You are on page 1of 6

Industry-Building

Electrical distribution
Solutions
Design of a protection system
The example
installation
In this document, The low-voltage installation used for this each supplying a MV/LV transformer
we design the example is supplied by two incoming feeders. (20 kV / 415 V, 1600 kVA), followed downstream
The design objectives include coordination of the by a low-voltage incoming circuit breaker (circuit
protection protective devices in the LV section with those breakers (A) and (B) respectively).
system for a located upstream of each MV/LV transformer. A coupling circuit breaker (C) is used to
low-voltage interconnect or isolate the two parts of the
installation. As indicated in the diagram below, the installation, in view of optimising power
installation is made up of two 20 kV availability if one of the incoming feeders fails.
This consists medium-voltage feeders protected by fuses,
in precisely
determining 20 kV
the necessary
protective 80 A 80 A

devices while
ensuring
maximum 20 kV/415 V 20 kV/415 V
discrimination at 1600 kVA
In 2253 A
1600 kVA
In 2253 A
all points in the Isc 36 kA Isc 36 kA

installation.

Main LV A B
switchboard
Masterpact Masterpact
NW25H1 NW25H1

C
Isc 72 kA Isc 36 kA Isc 72 kA

D Masterpact E
NW25H1
Masterpact Masterpact
NT08L1 NW10H2
700 A 750 A

cable cable

Isc 50 kA Isc 50 kA

F G
Compact Compact
NSX250H NSX250H
185 A 185 A

Installation diagram

DBTP107S0L1/EN Electrical installation


Solutions
Industry-Building
Sizing of the protective
devices
Discrimination is determined by Ratings of fuses on the MV feeders
selecting and setting the most The rated current on the MV feeders must be
downstream circuit breakers such calculated:
that the forces exerted on the In = 1 600 000 / (20 000 x √3) = 46 A.
Fuses with an 80 A rating should be selected,
installation are limited in the event in accordance with the manufacturer selection
of a fault, then moving upstream tables.
to ensure the best possible The inrush current and the overload current have
discrimination between each pair of to be taken into consideration.
upstream and downstream circuit
breakers. Ratings of circuit breakers (A) and (B) on
the LV feeders
The rated current on these LV incomers must be
calculated:
1600 kVA at 410 V corresponds to a rated
current of
1 600 000 / (410 x √3) = 2253 A.
Circuit breakers with a 2500 A rating are suitable.

Breaking capacity of the various devices


b Short-circuit currents at various points in the
installation:
Each transformer has a short-circuit current Isc
equal to 36 kA (due to the short-circuit power
and voltage of the transformer).
When the coupling circuit breaker is closed,
the short-circuit power downstream of circuit
breakers (A) and (B) is 2 x 36 = 72 kArms (if the
busbar impedances are neglected). Taking into
account the cable impedances, the short-circuit
current flowing through circuit breakers (F) and
(G) is only approximately 50 kA.

b Breaking capacity of the devices:


On the basis of the short-circuit currents at the
various points in the installation, it is possible
to determine the required breaking capacity for
each device.
Circuit breakers (D) and (E) must have a
breaking capacity greater than 72 kA. Circuit
breakers (A), (B) and (C) must have a breaking
capacity greater than 36 kA. Circuit breakers
(F) and (G) must have a breaking capacity of at
least 50 kA.

Electrical distribution
 Solutions
Industry-Building
Alternative with zone selective
interlocking
This alternative requires that circuit breakers (A), v if (C) is open, it will not send a signal to (A),
(B), (C), (D) et (E) be equipped with control units however (A) will not be subject to the short-
offering the zone selective interlocking function circuit.
(e.g. Micrologic 5.0 A). b In the event of a fault between (G) and (E):
v if (C) is closed, circuit breaker (E) is delayed
Description: 100 milliseconds and it sends a signal to (C) and
(B), which are delayed 200 milliseconds and do
Each control unit is equipped with two input not trip. In turn, (C) sends a signal to (A) and (B),
terminals, connected to the downstream devices, which are delayed 200 milliseconds and do not
and two output terminals, connected to the trip,
upstream devices. v if (C) is open, it will not send a signal to (A),
however (A) will not be subject to the short-
When a control unit detects a fault greater than circuit.
its short-time threshold, it shorts its two output b In the event of a fault between (E) and (C):
terminals. If an upstream control unit detects the v if (C) is closed, it trips instantaneously and
shorted input terminals, it activates the short- sends a signal to (A) and (B), which are delayed
time delay. Otherwise, its trips immediately. 200 milliseconds. In this way, the fault is no
longer supplied by the two feeders in parallel.
Implementation (A) remains closed and the left side of the
b The inputs on the first circuit breakers (D) and installation remains in service. After 200 ms, (B)
(E) are short-circuited on a permanent basis will trip to interrupt the supply of current by the
to ensure that their short-time delay is always transformer on the right.
activated. This guarantees discrimination with v if (C) is open, it will not send a signal to (B)
the downstream circuit breakers (Compact NS). and (B) will trip instantaneously.
b Next the various devices are wired as shown b In the event of a fault between (C) and (B),
in the diagram opposite. circuit breaker (B) trips instantaneously.
The direct wiring between (E) and (B) and It is clear that zone selective interlocking
between (D) and (A) ensure discrimination significantly limits the forces exerted on the
between these devices when the coupling installation and all the more so the higher the
(C) is open. Diodes are used to maintain fault occurs in the system. Without this function,
the independence of the two halves of the a fault occurring just downstream of (A) or
installation in this case by preventing (D) from (B) would produce tripping in over 300 ms,
acting on (B) and (E) from acting on (A). compared to just a few tens of milliseconds with
the function.

out out Alternative with two feeders


A B
ST delay 2 ST delay 2 with higher ratings
IN IN
Consider the same installation as presented
above, but in which the rating of the transformers
is increased to 2500 kVA and the current of the
circuit downstream of (E) is increased to 2200 A.
out
C Rating of the fuses on the MV feeders.
ST delay 2
The MV current is 72 A. Fuses rated 125 A
IN
are recommended, in compliance with the
manufacturer selection tables.

Breaking capacity of the various circuit breakers:


out out
b Circuit breaker (E)
D E Given that the Isc is greater than 100 kA, a
ST delay 1 ST delay 1
IN IN Masterpact NW25H2 (breaking capacity =
100 kA) cannot be used. A current-limiting circuit
breaker cannot be used either, because the rated
current does not exceed 2000 A (NW20L1).
Operation b Circuit breakers (A), (B) and (C)
For the In = 3520 A rating, Masterpact NW40H1
b In the event of a fault downstream of circuit circuit breakers (In = 4000 A, breaking capacity =
breaker (G): 65 kA, Icw = 65 kA/1 s) are suitable.
v if (C) is closed,(G) trips instantaneously and
(E) is delayed 100 milliseconds, i.e. it does not Device selection to ensure discrimination
trip. (E) sends a signal to (C) and (B), which No fundamental modifications are required. The
are delayed 200 milliseconds and do not trip. In time delay on circuit breaker (E) must be set to
turn, (C) sends a signal to (A) and (B), which are 0.1s. The time delay on circuit breaker (C) must
delayed 200 milliseconds and do not trip. As a be set to 0.2s. On circuit breakers (A) and (B),
result, only circuit breaker (G) trips, the time delay must be set to 0.3s.

 Electrical distribution
Solutions
Industry-Building
© 2008 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS


89, boulevard Franklin Roosevelt As standards, specifications and designs change from time to time, please ask for confirmation
F - 92505 Rueil-Malmaison Cedex (France) of the information given in this publication.
Tel : +33 (0)1 41 29 85 00
This document has been printed on ecological paper.
http://www.schneider-electric.com

Design: Schneider Electric


Photos: Schneider Electric
Printed:

DBTP107SOL1/EN 04-2008
Discrimination between circuit breakers blowing time of the MV fuses (the circuit-breaker
(E) and (C) curve must remain to the left of the fuse curve in
the figure below).
Discrimination is not indispensable between these
two circuit breakers if the two incoming feeders are Discrimination is evaluated for two types of
operational (in this case, opening of the coupling control units, standard selective control units and
circuit breaker does not interrupt the supply of IDMTL-curve control units.
power via (A) and (B)). However, discrimination
is indispensable if circuit breaker (B) is open, to
10 000
avoid interrupting the supply of power to the entire HVF curve
right-hand side of the installation. tr = 2 s
1000
80 A MT fuse
b Rated current In at (C): converted to BT
To ensure a maximum degree of flexibility, the 100
I2t curve
tr = 12 s
coupling device has the same rating as the circuit Isc max = 36 kA
breakers on the incoming feeders, i.e. In = 2500 10
short time
A. Given that the Isc is 36 kA, a selective circuit short time delay
breaker may be used, thus making possible time 1
pick up = 4 Ir setting = 0,3 s
discrimination with (E) and of course with (D)
because it is a current-limiting device. 0,1
For example, a Masterpact NW25H1
(In = 2500 A, breaking capacity = 65 kA at 415 V,
0,01
Icw = 65 kA/1 s). 0,100 1000 10 000 100 000
Discrimination sytem:
As Icw is equal to the breaking capacity,
the circuit breaker is not equipped with an Settings for standard selective control units
instantaneous self-protection trip and time b Long-time threshold
discrimination is maintained without any The non-tripping current of the fuse is far greater
limitations up to the breaking capacity. Circuit than the tripping current of the circuit breaker.
breaker (C) is therefore equipped with a The long-time threshold can therefore be set to
selective control unit, with the instantaneous its maximum value (i.e. Ir = In).
setting turned to the OFF position and the
short-time delay set to 0.2 (because the short- b Long-time delay and short-time pick-up
time delay on circuit breaker (E) is set to 0.1). The curve of the MV fuses is steeper that that of
the long-time function (I2t curve). The time delay
Discrimination between circuit breakers (tr) or the short-time pick-up (Isd) must be set
(D) and (C) to sufficiently low values. In this case, a good
The solution selected to ensure discrimination compromise would be Ir = 12 second (at 6 Ir) and
between (E) and (C) may also be used between Isd = 4Ir. (A detailed study taking into account the
(D) and (C) because (C) is totally selective up to downstream loads should be carried out).
its breaking capacity.
b Short-time delay
Given that the short-time delay is set to 0.3
Discrimination between circuit breakers (see above), the fuse and circuit-breaker curves
(C) and (B) and between (C) and (A) intersect at approximately 11 In. The guaranteed
level of discrimination must therefore be limited
(A) and (B) are selective circuit breakers,
to approximately 10 In, i.e. 25 kA rms for a
without an instantaneous self-protection
maximum short-circuit current Isc of 36 kA rms.
control unit. Again, time discrimination
is maintained up to the breaking capacity.
Settings for IDMTL-curve control units
Therefore, (A) and (B) are equipped with
selective control units, with the instantaneous With this type of control unit, it is possible to
settings turned to the OFF position and the adjust the slope of the long-time curve. In this
short-time delays set to 0.3 (because the short- case, the HVF (High Voltage Fuse) curve could
time delay on circuit breaker (C) is set to 0.2). be selected because it is the most similar to the
fuse curve (I4t curve).
Discrimination between circuit breakers With the same 1-second time delay at 6 In, the
(A) and (B) and the MV fuses sensitivity to high transient currents (switching or
To ensure discrimination, the tripping curves of start-up currents) is reduced and discrimination
the LV circuit breakers and the MV fuses must with the fuse is improved. In this case, there is
be compared. no longer any need to set the short-time delay to
For this, the curve of the MV fuses must be lower values.
converted to low-voltage values by multiplying
the current scale by the transformer ratio, i.e. in
this case, 20 000 / 410 = 48.8.

The tripping curve for circuit breakers (A) and (B)


must be adjusted such that for a given current,
the circuit-breaker tripping delay is less than the

 Electrical distribution
Solutions
Industry-Building
Device selection
to ensure discrimination
Principle Discrimination between circuit breakers
Discrimination is ensured by comparing the (G) and (E)
characteristics of each circuit breaker with the b Circuit breaker (G): In = 330 A, Isc = 50 kA
protective device (fuse or circuit breaker) located A 400 A circuit breaker may be used, for example
just upstream. The power circuit breakers a Compact NSX400H
located in the most downstream positions of (breaking capacity = 70 kA at 415 V).
the installation must be selected and set to
trip “as fast as possible” in order to limit the b Circuit breaker (E): In = 750 A, Isc = 72 kA
forces exerted on the installation in the event The same circuit breaker as (D) may be used,
of an overcurrent. Once the characteristics of however given that the current-limiting capacity
these circuit breakers have been established, of the Compact NSX400H is less than that of the
the system designer moves one step upstream Compact NSX250H, total discrimination would
to ensure discrimination between each circuit not be ensured between the two.
breaker pair (each downstream breaker and its
upstream neighbour). A selective circuit breaker may be used, in
which case the current-limiting capacity of
20 kV (G) may be called on to provide "pseudo-time
discrimination", if necessary. For example, a
80 A 80 A
Masterpact NW10H2 (In = 1000 A, breaking
capacity = 100 kA at 415 V, Icw = 85 kA rms/1 s).
20 kV/415 V 20 kV/415 V
1600 kVA
In 2253 A
1600 kVA
In 2253 A
Discrimination system:
Isc 36 kA Isc 36 kA Icw (85 kA) is less than the breaking capacity
(100 kA). This device is therefore equipped with
TGBT A Masterpact B Masterpact
NW25H1 NW25H1 an instantaneous self-protection trip (DIN) with
a threshold of 170 kA peak.
Isc 72 kA C Isc 36 kA Isc 72 kA With an Isc of 72 kA rms, the maximum peak
D E current at (E) is 72 x 2.3 = 165 kA peak.
Masterpact
Masterpact
NW25H1 Masterpact The DIN threshold will therefore never be
NT08L1 NW25H1
700 A 750 A
reached, i.e. DIN tripping will never occur and
discrimination is maintained.
What is more, in the event of a short-circuit at
cable cable
(G), the maximum peak current corresponding
to an Isc of 50 kA will be limited to 30 kA peak
Isc 50 kA Isc 50 kA
for (G).
F G Discrimination is therefore total, on the
Compact Compact
NSX250H NSX400H condition, however, that circuit breaker (E) be
185 A 330 A equipped with a trip unit with an instantaneous
setting higher than 30 kA peak, i.e. 30 / 2.04 =
14.7 kA rms = 14.7 In, and that the time delay
for the short-time protection function be set to
Discrimination between circuit breakers
0.1 (time delay = approximately 100 ms).
(F) and (D)
Alternative
b Circuit breaker (F): In = 185 A, Isc = 50 kA It is also possible to use a current-limiting device
A 250 A circuit breaker may be used, for example for (E), with a higher electrodynamic withstand
a Compact NSX250H (breaking capacity = 70 kA than (D). For example, a Masterpact NW10L1
at 415 V). (In = 1000 A, breaking capacity = 150 kA at 415
b Circuit breaker (D): In = 700 A, Isc = 72 kA V, Icw = 30 kA/1 s).
A 800 A circuit breaker may be used, for example
a Compact NS800L or a Masterpact NT08L1 Advantages of this alternative
(breaking capacity = 150 kA at 415 V). Due to its current-limiting capacity (125 kA peak
at 72 kA rms compared to 165 kA peak without
Discrimination system: current limiting), this type of circuit breaker
Device (F) is a current-limiting device (maximum significantly reduces the electrodynamic forces
let-through current = 22 kA peak for an Isc of exerted on the cables between (E) and (G). This
50 kA), which makes it suitable for “pseudo- circuit breaker is equipped with an instantaneous
time discrimination” in conjunction with circuit self-protection control unit set to 80 kA peak, which
breaker (D). will never be called upon in the event of a fault
However, circuit breaker (D) is also a current- downstream of (G) because the Isc is limited to 30
limiting device with a low electrodynamic kA peak. The result is again total discrimination, of
withstand capacity to ensure strong current the "pseudo-time discrimination" type, i.e. ensured
limiting. Consequently, the “SELLIM” principle is by the current-limiting capacity of the downstream
implemented here to obtain total discrimination device.
between (F) and (D). The “SELLIM” principle Note: in the event of a short-circuit, a non
stipulates that the upstream circuit breaker (D) current-limiting device at (G) would let through a
does not trip on the first current wave. peak current of 50 kA x 2.3 = 115 kA peak, which
would trip circuit breaker (E).

Electrical distribution
 Solutions
Industry-Building

You might also like