You are on page 1of 2

SIEMER Pages: 1 of 2

PRE-COMISSIONING TEST REPORT


TECHNOLOGIES

Client : KRISHNAPANTHAM PORT COMPANY LTD.


Project : 6.6 KV SWITCH GEAR PANEL FOR WAGON LOADING SYSTEM
Location : SS-3
Feeder Detail : PANEL 35 – 6.6 KV SWITCH BOARD SS3 SPACE CAPACITOR FEEDER -4 (2000) KVAR
Equipment Details : CB CURRENT TRANSFORMER
Make : PARGATI ELECTRICALS PVT. LTD.
Sr. No.
11/T-101077 : CORE RATIO CLASS VA
: Core-1 50/1 - -

I. Insulation Resistance Measurement : ( Values in M )


Secondary -Earth and Between Secondary tested with 500V.

REFRENCE VALUE
Secondary - Earth 459 M

II. CT SECONDARY WINDING RESISTANCE CHECK:

Terminal No. VALUE


1S1 – 1S2 0.23

________________________________________________________________________________________

Tested By : Vamish Umar Witnessed by: Witnessed by:

SIEMER Technologies VSE Ltd KPPCL

Date :
SIEMER Pages: 2 of 2
PRE-COMISSIONING TEST REPORT
TECHNOLOGIES

III. Primary Injection Test :

Primary Current Scondary Current

% Amp Amp

50 25 0.49

100 50 0.99

IV. Polarity Check :


Test set up with P1 +ve P2 -ve

S1 CLOCKWISE +ve kick with respect to S2

Result Core 1

1S1-1S2 OK

CT found healthy : YES

________________________________________________________________________________________

Tested By : Vamish Umar Witnessed by: Witnessed by:

SIEMER Technologies VSE Ltd KPPCL

Date :

You might also like