You are on page 1of 2

Crompton Greaves Limited

Self Powered Relay

Product Overview Technical Specification


The 'CGI 14S' Self Powered Numerical Protection Relay is designed for use
Burden < 5VA
in unmanned substation where dependable auxiliary power source is not
available. The relay derives power for its operation from main current IDMT 5 Settings Curves as per
transformers. It also comprises integrated communication protocols for IEC Standard: SI/VI/EI/LTI/DT
SCADA compliance.
Indications 4 LED Indications:
The relay has feature of IDMT, as well as, instantaneous protection for
both over current & earth elements. It accomplish Digital filtering of Power on
measured quantities by using discrete Fourier analysis to suppress high Alarm
frequency harmonics and transient DC components induced by faults or
Trip
system operations.
Error
The front panel features a 8-button keypad & a 16x2 LCD display that
provides an easy user interface. Frequency 50Hz

Salient Features CT Secondary 1 Amps


4
Auxiliary power supply not required. Over Current setting 20% – 200% (In Steps of 1%)
4
Communication port: RS485 / RS232(optional). Earth Fault setting 10% – 200% (In Steps of 1%)
4
Communication Protocol : IEC60870-5-1O3 & IEC 61850. High Set Features
4
Remote tripping via external voltage. High Set Over Current 100% – 1600% (In Steps of 1%)
4
Programming through local Key pad.
High Set Earth Fault 50% – 1600% (In Steps of 1%)
4
Selectable Definite Time or IDMT curves as per IEC standards.
Pick up Current 110% of Set Current
4
Password protection to guard against unauthorized access &
editing of settings. Re Set Current 90% of Set Current
4
Trip indication via external flag indicator with mechanical reset. Over Load Capacity 2 times rated current continuously
4
Two potential free alarm contacts, latched type (bi-stable relay). 20 times rated current for 3 sec.
4
Recording of ten last fault records with time stamp. Output Contacts Impulse O/p for tripping coil:
4
Parameterization & downloading of records through “CG View”
12-24 V DC ( Energy < 0.1W/Sec)
software (optional).
Potential free O/p contact:
Application
Two Change over contact for trip.
4
Primary circuit protection on distribution networks.
Auxiliary Power Supply Self Powered
4
Auxiliary protection for transformers, generators, motors.
Battery 3.7V/2000 mAH Li-ion
Digital Inputs 4 DI for Remote trip,
Fast trip & 2 spare.
Protection Relay & IED Self Powered Relay

Protection Functions
IEEE / ANSI Code IEC Symbol Function Name
50 / 51 3I>, 3I>> Over current protection
50N / 51N Io>, Io>> Earth fault protection

Typical Wiring Diagram

Crompton Greaves Ltd.,


Power Systems : M. V. Switchgear Division (S2)
A-3, MIDC, Ambad, Nasik - 422 010. India.
Tel. : +91 253 2382271 to 75
Email : mv.switchgear@cgglobal.com
Registered Office
CG House, 6th Floor, Dr. Annie Besant Road, Worli, Mumbai- 400 030.
www.cgglobal.com