Operating principle
3-phase voltage control relays monitor: Function Diagram
bb Undervoltage and overvoltage: Output 11-14, 21-24 open
Output 11-14, 21-24 closed
Un Phase/phase 208 V 220 V 380, 400, 415, 440 V 480 V
RM17UB310 > U (%) + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 10
< U (%) - 12…- 2 - 17…- 2 - 20…- 2 - 20…- 2
RM35UB30 > U (%) – + 2…+ 20 + 2…+ 20 + 2…+ 10
< U (%) – - 12…- 2 - 20…- 2 - 20…- 2

Un Phase/neutral 120 V 127 V 220, 230, 240, 260 V 277 V


RM35UB3N30 > U (%) + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 20
< U (%) - 20…- 2 - 20…- 2 - 20…- 2 - 20…- 2
bb Phase loss
bb Presence of neutral (RM35UB3N30 only)
bb Measurements are made between Phases for RM35UB330 and RM17UB310 and between Phase/Neutral for RM35UB3N30
bb Fault signaling is by LED
bb RM35UB relays can differentiate between the source of the fault (one LED for overvoltage threshold, one LED for undervoltage threshold)

bb Voltage switch operation:


vv Set the switch to the 3-phase supply voltage Un.
vv The position of this switch is only taken into account on energization of the device.
vv If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the
voltage selected at the time of energization preceding the change of position.
vv If the switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

RM35UB330
Overvoltage/undervoltage control
vv Phase loss bb The relay monitors:
150 V 150 V 150 V vv phase loss (U measured < 150 V)
vv the undervoltage
Phase L1 vv the overvoltage
Phase L2 bb Each threshold has its own independently adjustable time delay
Phase L3 from 0.3 to 30 s.
Relays R1/R2
bb If a voltage fault is detected, the corresponding relay (one
undervoltage output/one overvoltage output) opens at the end of the
vv Overvoltage and undervoltage time delay set by the user.
> bb If a phase loss is detected, both relays open instantly without waiting
Threshold U
Hysteresis for the end of the time delay set by the user.
L1
L2

L3 bb On energization of the device with a detected measured fault, the


Hysteresis
U<
relays stay open.
Threshold
Phases L1/L2/L3

Relay R1

Relay R2
Tt1 Tt2 Note: Tt 1: overvoltage threshold delay (adjustable on front panel)
Tt 2: undervoltage threshold delay (adjustable on front panel)

25
Operation (continued) Zelio Control – Monitoring &
Control Relays
3-phase voltage control relays
RM17UB3 and RM35UB3

Operating principle (continued)


RM35UB3N30
Overvoltage/undervoltage + absence of neutral control
vv Phase loss bb The relay monitors:
80 V 80 V 80 V vv presence of the neutral
vv the undervoltage
Phase L1 vv the overvoltage
vv phase loss (U measured < 80 V)
Phase L2
bb Each threshold has its own independently adjustable time delay from
Phase L3
Relays R
0.3 to 30 s.
bb If a voltage fault is detected, the corresponding relay (one
undervoltage output/one overvoltage output) opens at the end of the
vv Overvoltage and undervoltage time delay set by the user.
Threshold U > bb In the absence of either neutral or phase, both relays open instantly
Hysteresis
L1
without waiting for the end of the time delay set by the user.
L2
bb On energization of the device with a detected measured fault, the
Hysteresis L3 relays stay open.
Threshold U <
Phases L1/L2/L3

Relay R1

Relay R2 Note: Tt 1: overvoltage threshold delay (adjustable on front panel)


Tt1 Tt2 Tt 2: undervoltage threshold delay (adjustable on front panel)

RM17UB310
Overvoltage/undervoltage control
vv Phase loss bb The relay monitors:
150 V 150 V 150 V vv the undervoltage
vv the overvoltage
Phase L1
vv phase loss (U measured < 150 V)

Phase L2
bb An adjustable time delay from 0.3 to 30 s allows inhibition of the
output relay if a transient fault occurs.
Phase L3
Relays R bb If a voltage fault is detected, the relay opens at the end of the time
delay set by the user.
vv Overvoltage and undervoltage bb On energization of the device with a detected measured fault, the relay
stays open.
U> bb If phase loss is detected, the relay opens instantly.
Hysteresis
L1
L2

L3
Hysteresis
U<
Phases L1/L2/L3

Relays 11-12/11-14
R
Tt Tt Note: Tt: overvoltage and undervoltage threshold delay (adjustable on front panel)

26
References Zelio Control – Monitoring &
Control Relays
3-phase voltage control relays
RM17UB3 and RM35UB3

References
Function Measurement Output Reference Weight
PF153428A

PF153405A
range
V kg/lb
b Overvoltage and 220…480 a 1 CO RM35UB330 0.130/
undervoltage (Phase-phase) +1 CO 0.287
between phases 1 per threshold
5A

208…480 a 1 CO RM17UB310 0.080/


RM35UB330 RM17UB310
(Phase-phase) 5A 0.176
PF153428A

b Overvoltage and 120…277 a 1 CO RM35UB3N30 0.130/


undervoltage (Phase-neutral) +1 CO 0.287
between phases 1 per threshold
and neutral 5A
b Absence of neutral

RM35UB3N30

27
Presentation, Zelio Control – Monitoring &
description Control Relays
3-phase supply and motor temperature control relays
RM35TM

Presentation
RM35 Zelio multifunction control relays monitor the following functions on 3-phase
supplies:

Functions RM35TM50MW RM35TM250MW


Sequence of phases L1, L2, and L3
Phase loss
Motor temperature via PTC probe
Selection (with or without memory)
Test/Reset button

Function performed
RM35TM50MW RM35TM250MW Function not performed

Depending on the model, control relays:


bb Accept different nominal 3-phase voltages: 208...480 V a
bb Have phase and temperature control functions that are independent of one
another
bb Detect line breaks or short-circuit of the temperature probes
bb Selection (with or without memory) and Test/Reset function is available
bb Are designed for clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Control for connection of moving equipment (site equipment, agricultural
equipment, refrigerated trucks)
bb Control against reverse motor operation (lifting, handling, elevators,
escalators, etc.)
bb Control of sensitive 3-phase supplies
bb Emergency power supply switching in abnormal conditions
T1 T2 L1 L2 L3 T1 T2 Y1 L1 L2 L3

Description
RM35TM50MW, RM35TM250MW
4
1  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
2  Temperature contact (11-14)
5
R1 R1 3  Phase contact (21-24)
Un Un
R2 R2 4  Configuration: selection of temperature control operating mode (with or without
memory) Memory - No Memory
5  Pushbutton (activation of temperature control) Test/Reset
A1 A2 11 14 21 24 A1 A2 11 14 21 24

1 2 3 1 2 3
RM35TM50MW RM35TM250MW

<V< Yellow LED: relay output status indicator


Un Green LED: power ON indicator
L1
Yellow LED: relay output status indicator
L3 L2

28
Operation Zelio Control – Monitoring &
Control Relays
3-phase supply and motor temperature control relays
RM35TM

Operating principle
Relays RM35TM50MW and RM35TM250MW monitor: Function Diagram
bb Status of the 3-phase supply
Power supply off
bb Temperature of motors with embedded PTC probes
Power supply on
The 3-phase supply control function monitors: Output 11-14, 21-24 open
bb Correct sequence of phases L1, L2, and L3 Output 11-14, 21-24 closed
bb Phase loss

RM35TM50MW/RM35TM250MW
3-phase supply control
vv Sequence of phases L1, L2, and L3 bb As soon as phase sequence (L1, L2, and L3) and phase presence are
vv Phase loss considered to be correct, the output relay contact closes and LED R2 is lit.
100 V 100 V 100 V bb If total failure or drop in amplitude of a phase (U measured < 100 V)
or inversion of phase sequence is detected, the output relay contact opens and
Phase L1 LED R2 goes out.
L3
Phase L2
bb The result of the control is indicated by the status of output relay R2, NO contact
L2 21-24 is open in the event of a fault.
Phase L3
Phase
relay R2 21-24

Temperature control
v Motor temperature control via PTC probe bb The temperature control relay can take up to 6 PTC (positive temperature
Supply Un
coefficient) probes wired in series between terminals T1 and T2.
3100 W
bb A fault is declared when the resistance of the temperature sensing circuit
exceeds 3100 Ω.
1650 W
bb Return to normal status is detected when the resistance is once again
Resistance T1-T2 below 1650 Ω.
15 W
Temperature bb The result of the control is indicated by the status of the “temperature” output
relay R1 relay, NO contact 11-14 is open in the event of a fault.
bb Opening of the thermal sensing circuit, which has the same effect as a high
temperature (resistance exceeds 3100 Ω), is therefore interpreted as a fault.
bb Total short-circuiting of the temperature probe(s), detected when resistance is
less than 15 W ± 5 W, is treated as a fault.
bb LED R1 is on when the temperature is correct.

29
Operation (continued) Zelio Control – Monitoring &
Control Relays
3-phase supply and motor temperature control relays
RM35TM

Operating principle (continued)


RM35TM250MW
Configuration
This configuration is considered when relay RM35TM250MW is energized.

bb Set the switch to the required operating mode:


vv Temperature control without memory
vv Temperature control with memory
bb On energization, placing the switch in one of the five intermediate positions holds the relay in the open contact state and the detected error
is signaled by simultaneous flashing of the LEDs.
bb The position of the mode selector switch is taken into account on energization.
bb Any modification of its position during operation has no effect - the active configuration may therefore be different from that indicated by the
switch - the RM35TM250MW operates normally but the change in configuration is signaled by simultaneous flashing of the three LEDs.

Motor temperature control via PTC probe with memory


vv Memory bb Relay RM35TM250MW has a selector switch which allows the temperature
Test/Reset control operating mode to be configured with or without memory.

Supply Un
bb In “memory” mode, when a fault is detected, the “temperature” relay locks in the
open position.
Test/Reset
bb As soon as the temperature returns to the correct value, the relay can be
S2 T1/Y1 unlocked (reset), either by pressing the “Test/Reset” button (for at least 200 ms), or
3100 Ω by closing a volt-free contact (for at least 200 ms) between terminal Y1 and T1
1650 Ω (without a parallel load).
Resistance T1-T2 bb Relay RM35TM250MW can also be reset by switching off the power (see reset
15 Ω
time).
Temperature
relay R1

Use of “Test/Reset” button


vv No Memory bb Relay version RM35TM250MW has a “Test/Reset” button which can be used to
Test/Reset check that the temperature control function is working correctly and to reset this
Supply Un
function after locking in “memory” mode.
bb The press and release times are 50 ms for both functions.
Test/Reset
3100 Ω
bb When the temperature is normal, pressing the “Test/Reset” button simulates
1650 Ω overheating, the “temperature” output relay contact is open and the <V< LED is off.
bb If “memory” mode is not active, “fault” indication is maintained for as long as the
Resistance T1-T2 button is pressed.
15 Ω
Temperature
relay R1
bb If “memory” mode is active, “fault” indication is locked and the button needs to be
released and pressed again to reset the function.
bb In “memory” mode, when a fault has been detected and the temperature has
vv Memory returned to normal, the “temperature” control relay can be unlocked (reset) by
Reset Reset Reset
pressing the “Test/Reset” button.

Supply Un

Test/Reset
3100 W
1650 W

Resistance T1-T2
15 W
Temperature
relay R1

30
References Zelio Control – Monitoring &
Control Relays
3-phase supply and motor temperature control relays
RM35TM

References
Function Supply Measurement Output Reference Weight
PF156413A

voltage range
V V kg/lb
b Phase sequence 24…240 z 208…480 a 2 NO RM35TM50MW 0.120/
b Phase loss 5A 0.264
b Motor temperature
via PTC probe

RM35TM50MW
PF156414A

b Phase sequence 24…240 z 208…480 a 2 NO RM35TM250MW 0.120/


b Phase loss 5A 0.264
b Motor temperature
via PTC probe
b Selection (with or
without memory)
b “Test/Reset” button

RM35TM250MW

31
Presentation, Zelio Control – Monitoring &
description Control Relays
1-phase voltage control relays
RM17UAS and RM17UBE

Presentation
1-phase DC voltage measurement and control relays RM17UASpp and
RM17UBEpp monitor:
Functions RM17 RM17 RM17 RM17 RM17
UAS14 UAS15 UAS16 UBE15 UBE16
Overvoltage or undervoltage
Overvoltage and undervoltage
(window mode)
Ranges controlled 9…15 c 65…260 z 20…80 z 65…260 z 20…80 z

RM17UBEpp Function performed


Function not performed

Depending on the model, control relays:


bb Allow selection of operating mode
bb Monitor their own power supply measured as a true rms value
bb Are designed for clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Protection of electronic or electromechanical devices against overvoltage
and undervoltage
bb Emergency power supply switching at abnormal conditions

Description
A1 A2

RM17UASpp
<U >U

1 7  Configuration: selection of operating mode <U / >U, Memory - No Memory


2 8  Setting potentiometer
3 9  Hysteresis adjustment potentiometer H
Un
10  Time delay setting potentiometer Tt
R
4
11  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
12 11 14

5
RM17UASpp
Un Green LED: indicates that supply to the product is on
R Yellow LED: indicates relay output status

A1 A2

RM17UBE1p
6  Maximum voltage range selection and setting potentiometer
7  Minimum voltage range selection and setting potentiometer
1 8  Time delay setting potentiometer Tt
2
9  Spring for clip-on mounting on 35 mm/1.38 in.  5 rail
Un

3
R

12 11 14

4
RM17UBE1p
Un Green LED: indicates that supply to the product is on
R Yellow LED: indicates relay output status

32
Operation Zelio Control – Monitoring &
Control Relays
1-phase voltage control relays
RM17UAS and RM17UBE

Operating principle
Voltage control relays RM17UAS and RM17UBE monitor: Function Diagram
bb Voltage of 1-phase and DC supplies
Power supply off
bb RM17UASpp relays support two operating modes:
vv Overvoltage or undervoltage Power supply on
vv Fault memory selected or not Output 11-14, 21-24 open
bb An adjustable time delay, on crossing the thresholds, Output 11-14, 21-24 closed
provides immunity to transients, and helps prevent
spurious triggering of the output relay
bb Fault signaling is by LED

RM17 UAS14/UAS15/UAS16
The operating mode is determined by a switch:
bb Undervoltage with or without memory
bb Overvoltage with or without memory

The position of the configuration switch and the operating mode is read by the product on energization:
bb If the configuration switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to
indicate the position error.
bb If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the
function selected at the time of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

The undervoltage or overvoltage threshold value is set by a graduated potentiometer clearly indicating the voltage Un to be monitored. The
hysteresis is adjusted by a potentiometer graduated from 5…20% of the threshold setting. The hysteresis value must not exceed the limit
values of the measuring range.

Undervoltage/Overvoltage without memory


vv Undervoltage control <U, No Memory If the controlled voltage falls below the threshold setting for a time greater than that
Supply Un set on the front panel (0.1…10 s), the output relay opens and the R LED goes off. As
U soon as the voltage returns to a value above (or below) the threshold setting minus
Hysteresis (or respectively plus) the hysteresis, the relay instantly closes.
Threshold U <

Relays R11-12/11-14
Tt

vv Overvoltage control U>, No Memory If the controlled voltage exceeds the threshold setting for a time greater than that set
Supply Un on the front panel (0.1…10 s), the output relay opens and the R LED goes off. As
soon as the voltage returns to a value below the threshold setting plus the
Threshold U> hysteresis, the relay instantly closes.
Hysteresis
U
Relays R11-12/11-14
Tt

33
Operation (continued) Zelio Control – Monitoring &
Control Relays
1-phase voltage control relays
RM17UAS and RM17UBE

Operating principle (continued)


RM17 UAS14/UAS15/UAS16 (continued)
Undervoltage/Overvoltage with memory
vv Undervoltage control U<, Memory If “Memory” mode is selected, the relay opens when crossing of the threshold is
Supply Un detected and then stays in that position. The power needs to be switched off to reset
the product.
Hysteresis U
Threshold U <

Relays R11-12/11-14
Tt

vv Overvoltage control U>, Memory


Supply Un

Threshold U>
Hysteresis
U
Relays R11-12/11-14
Tt

Note: Tt: time delay after crossing of the threshold

RM17 UBE15/UBE16
Overvoltage + undervoltage control in window mode
Supply Un These relays operate in window mode where they check that the controlled voltage
stays between a minimum threshold and a maximum threshold.
Threshold U > bb The undervoltage or overvoltage threshold values are set by two graduated
Hysteresis potentiometers clearly indicating the voltage Un to be monitored. The hysteresis is
Hysteresis U fixed at 3% of the threshold setting.
Threshold U <
bb If the controlled voltage exceeds the high threshold setting, or falls below the low
Relays 11-12/11-14
R
threshold setting for a time greater than that set on the front panel (0.1…10 s), the
Tt Tt output relay opens and the R LED goes out. During the time delay, this LED flashes.
bb As soon as the voltage falls below the high threshold setting value minus the
hysteresis, or rises above the low threshold setting value plus the hysteresis, the
relay instantly closes.
bb On energization of the device with a detected measured fault, the relay stays open.

Note: Tt: time delay after crossing of the threshold

34
References Zelio Control – Monitoring &
Control Relays
1-phase voltage control relays
RM17UAS and RM17UBE
PF153411A

PF153411A
References
Function Ranges Output Reference Weight
controlled
V kg/lb
bb Overvoltage 9…15 c 1 CO RM17UAS14 0.080/
or undervoltage 5A 0.176

20…80 z 1 CO RM17UAS16 0.080/


5A 0.176
RM17UBE16 RM17UBE15

65…260 z 1 CO RM17UAS15 0.080/


5A 0.176

bb Overvoltage and 20…80 z 1 CO RM17UBE16 0.080/


undervoltage 5A 0.176
in window mode

65…260 z 1 CO RM17UBE15 0.080/


5A 0.176

35
Presentation, description, Zelio Control - Monitoring &
operation Control Relays
Multifunction 1-phase voltage control relays
RM35UA

Presentation
Multifunction voltage control relays RM35UA1pMW monitor both AC and DC
voltages.
Functions RM35UA11MW RM35UA12MW RM35UA13MW
Overvoltage or undervoltage (with or
without memory)
Range controlled 0.05…5 V 1…100 V 15…600 V
Function performed
Function not performed

Depending on the model, the control relays allow:


bb Automatic c or a recognition
RM35UA1pMW bb Measurement ranges from 0.05 V to 600 V
bb Selection between overvoltage and undervoltage
bb Measurement as a true rms value
bb Selectable memory function
bb Clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb DC motor overspeed control
bb Battery monitoring
bb Monitoring of AC or DC supplies
A1 A2 E3 E2 E1 M bb Speed monitoring (with tacho-generator)

Description
<U >U
RM35 UA11MW/UA12MW/UA13MW
1
2 1  Configuration: selection of operating mode <U / >U, (with or without memory)
3 Memory - No Memory
Un 2  Voltage threshold setting potentiometer U Value
R
4 3  Hysteresis adjustment potentiometer H
4  Time delay setting potentiometer Tt
5  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
12 11 14 22 21 24

5
RM35 UA11MW/UA12MW/UA13MW

Un Green LED: indicates that supply to the product is on


R Yellow LED: indicates relay output status
Operating principle
Multifunction voltage relays RM35UA1pMW: Function Diagram
bb Automatically recognize the form of Power supply off
c or a (50 or 60 Hz) signal
Power supply on
bb Fault signaling is by LED
Output 11-14, 21-24 open
Output 11-14, 21-24 closed

RM35 UA11MW/UA12MW/UA13MW
The operating mode is selected by using a switch:
bb Undervoltage with or without memory
bb Overvoltage with or without memory

The position of the switch and the operating mode is read by the product on
energization:
bb If the switch is set to an unacceptable position, the product detects a fault, the
output relay stays open and the LEDs flash to indicate the position error.
bb If the switch position is changed while the device is operating, all the LEDs flash,
but the product continues to operate normally with the function selected at the time
of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the
last energization, the LEDs return to their normal state.

The undervoltage or overvoltage threshold value is set by a potentiometer graduated


as a percentage of the scale value of Un to be monitored. The hysteresis is adjusted
by a potentiometer graduated from 5…50% of the threshold setting. The hysteresis
value must not exceed the limit values of the measuring range.

36
Operation (continued), Zelio Control - Monitoring &
references Control Relays
Multifunction 1-phase voltage control relays
RM35UA

Operating principle (continued)


RM35 UA11MW/UA12MW/UA13MW
Overvoltage without memory
bb Overvoltage control > U, without memory If the voltage controlled exceeds the threshold setting for a time greater than that
Supply Un set on the front panel (0.3…30 s), the output relay opens and the R LED goes off.
During the time delay, this LED flashes. As soon as the voltage drops below the
Threshold U >
value of the threshold setting, minus the hysteresis, the relay instantly closes.
Hysteresis
U
11-12/11-14
Relays R
21-22/21-24
Tt
Note: Tt: time delay after crossing of the threshold (adjustable on front panel)

Undervoltage without memory


bb Undervoltage control < U, without memory If the voltage controlled falls below the threshold setting for a time greater than
Supply Un that set on the front panel (0.3…30 s), the output relay opens and the R LED goes
off. During the time delay, this LED flashes. As soon as the voltage rises above the
U value of the threshold setting plus the hysteresis, the relay instantly closes.
Hysteresis
Threshold U <

11-12/11-14
Relays21-22/21-24
R
Tt
Note: Tt: time delay after crossing of the threshold (adjustable on front panel)

Overvoltage/undervoltage with memory


bb Undervoltage control < U, without memory If “Memory” mode is selected, the relay opens when crossing of the threshold is
Supply Un detected and then stays in that position. The power needs to be switched off to
reset the product.
Threshold U >
Hysteresis
U
11-12/11-14
Relays R
21-22/21-24

Tt

bb Undervoltage control < U, with memory


Supply Un

Hysteresis
U
Threshold U <

11-12/11-14
Relays R
21-22/21-24
Note: Tt: time delay after crossing of the threshold (adjustable on front panel)
Tt

References
Function Range Supply Output Reference Weight
controlled voltage
PF153418A

PF153418A

PF153418A

V V kg/lb
bb Overvoltage 0.05…5 24…240 z 2 CO RM35UA11MW 0.130/
or undervoltage 5A 0.287

1…100 24…240 z 2 CO RM35UA12MW 0.130/


5A 0.287

15…600 24…240 z 2 CO RM35UA13MW 0.130/


5A 0.287
RM35UA11MW RM35UA12MW RM35UA13MW

37
Presentation, Zelio Control - Monitoring &
description Control Relays
1-phase voltage control relays
RM22UA and RM22UB

Presentation
RM22UA and RM22UB 1-phase or DC voltage control relays monitor the following
functions:
Functions RM22 UA2●MR UA3●MR UA33MT UB34
Overvoltage (without memory)
Overvoltage or undervoltage
(with/without memory)
Overvoltage and undervoltage
(window mode)

Function performed
Function not performed
RM22UA21MR RM22UA31MR
RM22 control relays allow:
b Automatic AC or DC recognition
b Selection between overvoltage and undervoltage
b Monitoring of their own supply voltage measured as a true rms value
b Selectable memory function
b Clip-on mounting on a 5 rail

They feature a:
b Dial pointer LED indicator for relay power ON status
b Relay output status LED
b A sealable cover to help protect the settings
b A control status indicator LED

Applications
b Protection of electronic or electromechanical devices against overvoltage and
undervoltage
b Emergency power supply switching in abnormal conditions
b DC motor overspeed control
b Monitoring of AC or DC supplies
b Battery and speed monitoring (with tacho-generator)

A1 A2 M A1 A2 M Description
E1 E2 E3 E1 E2 E3
RM22UA2●MR, RM22UA3●MR, RM22UA33MT, RM22UB34
1  Configuration: selection of operating mode <U (undervoltage), >U (overvoltage),
RM22UA23MR RM22UA31MR
>U> (overvoltage and undervoltage), MEMORY - NO MEMORY (with or without
1
>U > > U>
MEMORY

MEMORY

memory)
NO

>U >U
<U <U

40 70 40 70

2c 2a
30 80 30 80

2a  Voltage threshold setting potentiometer U value


U
>U 20 90 Value 20 90
Value 10 100% 10 100%

20 35 20 35

4a 4b 2b  Undervoltage setting potentiometer <U


15 40 Hys/ 15 40
Hys
10 45 >U> 10 45
5 50% 5 50%
R 10 20 R

Tt 5

0,1
25
3 2c Overvoltage setting potentiometer >U
5
30s
DIAGNOSTIC
5 DIAGNOSTIC

3  Time delay adjustment potentiometer Tt


12 11 14 12 11 14 4a Hysteresis adjustment potentiometer Hys
4b  Hysteresis/overvoltage and undervoltage window mode adjustment
22 21 24 22 21 24
potentiometer Hys/>U>
RM22UA2pMR RM22UA3pMR
5 Diagnostic button
A1 A2 M A1+ A2- 6 Configuration: selection of On-delay or Off-delay
E1 E2 E3

RM22UA33MT RM22UB34

1 6
>U > > U>
MEMORY

DELAY
MEMORY

DELAY
OFF
ON
NO

>U >U
<U <U

40 70 160 220
140 240

2a 2c
U 30 80
>U 120 260
Value 20 90
100 280
10 100%
80 300V
20 35 160 220

2b
140 240

4b
Hys/ 15 40
<U 120 260
>U> 10 45
100 280
5 50% 80 300V
10 20 R 10 20 R

Tt 5 25
3 Tt 5 25
3
5
0,1 30s 0,1 30s
DIAGNOSTIC DIAGNOSTIC
5

12 11 14 12 11 14

22 21 24 22 21 24

RM22UA33MT RM22UB34

R Yellow LED: indicates relay output status

38
Operation Zelio Control - Monitoring &
Control Relays
1-phase voltage control relays
RM22UA and RM22UB

Operating principle
1-phase voltage control relays monitor: Function Diagram
bb the voltage of 1-phase and DC supplies
Power supply off
bb their own supply voltage for the RM22UB model
Power supply on
An adjustable time delay on threshold crossing, Output 11-14, 21-24 open
provides immunity to transients, and helps prevent Output 11-14, 21-24 closed
spurious triggering of the output relay.

RM22 UA2●MR/UA3●MR/UA33MT
The operating mode is determined by the user:
bb Undervoltage with or without memory
bb Overvoltage with or without memory

The position of the configuration switch and the operating mode is read by the product on energization:
bb If the configuration switch is set to an unacceptable position, the product detects a fault, the output relay stays open, and the LEDs flash to
indicate the position error.
bb If the configuration switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate
normally with the function selected at the time of energization preceding the position change.
bb If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

The undervoltage or overvoltage threshold value is set by means of a potentiometer graduated as a percentage of the scale value of U
to be monitored. The hysteresis is adjusted by means of a potentiometer graduated from 5…50% of the threshold setting. The hysteresis
value must not exceed the limit values of the measuring range.

Overvoltage without memory


bb Overvoltage control > U, without memory If the controlled voltage exceeds the threshold setting for a time greater than that
Supply Un set on the front panel (0.1…30 s), the output relay opens and the R LED goes off.
During the time delay, this LED flashes.
As soon as the voltage drops below the value of the threshold setting minus the
Threshold >U
hysteresis, the relay instantly closes.
Hysteresis
U
Relay R
outputs
Tt <Tt

Undervoltage without memory


bb Undervoltage control < U, without memory If the controlled voltage falls below the threshold setting for a time greater than
Supply Un that set on the front panel (0.1…30 s), the output relay opens and the R LED goes
off. During the time delay, this LED flashes.
U As soon as the voltage rises above the value of the threshold setting plus the
Hysteresis
Threshold <U hysteresis, the relay instantly closes.

Relay R
outputs
Tt <Tt

39
Operation (continued) Zelio Control - Monitoring &
Control Relays
1-phase voltage control relays
RM22UA and RM22UB

Operating principle (continued)


RM22 UA2●MR/UA3●MR/UA33MT (continued)
Overvoltage/undervoltage with memory
vv Overvoltage control > U, with memory If “Memory” mode is selected, the relay opens when crossing of the threshold is
Supply Un detected and then stays in that position. The power has to be switched off to reset
the product.
Threshold >U
Hysteresis
U Note: Tt: time delay after crossing of the threshold
Relay
outputs R
Tt

vv Undervoltage control < U, with memory


Supply Un

Hysteresis U
Threshold <U

Relay
R
outputs
Tt

RM22 UA3●MR/UA33MT/UB34
Overvoltage + undervoltage control relay in window mode
bb Overvoltage and undervoltage control These relays operate in window mode where they check that the controlled voltage
in window mode <U< stays between a minimum and a maximum threshold.
Supply Un bb The undervoltage or overvoltage threshold values are set by means of two
graduated potentiometers clearly indicating the Un to be monitored. The hysteresis
is fixed at 5% of the threshold setting.
Threshold >U
bb If the controlled voltage exceeds the high threshold setting or falls below the low
Hysteresis
Hysteresis U threshold setting for a time greater than that set on the front panel (0.1…30 s), the
Threshold <U output relay opens and the R LED goes off. During the time delay, this LED flashes.
Relay R
bb As soon as the voltage falls below the high threshold setting value minus the
outputs hysteresis, or rises above the low threshold setting value plus the hysteresis, the
Tt Tt
relay instantly closes.
bb On energization of the device with a detected measured fault, the relay stays
open.

Note: Tt: time delay after crossing of the threshold

40
References Zelio Control - Monitoring &
Control Relays
1-phase voltage control relays
RM22UA and RM22UB

References
PF143409

PF143412
Function Rated supply Measurement Time delay Output Reference Weight
voltage range
V V kg/lb
b Overvoltage 24…240 z 0.05…5 z No 2 CO 8 A RM22UA21MR 0.110/
without memory 0.242

24…240 z 1…100 z No 2 CO 8 A RM22UA22MR 0.110/


0.242

24…240 z 15…500 z No 2 CO 8 A RM22UA23MR 0.110/


0.242
RM22UA23MR RM22UA33MR
b Overvoltage or 24…240 z 0.05…5 z Off delay 2 CO 8 A RM22UA31MR 0.110/
undervoltage with/ (0.1...30 s) 0.242
without memory
b Overvoltage and
PF143413

PF143414

undervoltage in 24…240 z 1…100 z Off delay 2 CO 8 A RM22UA32MR 0.110/


window mode (0.1...30 s) 0.242
with memory

24…240 z 15…500 z Off delay 2 CO 8 A RM22UA33MR 0.110/


(0.1...30 s) 0.242

380…415 a 15…500 a Off delay 2 CO 8 A RM22UA33MT 0.110/


(0.1...30 s) 0.242

b Overvoltage and 110…240 z 80…300 z On/Off delay 2 CO 8 A RM22UB34 0.090/


RM22UA33MT RM22UB34 undervoltage in (0.1...30 s) 0.198
window mode
without memory

41
Presentation, Zelio Control - Monitoring &
description Control Relays
1-phase current control relays with integrated current
transformer
RM17JC

Presentation
The control relay RM17JC00MW is designed to monitor a currents.
Functions RM17JC00MW
Overcurrent (without memory)
Function performed
Function not performed

These control relays allow:


bb Integrated current transformer
bb Measurement range 2…20 A
bb Choice of action on the output relay
bb Clip-on mounting on a 5 rail
RM17JC00MW
They feature a control status indicator LED.

Applications
bb Load state control of motors and generators
bb Control of current drawn by a 3-phase motor
bb Monitoring of heating or lighting circuits
bb Control of pump draining (undercurrent)
bb Control of overtorque (crushers)
bb Monitoring of electromagnetic brakes or clutches

A1 Y1 A2 Description
RM17JC00MW
1  Overcurrent setting potentiometer
2  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail

Un

R 1

12 11 14

2
RM17JC00MW

Un Green LED: indicates that supply to the product is on


R Yellow LED: indicates relay output status

42
Operation, Zelio Control - Monitoring &
references Control Relays
1-phase current control relays with integrated current
transformer
RM17JC

Operating principle
Control relay RM17JC00MW is: Function Diagram
bb equipped with an integrated current transformer Power supply off
bb fault signaling is by LED
Power supply on

RM17JC00MW
Overcurrent detection
Overcurrent detection > I bb Relay RM17JC00MW controls overcurrent.
Supply Un bb The relay closes when the current exceeds the threshold setting on the front
panel and opens when it drops below the threshold minus the hysteresis.
I> bb When terminal Y1 is linked to A1 (+), the output is reversed. The relay opens
Hysteresis
I when the current exceeds the threshold setting on the front panel and closes
again when it drops below the hystereris value.
Y1 11-12
A1 Relays R
11-14

11-12
Y1 A1 Relays R
11-14

Reference
Function Supply Measurement Output Reference Weight
PF153412A

range
V A kg/lb
bb Overcurrent 24…240 z 2…20 1 CO RM17JC00MW 0.110/
5A 0.243

RM17JC00MW

43
Presentation, Zelio Control - Monitoring &
description Control Relays
1-phase current control relays
RM22JA and RM35JA

Presentation
RM22JA and RM35JA multifunction current control relays monitor the following
functions:
Functions RM22JA21MR RM22JA31MR RM35JA 32MR/32MT
Overcurrent
(without memory)
Overcurrent
(with/without memory)
Undercurrent
(with/without memory)
RM22JA21MR RM35JA32MT Overcurrent and
undercurrent
(with/without memory)
(window mode)

Function performed
Function not performed

These control relays enable:


b Automatic a or c recognition
b Selection between overcurrent and undercurrent
b Measurement as a true rms value
b Selectable memory function
b Clip-on mounting on a 5 rail

They feature:
b Dial pointer LED indicator for relay power ON status
b Relay output status LED
b A sealable cover to help protect the settings
b A control status indicator LED

Applications
b Excitation control of DC machines
b Load state control of motors and generators
b Control of current drawn by a 3-phase motor
b Monitoring of heating or lighting circuits
b Control of pump draining (undercurrent)
b Control of overtorque (crushers)
b Monitoring of electromagnetic brakes or clutches
A1 A2 M
Description
A1 A2 M

E1 E2 E3 E1 E2 E3 RM22JA21MR, RM22JA31MR, RM35JA32MR, RM35JA32MT


RM22JA21MR
1  Configuration: selection of operating mode <I (undercurrent), >I (overcurrent),
RM22JA31MR
>I> (overcurrent and undercurrent), MEMORY - NO MEMORY (with or without
1
>I > >I >
I I
MEMORY

I I

MEMORY
NO

>I >I
I I

I I

memory)
<I <I
I I

I I

40 70
40 70

6
30 80

2
>I % 30 80
I I

I%
I I

20 90

2  Current threshold setting potentiometer I%


20 90
10 100% 10 100%
20 35 20 35

3a 3b
15 40 40
15

3a  Hysteresis adjustment potentiometer Hys


Hys Hys/
10 45 >I >
I I

10 45
5 50%
5 50%
R R
10 20

Tt 5 25
4 3b  Hysteresis/overcurrent and undercurrent window mode adjustment
5
0,1 30s
DIAGNOSTIC DIAGNOSTIC
potentiometer Hys/>I>
4  Time delay adjustment potentiometer Tt
12 11 14 12 11 14
5  Diagnostic button
22 21 24 22 21 24 6 Overcurrent setting potentiometer >I
RM22JA21MR RM22JA31MR
A1 A2 E3 E2 E1 M A1 A2 E3 E2 E1 M

RM35JA32MR RM35JA32MT

1
YES NO

1
>I > >I > YES NO
I I
I I

>I > >I >


I I
I I

MEMORY > I >I


I I

I I

MEMORY > I >I


I I

I I

<I
I I

<I
I I

<I
I I

<I
I I

2
70

2
40
40 70
30 80
I% 30 80
I I

20 90 I%
I I

20 90
10 100%

3b
10 100%

3b
20 35
20 35
Hys/ 15 40
Hys/ 15 40
>I > 10 45
I I

>I > 10 45
I I

5 50%

4
5 50%

4
10 20 R
10 20 R
Tt 5 25 Tt 5 25

5
0,1 30s

5
0,1 30s
DIAGNOSTIC
DIAGNOSTIC

12 11 14 22 21 24 12 11 14 22 21 24

RM35JA32MR RM35JA32MT

R Yellow LED: indicates relay output status

44
Operation Zelio Control - Monitoring &
Control Relays
1-phase current control relays
RM22JA and RM35JA

Operating principle
Current control relays monitor the current of 1-phase Function Diagram
and DC supplies.
Power supply off
An adjustable time delay on threshold crossing provides Power supply on
immunity to transients, helping prevent spurious
Output 11-14, 21-24 open
triggering of the output relay.
Output 11-14, 21-24 closed

RM22JA●1MR/RM35JA32M●
The operating mode is determined by the user:
bb Undercurrent with or without memory
bb Overcurrent with or without memory

The position of the configuration switch and the operating mode is read by the product on energization:
bb If the configuration switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to
indicate the position error.
bb If the configuration switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally
with the function selected at the time of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

The undercurrent or overcurrent threshold value is set by means of a potentiometer graduated as a percentage of the scale value of I to be
monitored. The hysteresis is adjusted by means of a potentiometer graduated from 5…50% of the threshold setting. The hysteresis value
must not exceed the limit values of the measuring range.

Overcurrent/Undercurrent without memory


vv Overcurrent detection >I , without memory If the controlled current exceeds the threshold setting for a time greater than that
Supply Un set on the front panel (0.1…30 s), the output relay opens and the R LED goes off.
During the time delay, this LED flashes.
As soon as the current drops below the value of the threshold setting minus the
Threshold >I hysteresis, the relay instantly closes.
Hysteresis
I

Relay R
outputs
Tt <Tt

vv Undercurrent detection <I, without memory If the controlled current falls below the threshold setting for a time greater than that
Supply Un set on the front panel (0.1…30 s), the output relay opens and the R LED goes off.
During the time delay, this LED flashes.
As soon as the current rises above the value of the threshold setting plus the hys-
Hysteresis I teresis, the relay instantly closes.
Threshold <I
Note: Tt: time delay after crossing of the threshold
Relay R
outputs
Tt Tt

45
Operation (continued) Zelio Control - Monitoring &
Control Relays
1-phase current control relays
RM22JA and RM35JA

Operating principle (continued)


RM22JA●1MR/RM35JA32M● (continued)
Overcurrent/Undercurrent with memory
vv Overcurrent >I, with memory If “Memory” mode is selected, the relay opens when threshold crossing is
Supply Un detected and then stays in that position. The power has to be switched off to
I reset the product.

Threshold >I
Hysteresis

Relay
outputs R
Tt Tt

vv Undercurrent <I, with memory


Supply Un

Hysteresis
Threshold <I I Note: Tt: time delay after crossing of the threshold

Relay
outputs R
Tt Tt

RM22JA●1MR/RM35JA32M●
Overcurrent and undercurrent control in window mode
vv Overcurrent and undercurrent control in These relays operate in window mode where they check that the controlled
window mode <I<, without memory current stays between a minimum and a maximum threshold.
bb The undercurrent or overcurrent threshold values are set by means of two
Supply Un
graduated potentiometers clearly indicating the I to be monitored. The hysteresis
is fixed at 5% of the threshold setting.
Threshold >I bb If the controlled current exceeds the high threshold setting or falls below the
Hysteresis
<Tt U low threshold setting for a time greater than that set on the front panel (0.1…30 s),
Hysteresis
<Tt the output relay opens and the R LED goes off. During the time delay, this LED
Threshold <I flashes.
bb As soon as the current falls below the high threshold setting value minus the
Relay R hysteresis, or rises above the low threshold setting value plus the hysteresis, the
outputs Tt Tt relay instantly closes.
bb On energization of the device with a detected measured fault, the relay stays
open.

Note:Tt: time delay after crossing of the threshold

46
References Zelio Control - Monitoring &
Control Relays
1-phase current control relays
RM22JA and RM35JA

References
Function Rated Measurement Time Output Reference Weight
PF143415

PF143416

supply range delay


voltage
V kg/lb
b Overcurrent 24…240 z 4 mA…1 A z No 2 CO 8 A RM22JA21MR 0.110/
without memory 0.242

b Overcurrent with/ 24…240 z 4 mA…1 A z Off delay 2 CO 8 A RM22JA31MR 0.110/


without memory (0.1...30 s) 0.242
RM22JA21MR RM22JA31MR b Undercurrent with/
without memory
b Overcurrent and
undercurrent
(window mode)
PF143417

PF143418

with/without
memory 24…240 z 150 mA…15 A z Off delay 2 CO 8 A RM35JA32MR 0.120/
(0.1...30 s) 0.264

380…415 a 150 mA…15 A z Off delay 2 CO 8 A RM35JA32MT 0.120/


(0.1...30 s) 0.264

RM35JA32MR RM35JA32MT

47
Presentation, description, Zelio Control – Monitoring &
operation Control Relays
1-phase current control relays
RM35JA

Presentation
Multifunction current control relays RM35JA3pMW monitor both AC and DC
currents.
Functions RM35JA31MW RM35JA32MW
Overcurrent (with/without memory)
Undercurrent (with/without memory)
Range controlled 2 …500 mA 0.15…15 A
Function performed
Function not performed
RM35JA3pMW These control relays allow:
bb Automatic AC or DC recognition
bb Measurement ranges from 2 mA to 15 A
bb Selection between overcurrent and undercurrent
bb Measurement as a true rms value
bb Selectable memory function
bb Clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Excitation control of DC machines
bb Control of the load state of motors and generators
bb Control of current drawn by a 3-phase motor
bb Monitoring of heating or lighting circuits
bb Control of pump draining (undercurrent)
bb Control of overtorque (crushers)
bb Monitoring of electromagnetic brakes or clutches

A1 A2 E3 E2 E1 M
Description
RM35JA31MW, RM35JA32MW
1  Configuration: selection of operating mode <I / >I, (with or without memory)
<I >I

1
Memory - No Memory
2
3 2  Current threshold setting potentiometer I%
Un 4 3  Hysteresis adjustment potentiometer Hysteresis
R

4  Time delay adjustment potentiometer Tt


5
5  Starting inhibition time delay adjustment potentiometer Ti
12 11 14 22 21 24
6  Spring for clip-on mounting on 35 mm/1.38 in.  5 rail
6
RM35JA31MW, RM35JA32MW
Un Green LED: indicates that supply to the product is on
R Yellow LED: indicates relay output status Operating principle
Control relays RM35JA3pMW are Function Diagram
designed to: Power supply off
bb monitor a or c currents
Power supply on
bb automatically recognize the form of
c or a (50 or 60 Hz) signal Output 11-14, 21-24 open
bb directly monitor up to 15 A (above this Output 11-14, 21-24 closed
value a current transformer can be
connected)
bb signal detected faults by means of
LEDs

48
Operation (continued), Zelio Control – Monitoring &
references Control Relays
1-phase current control relays
RM35JA

Operating principle (continued)


RM35 JA31MW/JA32MW
The operating mode is selected by a switch:
bb Undercurrent, with or without memory
bb Overcurrent, with or without memory
The position of the switch and the operating mode is read by the product on energization:
bb If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to indicate the
position error.
bb If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the
function selected at the time of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.
The undercurrent or overcurrent threshold value is set by a potentiometer graduated as a percentage of the scale value of current I to be
monitored. The hysteresis is adjusted by a potentiometer graduated from 5…50% of the threshold setting and the value must not exceed the
limit values of the measuring range.
Overcurrent without memory
bb Overcurrent detection >I, without memory If the current controlled exceeds the threshold setting for a time greater than that set
Supply Un
on the front panel (0.3…30 s), the output relay opens and the LED goes off.
As soon as the current drops below the value of the threshold setting minus the
hysteresis, the relay instantly closes.
Threshold I>
Hysteresis
I
Relays R11-12/11-14
21-22/21-24

Ti Tt Tt Ti

Undercurrent without memory


bb Undercurrent detection < I, without memory If the current controlled falls below the threshold setting for a time greater than that
Supply Un
set on the front panel (0.3…30 s), the output relay opens and the LED goes off. As
soon as the current rises above the value of the threshold setting plus the hysteresis,
Hysteresis I the relay instantly closes.
Threshold I<

11-12/11-14
Relays R21-22/21-24
Ti Tt Tt Ti

Overcurrent/Undercurrent with memory


bb Overcurrent detection >I, with memory If “Memory” mode is selected, the relay opens when crossing of the threshold is
Supply Un detected and then stays in that position. The power needs to be switched off to reset
I the product.
Threshold I>
Hysteresis On energization, an inhibition time delay (1…20 s) makes it possible to inhibit current
peaks (or troughs) on start-up of equipment.
11-12/11-14
Relays R21-22/21-24
Ti Tt Ti Tt

bb Undercurrent detection < I, with memory


Supply Un

Hysteresis
Threshold I<
I
11-12/11-14
Relays R21-22/21-24
Note: T
 i: starting inhibition time (adjustable on front panel)
Ti Tt Ti Tt
Tt: time delay after crossing of the threshold (adjustable on front panel)

References
Function Range Supply Output Reference Weight
controlled
PF153420B

PF153420B

V kg/lb
b Overcurrent or 2 …500 mA 24…240 z 2 CO RM35JA31MW 0.130/
undercurrent 5 A 0.286

0.15…15 A 24…240 z 2 CO RM35JA32MW 0.130/


5 A 0.286

RM35JA31MW RM35JA32MW

49
Presentation, Zelio Control - Monitoring &
description Control Relays
Liquid level control relays
RM22LA and RM22LG

Presentation
RM22LA and RM22LG liquid level control relays control one or two liquid levels, with
a fill or empty function:
Functions RM22LA 32MR/32MT RM22LG 11MR/11MT
Level 1/Level 2
Fill operation
Empty operation
Low sensitivity
Standard sensitivity
High sensitivity

Function performed
RM22LG11MR RM22LA32MT Function not performed

RM22 liquid level control relays feature:


b A dial pointer LED indicator for relay power ON status
b A relay output status LED
b A sealable cover to help protect the settings
b A control status indicator LED
The relays are designed for clip-on mounting on a 5 rail.

Applications
These devices monitor the levels of conductive liquids.
They control the actuation of pumps or valves to regulate levels and can also help
prevent submersible pumps “dry running”, or tanks “overflowing”. They can also be
used to control dosing of liquids in mixing processes and to help protect heating
elements in the event of non-immersion.
They have a transparent, hinged cover on their front panel to avoid any accidental
alteration of the settings. This cover can be directly sealed.

b Application examples for compatible liquids:


v spring, town, industrial, and sea water
v metallic salt, acid, or base solutions
v liquid fertilizers
v non-concentrated alcohol (< 40%)
v liquids in the food processing industry: beer, coffee, etc.

A1 A2 NC A1 A2 NC
Description
Min Max C Min Max C RM22LG11MR, RM22LG11MT, RM22LA32MR, RM22LA32MT
1  Configuration: selection of the operating mode (Fill or Empty) and the sensitivity
RM22LG11MR
range (LS/St/HS)
RM22LG11MT

1 1
30
40 60
70 30
40 60
70 2  Sensitivity control potentiometer (kΩ or %)
2 2
Sens 80
20 Sens 20 80
10 90 10 90

3  Configuration: selection of the number of levels and the On/Off time delay
5 100 KΩ 5 100 KΩ

Level
3 Level
3
4  Time delay control potentiometer Tt
2 1 2 1

R R

DIAGNOSTIC
5 DIAGNOSTIC
5 5  Diagnostic button

12 11 14 12 11 14

RM22LG11MR RM22LG11MT

A1 A2 NC A1 A2 NC

Min Max C Min Max C

RM22LA32MR RM22LA32MT

1 1
HS LS HS LS
St. St. St. St.

LS HS LS HS
40 60 40 60
30 70 30 70

2 2
Sens 20 80 Sens 20 80
10 90 10 90
5 100% 5 100%

3 3
1 1 1 1
DELAY
DELAY

DELAY
DELAY

OFF
OFF

Level Level
ON
ON

2 2 2 2

10 20 R 10 20 R

Tt 5

0,1
25
4 Tt 5

0,1
25
4
5 5
30s 30s
DIAGNOSTIC DIAGNOSTIC

12 11 14 12 11 14

22 21 24 22 21 24

RM22LA32MR RM22LA32MT

R Yellow LED: indicates relay output status

50
Operation Zelio Control - Monitoring &
Control Relays
Liquid level control relays
RM22LA and RM22LG

Operating principle
Liquid level control relays are designed to measure and control the levels of Function Diagram
conductive liquids by means of resistive probes.
Power supply Off
The operating principle is based on measurement of the apparent resistance of the
liquid between two submerged probes. When this value is less than the threshold Power supply On
setting on the front panel of the device, the relay changes state. To avoid electrolytic Output 11-14, 21-24 open
phenomena, an AC current runs across the probes. Output 11-14, 21-24 closed
A selector switch on the front panel allows selection of the required function and the
sensitivity range. Control of a single level can be achieved by using the second se-
lector switch. In this case, the Max. level probe stays up in the air and an adjustable
time delay avoids any wave effect. Both products activate their output relay when a
tank is either emptying or filling.

RM22LA and RM22LG


A selector switch on the front panel of these relays allows selection of the required sensitivity range and the empty or fill function. A second
switch allows selection of the number of levels (1 or 2) and the type of time delay in the case of level 1 mode. The position of these
configuration switches is taken into account on energization.
b If the configuration switch is set to an unacceptable position, the product detects a fault, the output relay stays open, and the LEDs flash to
signal the position error.
b If the configuration switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally
with the function selected at the time of energization preceding the change of position.
b If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

Control of two levels, empty and fill function


vv Fill/Empty function (2 levels) bb Empty function
Supply Un level: 2, function:
-- LS (Low Sensitivity: 250 W…5 kW)
Max. level -- St (Standard Sensitivity: 5 kW…100 kW)
Min. level -- HS (High Sensitivity: 50 kW…1 MW)
Relay
The output relay stays open until the liquid reaches the Max. level probe.
outputs R As soon as the Max. level is reached, the contact closes and then allows emptying
Relay of the tank (valve opens, pump starts, etc.). When the level drops below the Min.
outputs R level, the contact opens to stop the emptying process.

bb Fill function
level: 2, function:
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)
The output relay stays energized until the liquid reaches the Max. level probe.
As soon as the Max. level is reached, the contact opens and the pump stops.
When the level drops below the Min. level, the contact closes again and
pumping restarts to raise the level.

51
Operation (continued) Zelio Control - Monitoring &
Control Relays
Liquid level control relays
RM22LA and RM22LG

Operating principle (continued)


RM22LA and RM22LG (continued)
Control of one level, empty function
vv Empty function T on bb Level: 1 - on delay functions:
Supply Un -- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level -- HS (High Sensitivity: 50 kW…1 MW)

Relay When the liquid level rises above the probe for a time greater than the time
outputs R delay value Tt set on the front panel, the relay is energized and stays energized
Tt Tt Tt until the liquid level drops back to the probe.
If the liquid drops back below the set level before the end of the time delay, the
relay is not energized.

vv Empty function T off bb Level: 1 - off delay functions:


Supply Un -- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level -- HS (High Sensitivity: 50 kW…1 MW)

Relay When the liquid level rises above the probe, the relay is energized instantly and
outputs R stays energized until the liquid again reaches the probe level for a time Tt set
Tt Tt Tt on the front panel.
If the liquid drops back below the set level before the end of the time delay
period, the relay stays energized.

Control of one level, fill function


vv Fill function T on bb Level: 1 - on delay functions:
Supply Un -- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level -- HS (High Sensitivity: 50 kW…1 MW)

Relay When the liquid level drops below the probe for a time greater than the time
outputs R delay value Tt set on the front panel, the relay is energized and stays energized
Tt
until the liquid level rises back up to the probe.
Tt Tt
If the liquid rises back above the set level before the end of the time delay
period, the relay is not energized.

vv Fill function T off bb Level: 1 - off delay functions:


Supply Un -- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level -- HS (High Sensitivity: 50 kW…1 MW)

Relay When the liquid level drops below the probe, the relay is energized instantly
outputs R and stays energized until the liquid level again reaches the probe level and
stays above it for a time greater than the time delay period Tt set on the front
Tt Tt Tt
panel.
If the liquid drops back below the set level before the end of the time delay
period, the relay stays energized.

Note: Tt: time delay after crossing of the threshold

52
References Zelio Control - Monitoring &
Control Relays
Liquid level control relays
RM22LA and RM22LG

References
PF143419

PF143420
Function Rated supply Measurement Time Output Reference Weight
voltage range delay
V Ω kg/lb
b Level 1/ 24…240 z 5 K…100 K No 1 CO 8 A RM22LG11MR 0.100/
Level 2 0.220
b Fill
operation
b Empty
operation

380…415 a 5 K…100 K No 1 CO 8 A RM22LG11MT 0.100/


0.220

RM22LG11MR RM22LG11MT
PF143421

PF143422

24…240 z 250...1 M On/Off 2 CO 8 A RM22LA32MR 0.110/


delay 0.242
(0.1...30 s)

380…415 a 250...1 M On/Off 2 CO 8 A RM22LA32MT 0.110/


delay 0.242
(0.1...30 s)

RM22LA32MR RM22LA32MT

53
Presentation, description, Zelio Control – Monitoring &
operation Control Relays
Level control relays
RM35L

Presentation
Level control relays RM35LM33MW and RM35LV14MW control 1 or 2 levels, with a
fill or empty function:
Functions RM35LM33MW RM35LV14MW
Level 1/Level 2
Fill / Empty operation
Detection by resistive probes
Detection by discrete sensors
Low / Standard / High sensitivity
RM35LpppMW Function performed
Function not performed

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED
The relays are designed for clip-on mounting on a 5 rail

Applications
These devices monitor the levels of conductive liquid or non-conductive material.
They control the actuation of pumps or valves to regulate levels, help protect
submersible pumps against dry running, or help protect tanks from “overflow”. They
can also be used to control dosing of liquids in mixing processes and help protect
heating elements in the event of non-immersion. They have a transparent, hinged
cover on their front panel to avoid any accidental alteration of the settings. This cover
can be directly sealed.
bb Application examples for RM35LM33MW:
vv spring water, town water, industrial water, and sea water
vv metallic salt, acid, or base solutions
vv liquid fertilizers and non-concentrated alcohol (< 40%)
vv liquids in the food processing industry: beer, coffee, etc.
bb Application examples for RM35LV14MW:
vv chemically pure water
vv fuels, liquid gases (inflammable)
vv oil, concentrated alcohol (> 40%)
A1 A2 Min Max C 12V12V Min Max 0V
vv ethylene, glycol, paraffin, varnish, and paints

Description
1 1 RM35LM33MW
2 2
1  Configuration: selection of operating mode / and of sensitivity range
3 3
Un
Tt
4
Tt
Un
LS, St, HS
R R 2  Sensitivity adjustment potentiometer %
3  Switch for selecting the number of levels
4  Time delay adjustment potentiometer Tt
12 11 14 22 21 24 A1 A2 12 11 14 5  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
5 4 RM35LV14MW
RM35LM33MW RM35LV14MW
2  Configuration: selection of operating mode / and of sensor type PNP, NPN
Tt Yellow LED: indicates timing status
3  Time delay adjustment potentiometer Tt
Un Green LED: indicates that supply to the product is on 4  Switch for selecting the number of levels
R Yellow LED: indicates relay output status 5  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail

Operating principle
Control relays RM35LM and RM35LV are Function Diagram
designed to control the levels of: Power supply off
bb Conductive liquid for RM35LM
Power supply on
(measures the levels by resistive probes)
bb Any other material for RM35LV Output 11-14, 21-24 open
(controls the levels of conductive liquids) Output 11-14, 21-24 closed
The operating principle is based on measurement of the apparent resistance of the
liquid between two submerged probes. When this value is less than the threshold
setting on the front panel of the device, the relay changes state. To avoid electrolytic
phenomena, an AC current runs across the probes.
A selector switch on the front panel allows selection of the required function and the
sensitivity range. Control of a single level can be achieved by using the second
selector switch. In this case, the Max. level probe stays up in the air and an
adjustable time delay avoids any wave effect.

54
Operation (continued) Zelio Control – Monitoring &
Control Relays
Level control relays
RM35L

Operating principle
RM35LM33MW
Relay RM35LV measures the levels by means of discrete sensors. These two products activate their output relay when a tank is either emptying
or filling.
bb A green Un LED indicates that the supply is on.
bb A yellow R LED indicates the state of the output relay.
bb A yellow Tt LED indicates that timing is in progress.
bb The green and yellow LEDs flash to indicate an unacceptable setting position.

A selector switch on the front panel of these relays allows selection of the required sensitivity range and the empty or fill function. A second switch allows
selection of the number of levels (1 or 2) and the type of time delay in the case of level 1 mode.

The position of these configuration switches is taken into account on energization.


bb If the configuration switch is set to an unacceptable position, the product detects a fault, the output relay stays open, and the LEDs flash to
signal the position error.
bb If the configuration switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally
with the function selected at the time of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

Control of two levels, empty and fill function


vv Fill/Empty function b Empty function
Supply Un level: 2, function:
-- LS (Low Sensitivity: 250 W…5 kW)
Max. level
-- St (Standard Sensitivity: 5 kW…100 kW)
Min. level -- HS (High Sensitivity: 50 kW…1 MW)
The output relay stays open until the liquid reaches the Max. level probe. As soon
Relays R as the Max. level is reached, the contact closes and allows emptying of the tank (valve
Relays
R
opens, pump starts, etc.). When the level drops below the Min. level, the contact
opens to stop the emptying process.
b Fill function
level: 2, function:
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
-- HS (High Sensitivity: 50 kW…1 MW)
The output relay stays energized until the liquid reaches the Max. level probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. level, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are being controlled, the anti-wave time delay function is not active.

Control of one level, empty function


vv Empty function T on b Level: 1 - on delay functions:
Supply Un
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level
-- HS (High Sensitivity: 50 kW…1 MW)
When the liquid level rises above the probe for a time greater than the time delay
Relays R
value Tt set on the front panel, the relay is energized and stays energized until the
Tt Tt Tt liquid level drops back to the probe.
If the liquid drops back below the set level before the end of the time delay, the relay
is not energized.

vv Empty function T off b Level: 1 - off delay functions:


Supply Un
-- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level
-- HS (High Sensitivity: 50 kW…1 MW)
When the liquid level rises above the probe, the relay is energized instantly and
Relays R
stays energized until the liquid again reaches the probe level for a time Tt set on the
Tt Tt Tt Tt front panel.
If the liquid drops back below the set level before the end of the time delay period,
the relay stays energized.

55
Operation (continued) Zelio Control – Monitoring &
Control Relays
Level control relays
RM35L

Operating principle (continued)


RM35LM33MW (continued)
Control of one level, fill function
vv Fill function T on bb Level: 1 - on delay functions:
Supply Un -- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level -- HS (High Sensitivity: 50 kW…1 MW)
11-12/11-14
When the liquid level drops below the probe for a time greater than the time delay
Relays R21-22/21-24
value Tt set on the front panel, the relay is energized and stays energized until the
Tt Tt Tt liquid level rises back up to the probe.
If the liquid rises back above the set level before the end of the time delay period, the
relay is not energized.

vv Fill function T off bb Level: 1 - off delay functions:


Supply Un -- LS (Low Sensitivity: 250 W…5 kW)
-- St (Standard Sensitivity: 5 kW…100 kW)
Level -- HS (High Sensitivity: 50 kW…1 MW)
11-12/11-14
When the liquid level drops below the probe, the relay is energized instantly and
Relays R21-22/21-24
stays energized until the liquid level again reaches the probe level and stays
Tt Tt Tt above it for a time greater than the time delay period Tt set on the front panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energized.

RM35LV14MW
A selector switch on the front panel allows selection of the function (empty or fill) and the type of sensor. A second switch allows selection of the
number of levels (1 or 2) and the type of time delay in the case of 1 level mode.

The position of these configuration switches is taken into account on energization.


bb If the configuration switch is set to an unacceptable position, the product detects a fault, the output relay stays open, and the LEDs flash to
signal the position error.
bb If the configuration switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate
normally with the function selected at the time of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the last energization, the LEDs return to their normal state.

Control of two levels


v Fill/Empty function bb Empty function
Supply Un Level: 2
The output relay stays open until the material reaches the Max. probe level. As
Max. level soon as the Max. level is reached, the contact closes and allows emptying of the
Min. level tank (valve opens, pump starts, etc.). When the level drops below the Min. probe
level, the contact opens to stop the emptying process.
Relays R

Relays R bb Fill function


Level: 2
The output relay stays energized until the material reaches the Max. probe. As soon
as the Max. level is reached, the contact opens and the pump stops. When the level
drops below the Min. probe level, the contact closes again and pumping re-starts to
raise the level.

Note: When two levels are being controlled, the anti-wave time delay function is not active.

Control of one level, empty function


v Empty function T on bb Level: 1 - on delay
Supply Un When the material level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energized and stays energized until the
Level material level drops back to the probe.
If the level rises above the probe before the end of time delay period, the relay is not
Relays R11-12/11-14 energized.
Tt Tt Tt

v Empty function T off bb Level: 1 - off delay


Supply Un When the material level rises above the probe, the relay is energized instantly and
stays energized until the material level again reaches the probe and stays below it
Level for a time greater than the time delay value Tt set on the front panel.
If the level drops back to below the probe before the end of time delay period, the
Relays R11-12/11-14 relay stays energized.
Tt Tt Tt Tt

56
Operation (continued), Zelio Control – Monitoring &
references Control Relays
Level control relays
RM35L

Operating principle (continued)


RM35LV14MW (continued)
Control of one level, fill function
vv Fill function T on bb Level: 1 - on delay
Supply Un When the material level drops below the probe for a time greater than the time
delay value Tt set on the front panel, the relay is energized and stays energized
Level until the material level again reaches the probe.
If the level rises above the probe before the end of time delay period, the relay is not
Relays R11-12/11-14 energized.
Tt Tt Tt

vv Fill function T off bb Level: 1 - off delay


Supply Un
When the material level drops below the probe, the relay is energized instantly and
stays energized until the material level again reaches the probe and stays above it
Level for a time greater than the time delay period Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
Relays R11-12/11-14
period, the relay stays energized.
Tt Tt Tt

References
Function Supply voltage Output Reference Weight
PF153429B

PF153422B

V kg/lb
Detection by 24…240 z 2 CO RM35LM33MW 0.130/
resistive probes 5A 0.287
(see page 68)

Detection by 24…240 z 1 CO RM35LV14MW 0.130/


discrete sensors 5A 0.287

RM35LM33MW RM35LV14MW

57
Presentation,description, Zelio Control - Monitoring &
operation Control Relays
3-phase and 1-phase pump control relays
RM35BA

Presentation
Measurement and control relay RM35BA10 is used for control and monitoring of
3‑phase and single‑phase pumps.
Functions RM35BA10
3-phase phase sequence
3-phase phase loss
3-phase overcurrent and undercurrent control
1-phase overcurrent and undercurrent control

Function performed
Function not performed
RM35BA10
These control relays allow:
vv Absence of one or more phases
vv Undercurrent for protection against dry running
vv Overcurrent for protection against overload
bb Acceptance of different nominal voltage values:
vv 208…480 V a in 3-phase mode
vv 230 V a in 1-phase mode
bb Clip-on mounting on a 5 rail
bb Monitoring of their own supply voltage measured as a true rms value

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Management of pumps
E1 L1 L2 L3
Description
RM35BA
1  Configuration: selection of active function and operating mode 3-ph/1-ph
1
(Double - Single)
>I
2
2  Overcurrent setting potentiometer > I
<I
3
Def.
Un 4 3  Undercurrent setting potentiometer < I
R
5 4  Time delay adjustment potentiometer Tt
5  Starting inhibition time delay adjustment potentiometer Ti
Y1 Y2 12 11 14
6  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
6
RM35BA Operating principle
Pump control relay RM35BA10 can operate Function Diagram
Def. Yellow LED: indicates fault present status
on a 1-phase or 3-phase supply and Power supply off
Un Green LED: indicates that supply to the product is on incorporates 3 functions in a single unit: Power supply on
R Yellow LED: indicates relay output status bb Current control
bb Phase presence control (in 3-phase mode) Output 11-14, 21-24 open
bb Phase sequence control (in 3-phase mode) Output 11-14, 21-24 closed
These relays have two operating modes which are designed to control a pump via
two external signal inputs (Y1 and Y2). These two signal inputs are controlled by
volt-free contacts.
Control signal inputs Y1 and Y2 can be connected to:
bb A level sensor
bb A level relay
bb A pressure sensor
bb A pushbutton, etc.
Fault signaling is by LEDs with differentiation of the reason for the fault.

RM35BA10
The following operating mode is selected by using a switch:
bb Single control
bb Double control
bb 1-phase or 3-phase supply
The position of the switch and the operating mode is read by the product on
energization.
bb If the switch position is changed while the device is operating, all the LEDs flash,
but the product continues to operate normally with the function selected at the time
of energization preceding the change of position.
bb If the configuration switch is returned to the original position selected prior to the
last energization, the LEDs return to their normal state.

58
Operation (continued), Zelio Control - Monitoring &
references Control Relays
3-phase and 1-phase pump control relays
RM35BA

Operating principle (continued)


RM35BA10 (continued)
Single control mode
vv Single control mode (3-ph/1-ph) This mode is designed to control a pump via an external signal. The relay output is
Supply Un closed when the signal is present at Y1 (contact closed). Y2 can be used to reset the
relay after a current fault.
Y1
Note: Ti: time delay to inhibit fault monitoring on pump starting (overcurrent and undercurrent,
Y2
setting on front panel)
Tt: time delay on occurrence of a fault (overcurrent or undercurrent, setting on front panel)
I.Def.
I. Def.: presence of a current fault (overcurrent or undercurrent)
Relays11-12
R
11-14

Ti Tt Tt Ti Ti Tt

Double control mode


vv Double control mode (3-ph/1-ph) This mode is designed to control a pump via two external control signals (Y1 and Y2).
Supply Un The output relay closes when both input signals are present (Y1 and Y2 closed). It
will open as soon as one of these signals disappears.
Y1

Y2
Note: Ti: time delay to inhibit fault monitoring on pump starting (overcurrent and undercurrent,
I.Def.
setting on front panel)
Tt: time delay on occurrence of a fault (overcurrent or undercurrent, setting on front panel)
Relays R11-12
11-14
I. Def.: presence of a current fault (overcurrent or undercurrent)
Ti Tt Tt Ti Ti Ti

1-phase or 3-phase supply control mode


vv Overcurrent detection > I bb If the control relay is configured for a 1-phase supply, it monitors the current
Supply Un consumed by the pump.
bb If the control relay is configured for a 3-phase supply, it monitors the current,
phase sequence and phase loss.
I>
I bb If a phase fault is detected, the output relay opens immediately.
bb On energization, if there is a phase sequence or phase loss fault, the output is
Relays R
11-12/11-14 unable to energize.
Ti Tt Ti
The overcurrent and undercurrent values are set by two separate potentiometers,
graduated from 1 to 10 A.
bb If a setting error occurs (low threshold greater than high threshold), the output
relay opens and all the LEDs flash to signal the error.
vv Undercurrent detection < I bb If a current fault occurs (overcurrent or undercurrent), the relay opens when the
Supply Un fault persists for longer than the threshold time delay setting.
I bb When the current returns to the correct value, the output relay continues to
remain open. It can only be re-energized by a RESET: either by switching off the
I< power, or by closing external contact Y2 (in single control mode).
bb An inhibition time delay on energization (Ti) allows detection of current peaks on
Relays R
11-12/11-14
motor starting.
Ti Tt Ti

Note: Ti: time delay to inhibit fault monitoring on pump starting (overcurrent and undercurrent,
setting on front panel)
Tt: time delay on occurrence of a fault (overcurrent or undercurrent, setting on front panel)

References
Function Current Supply Output Reference Weight
range voltage
PF153428A

controlled
A V kg/lb
3-phase: 1…10 bb 208…480 a, 1 CO RM35BA10 0.110/
bb Phase sequence 3-phase 5A 0.243
bb Phase loss
bb Overcurrent and bb 230 a,
undercurrent control 1-phase
1-phase:
bb Overcurrent and
undercurrent control

RM35BA10

59
Presentation, description, Zelio Control – Monitoring &
operation Control Relays
Frequency control relay
RM35HZ

Presentation
Frequency control relay RM35HZ monitors frequency variations on 50 or 60 Hz
AC supplies:
Functions RM35HZ21FM
Over-frequency (50 or 60 Hz)
Under-frequency (50 or 60 Hz)

Function performed
Function not performed

These control relays allow:


bb Over-frequency and under-frequency with two independent relay outputs
RM35HZ21FM bb Selectable memory function
bb Monitoring of their own supply voltage measured as a true rms value
bb Clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
Monitoring of electrical power sources:
bb Generating sets, wind turbines, micro-power stations, etc.
A1 A2
Description
RM35HZ21FM
1  Configuration: selection of 50/60 Hz frequency range and operating mode (with
1
or without memory) Memory - No Memory
2
3 2  Frequency tolerance multiplication setting potentiometer x1-x2
4
3  Low frequency threshold setting switch F <
R1
Un
5
4  High frequency threshold setting switch F >
R2

5  Time delay adjustment potentiometer


12 11 14 22 21 24 6  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
6
RM35HZ21FM
Operating principle
R1 Yellow LED: indicates relay status (high frequency
threshold) Frequency control relay RM35HZ monitors: Function Diagram
vv Frequency variations on 50 or 60 Hz
Un Green LED: indicates that supply to the product is on Power supply off
supplies
R2 Yellow LED: indicates relay status (low frequency threshold) vv Over-frequency and under-frequency via Power supply on
adjustment of two independent thresholds. Output 11-14, 21-24 open
(It has two relay outputs: one per threshold) Output 11-14, 21-24 closed
vv Fault signaling is by LED

bb Function selector switch:


vv Set the switch to a frequency of 50 or 60 Hz of the supply monitored, then select
Memory or No memory mode.
vv The position of the switch and the operating mode is read by the product on
energization.
vv If the switch is set to an unacceptable position, the product detects a fault, the
output relays stay open and the LEDs flash to indicate the position error.
vv If the switch position is changed while the device is operating, all the LEDs flash
but the product continues to operate normally with the function selected at the time
of energization preceding the change of position.
vv If the switch is returned to the original position selected prior to the last
energization, the LEDs return to their normal state.

60
Operation (continued), Zelio Control – Monitoring &
references Control Relays
Frequency control relay
RM35HZ

Operating principle (continued)


RM35HZ21FM
The under-frequency or over-frequency threshold values are set using two graduated potentiometers indicating the variation value of the
frequency to be monitored. A switch x1/x2 allows the control scale to be doubled. Hysteresis is fixed at 0.3 Hz.

Over-frequency and under-frequency without memory


vv Over-frequency and under-frequency control, without bb If the frequency of the voltage controlled exceeds the over-frequency threshold
memory setting for a time greater than that set on the front panel (0.1…10 s), the
Supply Un corresponding output relay opens and its LED goes off. During the time delay, this
LED flashes.
F > bb As soon as the frequency drops below the value of the threshold setting, minus
Hysteresis the hysteresis, the relay instantly closes.
Hysteresis F
bb If the frequency of the voltage controlled falls below the under-frequency
F < threshold setting for a time greater than that set on the front panel (0.1…10 s), the
11-12
corresponding output relay opens and its LED goes out. During the time delay, this
Relay R1 11-14 LED flashes.
Relay R2 21-22
21-24
bb As soon as the frequency rises above the value of the threshold setting, plus the
hysteresis, the relay instantly closes.
Tt Tt
bb On energization of the device with a detected measured fault, the relay stays
open.

Note: Tt: time delay after crossing of the threshold (adjustable on front panel)

Over-frequency and under-frequency with memory


vv Over-frequency and under-frequency control with If “Memory” mode is selected, the relay opens after the time delay and stays in that
memory position when crossing of the threshold is detected.
Supply Un The power needs to be switched off to reset the product.

F >
Hysteresis
Hysteresis F
F <
11-12
Relay R1 11-14

Relay R2 21-22
21-24

Tt Tt
Note:Tt: time delay after crossing of the threshold (adjustable on front panel)

Reference
Function Range Supply Output Reference Weight
controlled voltage
Zeliocontrol_528_RDSPH16045

V kg/lb
b Over- 40…60 Hz 120…277 a 1 CO + 1 CO RM35HZ21FM 0.130/
frequency (50 Hz) / 5A 0.287
and 50…70 Hz
under- (60 Hz)
frequency
50 or 60 Hz

RM35HZ21FM

61
Presentation, Zelio Control – Monitoring &
description Control Relays
Speed control relay
RM35S

Presentation
Speed control relay RM35S0MW monitors:
Functions RM35S0MW
Underspeed (with/without memory, with inhibition by external
contact S2)
Overspeed (with/without memory, with inhibition by external
contact S2)

Function performed
Function not performed

Speed control relay RM35S0MW measures via:


RM35S0MW bb A 3-wire PNP or NPN proximity sensor input
bb A Namur proximity sensor input
bb A 0-30 V voltage input
bb A volt-free contact input

These control relays allow:


bb Operation with either NO or NC sensors
bb Adjustable time between impulses from 0.05 s…10 min
bb Adjustable power-on inhibition time from 0.6 to 60 s
bb Inhibition controlled by an external contact
bb Clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Monitoring the speed or rate of rotary or linear movements in the following
applications:
vv conveyors/conveyor belts
vv packaging
vv material handling
Y1 12V 12V E1 E2 0V

Description
RM35S00MW
1 1  Configuration: selection of operating mode: Underspeed or overspeed
2 Underspeed/Overspeed
In
3 with or without memory Memory - No Memory
Un 4 2  Speed threshold setting potentiometer Value
R

3  Speed range selector switch


A1 A2 12 11 14
4  Starting inhibition time delay adjustment potentiometer Ti
5 5  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
RM35S0MW

In Yellow LED: indicates inhibition status (time delay or S2 input)


Un Green LED: indicates that supply to the product is on
R Yellow LED: indicates relay output status

62
Operation Zelio Control – Monitoring &
Control Relays
Speed control relay
RM35S

Operating principle
Relay RM35S0MW monitors the speed (rate, frequency) of a process Function Diagram
(conveyor, conveyor belt, etc.) using discrete sensors:
Power supply off
vv 3-wire PNP or NPN proximity sensor
vv 0-30 V voltage input Power supply on
vv NAMUR proximity sensor Output 11-14, 21-24 open
vv volt-free contact Output 11-14, 21-24 closed
It can be used for monitoring underspeed or overspeed.

RM35S0MW
The control relay measures the speed as follows:
vv The cycle of the process being monitored is a series of impulses characterized by a two-state signal: high and low.
vv The speed is obtained by measuring the period of this signal, from the detection of first change of state (either rising or falling edge).
vv Digital processing of the signal allows the disparity between the signals to be calculated.
vv On energization or after appearance (or reappearance) of the sensor signal, detection (characterization) of the signal requires processing
of one or two periods. During this time, control is inoperative.

The operating modes are selected by using the switch:


vv Underspeed without memory
vv Underspeed with memory
vv Overspeed without memory
vv Overspeed with memory

Underspeed control without memory


vv Underspeed control, without memory At the end of the starting inhibition time delay “Ti”, as soon as the speed measured
1 sec mini drops below the threshold setting, the output relay changes state from “closed” to
Supply Un “open”.
Hysteresis It returns to its initial state when the speed is again higher than the threshold plus
Threshold Vs V hysteresis (fixed at 5% of the threshold setting).
Ti Ti
When power is restored, after a break having lasted at least 1 s, the relay is in the
“closed” state during the time delay and stays in that state for as long as the speed
In
remains higher than the threshold.
Relays R
11-12/11-14

Underspeed control with memory


vv Underspeed control, with memory When relay RM35S has been configured in “memory” mode, if underspeed is
1 sec mini detected, the output relay stays in the “open” state, irrespective of any further
changes in the process speed.
Supply Un
50 ms mini It will not be able to return to the “closed” state until contact S2 closes (for at least
S2 50 ms).
Hysteresis
If, when S2 re-opens, the speed is not high enough, the relay returns to “open” state.
Threshold Vs V Relay RM35S can also be reset by a power break (at least 1 s); the relay then returns
to the “closed” state for at least the duration of the time delay, irrespective of the
Ti Ti
process speed.
In
Relays R11-12/11-14

63
Operation (continued) Zelio Control – Monitoring &
Control Relays
Speed control relay
RM35S

Operating principle (continued)


RM35S0MW
Underspeed control with inhibition by S2
vv With inhibition by S2 Inhib./S2 On energization, to allow the process being monitored to reach its nominal
operating speed, relay RM35S is inhibited for a time delay adjustable from
Supply Un 0.6…60 s. This time delay can be adjusted (shortened or lengthened) during
S2 inhibition.
Hysteresis Relay RM35S can also be inhibited by closing of contact S2: on starting, for
Threshold Vs V example, if the process run-up to speed time is greater than 60 s, or at any
Ti time during operation.
Whether it results from a starting inhibition time delay or closing of S2,
In inhibition keeps the output relay in the “closed” position and is signaled by
Relays R 11-12/11-14 illumination of the inhibition LED.
If, after lifting of inhibition (end of starting inhibition time delay or opening of
contact S2), the signal detection phase has not been completed, the relay
drops out after the set wait time between two impulses (measured from the
end of inhibition).
Inhibition should last as long as is necessary for the product to detect at least 2
periods.
When the signal has not been ‘characterized’ by the end of the inhibition
period, the “inhibition” LED flashes for as long as speed measurement is
impossible.
It is also possible to inhibit relay RM35S at any time, during operation, by
closing S2.

Overspeed control without memory


vv Overspeed control, without memory At the end of the starting inhibition time delay, “Ti”, as soon as the speed
1 sec mini measured is higher than the threshold setting, the output relay changes state
Supply Un
from “closed” to “open”.
It returns to its initial state when the speed is again lower than the threshold
Threshold Vs minus hysteresis (fixed at 5% of the threshold setting).
Hysteresis V When power is restored to relay RM35S, after a break having lasted at least
Ti Ti 1 s, the relay is in the “closed” state during the time delay and stays in that
state for as long as the speed remains lower than the threshold.
In

Relays R
11-12/11-14

Overspeed control with memory


vv Overspeed control, with memory When relay RM35S has been configured in “memory” mode, if overspeed is
1 sec mini
detected, the output relay stays in the “open” state, irrespective of any further
changes in the process speed.
Supply Un
It will not be able to return to the “closed” state until contact S2 closes (for at
50 ms mini
least 50 ms).
S2 If, when S2 re-opens, the speed is too high, the relay returns to the “open”
Threshold state.
Vs
Hysteresis V Relay RM35S can also be reset by a power break (at least 1 s); the relay then
returns to the “closed” state for at least the duration of the time delay,
Ti Ti irrespective of the process speed.
In
Relays R
11-12/11-14

64
Operation (continued), Zelio Control – Monitoring &
reference Control Relays
Speed control relay
RM35S

Operating principle (continued)


RM35S0MW
Overspeed control with inhibition by S2
vv With inhibition by S2. Inhib./S2 On energization, in order to allow the process being monitored to reach its nominal
Supply Un operating speed, relay RM35S is inhibited for a time delay adjustable from 0.6…60 s.
This time delay can be modified (shortened or lengthened) during inhibition.
S2 Relay RM35S can also be inhibited by closing of contact S2: on starting, for
Threshold Vs
Hysteresis V example, if the process run-up to speed time is greater than 60 s, or at any time
during operation.
Ti Whether it results from a starting inhibition time delay or closing of S2, inhibition
In keeps the output relay in the “closed” position and is signaled by illumination of the
Relays 11-12/11-14
R
inhibition LED.
If, after lifting of inhibition (end of starting inhibition time delay or opening of contact
S2), the signal detection phase has not been completed, the relay drops out after the
set wait time between two impulses (measured from the end of inhibition).
Inhibition should last as long as is necessary for the product to detect at least 2 periods.
When the signal has not been ‘characterized’ by the end of the inhibition period, the
“inhibition” LED flashes for as long as speed measurement is impossible.
It is also possible to inhibit relay RM35S at any time, during operation, by closing S2.

Reference
Function Supply Measurement Output Reference Weight
Zeliocontrol_528_ADSPH16039

voltage Input kg/lb


V
b Underspeed 24…240 z b 3-wire 1 CO RM35S0MW 0.130/
b Overspeed PNP or NPN 5A 0.287
proximity sensor
b Namur proximity
sensor
b 0-30 V voltage
b Volt-free contact

RM35S0MW

65
Presentation, description, Zelio Control - Monitoring &
operation Control Relays
Temperature control relays for elevator machine rooms
and 3-phase supplies
RM35ATL, RM35ATR, and RM35ATW

Presentation
Measurement and control relays RM35ATL0MW, RM35ATR5MW and
RM35ATW5MW are designed for monitoring the temperature in elevator machine
rooms, in compliance with directive EN81.
Functions RM35ATL0MW RM35ATR5MW RM35ATW5MW
Overtemperature (34…46 °C)
Undertemperature (-1…11 °C)
Phase sequence
Phase loss

RM35ATp0MW Function performed


Function not performed

These control relays allow:


bb PT100 input
bb Adjustable control around 5 °C and 40 °C
bb Independent adjustment of high and low thresholds
bb Possibility of integrated phase control
bb Clip-on mounting on a 5 rail

They feature:
bb A sealable cover to help protect the settings
bb A control status indicator LED

Applications
bb Temperature control for elevator machine rooms

A B B A B B
Description
RM35ATL0MW, RM35ATR5MW
1  High temperature threshold setting potentiometer q>
1 1
2  Potentiometer for adjustment of time delay on crossing of temperature
2 2 threshold Tt
3 3
>
Un
>
Un
3  Low temperature threshold setting potentiometer q<
< <
4  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
5  High temperature threshold contact (11-14)
A1 A2 12 11 14 A1 A2 11 14 21 24
6  Low temperature threshold contact (21-24)
6
7 5 7  High and low temperature threshold contacts
4 4
RM35ATL0MW RM35ATR5MW

> Yellow LED: indicates relay output status (high


temperature threshold)
Un Green LED: indicates that supply to the product is on
< Yellow LED: indicates relay output status (low
temperature threshold)

A B B L1 L2 L3 RM35ATW5MW
1  High temperature threshold setting potentiometer q>
1 2  Potentiometer for adjustment of time delay on crossing of
2 temperature threshold Tt
3 3  Low temperature threshold setting potentiometer q<
< <
Un
L1 4  Spring for clip-on mounting on 35 mm/1.38 in. 5 rail
L3 L2

5  Temperature relay contact (11-14)


6  Phase relay contact (21-44)
A1 A2 11 14 21 24

6
5
4
RM35ATW5MW
Operating principle
<q°< Yellow LED: indicates temperature relay output status R1 Temperature control relays for elevator Function Diagram
Un Green LED: indicates that supply to the product is on machine rooms are designed to monitor
L1
Power supply off
Yellow LED: indicates phase relay output status R2 the stated temperature between 5 °C and
L3 L2
Power supply on
40 °C in compliance with directive EN81.
Output 11-14, 21-24 open
Output 11-14, 21-24 closed

66
Operation (continued), Zelio Control - Monitoring &
references Control Relays
Temperature control relays for elevator machine rooms
and 3-phase supplies
RM35ATL, RM35ATR, and RM35ATW

Operating principle (continued)


RM35ATL0MW
Temperature control by PT100 probe
vv Temperature control by PT100 probe After a delay on pick-up after energization, and for as long as the temperature monitored
Supply Un by the PT100 probe remains between the two thresholds set on the front panel, the
output relay is closed and the yellow LEDs are on.
θ° > When the temperature crosses one of the threshold settings on the front panel (high or
Hysteresis
θ° low threshold), the time delay set on the front panel (Tt) is activated. The yellow LED
Hysteresis corresponding to the threshold crossed (low or high) flashes.
θ° < At the end of the time delay, if the temperature is still outside the threshold setting, the
output relay opens and the yellow LED corresponding to the threshold crossed goes out.
Relays R The output relay closes instantly (within the response time on disappearance of a fault)
Tt Tt when the temperature returns within the window of the two threshold settings on the
front panel, plus the fixed hysteresis.
If the PT100 probe is incorrectly wired (missing or short-circuited) the relay is open and
the 3 LEDs flash.
Note: Tt: time delay after crossing of the temperature threshold (adjustable on front panel)
RM35ATR5MW
Temperature control by PT100 probe
vv Temperature control by PT100 probe After a delay on pick-up after energization, and for as long as the temperature monitored
Supply Un by the PT100 probe remains between the two threshold settings on the front panel, the
output relays are closed and their yellow LEDs are on.
θ° >
When the temperature crosses one of the threshold settings on the front panel (high or
Hysteresis
θ° low threshold), the time delay set on the front panel (Tt) is activated. The yellow LED
Hysteresis corresponding to the threshold crossed (low or high), flashes.
θ° < At the end of the time delay, if the temperature is still outside one of the threshold
settings, the corresponding output relay opens and the yellow LED corresponding to the
Relay R1
threshold crossed goes out.
Relay R2 The output relay closes instantly (response time on disappearance of a fault) when the
Tt Tt temperature returns within the window of the two threshold settings on the front panel,
plus (or minus) the fixed hysteresis.
If the PT100 probe is incorrectly wired (missing or short-circuited) the relays are open
and the 3 LEDs flash.
Note: Tt: time delay after crossing of the temperature threshold (adjustable on front panel)
RM35ATW5MW
Temperature and phase control
vv Temperature control by PT100 probe After a delay on pick-up after energization, and for as long as the temperature monitored
vv Sequence of phases L1, L2, and L3 by the PT100 probe remains between the two threshold settings on the front panel, the
vv Phase loss temperature relay R1 is closed.
Supply Un
When the temperature crosses one of the threshold settings on the front panel (high or
low threshold), the time delay set on the front panel (Tt) is activated. The yellow
θ° > temperature LED flashes. At the end of the time delay, if the temperature is still outside
the threshold setting, the output relay R1 opens and the yellow LED goes out.
Hysteresis θ°
Hysteresis The output relay R1 closes instantly when the temperature returns to within the window
θ° < of the two threshold settings on the front panel, plus or minus the fixed hysteresis.
The device also monitors the correct sequence of phases L1, L2, and L3 of the 3‑phase
Relay R1 supply and total phase loss, even in the case of phase regeneration (< 70%).
After a delay on pick-up after energization, and for as long as phase presence and
Tt Tt
phase sequence are correct, relay R2 and the “phase” LED are On. When a fault
appears, the “phase” relay opens and the “phase” LED instantly goes out (response
time on appearance of a fault).
When the fault disappears, the phase control relay and LED are activated (response
time on disappearance of a fault).
If the PT100 probe is incorrectly wired (missing or short-circuited) relay R1 is open and
LED R1 flashes.
Note: Tt: time delay after crossing of the temperature threshold (adjustable on front panel)
References
Function Supply 3-phase Output Reference Weight
voltage control
Zeliocontrol_528_RDSPH16044

Zeliocontrol_528_RDSPH16044

V V kg/lb
bb Overtemperature: 34…46 °C 24…240 – 1 CO RM35ATL0MW 0.130/
bb Undertemperature z 5A 0.287
- 1…11 °C
– 2 NO RM35ATR5MW 0.130/
5A 0.287

bb Overtemperature: 34…46 °C 24…240 208…480 2 NO RM35ATW5MW 0.130/


bb Undertemperature - 1…11 °C z a 5A 0.287
bb Phase sequence
RM35ATL0MW RM35ATR5MW bb Phase loss

67
References Zelio Control - Monitoring &
Control Relays
Electrode holders and probes

Probes
Application No. Length Opera- Maximum Reference Weight
of ting pressure
probes temper-
ature
mm/in. °C/°F kg/cm2 kg/lb
Recommended 3 1000/ 80/ 2 RM79696044 0.800/
for drinks vending 39.37 176 1.764
machines and
where installation
space is limited
(Stainless steel)

Suitable for 1 1000/ 200/ 25 RM79696014 0.360/


boilers, pressure 39.37 392 0.794
vessels and high
temperature
conditions (1)
(304 stainless
steel)

Description Material Reference Weight


kg/lb
Protected probe Protective shell RM79696043 0.150/
561034

for mounting by suspension PUC (S7) 0.331


Electrode: stainless
steel

Description Type of Maximum operating Reference Weight


RM79696043
installation temperature
°C/°F kg/lb
Liquid level Suspended 100/ LA9RM201 0.100/
561089

control probe by cable 212 0.220

LA9RM201
(1) 3/8" BSP mounting thread with hexagonal head. Use a 24 mm (0.95 in.) spanner for tightening.

68
References (continued) Zelio Control - Monitoring &
Control Relays
Electrode holders and probes

Electrode holders
Description Material Reference Weight
kg/lb
Electrode for use up to 350 °C Ceramic-insulated RM79696006 0.150/
561035

561036

and 15 kg/cm2 (1) stainless steel 0.331

RM79696006

(1) 3/8" BSP mounting thread.

69
Index Product reference index

L
LA9RM201 68

R
RM17JC00MW 43
RM17TA00 21
RM17TE00 21
RM17TG00 13
RM17TG20 13
RM17TT00 21
RM17TU00 21
RM17UAS14 35
RM17UAS15 35
RM17UAS16 35
RM17UB310 27
RM17UBE15 35
RM17UBE16 35
RM22JA21MR 47
RM22JA31MR 47
RM22LA32MR 53
RM22LA32MT 53
RM22LG11MR 53
RM22LG11MT 53
RM22TA31 17
RM22TA33 17
RM22TG20 17
RM22TR31 17
RM22TR33 17
RM22TU21 17
RM22TU23 17
RM22UA21MR 41
RM22UA22MR 41
RM22UA23MR 41
RM22UA31MR 41
RM22UA32MR 41
RM22UA33MR 41
RM22UA33MT 41
RM22UB34 41
RM35ATL0MW 67
RM35ATR5MW 67
RM35ATW5MW 67
RM35BA10 59
RM35HZ21FM 61
RM35JA31MW 49
RM35JA32MR 47
RM35JA32MT 47
RM35JA32MW 49
RM35LM33MW 57
RM35LV14MW 57
RM35S0MW 65
RM35TF30 23
RM35TM50MW 31
RM35TM250MW 31
RM35UA11MW 37
RM35UA12MW 37
RM35UA13MW 37
RM35UB3N30 27
RM35UB330 27
RM79696006 69
RM79696014 68
RM79696043 68
RM79696044 68

70
Schneider Electric Industries SAS www.schneider-electric.com/relays
Head Office The information provided in this documentation contains general descriptions and/or technical
35, rue Joseph Monier characteristics of the performance of the products contained herein. This documentation is
F-92500 Rueil-Malmaison not intended as a substitute for and is not to be used for determining suitability or reliability of
France these products for specific user applications. It is the duty of any such user or integrator to
perform the appropriate and complete risk analysis, evaluation and testing of the products with
respect to the relevant specific application or use thereof. Neither Schneider Electric nor any
of its affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein.

Design: Schneider Electric


Photos: Schneider Electric
DIA5ED2160501EN

December 2016 - V1.1