PC-008 1R - 4/C 70 L1, L2, L3, N Cu, XLPE / SWA / PVC PLDB-1, F9 Air Compressor (K-27301) Power 45 77

Terminal Building HVAC Panel


PC-016 1R - 4/C 70 L1, L2, L3, N Cu, XLPE / SWA / PVC LPP-1, F1 Power 29.4 186
(HVAC-4)

PC-017 1R - 4/C 300 L1, L2, L3, N Cu, XLPE / SWA / PVC Power 455
PP-1 Junction Box (PP-1JB) at Loading
PLDB-1, F7 61
Platform
EC-017 1R - 1/C 120 GR - Y Cu, PVC, Un.Ar. Earth 455

Lighting Distribution Panel Offshore Area


PC-019 1R - 4/C 16 L1, L2, L3, N Cu, XLPE / SWA / PVC LPP-1, F12 Power 5.46 450
(LP-2)

PC-020 1R - 4/C 70 L1, L2, L3, N Cu, XLPE / SWA / PVC PLDB-1, F8 Terminal Building Panel (LP-5 ) Power 32.4 186

PC-022 1R - 4/C 10 L1, L2, L3, N Cu, XLPE / SWA / PVC PP-1, F2 QRH Mooring Dolphin-2 Power 7.5 160

PC-042 1R - 4/C 25 L1, L2, L3, N Cu, XLPE / SWA / PVC PLDB-1, F2 Fuel Oil Pump, P-27601 Power 7.5 200

PC-089 1R - 4/C 4 L1, L2, L3, N Cu, XLPE / SWA / PVC ELP-1, Ckt.-1,3,5 Jetty Access Road Ltg. Power 0.75 255

PC-097 1R - 4/C 4 L1, L2, L3, N Cu, XLPE / SWA / PVC ELP-2, Ckt.-1,3,5 Trestle Ltg. Power 1.00 210

Cathodic Protection Panel-2 for Fire water


PC-010 1R - 3/C 6 PH, N, E Cu, XLPE / SWA / PVC LPP-1 Power 1 86
Tank
Cathodic Protection Panel-1 for NG
PC-015 1R - 3/C 6 PH, N, E Cu, XLPE / SWA / PVC LPP-1 Power 1 20
Pipeline Protection
Lighting for Air Compressor shed & Fire
PC-050 1R - 4/C 10 PH, N, E Cu, XLPE / SWA / PVC LPP-1 Power 1.45 140
Water Pump house

PC-065 1R - 4/C 10 PH, N, E Cu, XLPE / SWA / PVC UPS-1 Distribution Panel Flow Computer Cabinet-2 Power 1.00 186

PC-066 1R - 3/C 6 PH, N, E Cu, XLPE / SWA / PVC UPS-1 Distribution Panel Supervisory Computer for Flow Meter Power 0.75 186

Operating Station for terminal Building


PC-067 1R - 3/C 6 PH, N, E Cu, XLPE / SWA / PVC UPS-1 Distribution Panel Power 0.75 186
PLC
Computer System for Mooring Hooks
PC-107 1R - 4/C 16 PH, N, E Cu, XLPE / SWA / PVC UPS-1 Distribution Panel Power 0.60 455
(Unloading Platform)

PC-108 1R - 3/C 25 PH, N, E Cu, XLPE / SWA / PVC DCDP-1 (LV ROOM) Fire Monitor - 1 (Unloading Platform) Power 0.12 430

PC-124 1R - 4/C 4 PH, N, E Cu, XLPE / SWA / PVC UPS-1 Distribution panel Magnetic Flowmeter (F & G) Power 0.03 100

PC-105 1R - 3/C 6 PH, N, E Cu, XLPE / SWA / PVC UPS-1 Distribution Panel Jockey Pump-1 Controller Power 1.00 85
Underground/
Tray/Conduit
Underground/
Tray/Conduit

Underground/
Tray

Underground/
Tray/Conduit
Underground/
Tray/Conduit

Tray/Conduit

Underground/
Tray/Conduit
Underground/
Tray/Conduit

Tray/Conduit

Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit
Underground/
Tray/Conduit