Professional Documents
Culture Documents
16 kV to 38 kV
vacuum circuit breaker operator module
instruction manual
Installation operation maintenance E50001-F710-A251-X-4A00
2
Table of contents
Introduction 4 -5
Note:
These instructions do not purport to cover
Receiving, handling and storage 6 -8 all details or variations in equipment, nor
to provide for every possible contingency
to be met in connection with installation,
operation or maintenance. Should further
Installation checks and functional tests 9 - 10
information be desired or should particular
problems arise that are not covered
sufficiently for the purchaser’s purposes,
Vacuum interrupter/operator 11 - 28
the matter should be referred to the local
sales office.
3
Introduction
4
Introduction
5
Receiving, handling and
storage
Heavy weight.
Improper lifting or hoisting can result in death, serious injury
or property damage.
Obtain the services of a qualified rigger prior to hoisting the
circuit breaker to assure adequate safety margins in the hoisting
equipment and procedures to avoid damage.
6
Receiving, handling and
storage
3. A
ny visible damage must be noted on 8. O
btain the original carrier inspection
the delivery receipt and acknowledged report and forward it with a copy of the
with the driver’s signature. The noted delivery receipt to Siemens.
damage should be detailed as much as Approval must be obtained by Siemens
possible. It is essential that a notation from the carrier before any repair work
"possible internal damage, subject to can be performed.
inspection" be included on the delivery
efore approval can be obtained,
B
receipt. If the driver will not sign the
Siemens must have the documents
delivery receipt with the damage
referenced in the paragraph above. The
noted, the shipment should not be
carrier inspection report and/or driver’s
signed for by the consignee or their
signature on the delivery receipt does
agent.
not constitute approval to repair.
4. N
otify Siemens medium-voltage
Note: Any determination as to whether the
customer service immediately of any
equipment was properly loaded or properly
damage, at +1 (800) 347-6659 or
prepared by shipper for over-the-road
+1 (919) 365-2200 outside the U.S.
travel cannot be made at the destination.
5. Arrange for a carrier inspection of the Shipments are not released from the
damage immediately. factory without a clear bill of lading.
Approved methods are employed for
Important: Do not move the equipment
preparation, loading, blocking and tarping
from the place it was set when unloading.
of the equipment before it leaves the
Also, do not remove or disturb packaging
Siemens factory. If the equipment is
or wrapping material prior to carrier
received in a damaged condition, this
damage inspection. Equipment must be
damage to the equipment has to have
inspected by carrier prior to handling after
occurred while en route due to conditions
receipt. This eliminates loss due to claims
beyond Siemens‘ control. If the procedure
by carrier that the equipment was
outlined above is not followed by the
damaged or further damaged on site after
consignee, purchaser or their agent,
unloading.
Siemens cannot be held liable for repairs.
6. Be sure the equipment is properly Siemens will not be held liable for repairs
protected from any further damage by in any case where repair work was
covering it properly after unloading. performed prior to authorization from
Siemens.
7. If practical, make further inspection for
possible concealed damage while the
carrier’s inspector is on site. If
inspection for concealed damage is not
practical at the time the carrier’s
inspector is present, it must be done
within 15 days of receipt of the
equipment. If concealed damage is
found, the carrier must again be
notified and inspection made prior to
taking any corrective action to repair.
Also notify Siemens immediately at
+1 (800) 347- 6659 or
+1 (919) 365-2200 outside the U.S.
7
Receiving, handling and
storage
Handling procedure Indoor storage
1. C
arefully remove the shipping carton Whenever possible, store the circuit
from the circuit breaker. Keep the breaker indoors. The storage environment
shipping pallet for later use if the must be clean, dry and free of such items
circuit breaker is to be stored prior to as construction dust, corrosive
its installation. atmosphere, mechanical abuse and rapid
temperature variations.
2. Inspect for concealed damage.
Notification to carrier must take place Outdoor storage
within 15 days to assure prompt claim
Outdoor storage is not recommended.
resolution.
When no other option is available, the
3. E
ach circuit breaker should be lifted circuit breaker must be completely covered
appropriately to avoid crushing the side and protected from rain, snow, dirt and all
panels of the circuit breaker, or other contaminants.
damaging the primary disconnect
Space heating
assemblies. Refer to Table 13 for circuit
breaker weights. Space heating must be used for both
indoor and outdoor storage to prevent
4. T
he palleted circuit breaker can be
condensation and corrosion. When
moved using a properly rated fork-lift
equipment is stored outdoors, 250 watts
vehicle. The pallets are designed for
per circuit breaker of space heating is
movement by a standard fork-lift
recommended. If the circuit breaker is
vehicle.
stored inside the switchgear enclosure and
Storage procedure the switchgear is equipped with space
heaters, energize the space heaters.
1. W
henever possible, install the circuit
breaker in its assigned switchgear
enclosure or end location for storage.
2. W
hen the circuit breaker needs to be
placed on its pallet for storage, be sure
the unit is securely bolted to the pallet
and covered with polyethylene film at
least 10 mils thick.
8
Installation checks and
functional tests
Introduction Spring-discharge check (refer to
Figure 1)
This section provides a description of the
inspections, checks and tests to be Perform the spring-discharge check before
performed on the circuit breaker module removing the circuit breaker from the
only. pallet or removing it from the switchgear.
Inspections, checks and tests without The spring discharge check should be
control power performed after de-energizing control
power. This check assures both the tripping
Vacuum circuit breakers are normally
and closing springs are fully discharged.
shipped with their primary contacts open
and their springs discharged. However, it is Note: Do not perform the spring-discharge
critical to first verify the discharged check if the circuit breaker is in the
condition of the spring-loaded CONNECT position. Open the circuit
mechanisms after de-energizing control breaker and rack to the DISCONNECT
power. position, and then perform the spring-
discharge check. For fixed-mounted circuit
De-energizing control power in
breaker applications, open the isolator
switchgear
switches on the line side and on the load
When the circuit breaker is mounted in side of the circuit breaker before
switchgear, open the control-power performing the spring-discharge check.
disconnect device in the metal-clad
1. Press red Trip pushbutton.
switchgear cubicle, outdoor circuit breaker
housing or other location. 2. Press black Close pushbutton.
In metal-clad switchgear, the control- 3. Press red Trip pushbutton again.
power disconnect device is normally
4. V
erify spring-condition indicator shows
located on the secondary-device panel in
DISCHARGED.
the upper cell of the vertical section. The
normal control-power disconnect device is 5. V
erify main contact status indicator
a pullout-type fuse holder. Removal of the shows OPEN.
fuse holder de-energizes control power to
the circuit breaker in the associated
switchgear cell. In some switchgear
assemblies, a molded-case circuit breaker
or knife switch is used in lieu of the
pullout-type fuse holder. Opening this
circuit breaker or switch accomplishes the
same result: control power is
disconnected.
9
Installation checks and
functional tests
Manual-spring charging check 1. O
pen control-power circuit by
opening the control power-
1. Insert the manual-spring charging
disconnect device.
crank into the manual-charge handle
socket (refer to Figure 1). Turn the 2. E
nergize (close) the control power-
crank clockwise (about 48 revolutions) circuit disconnect.
until the spring-condition indicator
3. U
se the Close and Open controls
shows the closing spring is CHARGED.
(refer to Figure 1) to first Close and
2. Repeat the spring-discharge check. then Open the circuit breaker
contacts. Verify contact positions
3. V
erify the springs are DISCHARGED and
visually by observing the OPEN/
the circuit-breaker primary contacts are
CLOSED indicator on the circuit
OPEN by indicator positions.
breaker.
As-found and vacuum-integrity check
4. D
e-energize control power by
tests
repeating Step 1. If a split-plug
Perform and record the results of both the
jumper was used for temporary
as-found insulation test and the vacuum-
control-power connections,
integrity check (dielectric) test. Procedures
disconnect the split-plug jumper from
for these tests are described in the
the switchgear first and next from
Maintenance section of this instruction
the circuit breaker.
manual beginning on page 29.
5. P
erform the spring-discharge check
Automatic spring-charging check
again. Verify that the closing spring is
The automatic spring-charging features
discharged and the primary contacts
of the circuit breaker must be checked.
of the circuit breaker are open.
Control power is required for
automatic spring charging to take place. Final mechanical inspections without
control power
Note: A temporary source of control 1. Make a final mechanical inspection of
power and test leads may be required if the circuit breaker. Verify the contacts
the control-power source has not been are in the open position, and the
connected to the switchgear or circuit closing spring is discharged.
breaker. Refer to the specific wiring
2. V
erify mechanical condition of
information and rating label for your
springs.
circuit breaker to determine the voltage
required and where the control-voltage 3. Check for loose hardware.
signal should be applied. When control
power is connected to the circuit breaker,
the closing spring should automatically
charge.
10
Vacuum interrupter/
operator
Introduction
The type 3AH vacuum circuit-breaker
operator is intended for application in a
drawout truck for use in medium-voltage
metal-clad switchgear and for stationary
applications, such as the type SDV6
outdoor distribution circuit breaker. The
type 3AH circuit breaker conforms to the
requirements of ANSI/IEEE standards,
including C37.20.2, C37.04, C37.06, Rating plate
C37.09 and C37.010.
11
Vacuum interrupter/
operator
When the two contacts separate, an arc
is initiated that continues conduction up
to the following current zero. At current
Fixed contact-current connection zero, the arc extinguishes and any
Ceramic insulator
conductive metal vapor that has been
created by and supported the arc
condenses on the contacts and on the
surrounding arc shield. Contact materials
Arc shield and configuration are optimized to
Fixed contact achieve arc motion and to minimize
Moving contact switching disturbances.
13
Vacuum interrupter/
operator
4. O perate all these functions
Pole head Upper post insulator
automatically through an electrical
Upper Operator housing charging motor, cutout switches, an
connection anti-pump relay, a close coil, an open
pad
coil and an auxiliary switch.
5. Provide indication of the circuit
breaker status (OPEN/CLOSED), spring
condition (CHARGED/DISCHARGED)
Strut and number of operations.
Vacuum
interrupter Construction
Moving The essential parts of the operating
contact mechanism are shown in Figures 6 and
Centering Lever 7. The control and sequence
piece of operation of the mechanism is
Jack
shaft described in Figure 8.
Terminal
clamp
Flexible
Motor-operating mechanism (refer to
connector Figure 6)
Eye bolt The spring-charging motor (50.4) is
Pole bottom bolted to the charging mechanism (50.2)
Insulating Contact pressure
coupler (48.0) spring (49.0) gear box installed in the operator
housing. Neither the charging
Angled lever Guide link Lower post insulator mechanism nor the motor require any
maintenance.
Figure 5: Pole assembly
Mode of operation
The operating mechanism is of the
When a opening command is given, the
stored-energy trip-free type. For
energy stored in the opening and contact
example, the charging of the closing
pressure springs (49.0) is released by
spring is not automatically followed by
pawl (64.2) (refer to Figure 7). The
the contacts changing position, and
opening sequence is similar to the
tripping function prevails over the
closing sequence. The residual force of
closing function.
the opening spring maintains the moving
contacts in the open position.
When the stored-energy mechanism has
been charged, the mechanism is ready
Operating mechanism
for a closing operation at any time.
The operating mechanism is comprised
The mechanical energy for carrying out
of the mechanical and electrical
an "Open-Close-Open" sequence for
components required to:
auto-reclosing duty is stored in the
1. Charge the closing spring with
closing and opening springs.
sufficient potential energy to close
the circuit breaker and to store
Charging
opening energy in the opening and
The details of the closing spring charging
contact pressure springs.
mechanism are shown in Figure 6. The
2. Mechanisms to release closing and
charging shaft is supported in the
opening actions.
charging mechanism (50.2), but is not
3. Means of transmitting force and
coupled mechanically with the charging
motion to each of the three vacuum
mechanism. Fitted to it are the crank
interrupters.
(62.2) at one end, and the cam (62.3),
together with lever (62.5), at the other.
14
Vacuum interrupter/
operators
Figure 6: Stored-energy operating mechanism (circuit breaker shown in OPEN position) (straight linkage shown)
62.1
62.5.2
62.2
68.0
53.0
55.1
62.0
53.1
50.4.1
54.1
55.0
54.0
50.4
68.1
64.0
58.0
59.0
50.2 - Charging mechanism gear box 58.0 - CLOSE/OPEN indicator 62.8.3 - Trip-free coupling lever*
50.3 - Charging flange 59.0 - Operations counter 63.0 - Jack shaft
50.3.1 - Driver (not visible) 60.0 - Operator housing 63.1 - Lever - phase C
50.4 - Spring-charging motor 88 61.8 - Shock absorber 63.5 - Lever - phase B
50.4.1 - Limit switches 62.0 - Closing spring 63.7 - Lever - phase A
50.5 - Manual spring-charging port 62.1 - Charging shaft 64.0 - Opening spring
53.0 - Close pushbutton 62.2 - Crank 68.0 - Auxiliary switch
53.1 - Close coil 52SRC 62.3 - Cam disc 68.1 - Auxiliary switch link
54.0 - Open pushbutton 62.5 - Lever
54.1 - Trip coil 52T 62.5.1 - Pawl roller (not visible) * For certain applications, the straight trip
55.0 - Closing spring-charge 62.5.2 - Close latch pawl coupling rod (62.8) is replaced by a
indicator 62.6 - Driver lever collapsible trip-free coupling system,
55.1 - Linkage 62.8 - Straight coupling rod* illustrated in Figures 7-11.
55.2 - Control lever 62.8.1 - Spring return latch (not shown)*
15
Vacuum interrupter/
operator
Closing (refer to Figures 6-11)
If the circuit breaker is to be closed
62.8.1 manually, the closing spring is released
by pressing the Close button (53.0). In
62.8.2
the case of remote electrical control, the
close coil 52SRC (53.1) unlatches the
62.8
closing spring (62.0).
54.0
As the closing spring discharges, the
charging shaft (62.1) is turned by crank
(62.2). The cam disc (62.3) at the other
64.3.1
end of the charging shaft actuates the
64.3 drive lever (62.6), with the result that
jack shaft (63.0) is turned by lever (63.5)
via the coupling rod (62.8). At the same
time, the levers (63.1), (63.5) and (63.7)
fixed on the jack shaft operate the three
54.0 - Open pushbutton *For type SDV6 and some fixed-
62.8 - Trip-free coupling rod* mounted circuit breakers, trip-free insulating couplers (48.0) (refer to
62.8.1 - Spring-return latch* coupling rod (62.8) is replaced Figure 5) for the circuit breaker poles.
62.8.2 - Trip-free coupling link with a straight coupling rod, and Lever (63.7) changes the OPEN/CLOSE
(draw bar)* other parts associated with indicator (58.0) over to OPEN. Lever
64.2 - Trip-latch pawl (not visible) drawout interlocking are (63.5) charges the opening spring (64.0)
64.3 - Lever eliminated.
64.3.1 - Pawl roller
during closing, and the circuit breaker is
latched in the closed position by lever
(64.3) with pawl roller (64.3.1) and by
pawl (64.2). Lever (63.1) actuates the
Figure 7: Stored energy operating mechanism (circuit breaker shown in CLOSED position)
(Drawout trip-free linkage shown)
auxiliary switch (68.0) through the
linkage (68.1).
16
Vacuum interrupter/
operator
Trip-free operation The parts modified or eliminated are
(refer to Figures 6 and 7) noted in the relevant figures. In these
Trip-free for all drawout circuit circuit breakers, the trip-free function is
breakers and some fixed-mounted accomplished by blocking the movement
circuit breakers of the close latch pawl (62.5.2) when the
The trip coupling rod (62.8 together with manual trip pushbutton is actuated.
62.8.1 and 62.8.2) permits the
immediate de-coupling of the drive lever Opening (refer to Figure 6)
(62.6) and the jack shaft (63.0) to If the circuit breaker is to be opened
override closing action by trip command manually, the opening spring (64.0) is
or by means of the racking interlocks. released by pressing the OPEN
The trip-free coupling rod (62.8) forms a pushbutton (54.0). In the case of an
link between the drive lever (62.6) and electrical command being given, the trip
the jack shaft (63.0). The rigidity of this coil 52T (54.1) unlatches the opening
link depends upon a spring-return latch spring (64.0).
(62.8.1) carried within the coupling rod.
The latch pivots within the coupling rod The opening spring (64.0) turns the jack
and is normally positioned to ensure the shaft (63.0) via lever (63.5); the
rigidity of the coupling rod. Trip-free sequence being similar to that for
coupling link (62.8.2) and trip-free closing.
coupling lever (62.8.3) cause the spring-
return latch position to be dependent Rapid auto-reclosing
upon the normal tripping components Since the closing spring is automatically
and the racking interlock. Thus, recharged by the motor operating
whenever a trip command is applied or mechanism when the circuit breaker has
the circuit breaker is not in the fully closed, the operating mechanism is
CONNECT or TEST position, the trip-free capable of an "Open-Close-Open" duty
coupling rod is no longer rigid, cycle as required for rapid auto-reclosing.
effectively decoupling the drive lever and
jack shaft. Under these conditions the The circuit breaker is suitable for use in
vacuum interrupter contacts cannot be applications with a rated reclosing-time
closed. interval of 0.3 seconds, per ANSI/IEEE
C37.06-2009.
Trip-free for the type SDV6 outdoor
distribution circuit breaker and some Manual operation
fixed-mounted circuit breakers Electrically operated vacuum circuit
For the type SDV6 outdoor distribution breakers can be operated manually if the
circuit breaker and some other fixed- control supply should fail.
mounted circuit breakers, the drawout
trip-free linkage (refer to Figures 7-11) is
replaced with simplified linkage. The
trip-free coupling rod (62.8) is replaced
with a straight coupling rod (refer to
Figure 6), and other parts associated
with drawout interlocking are eliminated.
17
Vacuum interrupter/
operator
Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
62.8.8
18
Vacuum interrupter/
operator
Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
.
19
Vacuum interrupter/
operator
Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring DISCHARGED
64.5
63.5
62.8
63.7
63.5
63.1
48.0
63.0
63.5
20
Vacuum interrupter/
operator
Figure 11: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring CHARGED
21
Vacuum interrupter/
operator
Manually charging the closing spring
(refer to Figures 13 and 14)
Insert the hand crank (50.0) with the
The special hand crank automatically over running coupling pushed forward
disengages if the spring-charging motor (50.6) through the opening (50.1) onto
operates. In order to avoid injuries as a
hand crank coupling (50.5) and turn it
result of the motor suddenly starting up,
the circuit breaker spring must only be clockwise (about 48 revolutions) until
charged manually with the special hand the closing-spring indicator (55.0) shows
crank (50.0). CHARGED. The hand crank is coupled
with the charging mechanism via an
over-running coupling; thus the operator
is not exposed to any risk should the
control supply be restored during manual
charging.
22
Vacuum interrupter/
operator
Figure 12: Operator sequential operation diagram
Closing Control Anti-pumping feature (52Y) assures a continuously applied closing command
voltage applied. does not cause the circuit breaker to reclose automatically after it has tripped
out on a fault.
Trip coil (52T) can Undervoltage device (27) is Undervoltage device (27) is activated Secondary shunt-
only be activated activated by opening a NC by closing NO contact, shorting the release (dual-trip)
when series contact in series with 27 or by 27 coil. The NO contact is only function activated by
connected 52a loss or reduction of tripping effective with the circuit breaker remote trip
contact is closed. voltage.1 closed. Resistor required.1 command contact
NO.1
23
Vacuum interrupter/
operator
The schematic shown in Figure 15 is
intended to aid in understanding the
50.1 53.0 mechanism operation discussed in this
instruction manual. It shows a drawout
circuit breaker as an example. Refer to the
50.0
schematic diagram furnished with your
circuit breaker for specific information.
Close coil (52SRC)
55.0 54.0 The close coil (3AY1510) is a standard
component of the circuit breaker that is
used to unlatch the stored energy of the
closing spring and thus close the circuit
breaker electrically. It is available for either
ac or dc operation. After completion of a
closing operation, the close coil is de-
energized internally. If operated with ac
voltage, a rectifier is installed in the circuit
50.0 - Hand crank breaker.
50.1 - Manual spring-charging port Trip coil (52T)
53.0 - Manual CLOSE button
The trip coil (3AY1510) is a standard
54.0 - Manual OPEN (TRIP) button component of the circuit breaker. The
55.0 - CHARGED/DISCHARGED indicator electrically supplied tripping signal is
passed on to the trip-latching mechanism
by means of a direct action solenoid
Figure 13: Use of manual spring-operation crank
armature and the circuit breaker is thus
opened. It is available for either ac or dc
operation. After completion of an opening
operation, the trip coil is de-energized
internally. If operated with ac voltage, a
50.5
rectifier is installed in the circuit breaker.
50.6
50.0
(+)
01
01 T
C
SD16 SD13
W 21 G R
LS21 41
22 52b
42
SD3 SD4 SD1
22 21 14
Motor 88 52Y LS3 52Y
21 22 13
13 31 24
LS41 31 52b 52a
DC supply 14 52Y 32 23
21 32
LS22
22 A1 A1 A1
52SRC 52Y 52T
22 22 A2 A2 SD14 A2
MI1 MI2 34
13 52a
21 21 LS9 33
TB 14
1 SD2
2
3
4
5
SD15 6
(-)
52a - Auxiliary switch is open when MI1, MI2 - Mechanical interlock Fuses in close circuit. Slugs in trip
circuit breaker is open circuit (fuses optional).
01/C - Control switch (CLOSE)
52b - Auxiliary switch is closed Shown with springs discharged, trip-
01/T - Control switch (TRIP) latch reset, circuit breaker open,
when circuit breaker is closed
R - Red indicating light connect or withdrawn position.
52SRC - Spring-release coil (CLOSE) (CLOSED)
52T - Shunt trip coil W hite indicating light
-W
52Y - Closing relay (anti-pump) (spring-charged)
25
Vacuum interrupter/
operator
Indirect releases - secondary shunt
21.0 25.0 27.0
release (dual trip) (52T1) or
undervoltage (27.0)
28
Maintenance
Failure to maintain the equipment can result in death, serious injury, property damage or
product failure, and can prevent successful functioning of connected apparatus.
The instructions contained herein should be carefully reviewed, understood and followed.
The maintenance tasks in Table 1 must be performed regularly.
29
Maintenance
30
Maintenance
The use of unauthorized parts in the repair of the equipment, or tampering by unqualified
personnel can result in hazardous conditions, that can result in death, serious injury or
property damage.
Follow all safety instructions contained herein.
31
Maintenance
32
Maintenance
33
Maintenance
34
Maintenance
35
Maintenance
Footnote:
36 1.
Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).
Maintenance
100,000
50,000
20,000
10,000
5,000
2,000
1,000
500
200
100
50
20
C A E
10
1 2 5 10 20 25 31.540 50 100
37
Appendix
100,000
50,000
20,000
10,000
5,000
2,000
1,000
500
200
100
50
20
D B F
10
1 2 5 10 20 40 50 63 100
38
Maintenance
39
Maintenance
40
Maintenance
4.76 19 14 20
8.25 36 27 38
15.0 36 27 38
15.5 50 38 53
27.6 60 45 64
38 80 60 85
41
Maintenance
6. D
isconnect the leads to the spring-
48.0 - Insulating coupler
charging motor.
48.6 - Lever
7. F
or drawout applications, connect all
points of the secondary disconnect
with a shorting wire. For stationary
applications, disconnect secondary
circuits for the operating mechanism
by disconnecting the multiple pin-plug
at the upper right corner of the
48.6 48.0 operator, and connect all pins on the
operator side with a shorting wire.
Connect the shorting wire to the high-
potential lead of the high-voltage
tester, and ground the circuit breaker
housing. Starting with zero voltage,
gradually increase the test voltage to
1,500 volts rms, 60 Hz. Maintain test
voltage for one minute.
8. If no disruptive discharge occurs, the
secondary control insulation level is
48.6 satisfactory.
9. D
isconnect the shorting wire, reattach
48.0 the multiple pin-plug (if applicable)
and reattach the leads to the spring-
Figure 23: Circuit breaker pole assembly/vacuum-check mechanical/contact-resistance charging motor.
test
10. P
erform contact-resistance tests of the
Insulation and contact-resistance test
primary contacts. The resistance
procedure
should be read between the lower and
1. O
bserve safety precaution listed in the upper connection pads (refer to Figure
danger and warning advisories for the 23).Contact resistance should not
vacuum integrity check tests (refer to exceed the values listed in Table 5.
pages 38-39).
2. C
lose the circuit breaker. Ground the
frame of the circuit breaker, and
ground each pole not under test. Use
manual charging, closing and tripping
procedures.
3. A
pply the proper ac or dc (refer to
Table 4) high-potential test voltage
between a primary conductor of the
pole and ground for one minute.
4. If no disruptive discharge occurs, the
insulation system is satisfactory.
5. A
fter test, ground both ends and the
middle of each vacuum interrupter to
dissipate any static charge.
42
Maintenance
2. R
emove any inter-phase and
outerphase barriers if furnished
(applicable for certain types only).
3. C
lean barriers and post insulators using
clean cloth dipped in isopropyl alcohol.
4. R
eplace all barriers. Check all visible
fasteners again for condition and
tightness.
Note: Do not use any cleaning compounds
containing chlorinated hydrocarbons, such
as: trichlorethylene, perchlorethylene or
carbon tetrachloride.
These compounds will damage the
phenylene ether copolymer material used
in the barriers and other insulation on the
circuit breaker.
43
Overhaul
44
Overhaul
45
Overhaul
30.0
36.1
28.1
29.3
29.2
29.1
36.3
40.0
48.6
48.5
48.0
48.9 48.9
46
Overhaul
2.4 F
asten the pole head to the post Position of torque wrench to avoid undue
insulator (16.1) "finger tight" using stressing of moving contact (36.1)
hex-head bolt, lock washer and flat
washer.
2.5 A
ttach struts (28.0) to the upper pole-
support (20.0), replace hardware Vacuum interrupter
(M10), but do not tighten at this
time.
2.6 C
ouple levers (48.6) and drive link
(48.9) to the eye bolt (36.3), using
the pin supplied. Apply retaining clips. Moving contact (36.1)
Appropriate pin is modestly Holding wrench
chamfered, not to be confused with Spacer (shoulder) (29.3)
pin for the insulating coupler.
2.7 R
aise the terminal clamp (29.2)
against the step or the spacer (if
applicable) of the moving contact
Terminal clamp (29.2)
(36.1) of the vacuum interrupter
(30.0) so that the radius of the
movable contact faces the connecting
surface of the flexible connector Torque wrench
(29.1). Employ technique illustrated Direction of force (P)
to fasten terminal clamp (refer to
Figure 25). Note opposing wrenches.
Tighten the bolt(s) of the terminal Figure 25: Illustration showing required technique for fastening terminal-clamp hardware
clamp to a torque of 40 Nm (30 ft-lb),
taking care to see that the terminal of
the vacuum interrupter is not the vacuum interrupter in pole head
subjected to excessive bending by turning and moving it slightly.
movement. Torque M12 bolt to 60 Nm (44 ft-lb)
Note: Excessive bending movement and M16 bolt to 130 Nm (96 ft-lb).
exerted while fastening the terminal clamp 2.10 The centering ring (28.1) has been
will damage the vacuum interrupter. loose and "floating" during
2.8 A
lign pole head (20.0) correctly and installation of the vacuum interrupter.
tighten bolt fastening it to the post Check that the movable contact is
insulator. Torque M16 bolt to 130 Nm free to move vertically without
(96 ft-lb). Fasten securely all bolts binding, and then tighten the
associated with struts (28.0). hardware which secures the
centering ring. Recheck that the
2.9 T
ighten vacuum interrupter fastening movable contact is free to move
bolt (31.2) on the pole head (20.0) vertically without binding.
holding the vacuum interrupter firmly
by its upper insulator and operate 2.11 Attach insulating coupler (48.0) and
levers (48.6), by hand, to see whether lever (48.6) together, using pin
the movable contact moves freely. If (48.5). Apply retaining clips. Correct
any binding or lack of freedom is pin has ends that have been
noted, loosen bolt (31.2) and adjust generously chamfered.
47
Overhaul
2.12 Open and close circuit breaker several 5. omplete all other maintenance
C
times and then check to see that all procedures. Completely reassembled
bolted joints and devices are tight. circuit breaker should pass the high-
potential test before it is ready for
3. C
hecking the contact stroke
service.
3.1 Open the circuit breaker.
Hydraulic shock absorber
3.2 F
ree insulating coupler (48.0) by
The mechanism is equipped with a
removing pin (48.5). The vacuum
hydraulic shock-absorber that functions
interrupter contacts must now close
when the circuit breaker opens (refer to
automatically as a consequence of
item 61.8 in Figure 6). The shock absorber
atmospheric pressure.
should require no adjustment. However, at
3.3 O
bserve the terminal clamp (29.2) maintenance checks, the shock absorber
through the openings on each side of should be examined for evidence of
the pole bottom (40.0). Using vernier leaking. If evidence of fluid leakage is
calipers, measure the distance from found, the shock absorber must be
the bottom surface of the terminal replaced to prevent damage to the vacuum
clamp to the bottom edge of the interrupter bellows.
cutout opening. Measure carefully
and record your result.
3.4 C
onnect the insulating coupler (48.0)
using pin (48.5) and the retaining
clips provided.
3.5 R
epeat the measurement described in
step 3.3 again with care to maximize
accuracy. Record your result.
3.6 D
etermine difference between the
measurements made under steps 3.3
and 3.5. Your results should be per
Table 7.
3.7 If you fail to achieve the listed results,
carefully repeat the entire procedure
making certain of your
measurements.
3.8 L oosen eye bolt locking nut on
insulating coupler (48.0), and retain
position of the eye. Make adjustments
in one-half turn increments. After
adjustment is completed, tighten eye
bolt locking nut to 26-34 ft-lb. (35-45
Nm).
4. A
fter eye bolt is tightened to proper
torque, repeat all measurement
procedures, making certain they are
in agreement with values indicated in
step 3.6.
48
Maintenance and
Troubleshooting
Table 7 Vacuum interrupter stroke
Footnotes:
1.
The vacuum interrupter type
designation is labeled on the Rated maximum Interrupting Rated short- Vacuum Continuous Stroke2
vacuum interrupter. If the vacuum
voltage class circuit current interrupter current
interrupter installed does not
match that indicated in this table, kV MVA kA Type A mm
contact the nearest Siemens
4.76 250 29 kA@4.76 kV; VS-17006 1,200, 2,000 7-9
representative.
36 kA@3.85 kV VS-17040 1,200, 2,000 7-9
2.
If you need assistance achieving
the indicated stroke setting, 4.76 350 41 kA@4.76 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
contact the nearest Siemens 49 kA@4.0 kV
representative. 8.25 500 33 kA@8.25 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
41 kA@6.6 kV
15.0 500 18 kA@15.0 kV; VS-17006 1,200, 2,000 7-9
23 kA@11.5 kV
15.0 750 28 kA@15.0 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
36 kA@11.5 kV VS-17040 1,200, 2,000 7-9
15.0 1,000 37 kA@15.0 kV; VS-15052 1,200, 2,000, 3,000 8.5-9.5
48 kA@11.5 kV
38.0 1,500 21 kA@38.0 kV; VS-30030 1,200, 2,000, 3,000 18-22
25 kA@23.0 kV
Rated maximum Interrupting Rated short- Vacuum Continuous Stroke2
voltage class circuit current interrupter current
kV kA kA Type A mm
4.76 31.5 31.5 kA@4.76 kV VS-17006 1,200, 2,000 7-9
VS-17040 1,200, 2,000 7-9
4.76 40 40 kA@4.76 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-17040 1,200, 2,000 7-9
4.76 50 50 kA@4.76 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
8.25 40 40 kA@8.25 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-17040 1,200, 2,000 7-9
15.0 20 20 kA@15.0 kV VS-17006 1,200, 2,000 7-9
15.0 25 25 kA@15.0 kV VS-17006 1,200, 2,000 7-9
15.0 31.5 31.5 kA@15.0 kV VS-17006 1,200, 2,000 7-9
VS-17040 1,200, 2,000 7-9
15.0 40 40 kA@15.0 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
VS-17040 1,200, 2,000 7-9
15.0 50 50 kA@15.0 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.0 63 63 kA@15.0 kV VS-17085 1,200, 2,000, 3,000 10-11
15.5 20 20 kA@15.5 kV VS-25008 1,200, 2,000 15-16
15.5 25 25 kA@15.5 kV VS-25008 1,200, 2,000 15-16
15.5 31.5 31.5 kA@15.5 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
15.5 40 40 kA@15.5 kV VS-15052 1,200, 2,000, 3,000 8.5-9.5
27.6 20 20 kA@27.6 kV VS-25008 1,200, 2,000 15-16
27.6 25 25 kA@27.6 kV VS-25008 1,200, 2,000 15-16
38.0 20 20 kA@38.0 kV VS-30030 1,200, 2,000, 3,000 18-22
38.0 25 25 kA@38.0 kV VS-30030 1,200, 2,000, 3,000 18-22
38.0 31.5 31.5 kA@38.0 kV VS-30041 1,200, 2,000, 3,000 18-22
38.0 40 40 kA@38.0 kV VS-30041 1,200, 2,000, 3,000 18-22
49
Maintenance and
troubleshooting
Table 8: Troubleshooting
50
Maintenance and
troubleshooting
Table 8: Troubleshooting (continued)
2. C
losing coil (52SRC) terminal A2 is
shorted-to-ground. Check to determine
if problems are in wiring or coil. Correct
as required.
Mechanical problem 1. M
echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
Circuit breaker will not trip Tripping coil or solenoid (52T) does not 1. S
econdary control power is de-
energize. There is no tripping sound. energized or control power fuses are
blown. Correct as indicated.
2. D
amage to wiring, terminals or
connectors. Check and repair as
necessary.
3. N
o tripping signal to secondary
disconnect contact C2. Check for
continuity and correct protective relay
logic.
4. S
econdary multi-pin plug contacts C1 or
D2 are not engaging. Check and replace
if required.
5. F
ailure of trip coil (52T). Check and
replace if necessary.
6. A
uxiliary switch 52a NO contacts 23 to
24 or 33 to 34 are open when circuit
breaker is closed. Check linkage and
switch. Replace or adjust as necessary.
Tripping coil (52T) energizes. No tripping 1. F
ailure of tripping spring or its
sound is heard, and circuit breaker contacts mechanical linkage. Check and replace
do not open. In other words, they remain if required.
closed.
Tripping coil (52T) energizes. Tripping 1. M
echanical failure of operating
sound is heard, but circuit breaker contacts mechanism. Check and contact the
do not open. factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
2. O
ne or more of the vacuum interrupters
are held closed. Check and replace as
necessary.
51
Maintenance and
troubleshooting
Table 8: Troubleshooting (continued)
2. C
heck for improper protective relay
logic.
Mechanical problem 1. M
echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
52
Appendix
ANSI/IEEE C37.06 control voltages Close coil Trip coil Spring charging motor
Nominal Range Run Inrush Charging
(Average)1 (Peak)
Close Trip A1 A1 A A Seconds
Footnotes:
1.
urrent at nominal voltage
C
2.
apacitor trip
C
3.
Value preceding slash (/) is the current for
the standard trip coil with standard rating
interrupting time. Value following (/) is
current for optional trip coil with three-cycle
interrupting time.
4.
---- means this selection is not available at this
voltage.
Inductive 10 6 3 10 6 3
Footnotes:
1.
wo contacts in series.
T
2.
ll switches are non-convertible.
A
53
Appendix
These ratings are in accordance Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis)
with:
Circuit Maximum Voltage Withstand voltage Continuous Short-circuit
NSI/IEEE C37.04-1999
A breaker type design range levels current7 (I)3,4
standard rating structure for voltage factor
ac high-voltage circuit (V)1 (K)2
breakers
kV rms Power Lightning A rms kA rms sym
NSI/IEEE C37.06-2009 AC
A frequency impulse
high-voltage circuit breakers kV rms (BIL)
kV crest
rated on a symmetrical
current basis - preferred 1,200, 2,000,
5-3AH-31.5 4.76 1.0 19 60 31.5
ratings and related required 3,000
capabilities for voltages 5-3AH-40 4.76 1.0 19 60
1,200, 2,000,
40
above 1,000 volts 3,000
1,200, 2,000,
NSI/IEEE C37.09-1999
A 5-3AH-50 4.76 1.0 19 60 50
3,000
standard test procedure for
1,200, 2,000,
ac high-voltage circuit 5-3AH-63 4.76 1.0 19 60 63
3,000
breakers rated on a
symmetrical current basis 1,200, 2,000,
7-3AH-40 8.25 1.0 36 95 40
3,000
NSI/IEEE C37.010-1999
A
application guide for ac high- 15-3AH-20 15.0 1.0 36 95 1,200, 2,000 20
voltage circuit breakers rated
on a symmetrical current 15-3AH-25 15.0 1.0 36 95 1,200, 2,000 25
basis. 1,200, 2,000,
15-3AH-31.5 15.0 1.0 36 95 31.5
Footnotes: 3,000
1.
Maximum design voltage for which 1,200, 2,000,
15-3AH-40 15.0 1.0 36 95 40
the circuit breaker is designed and 3,000
the upper limit for operation.
1,200, 2,000,
2.
K is listed for information purposes 15-3AH-50 15.0 1.0 36 95 50
3,000
only. For circuit breakers rated on
a "constant kA" ratings basis, the 1,200, 2,000,
15-3AH-63 15.0 1.0 36 95 63
voltage range factor is 1.0. 3,000
3.
All values apply to polyphase and
15.5-3AH-20 15.5 1.0 50 110 1,200, 2,000 20
line-to-line faults.
4.
Standard duty cycle is O - 0.3 s - CO
- 3 min. - CO. 15.5-3AH-25 15.5 1.0 50 110 1,200, 2,000 25
5.
Standard rating interrupting time is
five-cycles (83 ms). Optional rated
1,200, 2,000,
15.5-3AH-31.5 15.5 1.0 50 110 31.5
interrupting time of three-cycles (50
3,000
ms) is available (except with 24 Vdc 1,200, 2,000,
15.5-3AH-40 15.5 1.0 50 110 40
tripping). 3,000
6.
150 kV BIL is for drawout
applications. 200 kV BIL is for type 27-3AH-20 27.6 1.0 60 150 1,200, 2,000 20
SDV6 with appropriate construction.
7.
Continous current capability 27-3AH-25 27.6 1.0 60 150 1,200, 2,000 25
may be increased by the use of
forced-cooling (fan-cooling) in the 1,200, 2,000,
switchgear together with increased 38-3AH-20 38.0 1.0 80 150/2006 20
3,000
bus bar capacity.
1,200, 2,000,
38-3AH-25 38.0 1.0 80 150/2006 25
3,000
1,200, 2,000,
38-3AH-31.5 38.0 1.0 80 150/2006 31.5
3,000
1,200, 2,000,
38-3AH-40 38.0 1.0 80 150/2006 40
3,000
54
Appendix
83 / 5 2 40 47 40 62 104 5-3AH-40
83 / 5 2 50 47 50 78 130 5-3AH-50
83 / 5 2 63 47 63 98 164 5-3AH-63
83 / 5 2 40 47 40 62 104 7-3AH-40
83 / 5 2 20 47 20 31 52 15-3AH-20
83 / 5 2 25 47 25 39 65 15-3AH-25
83 / 5 2 40 47 40 62 104 15-3AH-40
83 / 5 2 50 47 50 78 130 15-3AH-50
83 / 5 2 63 47 63 98 164 15-3AH-63
83 / 5 2 20 47 20 31 52 15.5-3AH-20
83 / 5 2 25 47 25 39 65 15.5-3AH-25
83 / 5 2 40 47 40 62 104 15.5-3AH-40
83 / 5 2 20 47 20 31 52 27-3AH-20
83 / 5 2 25 47 25 39 65 27-3AH-25
83 / 5 2 20 47 20 31 52 38-3AH-20
83 / 5 2 25 47 25 39 65 38-3AH-25
83 / 5 2 40 47 40 62 104 38-3AH-40
55
Appendix
NSI/IEEE C37.04-1979
A
standard rating structure for kV MVA kV rms A rms ---- Power Lightning
ac high-voltage circuit frequency impulse
breakers rated on a kV rms (BIL)
symmetrical current basis kV crest
NSI/IEEE C37.010-1979
A
application guide for ac 1,200, 2,000,
15-3AH-750 13.8 750 15.0 1.30 36 95
high-voltage circuit breakers 3,000
rated on a symmetrical
current basis. 1,200, 2,000,
15-3AH-1000 13.8 1000 15.0 1.30 36 95
3,000
Footnotes: 3.
To obtain the required symmetrical interrupting
1.
Maximum design voltage for which the circuit capability of a circuit breaker at an operating
breaker is designed and the upper limit for voltage between 1/K times rated maximum
operation. design voltage and rated maximum design
2.
K is the ratio of the rated maximum design voltage, the following formula shall be used:
voltage to the lower limit of the range of Required symmetrical interrupting capability =
operating voltage in which the required rated short-circuit current (I) x [(rated maximum
symmetrical and asymmetrical interrupting design voltage)/(operating voltage)]. For
capabilities vary in inverse proportion to the operating voltages below 1/K times maximum
operating voltage. design voltage, the required symmetrical
interrupting capability of the circuit breaker shall
be equal to K times rated short-circuit current.
4.
Within the limitations stated in
ANSI/IEEE C37.04-1979, all values apply to
polyphase and line-to-line faults. For single
phase-to-ground faults, the specific conditions
stated in clause 5.10.2.3 of
ANSI/IEEE C37.04-1979 apply.
56
Appendix
Short- Interrupting Permissible Rated Maximum Short-time Closing and latching Circuit
circuit (at time9 tripping maximum symmetrical current (I) (momentary) breaker
rated delay (y) design interrupting (three type
maximum voltage (V) (K x I)5 seconds)
design divided by
voltage) K
(I)3, 4, 8 (= V/K)
kA rms sym ms / cycles Sec kA rms kA rms sym kA rms Asymmetrical Peak
(1.6 x (2.7 x
K x I)6 K x I)6
kA rms kA peak
5.
Current values in this row are not to be 9.
tandard rating interrupting time is five-cycles
S
exceeded even for operating voltage below (83 ms). Optional rated interrupting time of
1/K times rated maximum design voltage. For three-cycles (50 ms) is available (except with
operating voltages between rated maximum 24 Vdc tripping).
design voltage and 1/K times rated maximum 10.
High close and latch (momentary) rating
design voltage, follow Footnote 5. available for special application.
6.
Current values in this row are independent of 11.
Continuous current may be increased by the
operating voltage up to and including rated use of forced-cooling (fan-cooling) in the
maximum voltage. switchgear, together with increased bus bar
7.
"Nominal three-phase MVA class" is included for capacity.
reference only. This information is not listed in
ANSI C37.06-1987.
8.
Standard duty cycle is O - 15 s - CO.
57
Appendix
Table 13: Type 3AH vacuum circuit breaker weight in lbs (kg) (circuit breaker
operator only)
Footnote:
1.
Add 100 lbs (45 kg) for packaging.
58
Appendix
59
Published by and copyright © 2010:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
www.usa.siemens.com/energy