Vu ≔ 157.08 Fuerza Cortante ϕv ≔ 0.

90

Mu ≔ 862.35 ⋅ Momento Flector ϕf ≔ 0.90

Nu ≔ 0 Fuerza Axial (positivo si es tension) ϕc ≔ 0.75

f'c ≔ 4 Resistencia a la compresion del concreto a los 28 dias

fy ≔ 60 Esfuerzo limite de fluencia del acero de refuerzo

Es ≔ 29000 Modulo de elasticidad del acero de refuerzo

h ≔ 2400 Altura de Seccion

b ≔ 400 Ancho en compresion de la seccion

bv ≔ 400 Ancho efectivo que resiste el corte

de ≔ 2344 Distancia fibra en compresion a centroide de aceros

2
As ≔ 29 ⋅ 510 Area de acero longitudinal

2
Av ≔ 2 ⋅ 129 Area de acero transversal

s ≔ 200 Separacion entre aceros transversales

2
Act ≔ 0 Area de concreto en el lado de tracción por flexión (Si se necesita)

‾‾‾‾‾
f'c 4
Ec ≔ 15000 ――⋅ ―― = ⎛⎝2.467 ⋅ 10 ⎞⎠
2
―― 2

As ⋅ fy
a ≔ ―――― = 652.5
0.85 ⋅ f'c ⋅ b
⎛ a ⎞ 3
dv ≔ max ⎜de − ―, 0.9 de , 0.72 h⎟ = ⎛⎝2.11 ⋅ 10 ⎞⎠
⎝ 2 ⎠

Mu1 ≔ max ⎛⎝||Mu|| , ||Vu|| ⋅ dv⎞⎠

Mu1 = 862.35 ⋅

Mu1
―― + 0.5 Nu + ||Vu||
dv −3
εs1 ≔ ――――――― = 1.876 ⋅ 10
Es ⋅ As
εs2 ≔ ‖ if εs1 ≤ 0 ||
‖ ||
‖ M
‖ u1
+ 0.5 Nu + ||Vu|| | |
‖ ――
‖ ||
‖ dv
‖ ――――――― ||

‖ ‖ Es ⋅ As + Ec ⋅ Act | |
‖ else ||
‖ ‖ε |
‖ ‖ s1 ||

‖ −3 | |
εs ≔ ‖ if εs2 ≤ −0.40 ⋅ 10
||
‖ ‖ −0.40 ⋅ 10 −3 ||

‖ −3|
|
‖ else if εs2 ≥ 6.0 ⋅ 10 | |
‖ ‖ −3 ||
6.0 ⋅ 10
‖ ‖ ||
‖ else ||
‖ ‖ εs2
‖ ‖ ||

−3
εs = 1.876 ⋅ 10

4.8
β ≔ ―――― = 1.994
1 + 750 εs

θ ≔ 29 + 3500 εs = 35.568

‾‾‾‾
f'c
Vc ≔ 0.0316 β ―― ⋅ ⋅ bv ⋅ dv = 74.761

⎛ ⎞
Av ⋅ fy ⋅ dv ⋅ cot ⎜θ ⋅ ――

⎝ 180 ⎠
Vs ≔ ―――――――― = 160.542
s

Vc + Vs = 235.303

0.25 f'c ⋅ bv ⋅ dv = 593.278


Vn ≔ min ⎛⎝Vc + Vs , 0.25 f'c ⋅ bv ⋅ dv⎞⎠

ϕv ⋅ Vn = 211.773

Vu = 157.08

Vu
DC ≔ ――― = 0.742
ϕv ⋅ Vn

Verificacion_Cortante ≔ (DC < 1 , “OK” , “Revisar”))

Verificacion_Cortante = “OK”

FLong_prov ≔ As ⋅ fy FLong_prov = 623.904

||Mu|| Nu ⎛ ||Vu|| ⎞ ⎛ ⎞
FLong_req ≔ ―― + 0.5 ――+ ⎜―― − 0.5 Vs⎟ ⋅ cot θ ⋅ ―― FLong_req = 586.015
dv ⋅ ϕf ϕc ⎝ ϕv ⎜⎝ 180 ⎟⎠

Verificacion_Ref_Long ≔ ⎛⎝FLong_req < FLong_prov , “OK” , “Revisar”⎞⎠

Verificacion_Ref_Long = “OK”