You are on page 1of 60

Type 3AH 4.

16 kV to 38 kV
vacuum circuit breaker operator module
instruction manual
Installation operation maintenance E50001-F710-A251-X-4A00

Answers for energy.


Hazardous voltages and high speed moving parts.
Will cause death, serious injury or property damage.
Always de-energize and ground the equipment before
maintenance. Read and understand this instruction manual
before using equipment. Maintenance should be performed only
by qualified personnel. The use of unauthorized parts in the
repair of the equipment or tampering by unqualified personnel
will result in dangerous conditions which will cause death, severe
injury or equipment damage. Follow all safety instructions
contained herein.

Important I s trained in the proper care and use of


The information contained herein is protective equipment, such as: rubber
general in nature and not intended for gloves, hard hat, safety glasses or face
specific application purposes. It does not shields, flash clothing, etc., in
relieve the user of responsibility to use accordance with established safety
sound practices in application, installation, practices.
operation and maintenance of the Is trained in rendering first aid.
equipment purchased. Siemens reserves
the right to make changes in the Further, a qualified person shall also be
specifications shown herein or to make familiar with the proper use of special
improvements at any time without notice precautionary techniques, personal
or obligations. Should a conflict arise protective equipment, insulating and
between the general information shielding materials and insulated tools and
contained in this publication and the test equipment. Such persons are
contents of drawings or supplementary permitted to work within limited approach
material or both, the latter shall take of exposed live parts operating at 50 volts
precedence. or more shall, at a minimum, be
additionally trained in all of the following:
Qualified person
 he skills and techniques necessary to
T
For the purpose of this manual a qualified distinguish exposed energized parts
person is one who is familiar with the from other parts of electric equipment.
installation, construction or operation of
the equipment and the hazards involved.  he skills and techniques necessary to
T
In addition, this person has the following determine the nominal voltage of
qualifications: exposed live parts.

I s trained and authorized to  he approach distances specified in


T
de-energize, clear, ground and tag NFPA 70E and the corresponding
circuits and equipment in accordance voltages to which the qualified person
with established safety procedures. will be exposed.
 he decision-making process necessary
T
to determine the degree and extent of
the hazard and the personnel protective
equipment and job planning necessary
to perform the task safely.

2
Table of contents

Introduction 4 -5
Note:
These instructions do not purport to cover
Receiving, handling and storage 6 -8 all details or variations in equipment, nor
to provide for every possible contingency
to be met in connection with installation,
operation or maintenance. Should further
Installation checks and functional tests 9 - 10
information be desired or should particular
problems arise that are not covered
sufficiently for the purchaser’s purposes,
Vacuum interrupter/operator 11 - 28
the matter should be referred to the local
sales office.

Maintenance 29 - 43 The contents of this instruction manual


shall not become part of or modify any
prior or existing agreement, commitment
Overhaul 44 - 48 or relationship. The sales contract contains
the entire obligation of Siemens Energy,
Inc. The warranty contained in the contract
between the parties is the sole warranty of
Maintenance and troubleshooting 49 - 52
Siemens Energy, Inc. Any statements
contained herein do not create new
warranties or modify the existing warranty.
Appendix 53 - 58

3
Introduction

Hazardous voltage and high-speed moving parts.


Will cause death, serious injury and property damage.
Always de-energize and ground the equipment before
maintenance. Maintenance should be performed only by
qualified personnel. The use of unauthorized parts in the repair
of the equipment or by tampering by unqualified personnel will
result in dangerous conditions that will cause death, severe
injury or equipment damage. Follow all safety instructions
contained herein.

Introduction Signal words


The type 3AH vacuum circuit breaker The signal words "danger," "warning" and
module is designed to meet all applicable "caution" used in this instruction manual
ANSI, NEMA and IEEE standards. Successful indicate the degree of hazard that may be
application and operation of this encountered by the user. These words are
equipment depends as much upon proper defined as:
installation and maintenance by the user
Danger - Indicates an imminently
as it does upon the proper design and
hazardous situation which, if not avoided,
fabrication by Siemens.
will result in death or serious injury.
The purpose of this instruction manual is
Warning - Indicates a potentially
to assist the user in developing safe and
hazardous situation which, if not avoided,
efficient procedures for the installation,
could result in death or serious injury.
maintenance and use of the equipment.
Caution - Indicates a potentially hazardous
Contact the nearest Siemens
situation which, if not avoided, may result
representative if any additional
in minor or moderate injury.
information is desired.
Caution (without safety alert symbol) -
Indicates a potentially hazardous situation
which, if not avoided, may result in
property damage.

4
Introduction

Hazardous Procedures Field service operation and warranty


issues
In addition to other procedures described
in this instruction manual as dangerous, Siemens can provide competent, well-
user personnel must adhere to the trained field service representatives to
following: provide technical guidance and advisory
assistance for the installation, overhaul,
1. A
 lways work only on a de-energized repair and maintenance of Siemens
circuit breaker. The circuit breaker equipment, processes and systems.
should be isolated, grounded and Contact regional service centers, sales
have all control power removed offices or the factory for details, or
before performing any tests, telephone Siemens field service at
maintenance or repair. +1 (800) 347-6659 or +1 (919) 365-2200
2. A
 lways perform maintenance on the outside the U.S.
circuit breaker after the spring- For medium-voltage customer service
charged mechanisms are discharged issues, contact Siemens at
(except for test of the charging +1 (800) 347-6659 or +1 (919) 365-2200
mechanisms). Check to be certain outside the U.S.
that the indicator flags read OPEN and
DISCHARGED.
3. A
 lways let an interlock device or
safety mechanism perform its
function without forcing or defeating
the device.

5
Receiving, handling and
storage

Heavy weight.
Improper lifting or hoisting can result in death, serious injury
or property damage.
Obtain the services of a qualified rigger prior to hoisting the
circuit breaker to assure adequate safety margins in the hoisting
equipment and procedures to avoid damage.

Introduction Shipping damage claims


This portion of the instruction manual Important: The manner in which visible
covers the receiving, handling and storage shipping damage is identified by consignee
instructions for a type 3AH vacuum circuit prior to signing the delivery receipt can
breaker module. This section of the determine the outcome of any damage
instruction manual is intended to help the claim to be filed.
user identify, inspect and protect the
Notification to carrier within 15 days for
circuit breaker prior to its installation.
concealed damage is essential if loss
Receiving procedure resulting from unsettled claims is to be
eliminated or minimized.
Make a physical inspection of the shipping
container before removing or unpacking 1. W
 hen the shipment arrives, note
the circuit breaker. whether the equipment is properly
protected from the elements. Note the
Check for shipment damage or indications
trailer number the equipment arrived
of rough handling by the carrier. Check
on. Note also any blocking of
each item against the manifest to identify
equipment. During unloading, check
any shortages.
the actual equipment delivered to
Accessories (as applicable) such as the verify it agrees with the delivery
manual charging crank, racking crank or receipt.
split-plug jumper are shipped separately.
2. M
 ake immediate inspection for visible
damage upon arrival and prior to
disturbing or removing packaging or
wrapping material. This should be
done prior to unloading when possible.
When total inspection cannot be made
on vehicle prior to unloading, close
inspection during unloading must be
performed and visible damage noted
on the delivery receipt. Take pictures if
possible.

6
Receiving, handling and
storage

3. A
 ny visible damage must be noted on 8. O
 btain the original carrier inspection
the delivery receipt and acknowledged report and forward it with a copy of the
with the driver’s signature. The noted delivery receipt to Siemens.
damage should be detailed as much as Approval must be obtained by Siemens
possible. It is essential that a notation from the carrier before any repair work
"possible internal damage, subject to can be performed.
inspection" be included on the delivery
 efore approval can be obtained,
B
receipt. If the driver will not sign the
Siemens must have the documents
delivery receipt with the damage
referenced in the paragraph above. The
noted, the shipment should not be
carrier inspection report and/or driver’s
signed for by the consignee or their
signature on the delivery receipt does
agent.
not constitute approval to repair.
4. N
 otify Siemens medium-voltage
Note: Any determination as to whether the
customer service immediately of any
equipment was properly loaded or properly
damage, at +1 (800) 347-6659 or
prepared by shipper for over-the-road
+1 (919) 365-2200 outside the U.S.
travel cannot be made at the destination.
5. Arrange for a carrier inspection of the Shipments are not released from the
damage immediately. factory without a clear bill of lading.
Approved methods are employed for
Important: Do not move the equipment
preparation, loading, blocking and tarping
from the place it was set when unloading.
of the equipment before it leaves the
Also, do not remove or disturb packaging
Siemens factory. If the equipment is
or wrapping material prior to carrier
received in a damaged condition, this
damage inspection. Equipment must be
damage to the equipment has to have
inspected by carrier prior to handling after
occurred while en route due to conditions
receipt. This eliminates loss due to claims
beyond Siemens‘ control. If the procedure
by carrier that the equipment was
outlined above is not followed by the
damaged or further damaged on site after
consignee, purchaser or their agent,
unloading.
Siemens cannot be held liable for repairs.
6. Be sure the equipment is properly Siemens will not be held liable for repairs
protected from any further damage by in any case where repair work was
covering it properly after unloading. performed prior to authorization from
Siemens.
7. If practical, make further inspection for
possible concealed damage while the
carrier’s inspector is on site. If
inspection for concealed damage is not
practical at the time the carrier’s
inspector is present, it must be done
within 15 days of receipt of the
equipment. If concealed damage is
found, the carrier must again be
notified and inspection made prior to
taking any corrective action to repair.
Also notify Siemens immediately at
+1 (800) 347- 6659 or
+1 (919) 365-2200 outside the U.S.

7
Receiving, handling and
storage
Handling procedure Indoor storage
1. C
 arefully remove the shipping carton Whenever possible, store the circuit
from the circuit breaker. Keep the breaker indoors. The storage environment
shipping pallet for later use if the must be clean, dry and free of such items
circuit breaker is to be stored prior to as construction dust, corrosive
its installation. atmosphere, mechanical abuse and rapid
temperature variations.
2. Inspect for concealed damage.
Notification to carrier must take place Outdoor storage
within 15 days to assure prompt claim
Outdoor storage is not recommended.
resolution.
When no other option is available, the
3. E
 ach circuit breaker should be lifted circuit breaker must be completely covered
appropriately to avoid crushing the side and protected from rain, snow, dirt and all
panels of the circuit breaker, or other contaminants.
damaging the primary disconnect
Space heating
assemblies. Refer to Table 13 for circuit
breaker weights. Space heating must be used for both
indoor and outdoor storage to prevent
4. T
 he palleted circuit breaker can be
condensation and corrosion. When
moved using a properly rated fork-lift
equipment is stored outdoors, 250 watts
vehicle. The pallets are designed for
per circuit breaker of space heating is
movement by a standard fork-lift
recommended. If the circuit breaker is
vehicle.
stored inside the switchgear enclosure and
Storage procedure the switchgear is equipped with space
heaters, energize the space heaters.
1. W
 henever possible, install the circuit
breaker in its assigned switchgear
enclosure or end location for storage.
2. W
 hen the circuit breaker needs to be
placed on its pallet for storage, be sure
the unit is securely bolted to the pallet
and covered with polyethylene film at
least 10 mils thick.

8
Installation checks and
functional tests
Introduction Spring-discharge check (refer to
Figure 1)
This section provides a description of the
inspections, checks and tests to be Perform the spring-discharge check before
performed on the circuit breaker module removing the circuit breaker from the
only. pallet or removing it from the switchgear.
Inspections, checks and tests without The spring discharge check should be
control power performed after de-energizing control
power. This check assures both the tripping
Vacuum circuit breakers are normally
and closing springs are fully discharged.
shipped with their primary contacts open
and their springs discharged. However, it is Note: Do not perform the spring-discharge
critical to first verify the discharged check if the circuit breaker is in the
condition of the spring-loaded CONNECT position. Open the circuit
mechanisms after de-energizing control breaker and rack to the DISCONNECT
power. position, and then perform the spring-
discharge check. For fixed-mounted circuit
De-energizing control power in
breaker applications, open the isolator
switchgear
switches on the line side and on the load
When the circuit breaker is mounted in side of the circuit breaker before
switchgear, open the control-power performing the spring-discharge check.
disconnect device in the metal-clad
1. Press red Trip pushbutton.
switchgear cubicle, outdoor circuit breaker
housing or other location. 2. Press black Close pushbutton.
In metal-clad switchgear, the control- 3. Press red Trip pushbutton again.
power disconnect device is normally
4. V
 erify spring-condition indicator shows
located on the secondary-device panel in
DISCHARGED.
the upper cell of the vertical section. The
normal control-power disconnect device is 5. V
 erify main contact status indicator
a pullout-type fuse holder. Removal of the shows OPEN.
fuse holder de-energizes control power to
the circuit breaker in the associated
switchgear cell. In some switchgear
assemblies, a molded-case circuit breaker
or knife switch is used in lieu of the
pullout-type fuse holder. Opening this
circuit breaker or switch accomplishes the
same result: control power is
disconnected.

Hazardous voltage and high-speed moving parts.


Will cause death, serious injury and property damage.
Read instruction manuals, observe safety instructions and use
qualified personnel.

9
Installation checks and
functional tests
Manual-spring charging check 1. O
 pen control-power circuit by
opening the control power-
1. Insert the manual-spring charging
disconnect device.
crank into the manual-charge handle
socket (refer to Figure 1). Turn the 2. E
 nergize (close) the control power-
crank clockwise (about 48 revolutions) circuit disconnect.
until the spring-condition indicator
3. U
 se the Close and Open controls
shows the closing spring is CHARGED.
(refer to Figure 1) to first Close and
2. Repeat the spring-discharge check. then Open the circuit breaker
contacts. Verify contact positions
3. V
 erify the springs are DISCHARGED and
visually by observing the OPEN/
the circuit-breaker primary contacts are
CLOSED indicator on the circuit
OPEN by indicator positions.
breaker.
As-found and vacuum-integrity check
4. D
 e-energize control power by
tests
repeating Step 1. If a split-plug
Perform and record the results of both the
jumper was used for temporary
as-found insulation test and the vacuum-
control-power connections,
integrity check (dielectric) test. Procedures
disconnect the split-plug jumper from
for these tests are described in the
the switchgear first and next from
Maintenance section of this instruction
the circuit breaker.
manual beginning on page 29.
5. P
 erform the spring-discharge check
Automatic spring-charging check
again. Verify that the closing spring is
The automatic spring-charging features
discharged and the primary contacts
of the circuit breaker must be checked.
of the circuit breaker are open.
Control power is required for
automatic spring charging to take place. Final mechanical inspections without
control power
Note: A temporary source of control 1. Make a final mechanical inspection of
power and test leads may be required if the circuit breaker. Verify the contacts
the control-power source has not been are in the open position, and the
connected to the switchgear or circuit closing spring is discharged.
breaker. Refer to the specific wiring
2. V
 erify mechanical condition of
information and rating label for your
springs.
circuit breaker to determine the voltage
required and where the control-voltage 3. Check for loose hardware.
signal should be applied. When control
power is connected to the circuit breaker,
the closing spring should automatically
charge.

10
Vacuum interrupter/
operator
Introduction
The type 3AH vacuum circuit-breaker
operator is intended for application in a
drawout truck for use in medium-voltage
metal-clad switchgear and for stationary
applications, such as the type SDV6
outdoor distribution circuit breaker. The
type 3AH circuit breaker conforms to the
requirements of ANSI/IEEE standards,
including C37.20.2, C37.04, C37.06, Rating plate
C37.09 and C37.010.

The circuit breaker includes three CLOSE


vacuum interrupters, a stored-energy pushbutton
operating mechanism, necessary Opening for
electrical controls and interlock devices, manual spring-charging
disconnect devices to connect the circuit
breaker to both primary and control CHARGED/DISCHARGED OPEN
power (for drawout applications) and an indicator pushbutton
operator housing. In a typical installation CLOSED/OPEN
in a drawout truck, insulating barriers indicator
may be located between the vacuum
interrupters and along the sides. Operations counter

This section describes the operation of


Figure 1: Front panel controls of circuit breaker and manual charging of closing spring
each major subassembly as an aid in the
operation, installation, maintenance and
repair of the circuit breaker.
Pole head
Vacuum interrupters
The operating principle of the vacuum Upper Pole plate
connection
interrupter is simple. Figure 3 is a section pad
view of a typical vacuum interrupter. The
Upper post
entire assembly is sealed after a vacuum
insulator
is established. The vacuum interrupter
stationary contact is connected to the Mechanism
pole head of the circuit breaker. The housing
vacuum interrupter movable contact is
Vacuum
connected to the pole bottom and
interrupter
driving mechanism of the circuit breaker.
The metal bellows provide a secure seal Strut
around the movable contact, preventing
loss of vacuum while permitting vertical
motion of the movable contact. Lower post
insulator

Lower Contact pressure


connection spring
pad
Insulating
Pole bottom coupler

Figure 2: Vacuum circuit breaker operator module

11
Vacuum interrupter/
operator
When the two contacts separate, an arc
is initiated that continues conduction up
to the following current zero. At current
Fixed contact-current connection zero, the arc extinguishes and any
Ceramic insulator
conductive metal vapor that has been
created by and supported the arc
condenses on the contacts and on the
surrounding arc shield. Contact materials
Arc shield and configuration are optimized to
Fixed contact achieve arc motion and to minimize
Moving contact switching disturbances.

Primary connections (refer to Figure 2)


Figure 2 illustrates the pad provision to
Ceramic insulator
accept the primary connections. Each
Metal bellows circuit breaker has three upper and three
lower primary disconnect pad provisions,
Guide to allow connection to the switchgear.
For stationary circuit breaker
applications, bus conductors connect
Moving contact-current connection directly to these pads. Bolting
hardware is M12 x 1.75 grade 8. Torque
M12 bolts to 52 ft-lb (70 Nm).

Phase barriers (if applicable)


Plates of glass-polyester insulating
Figure 3: Vacuum interrupter cutaway view
material are attached to the circuit
breaker and provide suitable electrical
insulation between the vacuum
interrupter and primary conductors and
the cubicle.

Stored-energy operating mechanism


The stored-energy operating mechanism
of the circuit breaker is an integrated
arrangement of springs, coils and
mechanical devices designed to provide
a number of critical functions. The
energy necessary to close and open the
contacts of the vacuum interrupters is
stored in powerful opening and closing
springs. The closing springs are normally
charged automatically, but there are
provisions for manual charging. The
operating mechanism that controls
charging, closing and tripping functions
is fully trip-free. "Trip-free" requires that
the tripping function prevail over the
closing function as specified in ANSI/IEEE
C37.04-1999, clause 6.9.

Figure 4: Vacuum circuit breaker operator module


12
Vacuum interrupter/
operator
Vacuum interrupter/operator module Current-path assembly (refer to
The vacuum interrupter/operator module Figure 5)
consists of the three poles, each with its The current-path assembly consists of
vacuum interrupters and primary the pole head, the stationary contact and
insulators, mounted on the common the moving contact, that is connected to
operating mechanism housing. This the pole bottom by a terminal clamp
module is shown in Figure 4. and a flexible connector.

Construction (Refer to Figures 1, 2, 5, 6 Vacuum interrupter (refer to Figure 5)


and 7) The moving-contact motion is aligned
Each of the circuit breaker poles are fixed and stabilized by a guide bushing. The
to the rear of the operating mechanism metal bellows follows the travel of the
housing by two cast-resin insulators. The contact and seals the vacuum interrupter
insulators also connect to the upper and against the surrounding atmosphere.
lower pole supports that in turn support
the ends of the vacuum interrupter. The Switching operation (refer to Figures 5
pole supports are aluminum castings and 6)
(most 1,200 A, all 2,000 A and some When a closing command is initiated, the
3,000 A), copper castings (some closing spring (62.0), that was previously
3,000 A) or sheet steel (some 1,200 A). charged by hand or by the motor,
Primary disconnect stud extensions may actuates the moving contact through the
be attached directly to the upper and jack shaft (63.0), lever, contact pressure
lower pole connection pads. spring (49.0), insulating coupler (48.0)
and angled lever.
The energy-storing mechanism and all
the control and actuating devices are The forces that occur when the action of
installed in the operator housing. The the insulating coupler (48.0) is converted
mechanism is of the spring stored-energy into the vertical action of the moving
type and is mechanically and electrically contact are absorbed by the guide link,
trip-free. that pivots on the pole bottom and the
eye bolt.
The close-open indicator, closing spring-
charge indicator and the operation During closing, the opening spring
counter are located on the front of the (64.0) (refer to Figure 6) and the
operator housing. contact pressure springs (49.0) are
charged and latched by pawl (64.2)
The control connector for the control and (refer to Figure 7). The closing spring
signalling cables is a multi-contact plug (62.0) (refer to Figure 6) of the motor-
in most designs, although direct operated circuit breaker is recharged
connection to the switchgear is used immediately after closing.
for certain products.
In the closed state, the necessary contact
Circuit breaker pole (refer to Figure 5) pressure is maintained by the contact
The vacuum interrupter is bolted to the pressure springs (49.0) and the
upper pole head and the upper pole atmospheric pressure. The contact
head is rigidly connected to the operator pressure spring automatically
housing by the post insulator. The lower compensates for arc erosion, which is
part of the vacuum interrupter is very small.
stabilized against lateral forces by a
centering ring on the pole bottom. The
external forces due to switching
operations and the contact pressure are
absorbed by the struts.

13
Vacuum interrupter/
operator
4. O perate all these functions
Pole head Upper post insulator
automatically through an electrical
Upper Operator housing charging motor, cutout switches, an
connection anti-pump relay, a close coil, an open
pad
coil and an auxiliary switch.
5. Provide indication of the circuit
breaker status (OPEN/CLOSED), spring
condition (CHARGED/DISCHARGED)
Strut and number of operations.
Vacuum
interrupter Construction
Moving The essential parts of the operating
contact mechanism are shown in Figures 6 and
Centering Lever 7. The control and sequence
piece of operation of the mechanism is
Jack
shaft described in Figure 8.
Terminal
clamp
Flexible
Motor-operating mechanism (refer to
connector Figure 6)
Eye bolt The spring-charging motor (50.4) is
Pole bottom bolted to the charging mechanism (50.2)
Insulating Contact pressure
coupler (48.0) spring (49.0) gear box installed in the operator
housing. Neither the charging
Angled lever Guide link Lower post insulator mechanism nor the motor require any
maintenance.
Figure 5: Pole assembly
Mode of operation
The operating mechanism is of the
When a opening command is given, the
stored-energy trip-free type. For
energy stored in the opening and contact
example, the charging of the closing
pressure springs (49.0) is released by
spring is not automatically followed by
pawl (64.2) (refer to Figure 7). The
the contacts changing position, and
opening sequence is similar to the
tripping function prevails over the
closing sequence. The residual force of
closing function.
the opening spring maintains the moving
contacts in the open position.
When the stored-energy mechanism has
been charged, the mechanism is ready
Operating mechanism
for a closing operation at any time.
The operating mechanism is comprised
The mechanical energy for carrying out
of the mechanical and electrical
an "Open-Close-Open" sequence for
components required to:
auto-reclosing duty is stored in the
1. Charge the closing spring with
closing and opening springs.
sufficient potential energy to close
the circuit breaker and to store
Charging
opening energy in the opening and
The details of the closing spring charging
contact pressure springs.
mechanism are shown in Figure 6. The
2. Mechanisms to release closing and
charging shaft is supported in the
opening actions.
charging mechanism (50.2), but is not
3. Means of transmitting force and
coupled mechanically with the charging
motion to each of the three vacuum
mechanism. Fitted to it are the crank
interrupters.
(62.2) at one end, and the cam (62.3),
together with lever (62.5), at the other.

14
Vacuum interrupter/
operators
Figure 6: Stored-energy operating mechanism (circuit breaker shown in OPEN position) (straight linkage shown)

55.2 50.2 50.5 50.3 62.6 62.3 62.5

62.1
62.5.2
62.2
68.0
53.0

55.1
62.0
53.1
50.4.1
54.1

55.0
54.0
50.4
68.1
64.0

58.0

59.0

60.0 61.8 63.5 63.0 63.1

50.2 - Charging mechanism gear box 58.0 - CLOSE/OPEN indicator 62.8.3 - Trip-free coupling lever*
50.3 - Charging flange 59.0 - Operations counter 63.0 - Jack shaft
50.3.1 - Driver (not visible) 60.0 - Operator housing 63.1 - Lever - phase C
50.4 - Spring-charging motor 88 61.8 - Shock absorber 63.5 - Lever - phase B
50.4.1 - Limit switches 62.0 - Closing spring 63.7 - Lever - phase A
50.5 - Manual spring-charging port 62.1 - Charging shaft 64.0 - Opening spring
53.0 - Close pushbutton 62.2 - Crank 68.0 - Auxiliary switch
53.1 - Close coil 52SRC 62.3 - Cam disc 68.1 - Auxiliary switch link
54.0 - Open pushbutton 62.5 - Lever
54.1 - Trip coil 52T 62.5.1 - Pawl roller (not visible) * For certain applications, the straight trip
55.0 - Closing spring-charge 62.5.2 - Close latch pawl coupling rod (62.8) is replaced by a
indicator 62.6 - Driver lever collapsible trip-free coupling system,
55.1 - Linkage 62.8 - Straight coupling rod* illustrated in Figures 7-11.
55.2 - Control lever 62.8.1 - Spring return latch (not shown)*

15
Vacuum interrupter/
operator
Closing (refer to Figures 6-11)
If the circuit breaker is to be closed
62.8.1 manually, the closing spring is released
by pressing the Close button (53.0). In
62.8.2
the case of remote electrical control, the
close coil 52SRC (53.1) unlatches the
62.8
closing spring (62.0).
54.0
As the closing spring discharges, the
charging shaft (62.1) is turned by crank
(62.2). The cam disc (62.3) at the other
64.3.1
end of the charging shaft actuates the
64.3 drive lever (62.6), with the result that
jack shaft (63.0) is turned by lever (63.5)
via the coupling rod (62.8). At the same
time, the levers (63.1), (63.5) and (63.7)
fixed on the jack shaft operate the three
54.0 - Open pushbutton *For type SDV6 and some fixed-
62.8 - Trip-free coupling rod* mounted circuit breakers, trip-free insulating couplers (48.0) (refer to
62.8.1 - Spring-return latch* coupling rod (62.8) is replaced Figure 5) for the circuit breaker poles.
62.8.2 - Trip-free coupling link with a straight coupling rod, and Lever (63.7) changes the OPEN/CLOSE
(draw bar)* other parts associated with indicator (58.0) over to OPEN. Lever
64.2 - Trip-latch pawl (not visible) drawout interlocking are (63.5) charges the opening spring (64.0)
64.3 - Lever eliminated.
64.3.1 - Pawl roller
during closing, and the circuit breaker is
latched in the closed position by lever
(64.3) with pawl roller (64.3.1) and by
pawl (64.2). Lever (63.1) actuates the
Figure 7: Stored energy operating mechanism (circuit breaker shown in CLOSED position)
(Drawout trip-free linkage shown)
auxiliary switch (68.0) through the
linkage (68.1).

When the charging mechanism is


The crank (62.2) on the charging shaft
actuated by hand with a hand crank
(62.1) moves the linkage (55.1) by
(refer to Figures 13 and 14) or by a
acting on the control lever (55.2). The
motor (50.4), the flange (50.3) turns
closing spring charged indication is thus
until the driver (50.3.1) locates itself in canceled, and the limit switches (50.4)
the cutaway part of the cam disc (62.3),
switch in the control supply to cause the
thus causing the charging shaft to
closing spring to recharge immediately.
follow. The crank (62.2) charges the
closing spring (62.0). When the closing
spring has been fully charged, the crank
actuates the linkage (55.1) via the
control lever (55.2)
for the closing spring CHARGED indicator
(55.0), and actuates the limit switches
(50.4.1) for interrupting the motor
supply. At the same time, the lever
(62.5) at the other end of the charging
shaft is securely locked by the close latch
pawl (62.5.2). When the closing spring
is being charged, the cam disc (62.3)
follows along, and it is brought into
position for closing when the closing
spring is fully charged.

16
Vacuum interrupter/
operator
Trip-free operation The parts modified or eliminated are
(refer to Figures 6 and 7) noted in the relevant figures. In these
Trip-free for all drawout circuit circuit breakers, the trip-free function is
breakers and some fixed-mounted accomplished by blocking the movement
circuit breakers of the close latch pawl (62.5.2) when the
The trip coupling rod (62.8 together with manual trip pushbutton is actuated.
62.8.1 and 62.8.2) permits the
immediate de-coupling of the drive lever Opening (refer to Figure 6)
(62.6) and the jack shaft (63.0) to If the circuit breaker is to be opened
override closing action by trip command manually, the opening spring (64.0) is
or by means of the racking interlocks. released by pressing the OPEN
The trip-free coupling rod (62.8) forms a pushbutton (54.0). In the case of an
link between the drive lever (62.6) and electrical command being given, the trip
the jack shaft (63.0). The rigidity of this coil 52T (54.1) unlatches the opening
link depends upon a spring-return latch spring (64.0).
(62.8.1) carried within the coupling rod.
The latch pivots within the coupling rod The opening spring (64.0) turns the jack
and is normally positioned to ensure the shaft (63.0) via lever (63.5); the
rigidity of the coupling rod. Trip-free sequence being similar to that for
coupling link (62.8.2) and trip-free closing.
coupling lever (62.8.3) cause the spring-
return latch position to be dependent Rapid auto-reclosing
upon the normal tripping components Since the closing spring is automatically
and the racking interlock. Thus, recharged by the motor operating
whenever a trip command is applied or mechanism when the circuit breaker has
the circuit breaker is not in the fully closed, the operating mechanism is
CONNECT or TEST position, the trip-free capable of an "Open-Close-Open" duty
coupling rod is no longer rigid, cycle as required for rapid auto-reclosing.
effectively decoupling the drive lever and
jack shaft. Under these conditions the The circuit breaker is suitable for use in
vacuum interrupter contacts cannot be applications with a rated reclosing-time
closed. interval of 0.3 seconds, per ANSI/IEEE
C37.06-2009.
Trip-free for the type SDV6 outdoor
distribution circuit breaker and some Manual operation
fixed-mounted circuit breakers Electrically operated vacuum circuit
For the type SDV6 outdoor distribution breakers can be operated manually if the
circuit breaker and some other fixed- control supply should fail.
mounted circuit breakers, the drawout
trip-free linkage (refer to Figures 7-11) is
replaced with simplified linkage. The
trip-free coupling rod (62.8) is replaced
with a straight coupling rod (refer to
Figure 6), and other parts associated
with drawout interlocking are eliminated.

17
Vacuum interrupter/
operator
Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED

48.0 - Insulating coupler


50.3 - Charging flange
50.3.1 - Driver
53.0 - Close pushbutton
53.1 - Close coil 52SRC
54.0 - Open pushbutton
54.1 - Trip coil 52T
62.1 - Charging shaft
62.2 - Crank
62.5 62.5.1
62.2.2 - Closing-spring mounting
62.3 - Cam disc
62.1
62.5 - Lever
62.3 50.3 62.5.1 - Pawl roller
62.2 62.5.2 - Close latch-pawl
50.3.1 62.6 - Drive lever
62.5.2 62.8 - Trip-free coupling rod*
53.0 62.8.1 - Spring-return latch*
62.8.2 - Trip-free coupling link (draw bar)*
62.8.3 - Trip-free coupling lever*
62.8.5 - Push rod and cam assembly*
62.8.6 - Interlock lever push rod*
64.5* 62.8.7 - Interlock lever actuator*
62.6
62.2.2 62.8.8 - Trip-free actuator*
53.1
63.0 - Jack shaft
64.2.2 63.1 - Lever - phase C
63.5 - Lever - phase B
64.0*
62.8.1 63.7 - Lever - phase A
64.0 - Opening spring
64.2.1 64.2 - Trip-latch pawl
64.2.1 - Trip-latch pin
62.8.3 54.0
64.2.2 - Latching pawl-release lever
64.3 - Lever
62.8.2 64.3.1 - Jack-shaft pawl
64.5 - Opening-spring shaft
62.8*
64.2*
* For the type SDV6 outdoor circuit breaker
64.3.1* 63.5* and some fixed-mounted circuit breakers,
trip-free coupling rod (62.8) and other parts
62.8.5
associated with drawout interlocking are
eliminated.
64.5*
** Items moved from position shown in
63.0*
Figure 10 on trip operation. Underlined
63.7 62.8.7 items moved from position shown in
48.0*63.5* 63.5 62.8.6 Figure 9 on closed spring-discharge
63.1 operation.

62.8.8

18
Vacuum interrupter/
operator
Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
.

48.0 - Insulating coupler


50.3 - Charging flange
50.3.1 - Driver
53.0 - Close pushbutton
53.1 - Close coil 52SRC
54.0 - Open pushbutton
54.1 - Trip coil 52T
62.1 - Charging shaft
62.2 - Crank
62.2
62.2.2 - Closing-spring mounting
62.3 - Cam disc 50.3.1
62.5 - Lever 62.1 62.3
50.3
62.5.1 - Pawl roller
62.5.2 - Close-latch pawl 62.5
62.6 - Drive lever 62.5.1
62.8 - Trip-free coupling rod* 62.2.2
62.8.1 - Spring return-latch*
62.8.2 - Trip-free coupling link (draw bar)*
62.8.3 - Trip-free coupling lever*
62.8.5 - Push rod and cam assembly*
62.8.6 - Interlock lever push rod*
62.8.7 - Interlock lever actuator*
64.5*
62.8.8 - Trip-free actuator*
63.0 - Jack shaft
63.1 - Lever - phase C
63.5 - Lever - phase B
63.7 - Lever - phase A
64.0 - Opening spring 54.1*
64.2 - Trip-latch pawl
64.2.1 - Trip-latch pin
64.2.2 - Latching pawl-release lever
64.3 - Lever
64.3.1 - Jack-shaft pawl
64.5 - Opening-spring shaft
62.8*
* F
 or a type SDV6 outdoor circuit breaker and 64.2*
some fixed-mounted circuit breakers, trip- 64.3*
free coupling rod (62.8) and other parts 63.5*
associated with drawout interlocking are
eliminated.

** Items moved from position shown in


Figure 11 on trip operation. Underlined 63.0*
items moved from position shown in 63.7*
64.5*
Figure 8 on closed spring-discharge 48.0* 63.5* 63.5*
operation. 63.1*

19
Vacuum interrupter/
operator
Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring DISCHARGED

62.5.2 - Close latch-pawl


62.8.1 - Spring-return latch*
62.8.2 - Trip-free coupling link (draw bar)*
62.8.3 - Trip-free coupling lever*
62.8.5 - Push rod and cam assembly*
62.8.6 - Interlock lever push rod*
62.8.7 - Interlock lever actuator*
62.8.8 - Trip-free actuator*
62.5.1 63.1 - Lever - phase C
63.5 - Lever - phase B
62.5 63.7 - Lever - phase A
64.0 - Opening spring
62.1
64.2.1 - Trip-latch pin
64.2.2 - Latching pawl-release lever
62.2 64.3 - Lever
64.3.1 - Jack-shaft pawl
62.3
62.5.2 64.5 - Opening spring-shaft
53.0

* For the type SDV6 outdoor circuit breaker


and some fixed-mounted circuit breakers,
trip-free coupling rod (62.8) and other parts
64.5 62.6 associated with drawout interlocking are
53.1 eliminated.
62.2.2
** Numbered items moved from position
shown in Figure 9.

64.5
63.5
62.8

63.7
63.5
63.1
48.0
63.0
63.5

20
Vacuum interrupter/
operator
Figure 11: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring CHARGED

62.5.2 - Close latch pawl


62.8.1 - Spring return latch*
62.8.2 - Trip-free coupling link (draw bar)*
62.8.3 - Trip-free coupling lever*
62.8.5 - Push rod and cam assembly*
62.8.6 - Interlock lever push rod*
62.8.7 - Interlock lever actuator*
62.8.8 - Trip-free actuator*
63.1 - Lever - phase C
63.5 - Lever - phase B
62.2
63.7 - Lever - phase A
64.0 - Opening spring 50.3.1
62.3
64.2.1 - Trip-latch pin 62.1
64.2.2 - Latching pawl release lever 62.5 50.3
64.3 - Lever 62.5.1
64.3.1 - Jack shaft pawl
64.5 - Opening spring shaft 62.2.2

* For type SDV6 outdoor circuit breakers and


some fixed-mounted circuit breakers, trip-
free coupling rod (62.8), and other parts
associated with drawout interlocking are
eliminated.

** Numbered items moved from position


shown in Figure 10.

21
Vacuum interrupter/
operator
Manually charging the closing spring
(refer to Figures 13 and 14)
Insert the hand crank (50.0) with the
The special hand crank automatically over running coupling pushed forward
disengages if the spring-charging motor (50.6) through the opening (50.1) onto
operates. In order to avoid injuries as a
hand crank coupling (50.5) and turn it
result of the motor suddenly starting up,
the circuit breaker spring must only be clockwise (about 48 revolutions) until
charged manually with the special hand the closing-spring indicator (55.0) shows
crank (50.0). CHARGED. The hand crank is coupled
with the charging mechanism via an
over-running coupling; thus the operator
is not exposed to any risk should the
control supply be restored during manual
charging.

Manual closing (refer to Figure 6)


Press the close button (53.0). The CLOSE/
OPEN indicator (58.0) will then display
CLOSED and the closing spring condition
indicator (55.0) will now read
DISCHARGED.

Manual opening (refer to Figure 6)


The opening spring (64.0) is charged
during closing. To open the circuit
breaker, press the Open pushbutton
(54.0) and OPEN will be displayed by
indicator (58.0).

22
Vacuum interrupter/
operator
Figure 12: Operator sequential operation diagram

Closing Control Anti-pumping feature (52Y) assures a continuously applied closing command
voltage applied. does not cause the circuit breaker to reclose automatically after it has tripped
out on a fault.

Undervoltage device Spring-charge motor Continuous


27 picks up.1 (88.0) energized. closing command.

Closing spring fully


charged. Close coil (52SRC)
unlatches closing
LS21 and LS22 oper- LS3 opens in series LS41 closes to signal LS9 closes close spring and circuit
ate to de-energize with anti-pump relay closing spring is circuit only when breaker closes.
spring-charging (52Y). charged. closing spring is fully
motor (88.0). charged.
Motor cutoff
switches LS21, LS22
circuit circuit and LS3 are closed
breaker breaker because the closing
No action! Open 52b Close coil actuated spring is discharged.
closed. open.
in series with close through closed 52b
coil (52SRC) blocks Closing contacts and two
closing spring- command normally closed Before the spring-
release. when contacts of the anti- charge motor has
pump relay (52Y). recharged the
closing closing spring and
spring not opened LS3, anti-
charged. pump relay (52Y)
No action! Anti- The closing spring is The opening spring picks up and seals in.
pump relay (52Y) unlatched. is charged.
picks up through the
closed LS3 contact The anti-pump relay
and opens. (52Y) opens two
contacts in series
with the close coil
52a contacts in Circuit breaker The circuit breaker LS21 and LS22 close (52SRC).
series with the trip auxiliary contacts closes. to energize motor.
coil (52T) close to 52a and 52b change LS3 closes and LS4
enable a trip state. opens to cancel The close coil
opertion. closing spring signal. (52SRC) is now
blocked and cannot
be activated until
Rapid auto-reclosing. The closing spring is automatically recharged as described above. springs are fully-
Therefore, when the circuit breaker is closed both of its springs are charged. The closing spring charged and close
charges the opening spring during closing. As a result, the circuit breaker is capable of an command is
O-0.3s-CO-3 min-CO operating cycle. The dashed line shows the operating sequence initiated by removed.
the closing command.
Footnote:
Tripping
1
Optional items.
Trip
command.

Trip coil (52T) can Undervoltage device (27) is Undervoltage device (27) is activated Secondary shunt-
only be activated activated by opening a NC by closing NO contact, shorting the release (dual-trip)
when series contact in series with 27 or by 27 coil. The NO contact is only function activated by
connected 52a loss or reduction of tripping effective with the circuit breaker remote trip
contact is closed. voltage.1 closed. Resistor required.1 command contact
NO.1

Trip coil (52T) Undervoltage device Secondary release


unlatches the 27 unlatches the unlatches the
opening spring. opening spring.1 opening spring.1

Circuit breaker trips.

23
Vacuum interrupter/
operator
The schematic shown in Figure 15 is
intended to aid in understanding the
50.1 53.0 mechanism operation discussed in this
instruction manual. It shows a drawout
circuit breaker as an example. Refer to the
50.0
schematic diagram furnished with your
circuit breaker for specific information.
Close coil (52SRC)
55.0 54.0 The close coil (3AY1510) is a standard
component of the circuit breaker that is
used to unlatch the stored energy of the
closing spring and thus close the circuit
breaker electrically. It is available for either
ac or dc operation. After completion of a
closing operation, the close coil is de-
energized internally. If operated with ac
voltage, a rectifier is installed in the circuit
50.0 - Hand crank breaker.
50.1 - Manual spring-charging port Trip coil (52T)
53.0 - Manual CLOSE button
The trip coil (3AY1510) is a standard
54.0 - Manual OPEN (TRIP) button component of the circuit breaker. The
55.0 - CHARGED/DISCHARGED indicator electrically supplied tripping signal is
passed on to the trip-latching mechanism
by means of a direct action solenoid
Figure 13: Use of manual spring-operation crank
armature and the circuit breaker is thus
opened. It is available for either ac or dc
operation. After completion of an opening
operation, the trip coil is de-energized
internally. If operated with ac voltage, a
50.5
rectifier is installed in the circuit breaker.

50.6

50.0

50.0 - Hand crank


50.5 - Manual spring-charging port
50.6 - Over-running coupling

Figure 14: Use of manual spring-charging crank


24
Vacuum interrupter/
operator
Figure 15: Typical elementary diagram

(+)
01
01 T
C

SD16 SD13

W 21 G R
LS21 41
22 52b
42
SD3 SD4 SD1
22 21 14
Motor 88 52Y LS3 52Y
21 22 13
13 31 24
LS41 31 52b 52a
DC supply 14 52Y 32 23
21 32
LS22
22 A1 A1 A1
52SRC 52Y 52T
22 22 A2 A2 SD14 A2
MI1 MI2 34
13 52a
21 21 LS9 33
TB 14
1 SD2
2
3
4
5
SD15 6

(-)

SD11 SD9 SD7 SD5

54 64 91 101 74 84 111 121


52a 52a 52b 52b 52a 52a 52b 52b
53 63 92 102 73 83 112 122
SD12 SD10 SD8 SD6

88.0 - Spring-charging motor LS - Spring-charged switch Standard:

52a - Auxiliary switch is open when MI1, MI2 - Mechanical interlock Fuses in close circuit. Slugs in trip
circuit breaker is open circuit (fuses optional).
01/C - Control switch (CLOSE)
52b - Auxiliary switch is closed Shown with springs discharged, trip-
01/T - Control switch (TRIP) latch reset, circuit breaker open,
when circuit breaker is closed
R - Red indicating light connect or withdrawn position.
52SRC - Spring-release coil (CLOSE) (CLOSED)
52T - Shunt trip coil W  hite indicating light
-W
52Y - Closing relay (anti-pump) (spring-charged)

G - Green indicating light (TRIP)

25
Vacuum interrupter/
operator
Indirect releases - secondary shunt
21.0 25.0 27.0
release (dual trip) (52T1) or
undervoltage (27.0)

33.0 The indirect release provides for the


23.0 conversion of modest control signals into
31.0
11.0 powerful mechanical-energy impulses. It is
primarily used to open medium-voltage
13.0 7.0 circuit breakers while functioning as a
9.0 1.0
15.0 secondary shunt-release (dual trip) or
undervoltage device.
5.0 These releases are mechanical energy-
3.0 storage devices. Their internal springs are
charged as a consequence of the circuit
breaker mechanism operation. This energy
1.0 - Magnet core 15.0 - Tripping pin
is released upon application or removal (as
3.0 - Housing 21.0 - Locking pin appropriate) of applicable control voltages
5.0 - Mounting holes 23.0 - Striker pin (refer to Figures 16, 17 and 18).
7.0 - Magnet coil 25.0 - Latch The secondary shunt-release and
9.0 - Magnet armature 27.0 - Spring undervoltage release mounts to the
immediate right of the trip coil (54.1).
11.0 - Tension spring 31.0 - Striker-pin spring
Secondary shunt-release (52T1) (refer to
13.0 - Adjusting screw (factory-set) 33.0 - Terminal block
Figure 16)
for 11.0
A secondary shunt-release (extra-trip coil)
Figure 16: Construction of secondary shunt release (shown charged) (3AX1101) is used for electrical opening of
the circuit breaker by protective relays or
manual control devices when more than
Locked/unlocked selection screw one trip coil is required. The second trip
23.0 25.0 (undervoltage release only) coil is generally connected to a separate
auxiliary supply (dc or ac) from the control
29.0 supply used for the normal trip coil.
Undervoltage release (27.0) (refer to
Figures 17 and 18)
The undervoltage release (3AX1103) is
used for continuous monitoring of the
tripping supply voltage. If this supply
voltage falls excessively, the undervoltage
release will provide for automatic tripping
of the circuit breaker.
The undervoltage device may be used for
21.0 27.0
manual or relay tripping by employing a
contact in series with undervoltage device
21.0 - Locking pin holding coil. Relay tripping may also be
achieved by employing a normally open
23.0 - Striker pin
contact in parallel with the holding coil. If
25.0 - Latch this scheme is used, a resistor must be
27.0 - Spring provided to limit current when the
normally open contact is closed.
29.0 - Locked/unlocked selection screw
Secondary shunt and undervoltage
releases are available for all standard ANSI/
Figure 17: Latch details (shown charged) IEEE control voltages.
26
Vacuum interrupter/
operator
Construction and mode of operation of
secondary shunt-release and Position A: locked
undervoltage release (refer to Figures
16, 17 and 18)
The release consists of a spring-power
A
stored-energy mechanism, a latching 23.0
device and an electromagnet. B
29.0
These elements are accommodated side by
side in a housing (3.0), with a detachable
cover and three through-holes (5.0) for Position B: unlocked (operating position)
fastening screws. The supply leads for the
trip coil are connected to a terminal block
(33.0).
The energy-storing mechanism consists of A
23.0
the striker pin (23.0) and its operating
B
spring (31.0), which is mostly located 29.0
inside the striker pin (23.0). When the
spring is compressed, the striker pin is held
by a latch (25.0), whose sloping face is Cancel the lock for the undervoltage release by shifting the locking screw (29.0)
forced against the appropriately shaped from A to B.
striker pin (23.0) by spring (27.0). The 23.0 - Striker pin
other end of the latch (25.0) is supported 29.0 - Screw
by a partly milled locking pin (21.0),
pivoted in the cover sheets of the magnet
armature (9.0). The armature (9.0) is Figure 18: Undervoltage lock/operate selection
pivoted in front of the poles of the
U-shaped magnet core, (1.0) and is pulled
away from it by the tension spring (11.0).
If the magnet coil (7.0) of the secondary 01
shunt release 3AX1101 is energized by a T
trip signal, or if the tripping pin (15.0) is
mechanically actuated, magnet armature
(9.0) is swung against the pole faces. SD5
When this happens, the latch (25.0) loses
its support and releases the striker pin 24
(23.0) that is forced out by the spring 52a
(31.0). 23
120 or 240 Vac Capacitor
On the undervoltage release 3AX1103, the supply A1 (+)
latch (25.0) is held by the locking pin 52T 1
(-)
(21.0) as long as the armature (9.0) is A2 Resistor
energized. If the circuit of the magnet coil 34 2
(7.0) is interrupted, the armature (9.0) 52a
33 (+)
drops off, thus causing the latch (25.0) to Rectifier
lose its support and release the striker pin
(-)
(23.0).
Capacitor trip
Following every tripping operation, the
striker pin (23.0) must be reset to its
normal position by loading the spring
(31.0). This takes place automatically via
the operating mechanism of the circuit
breaker.
Figure 19: Capacitor-trip device
27
Vacuum interrupter/
operator
Since the striker pin of the undervoltage Shock absorber
release 3AX1103 is latched only when the
Circuit breakers are equipped with a
armature is energized, the undervoltage
hydraulic shock absorber (61.8) (refer to
release is provided with a screw (29.0), for
Figure 6). The purpose of this shock
locking the striker pin (23.0) in the normal
absorber is to limit overtravel and rebound
position for adjusting purposes or for
of the vacuum interrupter movable
carrying out trial operations during circuit
contacts during the conclusion of an
breaker servicing. Position A (locked)
opening operation. The shock absorber
disables the undervoltage release. Position
action affects only the end of an opening
B (unlocked) is the normal operating
operation.
position.
Auxiliary switch (52a/b)
Capacitor trip device
Figure 6 shows the circuit breaker
The capacitor trip device is an auxiliary
mounted auxiliary switch (68.0). This
tripping option providing a short-term
switch provides auxiliary contacts for
means of storing adequate electrical
control of circuit breaker closing and
energy to ensure circuit breaker tripping. If
opening functions. Contacts are available
provided, a capacitor trip device must be
for use in relaying and external logic
located on the drawout truck or in the
circuits. This switch is driven by linkage
stationary circuit breaker enclosure, as
(68.1) connected to the jack shaft (63.0).
space is not available inside the type 3AH
The auxiliary switch contains both "b"
operator housing.
(normally Closed) and "a" (normally Open)
This device is applied in circuit breaker contacts. When the circuit breaker is open,
installations lacking independent auxiliary the "b" contacts are closed and the "a"
control power or station battery. In such contacts are open.
installations, control power is usually
Spring-charging motor (88.0)
derived from the primary source. In the
event of a primary ac source fault or Spring-charging motors (50.4) (refer to
disturbance the capacitor trip device will Figure 6) are available for either ac or dc
provide short-term tripping energy for operation. If operated with ac voltage, a
circuit breaker opening due to protective rectifier is installed in the circuit breaker.
relay operation or operation of a circuit
breaker control switch.
The capacitor trip converts 120 or 240 Vac
control voltage to a dc full-wave voltage
that is used to charge a large capacitor to
the peak of the converted wave (refer to
Figure 19).

28
Maintenance

Failure to maintain the equipment can result in death, serious injury, property damage or
product failure, and can prevent successful functioning of connected apparatus.
The instructions contained herein should be carefully reviewed, understood and followed.
The maintenance tasks in Table 1 must be performed regularly.

Introduction and maintenance intervals For the safety of maintenance personnel as


well as others who might be exposed to
Periodic inspections and maintenance are
hazards associated with maintenance
essential to safe and reliable operation of
activities, the safety related work practices
the circuit breaker.
of NFPA 70E (especially chapters 1 and 2)
When circuit breakers are operated under should always be followed when working
"usual service conditions," maintenance on electrical equipment.
and lubrication are recommended at ten-
Maintenance personnel should be trained
year intervals (five-year intervals for the
in the safety practices, procedures and
type SDV6 outdoor distribution circuit
requirements that pertain to their
breaker) or at the number of operations
respective job assignments.
indicated in Table 2. "Usual" and "unusual"
service conditions for medium-voltage This instruction manual should be
metal-clad switchgear (includes circuit reviewed and retained in a location readily
breaker module) are defined in ANSI/IEEE accessible for reference during
C37.20.2, sections 4 and 8.1, ANSI/IEEE maintenance of this equipment.
C37.04, section 4 and ANSI/IEEE C37.010,
The user must establish a periodic
section 4. Generally, "usual service
maintenance program to ensure trouble-
conditions" are defined as an environment
free and safe operation. The frequency of
where the equipment is not exposed to
inspection, periodic cleaning and a
excessive dust, acid fumes, damaging
preventive maintenance schedule will
chemicals, salt air, rapid or frequent
depend upon the operation conditions.
changes in temperature, vibration, high
NFPA publication 70B, "Electrical
humidity and extreme temperatures.
equipment maintenance" may be used as a
The definition of "usual service conditions" guide to establish such a program.
is subject to a variety of interpretations.
Note: A preventive maintenance program
Because of this, you are best served by
is not intended to cover reconditioning or
adjusting maintenance and lubrication
major repair, but should be designed to
intervals based on your experience with
reveal, if possible, the need for such
the equipment in the actual service
actions in time to prevent malfunctions
environment.
during operation.
Regardless of the length of the
maintenance and lubrication interval,
Siemens recommends that circuit breakers
should be inspected and exercised
annually.

29
Maintenance

Hazardous voltage and high-speed moving parts.


Will cause death, serious injury and property damage.
De-energize before working on this equipment.
Read instruction manuals, observe safety instructions and use
qualified personnel.

Recommended hand tools Recommended maintenance and


lubrication
Metric hardware is used on these circuit
breakers. Periodic maintenance and lubrication
should include all the tasks shown in Table
The following list of hand tools describes
1. Recommended procedures for each of
those normally used in disassembly and re-
the listed tasks are provided in this section
assembly procedures:
of the instruction manual.
 pen-end wrenches: 7, 8, 10, 13, 17,
O
The list of tasks in Table 1 does not
19 and 24 mm
represent an exhaustive survey of
 pen-end wrench: 55 mm used to
O maintenance steps necessary to ensure
exchange shock absorber (Quantity: safe operation of the equipment. Particular
two pieces are required for the task) applications may require further
procedures. Should further information be
Sockets: 7, 8, 10, 13 and 17 mm
desired or should particular problems arise
 ocket: 36 mm (used for replacing post
S that are not covered sufficiently for the
insulators) User's purposes, the matter should be
referred to the local Siemens sales office.
Deep sockets: 19 and 24 mm
Checks of the primary power path
Hex keys: 5, 6, 8 and 10 mm
The primary power path consists of the
 orque wrench: 0-150 Nm
T
three vacuum interrupters, the three upper
(0-100 ft-lbs)
and the three lower primary disconnects
 crewdrivers: 0.032 x 1/4 in wide and
S (drawout only) or bus connections
0.055 x 7/16 in wide (stationary only). These components are
checked for cleanliness and condition. The
Pliers
vacuum interrupters are also checked for
Light hammer vacuum integrity.
Dental mirror Some test engineers prefer to perform the
contact-erosion check during the manual
Flashlight
spring-charging check of the operator,
Drift pins: 1/8, 3/16 and 1/4 in since charging of the springs is necessary
to place the contacts in the CLOSED
 etaining ring plier (external type, tip
R
position.
diameter 0.038 in).

30
Maintenance

The use of unauthorized parts in the repair of the equipment, or tampering by unqualified
personnel can result in hazardous conditions, that can result in death, serious injury or
property damage.
Follow all safety instructions contained herein.

Also, the vacuum-integrity check is usually Inspection items and tests


performed in conjunction with the high-
Primary-power path checks
potential tests.
Cleanliness check
These instructions assume these tests
(contact-erosion/manual spring-charging Inspection of flexible connectors
check and vacuum-integrity/high-potential Stored-energy operator-mechanism checks
tests) will be combined as described.
Maintenance and lubrication
Cleanliness check
Fastener check
Figure 2 is a side view of the circuit breaker
with the insulating barriers removed (if Manual-spring charging check
furnished) to show the vacuum interrupter, Contact-erosion check
and the upper and lower connection pads.
Electrical-control checks
All of these components must be clean
Wiring and terminals checks
and free of dirt or any foreign objects. Use
a dry lint-free cloth. For stubborn dirt, use Secondary-disconnect check (drawout only)
a clean cloth dipped in isopropyl alcohol
Automatic spring-charging check
(except for the vacuum interrupters). For
stubborn dirt on a vacuum interrupter use Electrical close and trip check
a cloth and warm water and a small Vacuum-integrity check
amount of mild liquid-household detergent
High-potential test
as a cleaning agent. Dry thoroughly using
a dry lint-free cloth. Insulation test
Contact-resistance test
Inspection of flexible connectors
Inspection and cleaning of circuit-breaker insulation
Inspect the flexible connectors that
Functional tests
connect the bottom movable contacts of
the vacuum interrupters to the lower
connection pad for tightness and absence Table 1: Maintenance tasks
of mechanical damage, burning or pitting.

31
Maintenance

Checks of the stored-energy operator  or all lubrication (except electrical


F
Circuit Number of
mechanism moving or sliding surfaces), use one of
breaker type years/closing
the following:
operations The stored-energy operator checks are
(whichever divided into mechanical and electrical   lüber Isoflex Topas L32
K
comes first) checks for simplicity and better (part 3AX11333H)
SDV6 5-years/ organization. This first series of checks
 
Klüber Isoflex Topas L32N (spray)
10,000 determine if the basic mechanism is clean,
operations
(part 15-172-879-201).
lubricated and operates smoothly without
control power. The contact-erosion check Source:
of the vacuum interrupter is also
All others 10-years/  lüber Isoflex Topas L32 or L32N:
K
performed during these tasks.
10,000 Klüber Lubrication North America L.P.
operations Maintenance and lubrication www.klueber.com.
Table 2 gives the recommended Fastener check
maintenance intervals for circuit breakers.
Inspect all fasteners for tightness. Both
These intervals assume that the circuit
Table 2: Maintenance and locknuts and retaining rings are used.
lubrication schedule breaker is operated under "usual service
Replace any fasteners that appear to have
conditions" as discussed in ANSI/IEEE
been frequently removed and replaced.
C37.20.2, section 4 (for drawout circuit
breakers) or ANSI/IEEE C37.04, section 4 Manual spring-charging and contact-
and elaborated in ANSI/IEEE C37.010, erosion checks
section 4 (for outdoor distribution circuit
Perform the manual spring-charging check
breakers). The maintenance and
contained in the section describing the
lubrication interval is the lesser of the
installation check and initial functional
number of closing operations or the time
tests (refer to pages 9-10). The key steps of
interval since last maintenance.
this procedure are repeated here:
The vacuum interrupter operator
1. Insert the hand-charging crank into the
mechanism is shown in Figure 20, with the
manual-charge socket at the front of
front cover removed to show construction
the operator control panel. Turn the
details. Both the opening spring and the
crank clockwise (about 48 revolutions)
closing spring are shown. The movable
to charge the closing spring. Continue
end of the closing spring is connected to a
cranking until the CHARGED flag
crank arm. The movable end of the
appears in the window of the spring
opening spring is connected to the jack
indicator.
shaft by a pull rod.
2. P
 ress the Close (black) pushbutton. The
Clean the entire stored-energy operator
contact-position indicator on the
mechanism with a dry, lint-free cloth.
operator control-panel should indicate
Check all components for evidence of that the circuit breaker contacts are
excessive wear. Place special attention Closed.
upon the closing spring-crank and the
insulating couplers and linkages.
Lubricate all non-electrical moving or
sliding surfaces with a light coat of
synthetic grease or oil. Lubricants
composed of ester oils and lithium
thickeners will be generally compatible.

32
Maintenance

Figure 20: Operator mechanism lubrication

Klüber L32 or Klüber L32N

33
Maintenance

High-speed moving parts.


Can result in serious injury.
Tripping spring is charged. If trip latch is moved, the stored-
energy springs will discharge rapidly.
Stay clear of circuit breaker components that are subject to
sudden, high-speed movement.

Figure 21: Contact-erosion check


mark dot circled in orange (shown
with circuit breaker OPEN)
3. P
 erform the contact-erosion check. Electrical control checks
Contact erosion occurs when high
The electrical controls of the circuit breaker
fault-currents are interrupted.
should be checked during inspections to
Determination of acceptable contact
verify absence of any mechanical damage,
condition is checked by the visibility of
and proper operation of the automatic
the white contact-erosion mark shown
spring-charging and Close and Trip circuits.
in Figure 21. The white contact-erosion
mark is located on the movable stem of Unless otherwise noted, all of these tests
the vacuum interrupter, near the are performed without any control power
plastic guide-bushing. The contact- applied to the circuit breaker.
erosion check procedure is:
Check of the wiring and terminals
a) Be sure the circuit breaker primary
1. P
 hysically check all of the circuit
contacts are Closed.
breaker wiring for evidence of
b) O
 bserve the white contact-erosion abrasion, cuts, burning or mechanical
mark (refer to Figure 21) of each damage.
pole. When any part of the white
2. C
 heck all terminals to be certain they
contact-erosion mark is visible,
are solidly attached to their respective
contact wear is within acceptable
device.
limits.
4. P
 ress the red Open pushbutton after
completing the contact-erosion check.
Visually verify the Discharged condition
of the closing spring and that the
circuit breaker contacts are Open.
5. P
 ress the black Close pushbutton.
Nothing should happen. The manual-
spring check should demonstrate
smooth operation of the operating
mechanism.

34
Maintenance

Hazardous voltage and high-speed moving parts.


Will cause death, serious injury and property damage.
Do not bypass interlocks or otherwise make interlocks
inoperative. Interlocks must be in operation at all times.
Read instruction manuals, observe safety instructions and use
qualified personnel.

Automatic spring-charging check 1. O


 nce the circuit breaker springs are
(control power required) charged, move the switchgear-
mounted Close/Trip switch to the Close
Repeat the automatic spring-charging
position. Verify by both the sound of
check described in the section describing
the circuit breaker closing and by the
the installation check and initial functional
main contact status indicator that the
tests (refer to pages 9-10).
circuit breaker contacts are closed.
Primary tasks of this check are:
2. A
 s soon as the circuit breaker has
1. T
 he circuit breaker must be energized closed, the automatic spring-charging
with control power for this check. process is repeated.
2. Energize the control-power source. 3. A
 fter a satisfactory close operation is
verified, move the switchgear-mounted
3. W
 hen control power is connected to
Close/Trip switch to the Trip position.
the circuit breaker, the closing spring
Verify by both the sound of the circuit
should automatically charge. Visually
breaker opening and by the main
verify that the closing spring is
contact status indicator that the circuit
charged.
breaker contacts are open.
Note: A temporary source of control power
4. A
 fter a satisfactory open operation is
and test leads may be required if the
verified, hold the circuit breaker
control-power source has not been
manual Trip button and apply and
connected to the switchgear or circuit
maintain an electrical close signal. The
breaker. When control power is connected
circuit breaker should close,
to the circuit breaker, the closing spring
immediately trip, the close spring
should automatically charge.
should charge, and the circuit breaker
Electrical close and trip check (control should not attempt to close again.
power required)
Completion of these checks demonstrates
A check of the circuit breaker control satisfactory operation of auxiliary
circuits shall be performed. This check is switches, internal relays and open and
made with the circuit breaker energized by close coils.
control power either from the switchgear
or an external control-power source.

35
Maintenance

Table 3: Typical vacuum interrupter contact life expectancy

Rated Interrupting Rated short-circuit current Vacuum Graph Right hand


maximum class interrupter limit of
voltage kV MVA type curve (refer
to Figure
22)1
4.76 250 29 kA @ 4.76 kV; 36 kA @ 3.85 kV VS-17006 A 36
VS-17040 E 36
4.76 350 41 kA @ 4.76 kV; 49 kA @ 4.0 kV VS-15052 B 49
8.25 500 33 kA @ 8.25 kV; 41 kA @ 6.6 kV VS-15052 B 41
15.0 500 18 kA @ 15.0 kV; 23 kA @ 11.5 kV VS-17006 A 23
15.0 750 28 kA @ 15.0 kV; 36 kA @ 11.5 kV VS-15052 B 36
VS-17040 E 36
15.0 1,000 37 kA @ 15.0 kV; 48 kA @ 11.5 kV VS-15052 B 48
38.0 1,500 21 kA @ 38.0 kV; 35 kA @ 23.0 kV VS-30030 D 35
Rated Interrupting Rated short-circuit current Vacuum Graph Right hand
maximum class interrupter limit of
voltage kV kA type curve (refer
to Figure
22)1
4.76 31.5 31.5 VS-17006 A 31.5
VS-17040 E 31.5
4.76 40 40 VS-15052 B 40
VS-17040 E 40
4.76 50 50 VS-15052 B 50
4.76 63 63 VS-17085 F 63
8.25 40 40 VS-15052 B 40
VS-17040 E 40
15.0 20 20 VS-17006 A 20
15.0 25 25 VS-17006 A 25
15.0 31.5 31.5 VS-17006 A 31.5
VS-17040 E 31.5
15.0 40 40 VS-15052 B 40
VS-17040 E 40
15.0 50 50 VS-15052 B 50
15.0 63 63 VS-17085 F 63
15.5 20 20 VS-25008 C 20
15.5 25 25 VS-25008 C 25
15.5 31.5 31.5 VS-15052 B 31.5
15.5 40 40 VS-15052 B 40
27.6 20 20 VS-25008 C 20
27.6 25 25 VS-25008 C 25
38.0 20 20 VS-30030 D 20
38.0 25 25 VS-30030 D 25
38.0 31.5 31.5 VS-30041 D 31.5
38.0 40 40 VS-30041 D 40

Footnote:
36 1.
Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).
Maintenance

Figure 22: Typical vacuum interrupter contact life curves

Load graph "A" vacuum interrupter type VS-17006


Load graph "C" vacuum interrupter type VS-25008
Load graph "E" vacuum interrupter type VS-17040

Permissible operating cycles

100,000

50,000

20,000

10,000

5,000

2,000

1,000

500

200

100

50

20
C A E
10
1 2 5 10 20 25 31.540 50 100

Breaking current (symmetrical value)

Note: Right-hand vertical segment of curve is located at the maximum


symmetrical interrupting current rating of the circuit breaker, as indicated
in Table 3.

37
Appendix

Figure 22: Typical vacuum interrupter contact life curves (continued)

Load graph "B" vacuum interrupter type VS-15052


Load graph "D" vacuum interrupter types VS-30030 and VS-30041
Load graph "F" vacuum interrupter type VS-17085

Permissible operating cycles

100,000

50,000

20,000

10,000

5,000

2,000

1,000

500

200

100

50

20
D B F
10
1 2 5 10 20 40 50 63 100

Breaking current (symmetrical value)

Note: Right-hand vertical segment of curve is located at the maximum


symmetrical interrupting current rating of the circuit breaker, as indicated
in Table 3.

38
Maintenance

Checks of the spring-charging motor Vacuum-integrity check (using


(88.0) mechanical test) (refer to Figure 23)
No additional checks of the spring- Before putting the circuit breaker into
charging motor are necessary. If it is service, or if a vacuum interrupter is
necessary to remove or replace the spring- suspected of leaking as a result of
charging motor, torque motor-mounting mechanical damage, check the vacuum
hardware to 7.3-8 ft-lb (10-11 Nm). integrity either mechanically as described
in this section, or alternatively, electrically
Anti-pump relay
using a high-potential test set as described
If it is necessary to remove the connections in the next section.
to the anti-pump relay, use care to avoid
Open and isolate the circuit breaker and
damaging the relay. Replace the relay if the
detach the insulating coupler (48.0) from
relay terminals are damaged or loose in
lever (48.6) (refer to Figure 23).
the relay body.
The atmospheric pressure will force the
Vacuum interrupters
moving contact of a hermetically sealed
The life expectancy of vacuum interrupters vacuum interrupter into the "Closed"
is a function of the numbers of position, causing lever (48.6) to move into
interruptions and magnitude of current the position shown in Figure 23.
interrupted (refer to Table 3 and Figure
A vacuum interrupter may be assumed to
22).
be intact if it shows the following
The vacuum interrupters must be replaced characteristics:
before the number of mechanical
1. A
 n appreciable closing force has to be
operations (listed in Table 2) are reached,
overcome when lever (48.6) is moved
or when the contacts have been eroded
to the "Open" position by hand (refer to
beyond allowed limits. Vacuum interrupter
Figure 23);
replacement procedures are detailed in the
following maintenance instructions. 2. W
 hen the lever is released, it must
automatically return to the "Closed"
The vacuum interrupter contact life curves
position with an audible sound as the
(refer to Figure 22) are offered as a guide
contacts touch.
to expected life.
After checking the vacuum, reconnect the
lever (48.6) to the insulating coupler
(48.0) (refer to Figure 23).

High-potential tests employ hazardous voltages.


Will cause death and serious injury.
Follow safe procedures, exclude unnecessary personnel and use
safety barriers. Keep away from the circuit breaker during
application of test voltages. Disconnect the split plug jumper
from between the circuit breaker and switchgear before
conducting high-potential tests.

39
Maintenance

Vacuum interrupters may emit X-ray radiation.


Can result in serious injury.
Keep personnel more than six feet away from a circuit breaker
under test.

High-potential tests Note: Do not use dc high-potential testers


incorporating half-wave rectification.
The next series of tests (vacuum-integrity
These devices produce high peak voltages.
test and insulation tests) involve use of
high-voltage test equipment. The circuit High peak voltages will produce X-ray
breaker under test should be inside a radiation. DC testers producing excessive
suitable test barrier equipped with warning peak voltages also show erroneous
lights. readings of leakage current when testing
vacuum circuit breakers.
Vacuum-integrity check (using dielectric
test) High-potential test voltages
A high-potential test is used to verify the The voltages for high-potential tests are
vacuum integrity of the circuit breaker. The shown in Table 4.
test is conducted on the circuit breaker
Note: This test includes not only the
with its primary contacts in the Open
vacuum interrupter, but also the other
position.
insulation components in parallel with the
Vacuum integrity test procedure vacuum interrupter. These include the post
insulators and the insulating coupler, as
1. O
 bserve safety precautions listed in the
well as the insulating (tension) struts
danger and warning advisories.
between the upper and lower vacuum
Construct the proper barrier and
interrupter supports. If these insulation
warning light system.
components are contaminated or
2. G
 round the frame of the circuit defective, the test voltage will not be
breaker, and ground each pole not sustained. If so, clean replace the affected
under test. components, and retest.
3. A
 pply test voltage (refer to Table 4)
across each pole for one minute (circuit
breaker Open).
4. If the pole sustains the test voltage for
that period, its vacuum integrity has
been verified.

40
Maintenance

Equipment Equipment rated Maximum ac Maximum dc


maximum voltage power-frequency rms test voltage average test
rating kV withstand kV (rms) kV voltage

4.76 19 14 20

8.25 36 27 38

15.0 36 27 38

15.5 50 38 53

27.6 60 45 64

38 80 60 85

Table 4: High-potential test voltages

As-found insulation and contact Insulation and contact-resistance test


resistance tests equipment
As-found tests verify the integrity of the In addition to the high-potential test
circuit breaker insulation system. Megger* equipment capable of test voltages as
or insulation resistance tests and contact- listed in Table 4, the following equipment
resistance tests conducted on equipment is also required:
prior to installation provide a basis of
A
 C high-potential tester with test
future comparison to detect changes in the
voltage of 1,500 volts, 60 Hz
protection afforded by the insulation
system. A permanent record of periodic T
 est equipment for contact-resistance
as-found tests enables the maintenance tests.
organization to determine when corrective
actions are required by watching for
significant deterioration in insulation
resistance, or increases in contact
resistance.
* Megger is a registered trademark of
Megger Group, Ltd.

41
Maintenance

6. D
 isconnect the leads to the spring-
48.0 - Insulating coupler
charging motor.
48.6 - Lever
7. F
 or drawout applications, connect all
points of the secondary disconnect
with a shorting wire. For stationary
applications, disconnect secondary
circuits for the operating mechanism
by disconnecting the multiple pin-plug
at the upper right corner of the
48.6 48.0 operator, and connect all pins on the
operator side with a shorting wire.
Connect the shorting wire to the high-
potential lead of the high-voltage
tester, and ground the circuit breaker
housing. Starting with zero voltage,
gradually increase the test voltage to
1,500 volts rms, 60 Hz. Maintain test
voltage for one minute.
8. If no disruptive discharge occurs, the
secondary control insulation level is
48.6 satisfactory.
9. D
 isconnect the shorting wire, reattach
48.0 the multiple pin-plug (if applicable)
and reattach the leads to the spring-
Figure 23: Circuit breaker pole assembly/vacuum-check mechanical/contact-resistance charging motor.
test
10. P
 erform contact-resistance tests of the
Insulation and contact-resistance test
primary contacts. The resistance
procedure
should be read between the lower and
1. O
 bserve safety precaution listed in the upper connection pads (refer to Figure
danger and warning advisories for the 23).Contact resistance should not
vacuum integrity check tests (refer to exceed the values listed in Table 5.
pages 38-39).
2. C
 lose the circuit breaker. Ground the
frame of the circuit breaker, and
ground each pole not under test. Use
manual charging, closing and tripping
procedures.
3. A
 pply the proper ac or dc (refer to
Table 4) high-potential test voltage
between a primary conductor of the
pole and ground for one minute.
4. If no disruptive discharge occurs, the
insulation system is satisfactory.
5. A
 fter test, ground both ends and the
middle of each vacuum interrupter to
dissipate any static charge.

42
Maintenance

Inspection and cleaning of circuit Functional tests Current Contact


breaker insulation rating resistance
Refer to the installation checklist in
A Micro-Ohms
1. P
 erform the spring-discharge check the installation checks and initial
(refer to page 9) on the circuit breaker functional tests section of this
after all control power is removed. The instruction manual (refer to pages
1,200 35
spring-discharge check consists of: 9-10). Functional tests consist of
performing at least three manual
a) P
 ressing the red Open pushbutton
spring-charging checks and three
b) P
 ressing the black Close pushbutton automatic spring-charging checks. 2,000 30
After these tests are complete, and
c) P
 ressing again the red Open
the springs are fully discharged, all
pushbutton.
fasteners and connections are
 ll of these controls are on the circuit
A checked again for tightness and 3,000 30
breaker front panel (refer to Figure 1). condition.
Visually verify the Discharged condition
of the springs. Table 5: Maximum contact-resistance

2. R
 emove any inter-phase and
outerphase barriers if furnished
(applicable for certain types only).
3. C
 lean barriers and post insulators using
clean cloth dipped in isopropyl alcohol.
4. R
 eplace all barriers. Check all visible
fasteners again for condition and
tightness.
Note: Do not use any cleaning compounds
containing chlorinated hydrocarbons, such
as: trichlorethylene, perchlorethylene or
carbon tetrachloride.
These compounds will damage the
phenylene ether copolymer material used
in the barriers and other insulation on the
circuit breaker.

43
Overhaul

Circuit Closing Introduction 1. R


 eplace vacuum interrupter;
breaker type operations instructions follow.
The following procedures along with the
troubleshooting charts in this instruction 2. Close coil (52SRC) and trip coil (52T).
manual (refer to pages 47-51), provide
a) R
 emove two "push on" terminal
maintenance personnel with a guide to
connections
identifying and correcting possible
SDV6 outdoor
distribution 10,000 malfunctions of the circuit breaker. b) Remove two M4 hex-head screws
circuit breaker and remove solenoid.
Circuit breaker overhaul
c) Install replacement coils with new
Table 6 gives the recommended overhaul
M4 x 10 hex-head screws (Siemens
schedule type 3AH operating mechanisms.
part # 00-000-443-820) and new
All others 10,000 These intervals assume that the circuit
lock washers for M4 (Siemens part #
breaker is operated under "usual service
00-000-288-316).
conditions" as discussed in ANSI/IEEE
C37.20.2 section 4 (for drawout circuit d) The coil-mounting screws must be
Table 6: Overhaul schedule breakers) or ANSI/IEEE C37.04 section 4 installed using thread locking
and elaborated in C37.010 section 4 (for adhesive (Loctite #222, Siemens
outdoor distribution circuit breakers). If the part 15-133-281-007) and primer
circuit breaker is operated frequently, the (Loctite primer T (#7471), Siemens
overhaul interval in Table 6 may coincide part 15-133-281-005).
with the maintenance interval in Table 2.
e) Connect wires to coils with new wire
Replacement at overhaul terminals (Siemens part # 15-171-
600-002).
The following components are replaced
during an overhaul of the circuit breaker, 3. L ubricate operating mechanism
when required: according to maintenance and
lubrication information (refer to page
 acuum interrupters as determined by
V
32).
vacuum integrity test, contact erosion
or according to overhaul schedule 4. W
 hen work is finished, operate circuit
(refer to Table 6) breaker and close and open several
times, and check that all screw
Close coil, 52SRC
connections are tight.
Trip coil, 52T
Replacement of vacuum interrupters
 rip-free drive bar mechanism (if
T
Replacement vacuum interrupters are
applicable).
furnished as a complete assembly. They
When these parts are changed, locking have been completely tested and
devices must also be removed and dielectrically and mechanically
replaced. These include lock washers, conditioned.
retaining rings, retaining clips, spring pins,
It is recommended that one vacuum
cotter pins, etc.
interrupter be removed and replaced
completely rather than removing two or
more vacuum interrupters at a time.
The following procedure in check list
format describes the procedure for
removing and replacing a vacuum
interrupter. Components may be identified
by reference to Figures 24 and 25.

44
Overhaul

Instructions herein apply for replacement 1.4 R


 emove coupling pin from the eye
of all vacuum interrupters except type VS- bolt (36.3).
17085 vacuum interrupters, and 1.5 F
 ree struts (28.0) from the pole head
interrupters on 3,000 A circuit breakers (20.0). Loosen the strut hardware on
having the flexible connector (refer to 29.1 the pole bottom (40.0) and swing the
in Figure 24) electron-beam welded to the struts forward and downward.
moving terminal (refer to 36.1 in Figure
24) of the vacuum interrupter. These 1.6 L oosen screws fastening the
interrupters must be replaced by factory- centering ring (28.1).
trained personnel. Contact Siemens 1.7 R
 emove bolt (31.2), lock washer and
medium-voltage customer service at +1 large washer at the stationary contact
(800) 347-6659 or +1 (919) 365-2200 of the vacuum interrupter (18 mm or
outside the U.S. 24 mm socket with extension).
1. Removing the vacuum interrupter 1.8 U
 sing a 24 mm socket with an
Note: Special care needs to be exercised in extension, loosen and remove hex-
removal or installation of hardware around cap screw fastening the pole head to
the bottom, or movable contact end, of the post insulator. Completely remove
the vacuum interrupter. the pole head and set aside.

The movable contact uses a metal bellows 1.9 G


 rasp the vacuum interrupter (30.0)
to maintain the vacuum seal while still and withdraw vertically. Assistance
permitting up and down motion of the may be required to work the terminal
contact. The bellows is rugged and clamp off the movable stem of the
reliable, and is designed to withstand years vacuum interrupter. DO NOT USE
of vertical movement. However, care UNDUE FORCE OR TWISTING MOTION.
should be exercised to avoid subjecting the If the terminal clamp (29.2) cannot be
bellows to excessive torque during removal easily removed, STOP!, check to be
and replacement. Twisting the bellows certain hardware is loose, and that
through careless bolt removal or the terminal clamp (29.2) is not
tightening may damage the vacuum binding.
interrupter, resulting in loss of vacuum 2. Installing a vacuum interrupter
integrity.
Note: Replacement vacuum interrupter
1.1 B
 efore starting work, the circuit (30.0) will be received from the factory
breaker should be isolated from all with an eye bolt (36.3) in place, adjusted
primary and control-power sources and torqued to specific requirements. DO
and all stored energy discharged by NOT ALTER THE ADAPTER (EYE-BOLT)
opening, closing and opening the SETTING.
circuit breaker by hand. Discharge any
static charge by grounding both ends 2.1 Inspect all silver-plated connection
and the middle of each vacuum surfaces for cleanliness. Clean only
interrupter. Carefully remove outer- with a cloth and solvent. Do not
phase and inter-phase barriers. abrade, as this will damage the silver
plating.
1.2 L oosen the lateral bolt(s) on terminal
clamp (29.2). Employ the illustrated 2.2 Insert vacuum interrupter (30.0) into
procedure to loosen clamp hardware the lower pole-support (40.0). Slip
(refer to Figure 25). terminal clamp (29.2) into position on
the movable stem.
1.3 W
 ithdraw pin (48.5) from insulating
coupler (48.0) and levers (48.6). 2.3 A
 lign vacuum interrupter and fasten
"finger tight" using heavy flat washer,
lock washer and bolt (31.2).

45
Overhaul

Figure 24: Vacuum interrupter replacement illustration

20.0 - Upper pole-support (pole-head)


28.0 - Strut
28.1 - Centering ring
29.1 - Flexible connector
20.0
29.2 - Terminal clamp
31.2
29.3 - Spacer (or shoulder)
30.0 - Vacuum interrupter
31.2 - Upper terminal-bolt
36.1 - Moving terminal
36.3 - Eye bolt (or adapter)
40.0 - Lower pole-support (pole-bottom)
48.0 - Insulating coupler
48.5 - Pin
28.0
48.6 - Angled lever
48.9 - Drive link

30.0

36.1

28.1
29.3

29.2
29.1

36.3

40.0
48.6
48.5
48.0

48.9 48.9

46
Overhaul

2.4 F
 asten the pole head to the post Position of torque wrench to avoid undue
insulator (16.1) "finger tight" using stressing of moving contact (36.1)
hex-head bolt, lock washer and flat
washer.
2.5 A
 ttach struts (28.0) to the upper pole-
support (20.0), replace hardware Vacuum interrupter
(M10), but do not tighten at this
time.
2.6 C
 ouple levers (48.6) and drive link
(48.9) to the eye bolt (36.3), using
the pin supplied. Apply retaining clips. Moving contact (36.1)
Appropriate pin is modestly Holding wrench
chamfered, not to be confused with Spacer (shoulder) (29.3)
pin for the insulating coupler.
2.7 R
 aise the terminal clamp (29.2)
against the step or the spacer (if
applicable) of the moving contact
Terminal clamp (29.2)
(36.1) of the vacuum interrupter
(30.0) so that the radius of the
movable contact faces the connecting
surface of the flexible connector Torque wrench
(29.1). Employ technique illustrated Direction of force (P)
to fasten terminal clamp (refer to
Figure 25). Note opposing wrenches.
Tighten the bolt(s) of the terminal Figure 25: Illustration showing required technique for fastening terminal-clamp hardware
clamp to a torque of 40 Nm (30 ft-lb),
taking care to see that the terminal of
the vacuum interrupter is not the vacuum interrupter in pole head
subjected to excessive bending by turning and moving it slightly.
movement. Torque M12 bolt to 60 Nm (44 ft-lb)
Note: Excessive bending movement and M16 bolt to 130 Nm (96 ft-lb).
exerted while fastening the terminal clamp 2.10 The centering ring (28.1) has been
will damage the vacuum interrupter. loose and "floating" during
2.8 A
 lign pole head (20.0) correctly and installation of the vacuum interrupter.
tighten bolt fastening it to the post Check that the movable contact is
insulator. Torque M16 bolt to 130 Nm free to move vertically without
(96 ft-lb). Fasten securely all bolts binding, and then tighten the
associated with struts (28.0). hardware which secures the
centering ring. Recheck that the
2.9 T
 ighten vacuum interrupter fastening movable contact is free to move
bolt (31.2) on the pole head (20.0) vertically without binding.
holding the vacuum interrupter firmly
by its upper insulator and operate 2.11 Attach insulating coupler (48.0) and
levers (48.6), by hand, to see whether lever (48.6) together, using pin
the movable contact moves freely. If (48.5). Apply retaining clips. Correct
any binding or lack of freedom is pin has ends that have been
noted, loosen bolt (31.2) and adjust generously chamfered.

47
Overhaul

2.12 Open and close circuit breaker several 5.  omplete all other maintenance
C
times and then check to see that all procedures. Completely reassembled
bolted joints and devices are tight. circuit breaker should pass the high-
potential test before it is ready for
3. C
 hecking the contact stroke
service.
3.1 Open the circuit breaker.
Hydraulic shock absorber
3.2 F
 ree insulating coupler (48.0) by
The mechanism is equipped with a
removing pin (48.5). The vacuum
hydraulic shock-absorber that functions
interrupter contacts must now close
when the circuit breaker opens (refer to
automatically as a consequence of
item 61.8 in Figure 6). The shock absorber
atmospheric pressure.
should require no adjustment. However, at
3.3 O
 bserve the terminal clamp (29.2) maintenance checks, the shock absorber
through the openings on each side of should be examined for evidence of
the pole bottom (40.0). Using vernier leaking. If evidence of fluid leakage is
calipers, measure the distance from found, the shock absorber must be
the bottom surface of the terminal replaced to prevent damage to the vacuum
clamp to the bottom edge of the interrupter bellows.
cutout opening. Measure carefully
and record your result.
3.4 C
 onnect the insulating coupler (48.0)
using pin (48.5) and the retaining
clips provided.
3.5 R
 epeat the measurement described in
step 3.3 again with care to maximize
accuracy. Record your result.
3.6 D
 etermine difference between the
measurements made under steps 3.3
and 3.5. Your results should be per
Table 7.
3.7 If you fail to achieve the listed results,
carefully repeat the entire procedure
making certain of your
measurements.
3.8 L oosen eye bolt locking nut on
insulating coupler (48.0), and retain
position of the eye. Make adjustments
in one-half turn increments. After
adjustment is completed, tighten eye
bolt locking nut to 26-34 ft-lb. (35-45
Nm).
4. A
 fter eye bolt is tightened to proper
torque, repeat all measurement
procedures, making certain they are
in agreement with values indicated in
step 3.6.

48
Maintenance and
Troubleshooting
Table 7 Vacuum interrupter stroke
Footnotes:
1.
The vacuum interrupter type
designation is labeled on the Rated maximum Interrupting Rated short- Vacuum Continuous Stroke2
vacuum interrupter. If the vacuum
voltage class circuit current interrupter current
interrupter installed does not
match that indicated in this table, kV MVA kA Type A mm
contact the nearest Siemens
4.76 250 29 kA@4.76 kV; VS-17006 1,200, 2,000 7-9
representative.
36 kA@3.85 kV VS-17040 1,200, 2,000 7-9
2.
If you need assistance achieving
the indicated stroke setting, 4.76 350 41 kA@4.76 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
contact the nearest Siemens 49 kA@4.0 kV
representative. 8.25 500 33 kA@8.25 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
41 kA@6.6 kV
15.0 500 18 kA@15.0 kV; VS-17006 1,200, 2,000 7-9
23 kA@11.5 kV
15.0 750 28 kA@15.0 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
36 kA@11.5 kV VS-17040 1,200, 2,000 7-9
15.0 1,000 37 kA@15.0 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
48 kA@11.5 kV
38.0 1,500 21 kA@38.0 kV; VS-30030 1,200, 2,000, 3,000 18-22
25 kA@23.0 kV
Rated maximum Interrupting Rated short- Vacuum Continuous Stroke2
voltage class circuit current interrupter current
kV kA kA Type A mm
4.76 31.5 31.5 kA@4.76 kV VS-17006 1,200, 2,000 7-9
VS-17040 1,200, 2,000 7-9
4.76 40 40 kA@4.76 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-17040 1,200, 2,000 7-9
4.76 50 50 kA@4.76 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
8.25 40 40 kA@8.25 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-17040 1,200, 2,000 7-9
15.0 20 20 kA@15.0 kV VS-17006 1,200, 2,000 7-9
15.0 25 25 kA@15.0 kV VS-17006 1,200, 2,000 7-9
15.0 31.5 31.5 kA@15.0 kV VS-17006 1,200, 2,000 7-9
VS-17040 1,200, 2,000 7-9
15.0 40 40 kA@15.0 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-17040 1,200, 2,000 7-9
15.0 50 50 kA@15.0 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.0 63 63 kA@15.0 kV VS-17085 1,200, 2,000, 3,000 10-11
15.5 20 20 kA@15.5 kV VS-25008 1,200, 2,000 15-16
15.5 25 25 kA@15.5 kV VS-25008 1,200, 2,000 15-16
15.5 31.5 31.5 kA@15.5 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.5 40 40 kA@15.5 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
27.6 20 20 kA@27.6 kV VS-25008 1,200, 2,000 15-16
27.6 25 25 kA@27.6 kV VS-25008 1,200, 2,000 15-16
38.0 20 20 kA@38.0 kV VS-30030 1,200, 2,000, 3,000 18-22
38.0 25 25 kA@38.0 kV VS-30030 1,200, 2,000, 3,000 18-22
38.0 31.5 31.5 kA@38.0 kV VS-30041 1,200, 2,000, 3,000 18-22
38.0 40 40 kA@38.0 kV VS-30041 1,200, 2,000, 3,000 18-22

49
Maintenance and
troubleshooting
Table 8: Troubleshooting

Problem Symptoms Possible causes and remedies


Circuit breaker fails to close. Closing spring will not 1. S
 econdary control circuit is de-energized or
automatically charge. control circuit fuses are blown. Check and
energize or replace if necessary.
2. S
 econdary multi-pin plug contacts A1 or
D16 are not engaging. Check and replace if
required.
3. D
 amage to wiring, terminals or connectors.
Check and repair as necessary.
4. F
 ailure of charging motor (88.0). Replace if
required.
5. M
 otor cut-off switch LS21 or LS22 fails to
operate. Replace if necessary.
6. M
 echanical failure of operating
mechanism. Check and contact the factory
or Siemens field service at +1 (800) 347-
6659 or +1 (919) 365-2200 outside the
U.S.
Closing springs charge Closing coil or solenoid 1. S
 econdary control circuit de-energized or
but circuit breaker does (52SRC) fails to control circuit fuses blown. Correct as
not close. energize. No sound of indicated.
circuit breaker closing.
2. N
 o closing signal to secondary disconnect
pin A2. Check for continuity and correct
protective relay logic.
3. S
 econdary disconnect contacts 13 or 15 are
not engaging. Check and correct as
required.
4. F
 ailure of anti-pump relay (52Y) contacts
21 to 22, 31 to 32 or 13 to 14. Check and
replace as required.
5. F
 ailure of close coil (solenoid) (52SRC).
Check and replace as required.
6. A
 uxiliary switch NC contacts 41 to 42 are
open when circuit breaker contacts are
open. Check linkage and switch. Replace or
adjust as necessary.
Closing coil energizes. 1. M
 echanical failure of operating
Sound of circuit breaker mechanism. Check and contact the factory
closing is heard, but or Siemens field service at +1 (800) 347-
circuit breaker contacts 6659 or +1 (919) 365-2200 outside the
do not close. U.S.

50
Maintenance and
troubleshooting
Table 8: Troubleshooting (continued)

Problem Symptoms Possible causes and remedies


Nuisance or false close Electrical problem 1. N
 uisance or false closing signal to
secondary disconnect multi-pin plug
contact. Check protective relay logic.
Correct as required.

2. C
 losing coil (52SRC) terminal A2 is
shorted-to-ground. Check to determine
if problems are in wiring or coil. Correct
as required.
Mechanical problem 1. M
 echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
Circuit breaker will not trip Tripping coil or solenoid (52T) does not 1. S
 econdary control power is de-
energize. There is no tripping sound. energized or control power fuses are
blown. Correct as indicated.

2. D
 amage to wiring, terminals or
connectors. Check and repair as
necessary.

3. N
 o tripping signal to secondary
disconnect contact C2. Check for
continuity and correct protective relay
logic.

4. S
 econdary multi-pin plug contacts C1 or
D2 are not engaging. Check and replace
if required.

5. F
 ailure of trip coil (52T). Check and
replace if necessary.

6. A
 uxiliary switch 52a NO contacts 23 to
24 or 33 to 34 are open when circuit
breaker is closed. Check linkage and
switch. Replace or adjust as necessary.
Tripping coil (52T) energizes. No tripping 1. F
 ailure of tripping spring or its
sound is heard, and circuit breaker contacts mechanical linkage. Check and replace
do not open. In other words, they remain if required.
closed.
Tripping coil (52T) energizes. Tripping 1. M
 echanical failure of operating
sound is heard, but circuit breaker contacts mechanism. Check and contact the
do not open. factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.

2. O
 ne or more of the vacuum interrupters
are held closed. Check and replace as
necessary.

51
Maintenance and
troubleshooting
Table 8: Troubleshooting (continued)

Problem Symptoms Possible causes and remedies


Nuisance or false trip Electrical problem 1. T
 ripping signal remains energized on
secondary multi-pin plug contact C2.

2. C
 heck for improper protective relay
logic.
Mechanical problem 1. M
 echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.

52
Appendix

Table 9: Circuit breaker control data

ANSI/IEEE C37.06 control voltages Close coil Trip coil Spring charging motor
Nominal Range Run Inrush Charging
(Average)1 (Peak)
Close Trip A1 A1 A A Seconds

24 Vdc 19 - 28 14 - 28 5.8 17/---- ---- ---- ----

48 Vdc 36 - 56 28 - 56 2.9 11.4/303 8 25 10

125 Vdc 100 - 140 70 - 140 1.0 4.8/7.43 4 18 10

250 Vdc 200 - 280 140 - 280 0.5 2.1/4.23 2 10 10

120 Vac 104 - 127 104 - 127 0.9 ----2 6 ---- 10

240 Vac 208 - 254 208 - 254 0.4 ----2 3 ---- 10

Footnotes:
1.
 urrent at nominal voltage
C
2.
 apacitor trip
C
3.
Value preceding slash (/) is the current for
the standard trip coil with standard rating
interrupting time. Value following (/) is
current for optional trip coil with three-cycle
interrupting time.
4.
---- means this selection is not available at this
voltage.

Table 10: Interrupting capacity auxiliary switch contacts2

Type of circuit Continuous current Control circuit voltage


amperes
120 Vac 240 Vac 48 Vdc 125 Vdc 250 Vdc

Non-inductive 10 10 5 10/301 9.6 4.8

Inductive 10 6 3 10 6 3

Footnotes:
1.
 wo contacts in series.
T
2.
 ll switches are non-convertible.
A

53
Appendix

These ratings are in accordance Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis)
with:
Circuit Maximum Voltage Withstand voltage Continuous Short-circuit
 NSI/IEEE C37.04-1999
A breaker type design range levels current7 (I)3,4
standard rating structure for voltage factor
ac high-voltage circuit (V)1 (K)2
breakers
kV rms Power Lightning A rms kA rms sym
 NSI/IEEE C37.06-2009 AC
A frequency impulse
high-voltage circuit breakers kV rms (BIL)
kV crest
rated on a symmetrical
current basis - preferred 1,200, 2,000,
5-3AH-31.5 4.76 1.0 19 60 31.5
ratings and related required 3,000
capabilities for voltages 5-3AH-40 4.76 1.0 19 60
1,200, 2,000,
40
above 1,000 volts 3,000
1,200, 2,000,
 NSI/IEEE C37.09-1999
A 5-3AH-50 4.76 1.0 19 60 50
3,000
standard test procedure for
1,200, 2,000,
ac high-voltage circuit 5-3AH-63 4.76 1.0 19 60 63
3,000
breakers rated on a
symmetrical current basis 1,200, 2,000,
7-3AH-40 8.25 1.0 36 95 40
3,000
 NSI/IEEE C37.010-1999
A
application guide for ac high- 15-3AH-20 15.0 1.0 36 95 1,200, 2,000 20
voltage circuit breakers rated
on a symmetrical current 15-3AH-25 15.0 1.0 36 95 1,200, 2,000 25
basis. 1,200, 2,000,
15-3AH-31.5 15.0 1.0 36 95 31.5
Footnotes: 3,000
1.
Maximum design voltage for which 1,200, 2,000,
15-3AH-40 15.0 1.0 36 95 40
the circuit breaker is designed and 3,000
the upper limit for operation.
1,200, 2,000,
2.
K is listed for information purposes 15-3AH-50 15.0 1.0 36 95 50
3,000
only. For circuit breakers rated on
a "constant kA" ratings basis, the 1,200, 2,000,
15-3AH-63 15.0 1.0 36 95 63
voltage range factor is 1.0. 3,000
3.
All values apply to polyphase and
15.5-3AH-20 15.5 1.0 50 110 1,200, 2,000 20
line-to-line faults.
4.
Standard duty cycle is O - 0.3 s - CO
- 3 min. - CO. 15.5-3AH-25 15.5 1.0 50 110 1,200, 2,000 25
5.
Standard rating interrupting time is
five-cycles (83 ms). Optional rated
1,200, 2,000,
15.5-3AH-31.5 15.5 1.0 50 110 31.5
interrupting time of three-cycles (50
3,000
ms) is available (except with 24 Vdc 1,200, 2,000,
15.5-3AH-40 15.5 1.0 50 110 40
tripping). 3,000
6.
150 kV BIL is for drawout
applications. 200 kV BIL is for type 27-3AH-20 27.6 1.0 60 150 1,200, 2,000 20
SDV6 with appropriate construction.
7.
Continous current capability 27-3AH-25 27.6 1.0 60 150 1,200, 2,000 25
may be increased by the use of
forced-cooling (fan-cooling) in the 1,200, 2,000,
switchgear together with increased 38-3AH-20 38.0 1.0 80 150/2006 20
3,000
bus bar capacity.
1,200, 2,000,
38-3AH-25 38.0 1.0 80 150/2006 25
3,000
1,200, 2,000,
38-3AH-31.5 38.0 1.0 80 150/2006 31.5
3,000
1,200, 2,000,
38-3AH-40 38.0 1.0 80 150/2006 40
3,000

54
Appendix

Interrupting Permissible Max. sym. % dc Short-time Closing and latching Circuit


time5 tripping delay interrupting component current (I) (3 (momentary) breaker type
(y) (I) s)

ms / cycles s kA rms sym % kA rms Asymmetrical Peak


(1.55 x I) (2.6 x I)
kA rms kA peak

83 / 5 2 31.5 47 31.5 49 82 5-3AH-31.5

83 / 5 2 40 47 40 62 104 5-3AH-40

83 / 5 2 50 47 50 78 130 5-3AH-50

83 / 5 2 63 47 63 98 164 5-3AH-63

83 / 5 2 40 47 40 62 104 7-3AH-40

83 / 5 2 20 47 20 31 52 15-3AH-20

83 / 5 2 25 47 25 39 65 15-3AH-25

83 / 5 2 31.5 47 31.5 49 82 15-3AH-31.5

83 / 5 2 40 47 40 62 104 15-3AH-40

83 / 5 2 50 47 50 78 130 15-3AH-50

83 / 5 2 63 47 63 98 164 15-3AH-63

83 / 5 2 20 47 20 31 52 15.5-3AH-20

83 / 5 2 25 47 25 39 65 15.5-3AH-25

83 / 5 2 31.5 47 31.5 49 82 15.5-3AH-31.5

83 / 5 2 40 47 40 62 104 15.5-3AH-40

83 / 5 2 20 47 20 31 52 27-3AH-20

83 / 5 2 25 47 25 39 65 27-3AH-25

83 / 5 2 20 47 20 31 52 38-3AH-20

83 / 5 2 25 47 25 39 65 38-3AH-25

83 / 5 2 31.5 47 31.5 49 82 38-3AH-31.5

83 / 5 2 40 47 40 62 104 38-3AH-40

55
Appendix

Table 12:Type 3AH vacuum


Circuit Nominal Nominal Maximum Continuous Voltage Withstand voltage
circuit breaker ratings (historic
"constant MVA" ratings basis) breaker voltage three- design current11 range levels
type class phase voltage factor
These ratings are in MVA (V)1 (K)2
accordance with: class7

 NSI/IEEE C37.04-1979
A
standard rating structure for kV MVA kV rms A rms ---- Power Lightning
ac high-voltage circuit frequency impulse
breakers rated on a kV rms (BIL)
symmetrical current basis kV crest

 NSI C37.06-1987 ac high-


A
5-3AH-250 4.16 250 4.76 1,200, 2,000 1.24 19 60
voltage circuit breakers
rated on a symmetrical
current basis - preferred 1,200, 2,000,
ratings and related required 5-3AH-350 4.16 350 4.76 1.19 19 60
3,000
capabilities
 NSI/IEEE C37.09-1979
A 1,200, 2,000,
7-3AH-500 7.2 500 8.25 1.25 36 95
standard test procedure for 3,000
ac high-voltage circuit
breakers rated on a 1,200, 2,000,
15-3AH-500 13.8 500 15.0 1.30 36 95
symmetrical current basis 3,000

 NSI/IEEE C37.010-1979
A
application guide for ac 1,200, 2,000,
15-3AH-750 13.8 750 15.0 1.30 36 95
high-voltage circuit breakers 3,000
rated on a symmetrical
current basis. 1,200, 2,000,
15-3AH-1000 13.8 1000 15.0 1.30 36 95
3,000

38-3AH-1500 38.0 1,500 38.0 1,200, 2,000 1.65 80 150

Footnotes: 3.
To obtain the required symmetrical interrupting
1.
Maximum design voltage for which the circuit capability of a circuit breaker at an operating
breaker is designed and the upper limit for voltage between 1/K times rated maximum
operation. design voltage and rated maximum design
2.
K is the ratio of the rated maximum design voltage, the following formula shall be used:
voltage to the lower limit of the range of Required symmetrical interrupting capability =
operating voltage in which the required rated short-circuit current (I) x [(rated maximum
symmetrical and asymmetrical interrupting design voltage)/(operating voltage)]. For
capabilities vary in inverse proportion to the operating voltages below 1/K times maximum
operating voltage. design voltage, the required symmetrical
interrupting capability of the circuit breaker shall
be equal to K times rated short-circuit current.
4.
Within the limitations stated in
ANSI/IEEE C37.04-1979, all values apply to
polyphase and line-to-line faults. For single
phase-to-ground faults, the specific conditions
stated in clause 5.10.2.3 of
ANSI/IEEE C37.04-1979 apply.

56
Appendix

Short- Interrupting Permissible Rated Maximum Short-time Closing and latching Circuit
circuit (at time9 tripping maximum symmetrical current (I) (momentary) breaker
rated delay (y) design interrupting (three type
maximum voltage (V) (K x I)5 seconds)
design divided by
voltage) K
(I)3, 4, 8 (= V/K)
kA rms sym ms / cycles Sec kA rms kA rms sym kA rms Asymmetrical Peak
(1.6 x (2.7 x
K x I)6 K x I)6
kA rms kA peak

29 83 / 5 2 3.85 36 36 58/7810 97/13210 5-3AH-250

41 83 / 5 2 4.0 49 49 78 132 5-3AH-350

33 83 / 5 2 6.6 41 41 66/7710 111/13010 7-3AH-500

18 83 / 5 2 11.5 23 23 37/5810 62/9710 15-3AH-500

28 83 / 5 2 11.5 36 36 58/7710 97/13010 15-3AH-750

37 83 / 5 2 11.5 48 48 77 130 15-3AH-1000

21 83/5 2 23.0 35 35 56 95 38-3AH-1500

5.
Current values in this row are not to be 9.
 tandard rating interrupting time is five-cycles
S
exceeded even for operating voltage below (83 ms). Optional rated interrupting time of
1/K times rated maximum design voltage. For three-cycles (50 ms) is available (except with
operating voltages between rated maximum 24 Vdc tripping).
design voltage and 1/K times rated maximum 10.
High close and latch (momentary) rating
design voltage, follow Footnote 5. available for special application.
6.
Current values in this row are independent of 11.
Continuous current may be increased by the
operating voltage up to and including rated use of forced-cooling (fan-cooling) in the
maximum voltage. switchgear, together with increased bus bar
7.
"Nominal three-phase MVA class" is included for capacity.
reference only. This information is not listed in
ANSI C37.06-1987.
8.
Standard duty cycle is O - 15 s - CO.

57
Appendix

Table 13: Type 3AH vacuum circuit breaker weight in lbs (kg) (circuit breaker
operator only)

Circuit breaker type Weight in lbs (kg)1

Maximum Interrupting Continuous current


voltage kV capability kA
(MVA) 1,200 A 2,000 A 3,000 A
symmetrical)
4.76 31.5 (250) 242 (110) 264 (120) ----
4.76 40 246 (112) 268 (122) 390 (177)
4.76 50 (350) 330 (150) 363 (165) 396 (180)
8.25 40 (500) 246 (112) 268 (122) 390 (177)
15.0 20 (500) 165 (75) 257 (117) ----
15.0 25 165 (75) 257 (117) ----
15.0 31.5 (750) 242 (110) 264 (120) ----
15.0 40 246 (112) 268 (122) 390 (177)
15.0 50 (1,000) 330 (150) 363 (165) 396 (180)
15.5 20 262 (119) 278 (126) ----
15.5 25 273 (124) 298 (131) ----
15.5 31.5 298 (135) 313 (142) 385 (175)
15.5 40 309 (140) 324 (147) 390 (177)
27.6 20 276 (125) 291 (132) ----
27.6 25 287 (130) 302 (137) ----
38.0 20 353 (160) 375 (170) 386 (175)
38.0 25 353 (160) 375 (170) 386 (175)
38.0 31.5 363 (165) 385 (175) ----
38.0 40 375 (170) 397 (180) 408 (185)

Footnote:
1.
Add 100 lbs (45 kg) for packaging.

58
Appendix

Table 14: Circuit breaker operating times (type 3AH3 operator)

Spring charging time ≤ 10 s


Up to 15.5 kV ≤ 55 ms
Close time from energizing close coil at rated
Over 15.5 kV up to 27.6 kV ≤ 65 ms
control voltage to contact touch (last pole)
Over 27.6 kV up to 38 kV ≤ 70 ms
Up to 15.5 kV ≤ 56 ms
5-cycle interrupting time
Over 15.5 kV up to 27.6 kV ≤ 56 ms
(83 ms)
Over 27.6 kV up to 38 kV ≤ 56 ms
Opening time from
energization trip coil at rated Up to 15.5 kV ≤ 43 ms
3.5-cycle interrupting time
control voltage to contact part Over 15.5 kV up to 27.6 kV ≤ 43 ms
(58 ms)
(last pole), not including Over 27.6 kV up to 38 kV ≤ 43 ms
arcing time
Up to 15.5 kV ≤ 38 ms
3-cycle interrupting time
Over 15.5 kV up to 27.6 kV ≤ 38 ms
(50 ms)
Over 27.6 kV up to 38 kV ≤ 38 ms

59
Published by and copyright © 2010:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany

Siemens Energy, Inc.


7000 Siemens Road
Wendell, North Carolina 27591 USA

For more information, contact


+1 (800) 347-6659

Order No. E50001-F710-A251-X-4A00


Replaces No. E50001-U229-A278-X-US00
Printed in USA

All rights reserved.


Trademarks mentioned in this document
are the property of Siemens AG, its affiliates
or their respective owners.

Subject to change without prior notice.


The information in this document contains
general descriptions of the technical options
available, which may not apply in all cases.
The required technical options should therefore
be specified in the contract.

www.usa.siemens.com/energy

You might also like