You are on page 1of 6

Arc Flash Evaluation and Hazard Mitigation

for the Colorado School of Mines


Electrical Power Distribution System
Charles A. Larkin, Janson Ferrera, Robert Kohl, Corey Lamb, Powell Margetts, and Ravel F. Ammerman, Ph.D.
Division of Engineering
Colorado School of Mines
Golden, CO 80401 USA
Email: rammerma@mines.edu

Abstract—An arc flash is the release of electrical energy during For the safety of personnel working on electrical equipment,
an arcing fault, which dissipates in the form of heat energy, arc flash analyses of power distribution systems is mandated
intense light, blast pressure, severe sound waves, electromagnetic by OSHA Standard 1910 Subpart S: Safety Standards for
radiation, and toxic gases. The thermal energy, concussive forces, Electrical Systems [1]. In addition, Article 130.3 of NFPA 70E
and flying debris can pose serious threats to the safety of states that “a flash hazard analysis shall be done in order to
personnel working in close proximity to electrical equipment. In
protect personnel” [3]. And Article 110.16 of the National
order to identify the severity of an arc flash hazard at the
Colorado School of Mines (CSM), an arc flash hazard evaluation Electrical Code requires that arc flash warning labels be placed
of the electrical power distribution system has been conducted. on any electrical equipment that might require inspection or
The arc flash analysis has been performed in accordance with maintenance [4]. Furthermore, the industry preferred method
NFPA 70E: Standard for Electrical Safety in the Workplace, and for an arc flash analysis is documented in IEEE 1584. The
IEEE 1584: Guide for Performing Arc Flash Hazard Calculations. results of an arc flash study include the determination of
The analysis of the existing system configuration has revealed incident energy levels, flash protection boundaries, and the
that many locations on the CSM campus are in the “dangerous” personal protective equipment (PPE) that should be worn by
arc flash hazard category, and consequently work cannot be personnel performing energized maintenance [5].
performed on energized equipment at these locations. With an
An arc flash hazard analysis of the Colorado School of
understanding of the thermal energy available, design
recommendations, including the selection and coordination of Mines power distribution system has been conducted to
fuses and circuit breakers, were investigated to reduce the identify the severity of an arc flash hazard throughout the CSM
severity of arc flash events. Implementation of the selected system. The study included all three-phase transformers on
protective devices can decrease the incident energy levels of CSM campus, and the incident energy available at the low-voltage
locations and eliminate any instances of “dangerous” hazard risk side of each transformer under a three-phase bolted fault
categories. Other hazard mitigation considerations include condition was estimated using SKM PowerTools and by
increasing the working distance, and utilizing arc suppression manual calculations. Subsequently, hazard mitigation
blankets while performing maintenance. In addition, electrician recommendations were determined in order to minimize
training to promote safe work practices is strongly encouraged.
incident energy levels, and to promote “safety by design.”
Also, arc flash training is strongly recommended for all CSM
I. INTRODUCTION
electrical workers to encourage safe work practices.
An arc flash event is a highly destructive electrical hazard as
recognized by the Occupational Safety and Health II. PROCEDURE
Administration (OSHA) [1]. An arc flash is the release of
electrical energy during an arcing fault, which dissipates in the A. System Verification
form of heat energy, intense light, blast pressure, severe sound Field verification of equipment ensures the arc flash hazard
waves, electromagnetic radiation, and toxic gases [2]. The calculations are accurate to the equipment in operation. During
release of energy is enough to ionize the surrounding air and field verification the nameplate information from each
vaporize equipment. The rapid expansion of vaporized metal is
transformer was photographed and recorded. In addition, the
equivalent to an explosion. Molten metal and copper shrapnel
conductor characteristics and the characteristics of the
may be expelled from the explosion. Intense blast pressure and
protective devices were documented. Furthermore, the
severe sound waves are also generated [3]. Arc flash events
can release enough energy to cause destruction of property and maximum available fault current from the utility, Xcel Energy,
severe personal injuries or even fatalities [1]. and trip settings for the recloser on campus were acquired
from the area engineer for the CSM campus [6]. The collected
system data was input to SKM PowerTools to analyze the
The work presented was supported in part by the Denver Section of the CSM power distribution system by performing a short circuit
IEEE Power & Energy Society and Industry Applications Society. study, a protective device study, and an arc flash hazard study.
B. Modes of Operation
The CSM power distribution system is designed as a loop The simplified method was chosen because the equations
with a switch near the center of the loop, which is normally outlined in the standards can be quite cumbersome. In
open, as illustrated in Fig. 1 [7]. However, this switch can be addition, the 3-4-5 method is based on the IEEE 1584
closed to back-feed buildings if a segment of the system fails equations, but will provide a conservative estimation.
or is shut-down for maintenance. While completing the study However, SKM was utilized to determine the arcing currents
several operating modes were considered. However, the results based on the IEEE 1584 and NFPA 70E calculation methods,
from analyzing the different operation modes showed little and the calculations described by the standards were
variation in incident energies at the low-side of the performed manually at several transformers.
transformers. This paper will focus on the low-voltage results D. Protective Device Study
for Normal Operation, which consists of the normally-open
The next step was to perform a protective device study to
switch being open while all other switches throughout the
determine the clearing device and clearing time for each arcing
CSM distribution system are closed. current. The time required to clear an arc is equivalent to the
duration of the arc, or the arcing time. The arcing time is
necessary to calculate the incident energy levels during the arc
flash hazard study. To complete the incident energy
calculations a maximum arc duration of two seconds was
assumed for each fault location as recommended in Section
B.1.2 of Annex B in IEEE 1584. Two seconds is a reasonable
maximum arcing time for calculations, because “it is likely that
a person exposed to an arc flash will move away quickly if it is
physically possible” [5].
SKM PowerTools was utilized to construct the time-current
characteristic (TCC) drawings for the protective devices. The
SKM software was also used to determine the arcing durations
for the IEEE 1584 and NFPA 70E calculation methods, and
the arcing times were verified by manually examining the TCC
drawings. Furthermore, the drawings were manually inspected
to estimate the arcing durations for the 3-4-5 method.
During the protective device study the TCC drawings were
Fig. 1. CSM power distribution system with normally-open switch [7]. also analyzed to identify miscoordination. Areas of
miscoordination are evident if the curves for the various
C. Short Circuit Study devices overlap [9]. In addition, miscoordination exists if the
During the short circuit study the bolted three-phase fault clearing device is a fuse or circuit breaker other than the
currents at each bus location were determined. Computing the protective device directly upstream of the fault location.
bolted fault currents was easily done by performing a short Protective device coordination was considered while selecting
circuit analysis in SKM. However, the SKM results were the recommended protective devices during hazard mitigation.
verified by manually calculating the bolted fault currents at the E. Arc Flash Hazard Study
low-side of each transformer. This was accomplished by
The arc flash evaluation was conducted using SKM
treating each 13.2 kV bus in the loop as an infinite bus. In
addition, the impedance of the cable between the bus and the PowerTools and the software determined the incident energy
transformer was ignored, and the impedance of the transformer level and arc flash boundary at the low-voltage side of each
was modeled as a pure reactance. This approach allowed the transformer. SKM was utilized to perform the evaluation using
maximum bolted fault current to be calculated for each the IEEE 1584 method and the NFPA 70E method.
transformer. Furthermore, it was assumed that the system Furthermore, the SKM results were verified by manually
voltage was at rated capacity (i.e. one per-unit). performing the analysis at several transformers using the
The bolted three-phase fault at the low-side of each equations described in Section 5 of IEEE 1584 and the
transformer was compared to the SKM calculations to verify equations outlined in Annex D.6 of NFPA 70E. Furthermore,
the results. It was seen that the manual calculations provided a the arc flash evaluation was conducted manually by
conservative estimate of the fault currents determined by implementing the 3-4-5 method, which allows the incident
SKM, as expected. Next, the bolted fault currents, Ibf, from the energy, E, to be determined directly from the three-phase
SKM short circuit study were used to manually determine the bolted fault current and arc duration, t. The incident energy
arcing fault currents, Ia, using the simplified 3-4-5 method level in cal/cm2 was calculated using (2) at the low-side of
derived by Ammerman, Sen, and Nelson, as shown in (1) [8]. each transformer [8].

I a = 0.6 I bf (1) E = 3.11I bf t (2)


To further illustrate the severity of arc flash hazard risks
Equation (2) is valid for system voltages 480 V and below. throughout the CSM system Fig. 3 groups the IEEE estimated
For the CSM power distribution system the secondary voltage energies by hazard risk category. The pie-chart indicates that
of each transformer is either 208 V or 480 V. The equation is 50% of the CSM incident energies are categorized as
based on the IEEE 1584 method, and assumes panelboard dangerous, and another 33% of the incident energies are
equipment type, an enclosed equipment configuration, an classified as third and fourth category hazard risks.
ungrounded system, and a working distance of 18 inches.
Consequently, (2) provides a conservative or worst-case
approximation of the incident energy level [8].

III. ARC FLASH STUDY RESULTS


The incident energies determined by the three calculation
methods are compared in Fig. 2. For each calculation method
transformers below 240 V, and less than 125 kVA have been
classified as hazard risk category zero as recommended in
Section 4.2 of IEEE 1584, which states that “equipment below
240 V need not be considered unless it involves at least one
125 kVA or larger low-impedance transformer in its
immediate power supply” [5]. The hazard risk categories have
also been superimposed on the chart. Fig. 2 indicates that
several CSM incident energies merit concern, and many
energy levels are greater than 25 and even 40 cal/cm2.
Fig. 3. IEEE incident energies by hazard risk category.

IV. IMPLICATIONS
The hazard risk categories determined during the arc flash
study indicate what level of protective clothing must be worn
by personnel performing energized maintenance on equipment
classified as a certain hazard risk. Table I outlines the hazard
risk categories, including the incident energy values for each
category, and the level of personal protective equipment (PPE)
that must be worn by personnel. The hazard risk categories are
established in NFPA 70E [3].

TABLE I
PPE REQUIREMENTS FOR EACH HAZARD RISK CATEGORY [3]

Hazard Risk Incident Energy Clothing


Clothing Description
Fig. 2. Incident energy comparison of calculation methods. Category (cal/cm2) Layers
0 0.0 – 1.2 Untreated Cotton 1
In addition, the figure indicates that the incident energy 1 1.2 – 4.0 FR Shirt & Pants 1
Cotton Underwear +
level varies depending on the calculation method. However, it 2 4.0 – 8.0 1 or 2
FR Shirt & Pants
is seen that the 3-4-5 method does conservatively track the Cotton Underwear +
IEEE 1584 results in most cases. The 3-4-5 method fails to 3 8.0 – 25 FR Shirt & Pants + 2 or 3
provide a conservative estimation of the IEEE incident energy FR Coverall
at Meyer Hall, Engineering Hall, and Weaver Towers due to Cotton Underwear +
3 or
4 25 – 40 FR Shirt & Pants +
the shape of the time-current characteristic curve of the Multi-Layer Flash Suit
more
protective device at each location. At the three buildings the Dangerous!! > 40 NONE AVAILABLE -
IEEE results utilize an arcing current, which is significantly
less than the arcing current predicted by the 3-4-5 method. The As indicated by the table PPE does not exist that would be
greater arcing current utilized by the 3-4-5 method as adequate to protect electrical workers at 50% of the CSM
compared to the IEEE method, and the shape of the TCC locations that are categorized as dangerous. Consequently,
drawing results in an arcing duration which is significantly maintenance cannot be performed on energized equipment at
shorter for the 3-4-5 method, and consequently, the incident these locations. Furthermore, the recommended PPE for the
energy determined by the 3-4-5 method is less than the energy other hazard risk categories is designed to limit the thermal
predicted by IEEE 1584. energy at the surface of the skin to 1.2 cal/cm2, which is the
minimum energy necessary to inflict a curable 2nd degree burn
on unprotected skin [5]. However, the PPE cannot protect an In some circumstances utilizing a new fuse is not sufficient
electrician from flying debris, such as copper shrapnel, or the to reduce the incident energy level to an acceptable value
blast pressure, which might impregnate an individual into a while maintaining system reliability. Implementing a different
wall. In addition, the possibility of electrocution exists at all fuse is constrained by the transformer inrush current at a given
hazard risk levels. fault location. The inrush current could cause “nuisance
After observing the values of the CSM incident energies it is tripping” if the time-current characteristic of the protective
evident that the hazards throughout the CSM power device is not chosen appropriately. In these cases a circuit
distribution system must be addressed to protect electrical breaker with adjustable settings is necessary. The circuit
workers. The Bureau of Labor Statistics indicates electrical breaker can have a “maintenance setting” that can limit the arc
hazards are one of the leading causes of fatalities in the
duration while an electrician is performing work on the
workplace. Between 1992 and 2002 more than 800
energized equipment. In addition, the circuit breaker setting
electricians, apprentices, electrical power installers, and
can be adjusted for typical system operation to avoid nuisance
repairers were killed due to electrical injuries, and many more
individuals were injured [10]. The Bureau of Labor Statistics tripping. Maintenance cannot be performed on energized
has estimated that arc flash injuries account for 77% of all equipment if the circuit breaker is configured with the “typical
electrical injuries. In addition, approximately five to ten arc operation” setting. At Hill Hall and the Student Center where
flash incidents occur in the United States everyday [11]. two of the three highest incident energies were observed
Besides the obvious increase in personal welfare, avoiding during the arc flash analysis of the existing CSM distribution
injuries and fatalities can save millions of dollars, since the system an S&C Vista, Tap Fault Interrupter circuit breaker
costs associated with workplace injuries are expensive. should be installed. It is important that circuit breakers be
installed at the recommended locations, because these are the
V. HAZARD MITIGATION most hazardous locations on campus.
Fig. 4 compares the IEEE incident energies of the system as
A. Protective Device Selection and Coordination it is currently designed with the IEEE estimated energies with
After examining the potential arc flash hazard risks the selected fuses and circuit breakers implemented. As is
throughout the CSM distribution system the next task was to demonstrated it is possible to dramatically decrease many of
determine design recommendations to minimize the risks and the CSM incident energy levels and with the design
to promote “safety by design.” The primary hazard mitigation recommendations none of the incident energies are classified
technique investigated was protective device selection and as dangerous. However, until the recommended protective
coordination to reduce arcing durations and to limit current. device changes can be implemented maintenance cannot be
The goal was to determine the best sizes and settings of the performed on energized equipment where the incident energy
protective devices in order to minimize incident energy levels level has been determined as greater than 40 cal/cm2, and
and PPE category requirements while also maintaining system
appropriate PPE must be worn when performing energized
reliability.
maintenance at other locations throughout the CSM power
The arc flash hazard analysis of the existing CSM system
distribution system as dictated by the calculated incident
revealed that several of the protective devices directly
upstream of the low-voltage fault locations must be changed to energy values.
alleviate incident energy levels and to reduce the hazard risks
to acceptable categories. The TCC drawings that were
constructed during the protective device study were examined
to determine possible protective device changes that could be
implemented to reduce the incident energies. The time-current
curve of the first protective device directly upstream of the
fault location where the incident energy was desired to be
reduced was shifted to decrease the arc duration by
appropriately selecting a different fuse or circuit breaker.
Selecting a different fuse to replace an existing fuse was
preferred as opposed to utilizing a circuit breaker due to the
costs associated with purchasing and installing the different
types of protective equipment. For twenty-five fault locations
it is possible to reduce the incident energy to an acceptable
level by changing the existing fuse to an S&C K-Speed fuse.
The appropriate cartridge setting of the K-Speed fuse is
dependent on the arcing current available at a given fault
location. However, at several locations where a fuse has been Fig. 4. Mitigated IEEE incident energies and existing system IEEE energies.
recommended it is possible to further decrease the incident
energy level by utilizing a circuit breaker, which can eliminate While selecting the recommended fuses and circuit breakers
any occurrence of hazard risk category four incident energies. protective device coordination was considered. The
examination of the drawings revealed that the existing
protective devices and the recommended devices are well D. Fiber Optic Detection
coordinated in most cases. Typically, miscoordination was Fiber optic detection is a modern technique to mitigate arc
observed at locations where an oil-immersed fuse is included flash hazards, which is being marketed in industry. The basic
at a transformer. Due to the configuration of the CSM premise of this detection method is to use fiber optic sensors
distribution system, most instances of miscoordination that or bare fiber optic cables to detect the intense light given off
were identified do not compromise system reliability, because by an arc flash. Two different types of sensors available for
the miscoordinated devices serve a single transformer or use in a fiber optic detection system are point sensors and bare
building. Since it was desired that the oil-immersed fuses fiber sensors. Point sensors are intended to be located in clear
remain unchanged the two instances of miscoordination that view of the energized components where an arc flash will most
compromise system reliability were ignored in favor of likely occur. Bare fiber sensors are used to monitor “large
providing protective device recommendations capable of distributed resources, such as switchgear system bus
minimizing incident energy levels. enclosures” [17]. When exposed to light the sensor can
B. Increasing the Working Distance produce a signal, which is sent to a relay, and the relay
communicates with circuit breakers that can quickly interrupt
Increasing the working distance can also reduce incident
the current and quench the arc [18]. Due to the significant
energy levels and mitigate arc flash hazards. For arcs in open
decrease in arc duration the incident energy is reduced, which
air the incident energy is inversely proportional to the square
creates a safer working environment for electricians
of the working distance, so increasing the distance can greatly
performing maintenance on the system. Fiber optic detection
decrease the energy level. The energy level is also decreased
of arc flash events is an effective hazard mitigation technique
as the working distance increases for arcs initiated in
that can be retrofitted to existing distribution systems.
enclosures. The use of extension tools, such as “hotsticks,” and
remote-operating systems can increase electrician safety when
VI. ARC FLASH TRAINING
working on energized equipment.
A hotstick is basically a long pole composed of insulating It has been estimated “up to 80% of electrical incidents are
material rated for a specific voltage level, and tools or fittings caused by human error” [18]. Consequently, one of the best
are attached to the end of the pole. Electricians can use methods to minimize exposure to arc flash incidents is through
hotsticks to perform energized maintenance while remaining at proper training and education, which must be provided to
a safe distance from equipment to avoid an arc flash. However, individuals working in close proximity to energized
utilizing extension tools could hinder the ability of an equipment. OSHA recommends safety awareness when
electrician to properly perform maintenance on energized working on electrical equipment, which includes an
equipment. To ensure safety electricians using extension tools understanding of electrical hazards and safety related work
should generally wear additional PPE, such as gloves and a practices [18]. In addition, NFPA 70E clearly states that
face-shield [12]. employees are to be trained regarding the relationship between
In addition, remote-controlled devices and systems can be electrical hazards and possible injury [19]. Personnel involved
used for racking a circuit breaker into and out of electrical with the operation or maintenance of electrical equipment must
switchgear. Many of these devices can be used without any understand the risks associated with their job, including a basic
modifications to the existing system, and the devices are also understanding of the causes and consequences of exposure to
portable [13]. Remote-racking of breakers allows an an arc flash. The significance of potentially fatal burns, molten
electrician to work up to 40 ft away from the electrical copper shrapnel, and concussive force from the blast are key
equipment. However, working from greater distances can limit dangers to be discussed during training.
the ability of an electrician to detect problems during After an arc flash hazard analysis has been performed the
maintenance, and some remote-racking devices have been results of the evaluation should be presented to personnel
known to rack improperly positioned breakers, which could working on the system, and based on the incident energy
potentially damage the equipment [14]. workers must understand what level of personal protective
equipment (PPE) is necessary, how to correctly wear PPE, and
C. Arc Suppression Blanket the limitations of the PPE [18]. In addition, electricians must
Another consideration is to use an arc suppression blanket be able to interpret arc flash hazard warning labels, and
to isolate conductors while performing maintenance on personnel must understand the arc flash warning labels are
energized equipment. The blankets are typically constructed of almost out-dated as soon as they are adhered to the electrical
Kevlar and Nomex or canvas [15]. Despite its name an arc equipment. Personnel should be advised that protective device
suppression blanket does not actually suppress an arc, but it changes and changes to the overall system, such as new
does redirect the thermal energy and pressure waves away buildings or new electrical equipment, could cause the warning
from a worker. Laboratory experiments have demonstrated the label to be inaccurate. Furthermore, electricians must be aware
effectiveness of arc suppression blankets, but the performance of the arc flash protection boundaries for all locations
of a blanket is highly dependent on proper installation. Tests throughout the distribution system. The approach boundaries
performed at 6.2 kV, and 20 to 25 kA with an arc duration of for shock protection and flash protection, such as the limited,
ten to twelve cycles have shown that a properly installed restricted, and prohibited approach boundaries should be
blanket can dramatically decrease injuries sustained due to known, and individuals must avoid working in hazardous areas
thermal energy and flying debris [16]. without the proper PPE or without proper qualification [19].
VII. CONCLUSION IX. REFERENCES
An arc flash analysis of the CSM electrical power [1] R. F. Ammerman, “Engineering Standards and Professional Responsibility,”
in Senior Design Course Lectures, Golden, CO, Sep. 2008, [Online]
distribution system has been conducted to identify the severity
Available: http://egweb.mines.edu/eggn491/lecture/Safety-
of an arc flash hazard at the Colorado School of Mines. The Liability/Safety%20Presentation%20(RFA%20Fall%2008).pdf
arc flash evaluation has been performed in accordance with [2] Wikipedia, “Arc Flash,” Wikipedia: The Free Encyclopedia, Nov. 2008,
NFPA 70E: Standard for Electrical Safety in the Workplace, [Online] Available: http://en.wikipedia.org/wiki/Arc_flash
and IEEE 1584: Guide for Performing Arc Flash Hazard [3] NFPA 70E-2004, Standard for Electrical Safety in the Workplace,
National Fire Protection Association, Quincy, MA.
Calculations. The analysis of the existing system configuration [4] NFPA 70, National Electrical Code 2008, National Fire Protection
has revealed that many locations on the CSM campus are Association, Quincy, MA.
categorized as dangerous, and maintenance cannot be [5] IEEE 1584-2002, IEEE Guide for Performing Arc-Flash Hazard
performed on energized equipment at these locations until Calculations, IEEE, New York, NY.
[6] M. Staggs, letter from Xcel Energy describing the available fault
modifications to the protective devices are implemented. currents and recloser information for the CSM Campus, Xcel Energy,
It was determined that installing twenty-five S&C K-Speed Denver, CO, Sep. 2008.
fuses, and two S&C Vista circuit breakers can decrease the [7] R. J. Hubbard, C. W. Mielke, J. C. Ray, D. H. Shaffer, P. K. Sen,
incident energy levels of CSM locations and eliminate any and R. F. Ammerman, “Future Energy Needs and Sustainable Energy
Applications for the Colorado School of Mines (CSM) Campus: Needs
instances of dangerous hazard risk categories. In addition, for the Year 2020 and Beyond; “A Capstone Senior Design Project”,” in
increasing the working distance and utilizing arc suppression Proc. 37th Annual North American Power Symposium, Ames, Iowa,
blankets while performing maintenance should be considered Oct. 2005, pp. 603-610.
to minimize the arc flash hazard risk imposed on electricians. [8] R. F. Ammerman, P. K. Sen, and J. P. Nelson, “Electrical Arcing
Phenomena: a Historical Perspective and Comparative Study of the
Furthermore, electrician training to promote safe work
Standards IEEE 1584 and NFPA 70E,” in IEEE Industry Applications
practices is strongly recommended. Arc flash training can Magazine, vol. 15, no. 3, May/June, 2009, pp. 42-52.
increase worker awareness of arc flash hazards, teach workers [9] Quadrelec Engineering, “Protective Device Coordination Studies,”
to respect arc flash warning labels, and emphasize the Quadrelec Engineering Corporation, 2005, [Online]
importance of wearing proper protective equipment while Available: http://www.quadrelec.com/pages/studies_protective.html
[10] J. C. Cawley, and G. T. Homce, “Trends in Electrical Injury in the U.S.,
performing energized maintenance. 1992-2002,” IEEE Trans. Industry Applications, vol. 44, no. 4,
July/Aug., 2008.
VIII. ACKNOWLEDGEMENTS [11] S. Singh, “New Technology to Trap Killer Sparks,” IEEE Spectrum
Online, Mar. 2009, [Online]
The authors gratefully acknowledge Ted Trimmer and the Available: http://www.spectrum.ieee.org/mar09/8067
CSM electrical workers for their assistance throughout [12] J. Cadick, M. Capelli-Schellpfeffer, and D. Neitzel, Electrical Safety
Handbook, 3rd ed., McGraw-Hill, New York, NY, 2005.
completion of the CSM Arc Flash Hazard Study. Their
[13] CBS ArcSafe, “Remote Racking Systems for Circuit Breakers,” CBS
experience, expertise, and advice significantly contributed to ArcSafe, 2009, [Online]
the success of the project. Available: http://www.remoterackingsolutions.com/index.htm
In addition, special thanks are due to SKM PowerTools for [14] Electric Power Engineering Forum at Eng-Tips, “Remote Racking
Circuit Breakers,” Eng-Tips Forums, 2009, [Online]
providing an enhanced version of the Arc Flash Hazard Available: http://www.eng-tips.com/viewthread.cfm?qid=180491&page=7
evaluation software, which was crucial to the successful [15] Alliance Suppliers, “Electrical Arc Suppression Blanket” Alliance
completion of the project. Suppliers Inc., Roswell, GA, 2009, [Online]
Available: http://www.asiarcflashsolutions.com/electrical_arc_suppression_blanket
The authors also gratefully acknowledge The Denver [16] Estex Manufacturing Co., “Arc Suppression Blanket: BlastMat,” Estex
Section of the IEEE Power & Energy Society and Industry Manufacturing Co. Inc., Apr. 2007, [Online]
Applications Society for providing essential funding, and the Available: http://www.estexmfg.com/videos/Blast%20Mat.wmv
[17] Schweitzer Engineering Laboratories, “SEL-751A Feeder Protection
organization encouraged the professional development of the Relay Instruction Manual” Schweitzer Engineering Laboratories, Inc.,
student team members by providing the opportunity to present Pullman, WA, Jan. 2009.
the project to practicing engineers. [18] C. Inshaw, and R. A. Wilson, “Arc Flash Hazard Analysis and
Mitigation,” in Proc. Western Protective Relay Conference, Spokane,
WA, Oct., 2004.
[19] NFPA 70E-2009, Standard for Electrical Safety in the Workplace,
National Fire Protection Association, Quincy, MA.

You might also like