Live Loads:

Occupancy:

Roof deck = 1.9 kPa

Wards and rooms = 1.9 kPa

Laboratories and operating rooms = 2.9 kPa

Dining rooms and restaurants = 4.8 kPa

Recreational Areas = 3.6 kPa

Offices = 2.4 kPa

Storage = 6 kPa

Computer rooms = 4.8 kPa

Corridors above ground floor = 3.8 kPa

Special load:

Ceiling Framing = 1.0 kPa

Total live load = 2.9 kPa

Dead Loads:

Weight of concrete = unit weight of concrete + Thickness of the slab

= 23.6 kN/m3 (0.21m)

Weight of concrete = 4.956 kPa

Mechanical duct allowance = 0.20 kPa

Electrical duct allowance = 0.10 kPa

Water proofing membrane (Bituminous, gravel covered) = 0.26 kPa

Concrete fill finish = 0. 023 kPa

Gypsum board = 0.008 kPa

Solid flat tile on 25mm mortar base = 1.10 kPa


partition = 1 kPa

Windows, glass, frame, and sash = 0.38 kPa

LIVE LOADS AND DEAD LOADS ACTING ON SECOND FLOOR


S1

DEAD LOAD
Weight of concrete = 4.956 kPa
Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
partition = 1 kPa
DEAD LOAD= 7.36 kPa
LIVE LOAD
Wards and rooms = 1.9 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD = 2.9 kPa

S2 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
DEAD LOAD TOTAL =6.36 kPa
LIVELOAD

Ceiling Framing = 1.0 kPa


Roof deck = 1.9 kPa

LIVE LOAD TOTAL=2.9 kPa

S3 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
partition = 1 kPa
DEAD LOAD= 7.36 kPa
LIVE LOAD

Ceiling Framing = 1.0 kPa


Corridors above ground floor = 3.8 kPa

LIVE LOAD TOTAL=4.8 kPa

S4 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
DEAD LOAD TOTAL =6.364 kPa

LIVE LOAD

Ceiling Framing = 1.0 kPa


Corridors above ground floor = 3.8 kPa
LIVE LOAD TOTAL=4.8 kPa

S5 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
partition = 1 kPa
DEAD LOAD= 7.36 kPa

LIVE LOAD
Recreational Areas = 3.6 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD TOTAL=4.6 kPa

S6 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
partition = 1 kPa
DEAD LOAD= 7.36 kPa
LIVE LOAD
STORAGE = 6 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD TOTAL=7 kPa

S7 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
DEAD LOAD TOTAL =6.36 kPa
LIVE LOAD
Recreational Areas = 3.6 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD TOTAL=4.6 kPa

S8

DEAD LOAD

Weight of concrete = 4.956 kPa


Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Concrete fill finish = 0. 023 kPa
DEAD LOAD= 5.09 kPa

LIVE LOAD

Ceiling Framing = 1.0 kPa


LIVE LOAD TOTAL=1 kPa

S9 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
partition = 1 kPa
DEAD LOAD= 7.36 kPa
LIVE LOAD
Laboratories and operating rooms = 2.9 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD TOTAL=3.9 kPa

S10 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
DEAD LOAD TOTAL =6.36 kPa

LIVE LOAD
Laboratories and operating rooms = 2.9 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD TOTAL=3.9 kPa

S11 DEAD LOAD

Weight of concrete = 4.956 kPa


Mechanical duct allowance = 0.20 kPa
Electrical duct allowance = 0.10 kPa
Gypsum board = 0.008 kPa
Solid flat tile on 25mm mortar base = 1.10 kPa
partition = 1 kPa
DEAD LOAD= 7.36 kPa
LIVE LOAD

STORAGE = 12 kPa
Ceiling Framing = 1.0 kPa
LIVE LOAD TOTAL=13 kPa
In order for this project study to be possible, we would like to acknowledge architect…