You are on page 1of 124

CONSTRUCTION OF

DOHA COLLEGE NEW CAMPUS PROJECT


AL WAJBA DOHA, QATAR
IFC ISSUE – Rev- 0
31/01/2018
VOLUME 2 OF 4
PART – 4

B.M.S. SPECIFICATION
.
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

CONSTRUCTION OF DOHA COLLEGE


NEW CAMPUS PROJECT
AL WAJBA DOHA, QATAR

B.M.S SPECIFICATION

INDEX
CL. NO. TITLE PAGE NO

INDEX……………………………………………………………………………………………………B - 2

PART 'A' : GENERAL ................................................................................................... B - 6

A.1 SCOPE OF WORK AND GENERAL REQUIREMENTS............................................B - 6


A.2 BMS SYSTEM ...........................................................................................................B - 9
A.3 SYSTEM INTEGRATION INTERFACES .................................................................B - 10
A.4 BMS ALARM PRIORITIES.......................................................................................B - 12
A.5 SYSTEM PERFORMANCE .....................................................................................B - 12
A.6 REFERENCE AND STANDARDS ...........................................................................B - 13
A.7 WARRANTY ............................................................................................................B - 14

PART ‘B’ : DESCRIPTIONS OF OPERATIONS .................................................................. B - 15

B.1 GENERAL ................................................................................................................B - 15

B.2 CHILLED WATER SYSTEMS ..................................................................................B - 15


B.2.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 15
B.2.2 CONTROL STRATEGY (BOTH CHILLERS SYSTEM) ...........................................B - 16
B.2.3 PRESSURIZATION UNITS (BOTH SYSTEM).........................................................B - 17
B.2.4 PRIMARY CHW PUMPS .........................................................................................B - 17
B.2.5 SECONDARY CHW DISTRIBUTION SYSTEM.......................................................B - 17

B.3 HEAT PUMPS HEATING & COOLING SYSTEMS FOR SWIMMING POOL WATER . 19
(LEARNER & COMPETITION) ................................................................................B - 19
B.3.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 19
B.3.2 CONTROL STRATEGY ...........................................................................................B - 19
B.3.3 CIRCULATION PUMPS ...........................................................................................B - 20

B.4 AIR HANDLING SYSTEMS .....................................................................................B - 21


B.4.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 21
B.4.2 NORMAL OPERATION ...........................................................................................B - 21
B.4.3 OPTIMIZED START STOP ROUTINE .....................................................................B - 22
B.4.4 FIRE MODE .............................................................................................................B - 23
B.4.5 FIREMAN’S OVERRIDE ..........................................................................................B - 23

B.5 THERMAL WHEEL HEAT RECOVERY FRESH AIR VENTILATION......................B - 24


B.5.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 24

________________________________________________________________________________
B-2
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

B.5.2 NORMAL OPERATION ...........................................................................................B - 24

B.6 FAN COIL UNITS AIR CONDITIONING SYSTEMS ................................................B - 25


B.6.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 25
B.6.2 NORMAL OPERATION ...........................................................................................B - 25
B.6.3 FIRE MODE .............................................................................................................B - 25

B.7 ITC CENTER BLOCK S-5 & P-1 AIR CONDITIONING ...........................................B - 26
B.7.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 26
B.7.2 CONTROL STRATEGY ...........................................................................................B - 26
B.7.3 NORMAL OPERATION ...........................................................................................B - 26

B.8 ELECTRICAL SUBSTATION AIR CONDITIONING ................................................B - 27


B.8.1 OUTLINE SYSTEM DESCRIPTION ........................................................................B - 27
B.8.2 CONTROL STRATEGY ...........................................................................................B - 27
B.8.3 NORMAL OPERATION ...........................................................................................B - 27

B.9 SECURITY HUTT AIR CONDITIONING & TOILET EXTRACT SYSTEMS .............B - 28

B.10 KITCHEN VENTILATION SYSTEMS (SPECIALIST CONTRACTOR BY THE CLIENT)28


B.10.1 OUTLINE SYSTEM DESCRIPTION .........................................................................B - 28
B.10.2 NORMAL OPERATION ............................................................................................B - 28
B.10.3 FIRE MODE ..............................................................................................................B - 28

B.11 TOILET EXTRACT VENTILATION SYSTEMS .........................................................B - 28


B.11.1 OUTLINE SYSTEM DESCRIPTION .........................................................................B - 28
B.11.2 NORMAL OPERATION ............................................................................................B - 29
B.11.3 FIRE MODE ..............................................................................................................B - 29

B.12 FIRE COMMAND CENTRE ......................................................................................B - 29


B.12.1 OUTLINE SYSTEM DESCRIPTION .........................................................................B - 29

B.13 FIRE PUMP ROOM ..................................................................................................B - 31


B.13.1 OUTLINE SYSTEM DESCRIPTION .........................................................................B - 31
B.13.2 FIRE MODE ..............................................................................................................B - 31

B.14 SMOKE CONTROL SYSTEMS ................................................................................B - 32


B.15 FIRE ALARM INTERFACE .......................................................................................B - 32
B.16 FIRE ALARM CONDITION .......................................................................................B - 32
B.17 GENERAL VENTILATION SYSTEMS CONTROL IN A FIRE SITUATION ..............B - 33
B.18 LIFE SAFETY GENERATOR (LSG) FUEL TRANSFER SYSTEMS ........................B - 33

B.19 DOMESTIC WATER SYSTEMS ...............................................................................B - 35


B.19.1 OUTLINE SYSTEM DESCRIPTION .........................................................................B - 35
B.19.2 BOOSTED COLD-WATER SUPPLY ........................................................................B - 35
B.19.3 DOMESTIC HOT WATER SUPPLY .........................................................................B - 35

B.20 IRRIGATION WATER SYSTEMS .............................................................................B - 37


B.21 MISCELLANEOUS MONITORING ...........................................................................B - 37
B.22 REFINEMENT OF THE CONTROL STRATEGY......................................................B - 38

________________________________________________________________________________
B-3
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

B.23 ELECTRICAL SYSTEMS ..........................................................................................B - 38


B..23.1 POINTS FOR ALL ELECTRICAL ITEM ....................................................................B - 38

PART 'C' : SUBMITTALS...................................................................................................... B - 40

C.1 ACTION SUBMITTALS .............................................................................................B - 40


C.2 INFORMATIONAL SUBMITTALS .............................................................................B - 41
C.3 CLOSEOUT SUBMITTALS .......................................................................................B - 41
C.4 MAINTENANCE MATERIAL SUBMITTALS .............................................................B - 42
C.5 QUALITY ASSURANCE ...........................................................................................B - 42
C.6 DELIVERY, STORAGE, AND HANDLING................................................................B - 42
C.7 COORDINATION ......................................................................................................B - 42

PART 'D' : PRODUCTS......................................................................................................... B - 44

D.1 CONTROL PANELS .................................................................................................B - 44


D.2 BMS SYSTEM STRUCTURE ...................................................................................B - 45
D.5 SYSTEM ADDRESSING ..........................................................................................B - 46
D.6 ORIGINAL EQUIPMENT MANUFACTURER (OEM) SUPPLIED COMPONENTS ..B - 47
D.7 OPERATOR INTERFACES ......................................................................................B - 47
D.8 OPERATOR INTERFACES FACILITIES ..................................................................B - 48
D.9 MAIN OPERATOR STATION ...................................................................................B - 50
D.10 SOFTWARE..............................................................................................................B - 54
D.11 OUTSTATION LOCAL USER INTERFACE/KEYPADS ............................................B - 58
D.12 REMOTE PRINTER ..................................................................................................B - 58
D.13 AUTODIAL MODEM .................................................................................................B - 59
D.14 FIRE DETECTION/BMS SYSTEM CONNECTION ..................................................B - 59
D.15 BUILDING SYSTEM CONTROLLERS .....................................................................B - 59
D.16 OUTSTATIONS ........................................................................................................B - 62
D.17 PLANT CONTROL PROCESSORS .........................................................................B - 66
D.18 FIELD PERIPHERAL EQUIPMENT..........................................................................B - 72
D.19 FIELD OUTPUT DEVICES .......................................................................................B - 79
D.20 METERING ...............................................................................................................B - 83
D.21 DOCUMENTATION ..................................................................................................B - 85
D.22 SOFTWARE AND EQUIPMENT MAINTENANCE AND UPDATES .........................B - 87

PART 'E' : EXECUTION ........................................................................................................ B - 88

E.1 INSTALLATION OF HVAC CONTROL SYSTEM WIRING ........................................B - 88


E.2 LOCATION OF EQUIPMENT ....................................................................................B - 88
E.3 EQUIPMENT IDENTIFICATION ................................................................................B - 89
E.4 FIELD QUALITY CONTROL ......................................................................................B - 92
E.5 WARRANTY ..............................................................................................................B - 93
E.6 COMMISSIONING .....................................................................................................B - 93
E.7 ADJUSTING ...............................................................................................................B - 94
E.8 DEMONSTRATIONS AND OPERATION TRIALS .....................................................B - 96
E.9 OPERATING TRAINING AND MAINTENANCE ........................................................B - 99

PART 'F' : BMS POINTS SCHEDULE I/O .......................................................................... B - 101

F.1 AIR CONDITIONING & VENTILATION SYSTEM ....................................................B - 101

________________________________________________________________________________
B-4
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

F.2 PLUMBING / DRAINAGE / FIREFIGHTING SYSTEM .............................................B - 108


F.3 ELECTRICAL SYSTEM ...........................................................................................B - 112

*******************************************

________________________________________________________________________________
B-5
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

PART 'A' : GENERAL

A.1 Scope of Work and General Requirements

This specification covers the design detailing, supply, installation and


commissioning of the BMS and automatic controls installation for the Doha
College Al Wajba new campus.

a) A specialist BMS subcontractor shall be appointed to carry out this work.


Power wiring into the distributed field equipment such as inverters on fan and
pump motors and BMS control panels shall be by the electrical / HVAC & P&D
subcontractor. Power and control wiring out of the distributed field equipment
shall be by the BMS subcontractor.
b) The BMS subcontractor shall detail and finalize the BMS Controls performance
design and undertake all aspects of the project associated with the BMS and
Automatic Controls. The complete project specifications and drawings,
particularly the Mechanical, Electrical, Public Health and Communications
divisions indicate the extent of work of the BMS installation and should be read
in conjunction with this section. The scope of works for the BMS subcontractor
covers all areas of the project.
c) The BMS subcontractor shall make sure that the system allows for expansion
by up to 20% in the number of points without additional hardware. The
specialist shall include in his tender price for all the BMS, controls and the
control panels required for the control of all the plant indicated in the MEP
drawings, schedules and specifications.
d) The specialist BMS subcontractor shall provide a Building Management and
Automatic Control System with for the building services installations to include
monitoring, trend logging, alarming, sequence control and environmental
control of the mechanical and electrical plant and equipment for the project.
e) The BMS system design shall be detailed and finalized by the BMS specialist
subcontractor in line the requirements of the full project MEP services
specifications and drawings. The specialist subcontractor shall also supply all
materials, install, and commission and finally set up, adjust and tune the
installation to meet intent of the performance specification and the operational
requirements. Unless indicated otherwise supply inverters, control
components and equipment from one manufacturer throughout up to Engineers
approval.
f) The BMS system specialist Contractor shall take due account of possible
phasing of the works and shall agree a programme for completion in stages
with the MEP subcontractor.
g) The BMS Controls System Specialist Contractor shall provide the following
minimum services:

________________________________________________________________________________
B-6
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

1. Provide wiring and layout diagrams for all BMS control panels indicating
all necessary interfaces, hardware, power and control circuitry. All wiring
is to be indicated including "internal" wiring and "field" wiring to remote
devices. Details to be fully coordinated with as-manufactured details from
all other contract divisions and parties including mechanical and
electrical.
2. Provide and select all sensors, switching, contactors, VSD inverters,
control valves and control dampers with suitable actuators according to
authority, flows and static and differential pressure ratings required.
(Installation by MEP subcontractor and kitchen Sub-contractor)
3. Provide supervision during installation of control devices to ensure
correct incorporation into the works.
4. Provide resources to install and finally terminate all BMS equipment,
control panels and network and field controls devices and wiring.
5. Provide resources necessary to label and identify the complete control
system.
6. Provide resources necessary to commission the control systems and
provide test results and documentation for approval.
7. Provide a detailed description of operation of the control systems with
operating parameters, set points and interfaces with other systems.
8. Provide thorough client instruction and training, using clear and concise
operating and maintenance manuals to enable client troubleshooting for
the control system.
9. Provide wiring diagrams showing connection details to all field located
devices.
10. Update drawings and other material as necessary to suit plant and
equipment actually installed.
11. Provide specific routines and specialist software to suit the performance
requirements of this specification.
12. Provide all hardware necessary to comply with this performance
specification.
13. Provide all software to control systems in accordance with the
performance requirements of this specification.
14. Provide a simple user guide specially written for the use of ordinary non-
technical occupants of the apartments and offices which shall explain
clearly the operation of the air conditioning controls in layman’s terms.

h) The Building Management System (BMS) shall control and monitor the building
services providing feedback of plant performance for analysis, and full control
of the plant connected as defined in this Specification. The BMS shall comprise
a series of intelligent outstations, operator terminals and peripherals connected
by a hard-wired or wireless LANs.
i) Ease of use and appropriate and intuitive human interfaces for a layperson is a
key requirement of this specification and such devices shall be selected with

________________________________________________________________________________
B-7
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

attention to detailed performance and good architectural fit. These devices


must be approved by the Supervision Consultant before use.
j) The BMS subcontractor shall co-operate and co-ordinate with other divisions
performing work on this project as necessary to achieve a complete operational
installation. The BMS subcontractor shall also consult the drawings and
specifications of all trades to determine the nature and extent of others’ work.
k) It shall be the duty of the BMS subcontractor to work in co-operation with other
Contractors, and with other sub-contractors, rendering assistance and
arranging the works so that the entire project shall be delivered in an
expeditious, professional and timely manner.
l) The BMS system is required to interface and integrate communications with
the chillers air handlings units, ventilation fan controllers, fan coil units, pump
speed controllers etc. such that all the manufacturers standard operating
parameters are available for display and adjustment via the BMS system.
m) The mechanical services plant and equipment shall be controlled by a
complete system of electronic and electrically operated equipment to provide
full environmental control from either a single stand-alone outstation or a
number of outstations if preferable to the Controls Specialist. The system shall
communicate with the ‘central supervisor’ located in the Energy Managers
office, via the site wide Ethernet and hubs
which shall be extended to cover all new equipment.
n) The Controls Specialist shall design, select, supply and install all necessary
material and labour for the complete installation including, but not limited to,
temperature sensors, control valves, thermostats, actuators, dampers,
pressure switches, inverters relays, contactors, starters, control field wiring,
control panels etc. from a single manufacturer.
o) All power wiring and connections to mechanical equipment and interfaces shall
be by the Controls Specialist. All ELV field wiring and connections to all
controls elements shall be part of the Controls Specialist. Minor containment
eg. conduits shall be by the Controls Specialist. Major containment e. cable
tray and basket shall be by the Electrical contractor.
p) Commissioning and testing of the complete control system shall be carried out
by the Controls Specialist including all calibration and final adjustment carried
out to the satisfaction of the Engineer in accordance with the ASHRAE
Guideline 13-2015 for direct digital Controls Systems. Additionally, Controls
Specialist shall be fully responsible for instructing the Facilities Management
Team in the proper use of the equipment supplied and provide
manuals/drawings as called for elsewhere in the contract.
q) The siting of items of control equipment shall always be such that access for
adjustment and maintenance purposes are not impeded. However, where
items of control equipment are mounted in accessible positions within occupied
areas the control items shall be provided with facilities to discourage
unauthorized interference.

________________________________________________________________________________
B-8
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

r) Control systems shall be arranged such that, in the event of electrical power
failure or other abnormal operating conditions, inherent fail-safe features
prevent potentially hazardous conditions arising. It shall be arranged that in the
event of fire, all items of mechanical equipment shall be shut down indirectly
from the Fire Alarm panel via the BMS.
s) All BMS generated alarms shall be generated in the form of an email, sent to
the facilities manager (mobile hand-held device).

A.2 BMS System

a) The Building management system provided shall include the capability for
multiple users to access the BMS simultaneously from remote locations via the
intranet using dedicated VPN profiles created in the main server. All the
authorization levels of system accessibility are stored within this profile.
Internet access shall be accomplished by use of standard Internet browser
software applications such as Firefox or Microsoft Internet Explorer and shall
not require the use of proprietary access software but shall be high level
password protected. Interface shall be to the entire BMS and shall provide the
capability to monitor all I/O and adjust parameters.
b) The BMS system shall use an open protocol system and fully support a multi-
vendor and system integration environment. To accomplish this effectively, the
BMS shall support and principally use only open communication protocol
standards, and be able to also integrate a wide variety of third party devices
and applications via existing vendor protocols and through the latest software
standards.

c) Specifically, the BMS shall be able to demonstrate:

1. An open and published network protocol


2. Demonstrated and certified connection to a minimum of 200 third-party
device
3. Ability to connect with LonMark and/or BACnet-certified open protocol
devices. Such devices should be able to communicate with BACnet/IP
open protocol standard with the system level peripherals.
4. Must be able to use TCP/IP networking protocol and access all data using
a standard WEB browser such as Firefox or Internet Explorer.
5. Workstation applications must be able to exchange and display graphically
data supplied through third party OBIX, OPC (OLE for Process Control)
Servers and BACnet interfaces and shall be configured to accept data from
the other intelligent systems within the buildings in order to provide

________________________________________________________________________________
B-9
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

supplementary and centralized graphics and alarms of this information in


similar format to the interfaces for internal information on HVAC equipment.
6. The system must be configured and commissioned to export of data to the
Planned Preventive Maintenance programme (PPM), facility and energy
management applications and business reports.

d) The main BMS backbone shall be Fibre and copper running with TCP/IP
standard and shall reside on a bespoke network with the ability to connect to
the client’s Intranet. The BMS workstations and Network Controllers shall
connect directly to the BMS backbone. Network Controller sub-LANs shall be
open protocol such as LON works, BACnet/IP or equal and approved.
Networks shall employ dual redundant communication paths especially in
network dependent applications (such as, but not exclusively, duty/standby and
load sequencing operations) where transmittal of information is vital to the
correct function of the building. All controllers and network devices necessary
for the continued operation of building during power failure shall be supplied
with monitored UPS units by the BMS supplier. All BMS network wiring is to be
the responsibility of the BMS Specialist. This shall include any connections to
the TCP/IP backbone, wiring to FCUs, AHUs, AC Units and any other items of
plant that are to controlled/monitor by the BMS.

A.3 System Integration Interfaces


a) The system shall include the necessary integration hardware and software to
allow this system to integrate with the other control, monitoring, mobile alarm
and information management systems to be operated by the Client over their
ICS network. The contractor shall ensure that a compatible common open
protocol output formats (i.e. BACnet, MODBUS, OPC, OBIX or XML as
required by the application and site wide protocol standards) are provided from
all management and intelligent metering systems and allow for full liaison to
coordinate these outputs with the other intelligent building systems to ensure
common standards and full intercommunication.
b) The specialist contractors and suppliers shall make allowances in their tenders
for all hardware, software and engineering/liaison/workshops/information
exchange needed to achieve a working integration with the other building
systems servers and Graphical User Interfaces. This shall include providing
tables of BMS controller data to allow integration and adoption of naming
conventions to ensure site wide coordination.
c) In particular, BACnet system provided by BMS vendor should comply with the
following basics requirement of BACnet system:

1. BBMD (BACnet Broadcast Management Device) functionality must be


available in the BACnet device to allow communication over different
networks / VLAN.
________________________________________________________________________________
B - 10
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

2. Foreign device registration to be enabled in the BACnet device in which


BBMD function is enabled.
3. Option to modify BACnet PORT number.
4. Unique Network Number – BACnet controllers are grouped into different
BACnet networks based on site requirement, care should be taken while
allocating network numbers for different BACnet networks to make sure that
duplication of networks can be avoided.

5. Unique device ID – Every BACnet device should have device number which
is used for communicating to corresponding device. Device number
allocation should be done in such a way that device IDs are not duplicating
in the system.
6. BACnet vendor should submit PICS document explaining features of the
BACnet system.
7. BACnet system should be capable of working in multiple VLAN
environments with capability to route alarm/event/trend data to/from different
buildings.
8. BACnet system installed in every building should have feature of
adding/modifying alarm recipients.

d) Configuration Requirement from BMS System for Alarms:

1. Alarms must be generated from the source Supervisory Controller.


2. The BACnet device must have the option of ‘Notification class object’ for
Alarms. This option must be enabled by the system provider using either of
the following methods:

i. Client’s BACnet ‘Device Id’ address must be ‘Registered’ manually into


the BACnet Supervisory controller by the Provider / Contractor.
ii. Enable automatic ‘Registering’ of the MSI BACnet ‘Device Id’ as a
‘Notification client’ from the MSI system, on the 3rd party BACnet
device.
iii. Each BACnet object for ‘Alarms’ must be configured by System
provider, for parameters like Reference value, Time delay, High limit,
Low limit
iv. Note: Data to be provided to 3rd party contractor by MSI, for
configuration are: BACnet Port number and MSI BACnet Device ID.

e) Following are the typical requirements: Data required from the BMS System
Provider: Data points file in soft copy format, containing the following details:
Object name, Object type, Object instance, Device ID and Object description.
f) Reduced data points such as Common Alarms at Zone or Area level. Points
can also be reduced by assigning multiple states/status to a single data point
such as Alarm, Trouble, and Supervisor etc.
________________________________________________________________________________
B - 11
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

g) Graphical presentations with references to the BACnet points used in the


diagrams. The images and points must match with the actual graphics used in
the BMS. It should also ensure that the given information will suffice
independent design of similar presentation on another system without referring
physically to the original system or any other individual entity.
h) Method statements should be included to explain the graphics, points and
layout of the system.
i) List of Schedules, Trend points, Flow meters and Consumption in BACnet
format
j) The BMS supervisory controller database would be programmed with the
complete set of I/O Points along with necessary alarm and other control
information. The MSI database shall be programmed to automatically generate
various events and control actions on the basis of received data from the BMS
& other sub systems. In addition, the database can be able to configure from
any operator station on the network. The I/O Point information can be modified
on-line without affecting the entire Server.
k) The system shall utilize the passive ICT infrastructure and active ICT
infrastructure for information communication backbone where they have been
provided for this purpose by including IP enabled communication
interfaces/Gateways. Reference shall also be made to these specification
Divisions for the specified cabling. Where supplementary local networks and
field bus communications networks are required to complete the system, these
shall be provided and installed by the BMS subcontractor.

A.4 BMS Alarm Priorities


a) Equipment alarms shall be indicated locally at the field equipment controller, at
the front end BMS supervisor computer and in text format on remote mobile
devices carried by FM staff (pager, SMS text, instant message, email or
similar).
b) The minimum typical requirements for alarms and identifies typical alarm
priorities; level 1 (high priority), level 2 (medium priority) and level 3 (low priority
or maintenance flag). The actual alarm prioritization shall be developed and
implemented during commissioning with input from the client and the facilities
management team.

A.5 System Performance


a) Comply with the following performance requirements:

1 Graphic Display: Display graphic with minimum 20 dynamic points with


current data within 10 seconds.

________________________________________________________________________________
B - 12
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

2 Graphic Refresh: Update graphic with minimum 20 dynamic points with


current data within 8 seconds.
3 Object Command: Reaction time of less than two seconds between
operator command of a binary object and device reaction.
4 Object Scan: Transmit change of state and change of analogue values
to control units or workstation within six seconds.
5 Alarm Response Time: Annunciate alarm at workstation within 45
seconds. Multiple workstations must receive alarms within five seconds
of each other.
6 Program Execution Frequency: Run capability of applications as often as
five seconds, but selected consistent with mechanical process under
control.
7 Performance: Programmable controllers shall execute DDC PID control
loops, and scan and update process values and outputs at least once per
second.
8 Reporting Accuracy and Stability of Control: Report values and maintain
measured variables within tolerances as follows:

i. Water Temperature: Plus or minus 0.5°C.


ii. Water Flow: Plus or minus 5 percent of full scale.
iii. Water Pressure: Plus or minus 2 percent of full scale.
iv. Space Temperature: Plus or minus 0.5 C.
v. Ducted Air Temperature: Plus or minus 0.5 C.
vi. Outside Air Temperature: Plus or minus 1.0 C.
vii. Dew Point Temperature: Plus or minus 1.5 C.
viii. Temperature Differential: Plus or minus 0.15 C.
ix. Relative Humidity: Plus or minus 5 percent.
x. Airflow (Pressurized Spaces): Plus or minus 3 percent of full scale.
xi. Airflow (Measuring Stations): Plus or minus 5 percent of full scale.
xii. Airflow (Terminal): Plus or minus 10 percent of full scale.
xiii. Air Pressure (Space): Plus or minus 2.5Pa.
xiv. Air Pressure (Ducts): Plus or minus 25 Pa.
xv. Carbon Monoxide: Plus or minus 5 percent of reading.
xvi. Carbon Dioxide: Plus or minus 50 ppm.
xvii. Electrical: Plus or minus 5 percent of reading.

A.6 Reference and Standards

a) The latest edition of the following standards and codes in effect and
amended as of supplier's proposal date, and any applicable subsections
thereof, shall govern design and selection of equipment and material
supplied:

1. American Society of Heating, Refrigerating and Air Conditioning


________________________________________________________________________________
B - 13
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

Engineers (ASHRAE).

2. ANSI/ASHRAE Standard 135-2008, BACnet.

3. Uniform Building Code (UBC), including local amendments.

4. UL 916 Underwriters Laboratories Standard for Energy Management


Equipment. Canada and the US.

5. National Electrical Code (NEC).

6. FCC Part 15, Subpart J, Class A.

7. EMC Directive 89/336/EEC (European CE Mark).

8. UL-864 UUKL listing for Smoke Controls for any equipment used in
smoke control sequences.

b) City, county, state, and federal regulations and codes in effect as of


contract date.

c) Except as otherwise indicated, the system supplier shall secure and pay
for all permits, inspections, and certifications required for his work, and
arrange for necessary approvals by the governing authorities.

A.7 Warranty

Shall comply with QCS 2014 Section 22.

The Contractor shall guarantee for a period of 400 days after the practical
completion of the installation that all plant and equipment shall operate free
of any defects due to defective material and bad workmanship and that any
part found defective during this period shall be replaced free of cost by the
Contractor.

Maintenance period for all BMS System all controls, components and
systems etc., shall start only after regular electricity power supply is
available at site.

If the defects are not rectified within a reasonable period, the Client may
proceed to do so by another agency at the Contractor's entire risk and
expense without prejudice to any rights of the Client.

________________________________________________________________________________
B - 14
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

PART ‘B’ : DESCRIPTIONS OF OPERATIONS

B.1 General
a) The BMS control performance specification for the various systems is
described in the following sections. The BMS specialist subcontractor shall
develop, detail and finalize these descriptions of system operation and liaise
with the other contract parties to ensure the latest as-built information is
incorporated in the final control hardware and software system solution.

B.2 Chilled Water Systems

B.2.1 Outline System Description


a) The chilled water system for the secondary school & central hub buildings
(secondary + H1 block) is provided by the air-cooled chillers within chiller
compound located on the roof of the block C2.
b) The chilled water system for the primary school & sports block (primary
+C1+C2+C3) buildings is provided by the air-cooled chillers within chiller
compound 2 located in the on the roof of the secondary sports block C2.
c) Both the chilled water system shall be interlinked with isolating valves
connected with main header. So that chilled water can be circulated to each
other circuited if required.
d) The air-cooled chiller water systems for the chiller compound 1 comprise:

1 5+1 Air cooled chillers sized at of the full load duty each with one chiller
standby.
2 Standby chiller to meet possible future expansion requirements.
3 Integral primary pump per chiller sized at 100% of the chiller full load
duty.
4 Constant flow /variable temperature primary chilled water circuit
operating at 6.6°C (44° F) flow and 12.2°C (54° F) return,
5 4 lead/lag CHW secondary pumps sized at 33.3% of the full load duty.
One number act as standby.
6 Constant temperature/variable flow chilled water circuit to the AHUs and
FCUs operating at 6.6°C (44° F) flow and 12.2°C (54° F) return.
7 Allowance in the chilled water pipework sizing to accommodate possible
future expansion requirements, including valved-off connections at the
top of building CHW pipework risers for ease of extension to additional
upper floors.
8 Pressurization unit

e) The air-cooled chiller water systems for the chiller compound 2 comprise:

________________________________________________________________________________
B - 15
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

1 4 Air cooled chillers sized at same capacity of circuit & chiller compound I
area as full load duty and will meet future load of these block listed
above.
2 Heat pump for swimming pool (Learning & Competition) water heating
and cooling are specified in the pool plant system of each pool. Refer
plumbing Swimming Pool Plant specification.
3 Provision for one additional chiller to meet possible future expansion
requirements, including valved-off connections.
4 Integral primary pump per chiller sized at 100% of the chiller full load
duty.
5 Constant flow /variable temperature primary chilled water circuit operating
at 6.6°C (44° F) flow and 12.2°C (54° F) return,
6 3+1 lead/lag CHW secondary pumps sized same capacity of the full load
duty and one act as standby.
7 Constant temperature/variable flow chilled water circuit to the AHUs and
FCUs operating at 6.6°C flow and 12.2°C return.
8 Allowance in the chilled water pipework sizing to accommodate possible
future expansion requirements, including valved-off connections at the
top of building CHW pipework risers for ease of extension to additional
upper floors.
9 Pressurization unit

B.2.2 Control Strategy (Both Chillers System)

a) The chiller shall be initiated and sequenced in a lead/lag arrangement, as


described below.
b) The lead chiller is enabled by the BMS when either of the CHW secondary
circuit lead pumps are enabled.
c) The lead and lag chillers shall be automatically rotated to ensure even run
hours, whilst the next available lag chiller shall be automatically enabled if a
duty chiller fails.
If the chiller combination is unable to reduce the return water temperature to
set point after a sustained period (15 minutes – adjustable), then the next
chiller combination shall be enabled, and so on. The chillers will then load and
unload in the following sequence to match the increase or decrease in cooling
load:
d) Increasing load: Lead → Lead+Lag1 → Lead+Lag1+Lag2 →
Lead+Lag1+Lag2+Lag3 → Lead+Lag1+Lag2+ Lag3+Lag4 etc.
e) The loading sequence is reversed, upon a reduction in the cooling load.
f) Each packaged chiller shall include: microprocessor controller with touch
screen and display; compressor sequencing controls; integral protection and
fault monitoring devices; water flow proving; internal/external sensors; integral

________________________________________________________________________________
B - 16
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

shunt pumps and expansion system; return water temperature control; BMS
interface for remote enabling, alarm monitoring & set point adjustment.
g) Once enabled, the chiller shall then operate under their own integral controls to
maintain the chilled water return temperature at set point. The chiller control
unit shall provide P+I control of the chilled water return temperature through
sequencing the of the compressors and modulation of the electronic expansion
valve on the evaporator.
h) The BMS shall interface with the chiller control unit to provide chiller enable,
remote reset of the chiller flow temperature set point and monitoring of the
common fault alarm.

B.2.3 Pressurization Units (Both System)


a) The CHW distribution system shall be a sealed system with a packaged
pressurization unit to maintain the working pressure within preset limits during
both normal operation and shut-down.
b) The pressurization unit shall include manufacturers integral control panel, and
duty/standby pumps. The BMS shall monitor a common fault signal via volt free
contact which shall be interlocked with system operation.

B.2.4 Primary CHW Pumps


a) The respective chiller duty primary CHW pump is enabled by the BMS via the
pump control panel, when the chiller is enabled.
b) Lead-lag pumps and chiller shall be automatically rotated to ensure even run
hours, whilst the next available lag pump shall be automatically enabled if a
duty pump fails.
c) Fault monitoring is provided by differential pressure switches installed across
each pump. A common fault alarm, run status and availability status signal
shall be relayed to the BMS system from each pump variable speed control
panel.

B.2.5 Secondary CHW Distribution System


a) The CHW distribution systems shall be a variable volume and shall typically
utilize 2-port control valves at each FCU and 3-port control valves for each
AHU shall be installed on the AHU/FCU at the end of each branch circuit in
order to maintain the minimum flow required by the turndown limit of the pump
VSDs.
b) The secondary CHW pump speeds shall be modulated in sequence to maintain
the preset differential pressure at the end of the chilled water branch circuits,
as sensed by the differential pressure sensors installed in these locations. The
differential pressure sensor set points shall be user configurable and
determined during commissioning by measurement of the static pressure
differential at the sensors.
________________________________________________________________________________
B - 17
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

c) The lead secondary CHW pump is enabled by the BMS via the pump variable
speed drive (VSD), if any of the respective control valves on the chilled water
circuit are more than 20% open. The VSD speed is then controlled by the BMS
to maintain the preset pressure at the differential pressure sensor.
d) If the secondary pump combination is unable to maintain the differential
pressure at set point when operating at 100% speed after a sustained period
(15 minutes – adjustable), then the next lag pump shall be enabled and
modulated until the setpoint if achieved, and so on. The pumps will then load
and unload in the following sequence to match the increase or decrease in
chilled water demand:
e) Increasing chilled water demand: Lead → Lead+Lag1 → Lead+Lag1+Lag2
→ Lead+Lag1+Lag2+Lag3→ Lead+Lag1+Lag2+ Lag3+Lag4 etc.
f) The loading sequence is reversed, upon a reduction in the chilled water
demand.
g) When there is no demand (ie. the 2-port control valves are all closed), the lead
chilled water pump shall be disabled and the lead water chiller shutdown after
the minimum required run-on period.
h) Final detailing of the integration of the controls between the chiller, pumps and
BMS shall be dependent on and specific to the particular equipment
manufacturers selected and shall be carried out by the Controls Specialist
coordinating with the boiler and pump suppliers to achieve the most energy
efficient integrated working system.

________________________________________________________________________________
B - 18
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

B.3 Heat Pumps Heating & Cooling Systems for Swimming Pool Water
(learner & Competition)

B.3.1 Outline System Description


a) The primary source of heating and cooling for the Swimming pool water shall
be provided by a closed loop Heat Pump system comprising of the following:

1 2+1 Air cooled heat pump total capacity of heating of (240 + 90) kw heat
output at 280C and cooling capacity of (196+64) kw output at 320C for the
completion pool is provided.
2 2 No. air cooled heat pump total heating capacity of 180 kw heat output at
280C and cooling capacity of 128 kw out at 320C for learner pool is
provided.
3 Each swimming pool plant (learner and competition) is provided.
Individually 2 nos. circulation pumps for these heat pumps and each pump
is size at 60 % of the full load duly.

B.3.2 Control Strategy


a) The heat pump system and associated primary circulation pump shall be
initiated and sequenced in a lead/lag arrangement, as described below.
b) The lead heat pump is enabled by the BMS when either of the circulation pump
lead pumps are enabled. The lead heat pump shall be automatically rotated to
ensure even run hours, whilst the lag heat pump shall be automatically enabled
if a duty heat pump chiller fails.
c) If the heat pump combination is unable to raise the return water temperature to
set point after a sustained period (15 minutes – adjustable), then the lag heat
pump shall be enabled.
d) The loading sequence is reversed, upon a reduction in the heating demand.
e) The heat pump shall be capable of and configured/commissioned for
simultaneous cooling & heating depending upon water temperature
requirement.
f) Each packaged heat pump shall include: microprocessor controller with touch
screen and display; compressor sequencing controls; integral protection and
fault monitoring devices; water flow proving; internal/external sensors; pumps
and expansion system; return water temperature control; BMS interface for
remote enabling, alarm monitoring & set point adjustment.
g) Once enabled, the heat pump shall then operate under their own integral
controls to maintain the pool water temperature at set point. The heat pump r
control unit shall provide P+I control of the pool water return temperature
through sequencing the of the compressors and modulation of the electronic
expansion valve on the evaporator.

________________________________________________________________________________
B - 19
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_________________________________________________________________________

h) The BMS shall interface with the heat pump control unit to provide heat pump r
enable, remote reset of the heat pump r flow temperature set point and
monitoring of the common fault alarm.

B.3.3 Circulation Pumps


a) The respective heat pump circulation pump is enabled by the BMS via the
pump control panel, when the heat pump chiller is enabled.
b) The lag heat pump circulation pump shall be enabled when the lag heat pump
chiller is enabled. Automatically rotated to ensure even run hours, whilst the
next available lag pump shall be automatically enabled if a duty pump fails.
c) Fault monitoring is provided by differential pressure switches installed across
each pump. A common fault alarm, run status and availability status signal
shall be relayed to the BMS system from each pump control panel.
d) When there is no demand for heating & cooling, the lead circulation pump shall
be disabled and the lead heat pump shutdown after the minimum required run-
on period.
e) Final detailing of the integration of the controls between the heat pump chiller,
pumps and BMS shall be dependent on and specific to the particular
equipment manufacturers selected and shall be carried out by the Controls
Specialist coordinating with the boiler and pump suppliers to achieve the most
energy efficient integrated working system.

________________________________________________________________________________
B - 20
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.4 Air Handling Systems

B.4.1 Outline System Description

a) Air handling systems serve the following areas:

i. Fresh air and general extract ventilation of the teaching & staff areas
throughout the Secondary, Primary and Central Hub blocks is typically
provided by roof mounted Heat Recovery air handling units.
ii. Air conditioning of the large double height assembly spaces provided by
roof mounted Single Thermal Wheel Heat Recovery (STWHR) air
handling units, due to the lower supply air temperature required to
provide space cooling. Supply air distribution generally comprises high
level mixing air supply.
iii. Air conditioning of the various area is provided by roof mounted
recirculating air handling units with fresh air mixing damper sections
incorporated for occupant fresh air and humidity control.
iv.
v. Air conditioning of the large double height swimming pool halls is
provided by roof mounted recirculating air handling units with fresh air
mixing damper sections incorporated for occupant fresh air and humidity
control.
vi. Extract ventilation of each swimming pool hall is provided by roof
mounted extract fans, 50% connected to low level extract integrated into
the seating at the pool edge and 50% from roof level.
vii. Fresh air and extract ventilation of the sports block pool spectator and
wet changing facilities is typically provided by roof mounted Heat
Recovery air handling units.
viii. Fresh air and extract ventilation of the sports block dry changing facilities
and teaching spaces is typically provided by roof mounted Thermal
Wheel Heat Recovery air handling units.
ix. Air conditioning of the large double height sports halls provided by roof
mounted Single Thermal Wheel Heat Recovery air handling units, due to
the lower supply air temperature required to provide space cooling.
Supply air distribution generally comprises high level mixing air supply.
x. Cooling of the electrical sub-station LV room is provided with high
capacity ceiling suspended air handling unit.
xi. Toilet extract is provided by roof mounted exhaust fans with make-up air
provided by the general ventilation systems as detailed on design
drawings.

B.4.2 Normal Operation

________________________________________________________________________________
B - 21
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

a) The AHU components shall be controlled by the BMS through DDC Control
panels and VFD to maintain the supply air temperature and humidity (or the
space supply air temperature and humidity as applicable) to set point, as
measured by temperature and humidity sensors installed in the supply
ductwork (or space). The set points shall be adjustable with suitable password
authorization from the BMS front end supervisor graphics.
b) The supply air temperature set point shall be reset by cascade control from the
conditions measured in the supplied building spaces. The amount of set point
reset shall be limited to +/- 2˚C, adjustable at the BMS supervisor. Where
more than one AHU supplies a common space the AHUs will generate and
control on a common supply set point.
c) Pressure sensors across all fans and filters shall be monitored and used to
indicate and generate alarms at the BMS supervisor and printer during flow
failure or filter dirty conditions.
d) All valve positions and all the intermediate process temperatures, e.g. all off
coil and off wheel temperatures and humidity’s, shall be monitored and
displayed on the BMS supervisor graphics to assist facility management in fault
diagnosis.
e) Plant Alarms shall be generated for all significant (+/- 2°C) temperature
deviations and plant fults.
f) All sensor readings and all control actions shall be trend logged for
commissioning, fault diagnosis and maintenance purposes.
g) A high-level CO2 threshold shall be set, typically 1000ppm, to provide a visual
or audible alarm if the CO2 sensors detect CO2 concentrations above this
level.
h) Outdoor air intake air flow sensors shall monitor the outdoor air flow rate that
the HVAC equipment is providing. Plant alarms shall be generated for all
significant (-15%) air flow deviations from the designed minimum outdoor air
flow rate. The monitoring system shall be configured to deliver a visible or
audible alert to the system operator to indicate that operational adjustments
may be necessary.

B.4.3 Optimized Start Stop Routine


a) The plant shall operate under user adjustable time schedules for each AHU to
be agreed with the building operator. An optimum start stop routine shall be
incorporated to ensure that the spaces are at set point at the start of the
programmed occupancy period.
b) Where any floor or area is out of occupancy the system shall be enabled in
fabric protection mode to maintain a “set back” condition of minimum 14°C,
maximum 32°C, adjustable from the BMS supervisor front screen. If this
condition is detected in an unoccupied area then the AHU and the associated
FCU’s serving the area shall operate to elevate or reduce space temperatures
below the unoccupied threshold.
________________________________________________________________________________
B - 22
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

c) An optimizer shall be used to ensure that conditions in the controlled spaces


are within tolerance at the start of the scheduled occupancy time. The amount
of pre-occupancy advanced start shall be limited to 1 hour (user adjustable).

B.4.4 Fire Mode


a) On receipt of an alarm signal from the fire alarm system the supply fan and
extract fan shall be shut down.

B.4.5 Fireman’s Override

a) On receipt of a fireman’s override signal from the fire alarm system, the AHU
supply and extract fans shall be started and the motorized shutoff dampers
open, in order to purge cold smoke if any from the Staff Processing area and
start the HVAC System.

________________________________________________________________________________
B - 23
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.5 Thermal Wheel Heat Recovery Fresh Air Ventilation

B.5.1 Outline System Description


a) The Thermal Wheel Heat Recovery (TWHR) air handling units are specified for
heat recovery from the exhaust air stream, in order to provide lower energy
conditioned fresh air and general extract ventilation.
b) The TWHR air handling unit is capable of reducing the sensible cooling energy
required to coil and dehumidify the incoming fresh air by up to 75% by
recovering the residual coolth (or heat) from the outgoing exhaust air. This
significantly reduces the cooling energy required for the building.
c) The double stack TWHR air handling unit comprises the supply air section on
the bottom level and the exhaust air section on the top level, connected by a
high efficiency rotary heat exchanger (thermal wheel). The supply air section
incorporates an outdoor air intake motorized damper, 2-stage air filters, thermal
wheel, supply air fan and chilled water cooling coil. The exhaust air section
incorporates an exhaust air intake motorized damper, high capacity bag air
filters, thermal wheel and exhaust air fan. Where free cooling is available
directly from the incoming outside air, the thermal wheels shall be disabled.

B.5.2 Normal Operation


a) The TWHR air handling unit shall be enabled by the BMS through DDC control
panels and VFD in accordance with the preset time schedule to provide the
minimum acceptable background ventilation for the permanent occupants in
the Goods Processing area and to provide positive pressurization of the
building against outside air infiltration.
b) Once enabled, the TWHR AHU motorized shut-off dampers fully are opened,
and the TWHR AHU supply and exhaust fans are enabled to operate at their
preset minimum speed (initially set to 40%) via their integral VSDs.
c) The amount of fresh air shall be controlled to ensure it is sufficient to maintain
the air quality set point as measured by CO2 sensors in the occupied zone or
in the return air ducts. The set point shall be user adjustable and set initially to
800ppm CO2. The BMS shall select the highest CO2 sensor value.
d) Furthermore, the AHU components shall be controlled by the BMS to maintain
the supply air temperature to set point, as measured by a temperature sensor
installed in the supply ductwork. The supply air humidity shall also be
monitored via a humidity sensor installed in the supply ductwork.
e) The supply temperature set point shall be set to 14˚C to initially. The required
supply conditions shall be achieved, firstly by operation of the thermal wheel,
then by operation of the two-port control valve on the cooling coil in sequence.

________________________________________________________________________________
B - 24
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.6 Fan Coil Units Air Conditioning Systems

B.6.1 Outline System Description

a) Fan coil unit air conditioning is provided to the following areas:

i. Air conditioning of the teaching & staff areas throughout the Secondary,
Primary and Central Hub blocks is typically provided by in-ceiling fan coil
units.
ii. Air conditioning of the atriums in the middle of selected teaching blocks is
provided by high capacity vertical type of air handling unit installed in plant
room at ground floor level or first floor level.

b) Each fan coil unit typically comprises a return air plenum with return air
temperature sensor, air filter, chilled water coil, monitored condensate drip
tray, variable speed EC/DC motor supply fans, supply plenum/duct with
supply air temperature sensor, supply ductwork, supply and return air
circular/square diffusers and Co 2 Monitor in rooms.

B.6.2 Normal Operation


a) Fan coil unit shall be operated by local DP switch
b) Contractor shall supply and installed the DDC for each fan coil or common for
FCU in the room. DDC shall be linked to Co2 monitor and BMS system.
c) A motorized two way modulating type diverter valve shall be installed in the
return line of each fan coil unit class room /office fan coil unit.,
d) Fan coil unit shall be connected to room thermostat which shall be operated by
the teacher / Staff only.
e) The diverter valve shall regulate the flow of chilled in response to signal from
DDC controller have temperature sensor in the return air duct and remote set
point in the thermostat.

B.6.3 Fire Mode


a) On receipt of an alarm signal from the fire alarm system, the FCU shall be
disabled.

________________________________________________________________________________
B - 25
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.7 ITC Center Block S-5 & P-1 Air Conditioning

B.7.1 Outline System Description


a) Air Conditioning of the ICT Centers (Main Server Rooms) is provided by duty
precision air conditioning unit connected to the building chilled water cooling
systems, with standby DX Precision AC unit.
b) High capacity, higher static pressure down flow precision unit with a high
sensible heat ratio are used to meet the cooling demand.
c) Smoke detected linked to the fire alarm panel shall shown the Unit in the
event of fire or smoke being detected within the ICT equipment rooms and
prior to activation of the gas suppression system.
d) The high capacity Precision unit and associated controls shall be supported
from the essential electrical supply.

B.7.2 Control Strategy


a) The Main Server Rooms space temperature shall be maintained at 20°C with
humidity control.

B.7.3 Normal Operation


a) The high capacity precision AC unit operate 24/7 to provide continuous
ventilation and cooling to the Main Server Rooms
b) The high capacity Precision unit components shall be controlled by the BMS
to maintain the space air temperature and humidity to set point, as measured
by wall mounted or return air temperature and humidity sensors.
c) The required room conditions shall be achieved by modulation of the three-port
control valves on the Precision unit cooling coils or by modulation of the
cooling control unit supplying the standby DX Precision unit.
d) The standby DX Precision unit is enabled by the BMS using standby control
and 2-stage temperature control via the room temperature sensor and humidity
sensor.
e) In the event that the duty Precision unit goes into fault or the room temperature
rises above the 2nd-stage cooling set point, then the standby DX Precision unit
shall be enabled. The 1st-stage cooling set point shall be set to 20°C and the
2nd-stage cooling set point shall be set to 24°C. The standby unit shall be
disabled when the duty Precision unit fault is cleared and the unit returned
and/or when the room temperature drops below 20°C.
f) Once enabled, the DX Precision unit shall operate under their own on-board
controls via the temperature / humidity controller.
g) The BMS shall provide enable, status and fault monitoring as per the standard
DX Precision unit requirements.
h) Room over temperature alarm shall be provided. The initial set point shall be
24°C.

________________________________________________________________________________
B - 26
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.8 Electrical Substation Air Conditioning

B.8.1 Outline System Description


a) Air Conditioning of the Electrical Substations is provided by Celling
suspended AHU connected to the building chilled water cooling systems.
b) High capacity, higher static pressure ducted AHU with a high sensible
heat ratio are used to meet the cooling demand.
c) High capacity AHU shall consist of pre-filter, cooling coil, supply fan(s),
supply & return ductwork and grilles.
d) The high capacity AHU and associated controls shall be supported from
the essential electrical supply.

B.8.2 Control Strategy


a) LV Switch room space temperature shall be maintained at maximum 28°C.

B.8.3 Normal Operation

a) The high capacity AHU operates 24/7 to provide continuous ventilation and
cooling to the electrical substations.
b) The high capacity AHU components shall be controlled by the BMS to
maintain the space air temperature to setpoint, as measured by wall
mounted or return air temperature and humidity sensors.
c) The required room conditions shall be achieved by modulation of the
three-port control valves on the AHU cooling coils or by modulation of the
cooling control unit supplying the standby AHU.
d) Once enabled, the AHU shall operate under their own on-board controls
via the wall mounted controller.
e) The BMS shall provide enable, status and fault monitoring as per the
standard AHU requirements.

________________________________________________________________________________
B - 27
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.9 Security Hutt Air Conditioning & Toilet Extract Systems


a) Cooling of the 4No. Security room at the perimeter entrances is provided
split system units (one per Security room).
b) Extract ventilation of the toilet within each Security Hut is provided by a
wall mounted extract fan operated off the light switch with an integral run-
on timer set to 5 minutes (adjustable).
c) No interface with the main buildings fire alarm system is required.

B.10 Kitchen Ventilation Systems (Specialist Contractor by the Client)

B.10.1 Outline System Description


a) Kitchen ventilation systems comprise:

1 Supply & Extract ventilation for the kitchen is provided by a roof


mounted supply and extract fans, connected to the cooking hoods and
extract canopies with grease filters.
2 Make-up air provided directly to the cooking hoods by the dedicated
supply air fans mounted on the roof with complete air filtration / sand
trap etc.
3 Specialist contactor to adjust air quantity by their design for kitchen Air
supply and exhaust as required and provided all accessories up to
Clients approval.

B.10.2 Normal Operation


a) The kitchen supply and exhaust ventilation systems shall be enabled by
the BMS in accordance with the preset time schedule.
b) Airflow status shall be provided by current sensing switches (or alternative
approved method).

B.10.3 Fire Mode


a) On receipt of an alarm signal from the fire alarm system, the ventilation
fans shall shutdown.

B.11 Toilet Extract Ventilation Systems

B.11.1 Outline System Description

________________________________________________________________________________
B - 28
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

a) Toilet extract is provided by roof mounted Twin exhaust fans, with make-
up air provided by the general ventilation systems.

B.11.2 Normal Operation


a) The ventilation systems shall be enabled by the BMS in accordance with
the preset time schedule.
b) Once enabled, the exhaust fans are enabled to operate at their preset
maximum speeds.
c) Airflow status shall be provided by current sensing switches (or alternative
approved method).

B.11.3 Fire Mode


a) On receipt of an alarm signal from the fire alarm system, shall close and
the ventilation fans shall shutdown.

B.12 Fire Command Centre

B.12.1 Outline System Description


a) The Fire Command Centre (FCC) located in the C-3 block, shall contain
control and supervisory equipment /panel in accordance with NFPA 101
and the following:
1) Main fire alarm panel (MFAP)
2) Emergency voice communication control panel
3) Fire fighter’s smoke control station (NFPA 92A)

b) In accordance with the Qatar Civil Defence (QCD) Fire Safety Guidelines
(FSG):
1) The Air conditioning or Mechanical ventilation (ACMV) for the Fire
Command Centre shall be provided with secondary power supply
and shall have ductwork independent of any other ductwork serving
other parts of the building.
2) Any part of the supply duct running outside of the Fire Command
Centre which it serves shall be either enclosed or constructed to give
a fire resistance rating of at least 2 hours.
3) The minimum outdoor air supply in non-air conditioned Fire
Command Centre shall be 6 air changes per hour.
c) To this effect, the FCC shall be provided with the following:

1) In-ceiling FCU with full ducted supply and free return, contained
within the ceiling void above the FCC.
2) Fire rated fresh air duct direct to outside providing minimum fresh air
as per ASHRAE standards.
________________________________________________________________________________
B - 29
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

3) The FCU will provide the motive force for drawing in the fresh air.
Which is supplied in the ceiling void by air handling unit on the roof.
4) All lighting and equipment essential for emergency operation in the
FCC hall also be connected to secondary power supply by fire
resistant cables complying with NFPA 70. This includes the FCU
(and fresh air fan, if required).

d) The ACMV systems shall operate based upon end user requirement of
Doha College Operation.

________________________________________________________________________________
B - 30
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.13 Fire Pump Room

B.13.1 Outline System Description


a) The Fire Pump Room is located in the Primary Sports block C1 at Ground
floor, and contains the following:

1) Electric duty sprinkler pump


2) Diesel standby sprinkler pump & associated day storage tank
3) Sprinkler jockey pump
4) Electric duty hydrant pump
5) Diesel standby hydrant pump & associated day storage tank
6) Hydrant jockey pump
7) Sprinkler alarm panel
8) Associate fire pump control panels

b) In accordance with the Qatar Civil Defence (QCD) Fire Safety Guidelines
(FSG):

1) Where located within a building, a separate and dedicated


ventilation system shall be provided for the fire pump room as
detailed on the drawing.
2) Ventilation system must draw fresh air directly from outside the
building.
3) Exhaust fans must be rated for hot gases at 250°C for 2 hours.
4) Power supplies for the exhaust fans must be from Class 1 central
emergency generator through fire rated cables having a minimum 2-
hour fire resistance rating.

c) To this effect, the Fire Pump Room shall be provided with the following:

1) Passive outside air intake with MFSD fitted on the inside of the
intake louvre.
2) Duty in-line axial exhaust fan installed on the roof, drawing outside
air through the fire pump room and across the diesel fire pumps
when operating, then discharging through an exhaust louvre to
outside via fire rated ductwork. Similarly, a MFSD shall be fitted on
the inside of the exhaust louvre.

B.13.2 Fire Mode


a) On receipt of a sprinkler and /or hydrant pump activation signal from the fire
alarm system, the MFSDs shall open and the duty exhaust fan shall be
enabled.
b) Airflow status shall be provided by current sensing switches (or alternative
approved method).

________________________________________________________________________________
B - 31
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.14 Smoke Control Systems


a) The following smoke control systems are provided:

1. All Atriums, dining, auditorium, sports hall, swimming pool etc. smoke
controls:

i. Mechanical smoke extract ventilation of these areas are provided in


accordance with QCD Fire Safety Guidelines, as these areas forms
part of the fire egress path (unlike other buildings).
ii. Roof mounted duty in-line axial exhaust fans, drawing exhaust air
from high level of the atrium and discharging above the roof, in
order to maintain a smoke free layer within the occupied zone of
Level 01, thus enabling occupants to evacuate the building safely.
iii. Make-up air via the automatic fresh air intake Glass Panel, which
shall open automatically. When smoke exhaust system operated by
Civil Defense / Authorized Staff.

b) Upon activation of a fire or smoke detection or sprinkler head within these


areas Form block S3, the fire alarm system shall enable the smoke
clearance systems via the fire fighter’s smoke control station in the FCC
c) The MFSDs on the exhaust fan inlet shall open and the duty exhaust fan
shall be enabled.
d) Should the duty exhaust fan fail then the standby exhaust fan shall be
enabled.
e) The ventilation plant serving the rest of the building shall remain shut down.

B.15 Fire Alarm Interface


a) Fire alarm interfaces with the BMS systems are detailed in the electrical
drawings, specifications and schedules.
b) The BMS shall monitor the fire alarm signals from the building fire alarm
panel and fireman’s override controls, and shall shutdown/enable
mechanical services plant in accordance with the Fire Safety Strategy
Report Cause & Effect Matrix.

B.16 Fire Alarm Condition


a) On receipt of an alarm signal from the fire alarm system, the BMS shall:

1) All air handling units shall shut down.


2) All fan coil units shall shut down.
3) All ventilation fans shall shut down.
4) All chiller plant and associated pumps shall shut down

b) All air conditioning plant serving ICT Equipment Rooms shall remain
operational.
________________________________________________________________________________
B - 32
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.17 General Ventilation Systems Control in a Fire Situation


a) The BMS shall interface with the fire alarm system contacts and the
following alarms shall also be picked up from the Main Fire Alarm Panels.

1) Common Panel Fault


2) Fire Condition
3) Fault condition

b) On fire alarm initiation, a fire signal shall be relayed by the fire alarm to the
appropriate motor control centre panel (MCCP), inverters and motorized
fire and smoke dampers (MFSDs) depending on the location where the fire
is detected.
c) Multiple read back alarms from plant shall be prevented by the software
alarm masking and duplication by the BMS of the actions of the fire alarm
command. The plant shall then operate as per the detailed Fire Alarm
cause and effect strategy matrix, but as a general overview only and to be
confirmed by the BMS subcontractor during commissioning, in the following
manner:
d) All supply fans for a specific area in alarm shall shut down.
e) Extract fans shut down.
f) When the fire alarm panel is reset, the plant shall automatically come in to
operation in a pre-programmed orderly and staggered sequence which
minimizes the start-up load upon the individual panels and electrical
system.
g) When the fire alarm system goes into an evacuation state, for a particular
area or areas of the buildings, the fire dampers shall operate and the
relevant fans shall come into operation.
h) Wiring from fire alarm and fireman’s override inputs and from control panels
to smoke dampers shall be in fire resistant cable e.g. Pirelli FP400 to BS
6387. See electrical and fire alarm specification for detailed cable
specifications.

B.18 Life Safety Generator (LSG) Fuel Transfer Systems


a) Life Safety Generators (LSG) are provided on the roof above the following
electrical substations:

1. Electrical Substation (block S1)


2. Electrical Substation (block H1)
3. Electrical Substation (block C1)
4. Electrical Substation (block C2)
5. Electrical Substation (block C3)

b) Each LSG is provided with day tank incorporated into the generator sub-
base, sized for a minimum of 4hrs full load continuous operation of the

________________________________________________________________________________
B - 33
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

LSG, thus providing a 1hr buffer over the QCD requirement for 3hr
autonomy.

c) There is no bulk fuel storage facility. Instead there is a manual operated


fuel transfer system per LSG comprising of the following:

1) Fuel fill valve assembly


2) Fire valve
3) Bunded tank sized for 110% of the day tank capacity, with high
and low level alarms
4) Bund tank air vent to atmosphere
5) Gear transfer pump with non-return valve & manual direct start-up
box.
6) Supply and overflow pipework to the roof mounted LSG, enclosed
within outer tube casing (pipe-in- pipe)

d) When a LSG fuel tank gauge drops below 3/4 full, then an external audible
alarm shall sound and a flashing beacon shall illuminate outside the
substation to indicate that the LSG day tank needs refueling.
e) The fuel system shall be hardwired to operate as a standalone system. It
shall be interlocked with the fire alarm system and local emergency shut off
devices.

________________________________________________________________________________
B - 34
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.19 Domestic Water Systems

B.19.1 Outline System Description


a) The domestic water systems comprise:

I. Incoming main pressure potable cold water supply from the street,
complete with KahraMaa water bulk utility meter.
II. 48 hours ambient potable water storage in the 2-section below
ground potable water storage tank.
III. Booster pumpsets for the potable domestic water supplies.
IV. Central domestic hot water generation and storage to the following
areas:
a) Primary Sports blocks C1 provided by calorifiers with electric
immersion heaters.
b) Secondary Sports blocks C2 provided by calorifiers with LTHW
heating coils.
c) Primary Kitchen in block P1 provided by calorifiers with electric
immersion heaters by the specialist sub-contractor.
V. Local electric hot water heating (only where required).
VI. Domestic water pump room is common with irrigation pumps room.

B.19.2 Boosted Cold-Water Supply


a) Each packaged booster sets shall have internal controls supplied by the
booster set manufacturer. A pressure transducer supplied by the
manufacturer shall be fitted into the pipework by the MEP Contractor to
maintain a constant pressure.
b) Once enabled by the BMS, the booster set shall operate under the dictates
of its own integral control panel. A serial interface using MODbus or
BACnet protocols shall be integrated into the BMS to give full diagnostic
information for display on the BMS supervisor graphics.
c) Provide for high level, low level and overflow alarms from each tank
section.
d) Provide for common alarms from all booster sets.
e) The BMS shall monitor and control the circulating pump for the potable
water service storage tanks.

B.19.3 Domestic Hot Water Supply

a) The domestic hot water system (DHW) consists of:

1 Central domestic hot water generation and storage within the Sports
blocks C1 & C2 provided by calorifiers with LTHW heating coils and
________________________________________________________________________________
B - 35
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

electric immersion heaters. A pumped DHW return loop is provided to


prevent deadleg.
2 Local electric hot water heating only where required eg. kitchens, staff
rooms, cleaner’s sinks.

b) In the event that the DHW storage cylinder temperature drops below 60°C,
an alarm condition shall be raised.
c) Blending valves are typically provided at the point of use eg. at showers.

________________________________________________________________________________
B - 36
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.20 Irrigation Water Systems


a) An irrigation system is provided for the external landscape planted areas,
as detailed on the irrigation drawings and in the irrigation specification. The
irrigation system has an underground water storage tank and associated
pump room comprising:

1. Underground reinforced concrete water storage tank sized for 1 day


water consumption.
2. 2 nos. storm water tanks to be also used for irrigation purpose and to
be provided with filters and pump.
3. 2 @ 100% duty/standby booster pumps
4. Sump pump
5. Alarm monitoring, as detailed on the BMS Points Schedule.

b) The irrigation water storage tank shall be provided with the following water
level monitoring, to be centrally monitored by the BMS:

6. low level alarm


7. high level alarm
8. water temperature

c) The irrigation booster pumpsets, sump pumps, irrigation zone control


valves etc. shall be enabled by the central irrigation control system, which
shall have an operator workstation inside the FM building (location to be
confirmed by FM in due course). The BMS shall provide parallel status and
fault monitoring only of key equipment items in order to alert FM staff of any
problems with the irrigation system.
d) The irrigation pump room domestic with pump room is provided with
mechanical fresh air ventilation at 6ach for occupancy and positive
pressurization to prevent dust ingress by a small axial supply fan with filter
unit. The fresh air supply fan shall operate on a continuous 24/7 basis. The
BMS shall monitor the run and fault status.
e) Cooling of common pump room is provided with fan coil unit. Once
enabled, the FCU shall operate under their own on-board controls via the
wall mounted controller. The BMS shall monitor the run status and common
alarm output from each AHU.

Storm water underground pump room to be provided with air intake and
exhaust fan for ventilation.

B.21 Miscellaneous Monitoring


a) The BMS shall monitor the miscellaneous equipment as listed in the BMS
Points Schedule.

________________________________________________________________________________
B - 37
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

B.22 Refinement of the Control Strategy


a) The Controls Specialist shall allow for refining the control strategy during
commissioning and seasonal revisits post occupancy to achieve good
control in the controlled space once the building is operational.
b) The Controls Specialist shall allow to adjust control thresholds and %
opening limits and scaling during commissioning and operation to get the
best conditions in the controlled space. This is especially required in
naturally ventilated spaces and those spaces served by displacement
ventilation systems, but shall apply to all systems installed under this
contract.

B.23 Electrical Systems

All electrical system items to be control and monitor by BMS system i.e. DB’s
lift, fire alarm / fire detection, all system etc. shall be as per electrical
specification and designed drawings.

BMS contractor to co-ordinate the all items with electrical contractor for alarms
status, monitoring etc.

B..23.1 Points for all Electrical Item

Panels and Metering System

LV Panels
SMDB Panels
ACCP Panels
EMSDB Panels

LV Supply

LV Panel
LV Supply Failure

UPS Supply

UPS Supply – ON/OFF/TRIP/Healthy


________________________________________________________________________________
B - 38
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

UPS at ICT HUB – For ICT


UPS at ICT HUB – For CCTV
UPS at ICT Server – For Main Server

Central Battery System

All Central Batteries

Lighting Control System

All LCP panels

Generator control panel

All generator at different roof locations

i. Standby generator run status


ii. Standby generator fault status
iii. Overflow tank level
iv. Overflow tank high level alarm
v. Diesel fuel leak detection system status
vi. Diesel fuel leak detection system alarm

Fire alarm control Panels (All Main & Submain panels)

Fire Alarm ON/OFF/Normal Status

PAVA (All Main & Submain panels)

PAVA ON/OFF/Normal Status

Lifts – (All Lifts)

Lifts - ON/OFF/Normal Status

Gate Barriers (ALL)

Gate Barriers ON/OFF/Normal Status

________________________________________________________________________________
B - 39
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

PART 'C' : SUBMITTALS

C.1 Action Submittals


a) Product Data: Include manufacturer's technical literature for each control
device. Indicate dimensions, capacities, performance characteristics, electrical
characteristics, finishes for materials, and installation and startup instructions for
each type of product indicated.

i. DDC System Hardware: Bill of materials of equipment indicating


quantity, manufacturer, and model number. Include technical data for
operator workstation equipment, interface equipment, control units,
transducers/transmitters, sensors, actuators, valves, relays/switches,
control panels, and operator interface equipment.
ii. Control System Software: Include technical data for operating system
software, operator interface, colour graphics, and other third-party
applications.
iii. Controlled Systems: Instrumentation list with element name, type of
device, manufacturer, model number, and product data. Include
written description of sequence of operation including schematic
diagram.

b) Shop Drawings: Detail equipment assemblies and indicate dimensions,


weights, loads, required clearances, method of field assembly, components, and
location and size of each field connection.
i. Bill of materials of equipment indicating quantity, manufacturer, and
model number.
ii. Schematic flow diagrams showing fans, pumps, coils, dampers, valves,
and control devices.
iii. Wiring Diagrams: Power, signal, and control wiring.
iv. Details of control panel faces, including controls, instruments, and
labeling.
v. Written description of sequence of operation.
vi. Schedule of dampers including size, leakage, and flow characteristics.
vii. Schedule of valves including flow characteristics.
viii. DDC System Hardware:
1) Wiring diagrams for control units with termination numbers.
2) Schematic diagrams and floor plans for field sensors and control
hardware.
3) Schematic diagrams for control, communication, and power
wiring, showing trunk data conductors and wiring between
operator workstation and control unit locations.

________________________________________________________________________________
B - 40
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

ix. Control System Software: List of colour graphics indicating monitored


systems, data (connected and calculated) point addresses, output
schedule, and operator notations.
x. Controlled Systems:
1) Schematic diagrams of each controlled system with control points
labelled and control elements graphically shown, with wiring.
2) Scaled drawings showing mounting, routing, and wiring of
elements including bases and special construction.
3) Written description of sequence of operation including schematic
diagram.
4) Points list.
c) Samples for Initial Selection: For each colour required, of each type of
thermostat or sensor cover with factory-applied colour finishes.
d) Samples for Verification: For each colour required, of each type of thermostat
or sensor.

C.2 Informational Submittals


a) Data Communications Protocol Certificates: Certify that each proposed DDC
system component complies with ASHRAE 135.
b) Data Communications Protocol Certificates: Certify that each proposed DDC
system component complies with BACNet.
c) Qualification Data: For Installer and manufacturer.
d) Software Upgrade Kit: For Owner to use in modifying software to suit future
systems revisions or monitoring and control revisions.
e) Field quality-control test reports.

C.3 Closeout Submittals


a) Operation and Maintenance Data: For HVAC instrumentation and control
system to include in emergency, operation, and maintenance manuals. In
addition to items specified in "Operation and Maintenance Data," include the
following:
1. Maintenance instructions and lists of spare parts for each type of control
device and compressed-air station.
2. Interconnection wiring diagrams with identified and numbered system
components and devices.
3. Keyboard illustrations and step-by-step procedures indexed for each
operator function.
4. Inspection period, cleaning methods, cleaning materials recommended,
and calibration tolerances.
5. Calibration records and list of set points.

b) Software and Firmware Operational Documentation: Include the following:

________________________________________________________________________________
B - 41
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

1 Software operating and upgrade manuals.


2 Program Software Backup: On a magnetic media or compact disc,
complete with data files.
3 Device address list.
4 Printout of software application and graphic screens.
5 Software license required by and installed for DDC workstations and
control systems.

C.4 Maintenance Material Submittals


a) Furnish extra materials described below that match products installed and that
are packaged with protective covering for storage and identified with labels
describing contents.

1 Replacement Materials: One replacement diaphragm or relay mechanism


for each unique valve motor, controller, temperature sensor, CO2 sensor,
positioning relay etc.
2 Maintenance Materials: One temperature sensor/CO2 sensor adjusting
key(s).
3 Maintenance Materials: One pneumatic thermostat test kit.

C.5 Quality Assurance


a) Installer Qualifications: Automatic control system manufacturer's authorized
representative who is trained and approved for installation of system
components required for this Project.
b) Electrical Components, Devices, and Accessories: Listed and labeled as
defined in NFPA 70, Article 100, by a testing agency acceptable to authorities
having jurisdiction, and marked for intended use.
c) Comply with ASHRAE 135 for DDC system components.

C.6 Delivery, Storage, and Handling


a) Factory-Mounted Components: Where control devices specified in this Section
are indicated to be factory mounted on equipment, arrange for shipping of
control devices to equipment manufacturer.
b) System Software: Update to latest version of software at Project completion.

C.7 Coordination
a) Coordinate location of thermostats, humidistats, and other exposed control
sensors with plans and room details before installation.
b) Coordinate equipment with Intrusion Detection to achieve compatibility with
equipment that interfaces with that system and with building master clock.
c) Coordinate equipment with Access Control to achieve compatibility with
equipment that interfaces with that system.

________________________________________________________________________________
B - 42
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

d) Coordinate equipment with Digital, Addressable Fire-Alarm System to achieve


compatibility with equipment that interfaces with that system.
e) Coordinate supply of conditioned electrical branch circuits for control units and
operator workstation.
f) Coordinate equipment with Electrical Power Monitoring and Control to achieve
compatibility of communication interfaces.
g) Coordinate size and location of concrete bases. Cast anchor-bolt inserts into
bases. Concrete, reinforcement, and formwork requirements are specified in
Cast-in-Place Concrete.

________________________________________________________________________________
B - 43
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

PART 'D' : PRODUCTS

D.1 Control Panels


a) The BMS specialist shall provide local BMS DDC Control Panels containing
intelligent controllers and associated control equipment and wiring for the local
control of field equipment for the entire project as described herein and also as
detailed on the mechanical and electrical drawings. The electrical distribution
for the field equipment shall be fed direct as per the electrical Division 26
specifications and drawings.
b) Motor Control Centers and Panels (MCCP) all ACCP to be manufactured in
accordance with BS EN 60439 and shall be provided by electrical contractors,
HVAC & P&D contractors as specified in their respective specification.
c) MCCPs shall be provided as listed in the Equipment Power Schedule indicated
on the power layout on the drawings. “Refer Electrical drawings” and
specifications.
d) BMC contractor to co-ordinate with electrical contractor, HVAC Contractor and
P&D contractor and P&D contractor for all BMS requirement.

________________________________________________________________________________
B - 44
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

D.2 BMS System Structure


a) The Building Management System shall have a PC based web server
supervisor/front end, and have a networked distributed intelligent
controller/outstation structure. The integration with all the other intelligent systems
in the building shall take place at management architecture level, PC to PC using
the LAN. Allow for full OPC and ODBC protocol server and client functionality and
all necessary liaisons with other contract divisions and section providers to effect
a full integration. While some of the following features may not be required as
functions within this current application, they shall be inherent in the design and
may be required for future system expansion:

1 Autonomous Local and Wide Area Networks, electrically and operationally


independent of each other. Capable of connecting up to 12,000 networked
devices such as sensors and actuators, and greater than 250,000 points. Able
to support any number of user terminals, either LAN, WAN or locally
connected. The interchange of data between network devices shall be without
recourse to any central or host computer. The backbone network shall be
based on a building controls industry standard of Ethernet, TCP/IP, BACnet/IP
or industrial Ethernet equal and approved. The network shall operate at a
minimum communication speed of 10 to 100 Mbs baud, with full peer-to-peer
network communication.
2 Standard RS232 or USB interfaces with the ability to communicate with other
PC based systems in local mode. The BMS shall network multiple operator
workstations, network controllers, system controllers, and application-specific
controllers. The first tier network shall provide communications between
operator workstations and first tier DDC (Direct Digital Control) controllers.
3 Have in-built protection against site local lightning strikes, mains surges and
external EM radiation causing the total malfunction of the system. All
components shall comply with EU EMC emission standards.
4 Have monitoring facilities to detect failed outstations and other network
communications devices.
5 Methods of integration shall include building industry standard protocols such
as BACnet/ IP, LonMark/LonTalk, Fast.dde, OLE for Process Control (OPC) or
integrator interfaces between co- operating manufacturer’s systems.
6 Communicate to user terminals and other sites by Ethernet, PSTN, Cellular,
private telephone systems and radio paging. Connect remote printers to the
network for the relay/direct reporting of alarm messages from network devices.
7 System devices shall communicate via the network to send alarms and
monitoring or control data on a request or send basis. A message shall be
acknowledged by the receiving device. If not acknowledged, the message
shall be repeated by the sending device.
8 Battery back-up of network devices should be available for the full operation of
the item for the times indicated in the particular specification.
________________________________________________________________________________
B - 45
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

9 The system shall allow full access via laptop computers at each outstation, for
both commissioning and fault Diagnostic Procedures.

b) The programmable levels of access assigned to individual system operators and


engineers. The password structure shall ensure protection to change any
setpoint, sequence selection, control and monitoring parameter or any equipment
configuration. A common overall system password set and procedure shall be
provided whether access is gained from operators’ terminals, Laptop computers or
keypads on single or multi-site schemes. Manual overrides and set point
adjustments shall have individual programmable levels to control access
according to responsibility and competence of the individual to the priority of the
adjustment. The highest level of password shall access the engineers’ utility for
both outstations and user terminal configuration. At operator terminals a user
logging-on shall be recorded with time/date. Logging off shall be by command or
time-out from non-use of the keyboard or mouse with the event again recorded.
c) The system engineer shall be able to add/delete operators and change levels of
their access. Users shall be able to change their password/pin numbers at will.
d) The BMS shall be integrated with the other intelligent systems in the Heart of
Doha in line with all the contract division specifications and schematics. Industry
standard open protocols shall be adopted to enable full two way transfer of data
and interoperability subject to user password authorisation. All gateways, devices
and routers required shall be provided. High level integration shall be via open,
e.g. OPC and ODBC standards and where appropriate lower level hard wired
connections shall be used.
e) The final system design and network detailing, systems integration of the common
front end information and generation of common format graphics, trend logs,
alarms and management information to provide a full working integrated BMS
installation shall be performed by a BMS subcontractor.

D.5 System Addressing


a) System point addressing shall be by English language text identifiers and
operating selectors via menus and programmable cross references. Forms of
numeric and mnemonic addressing are not acceptable. Multiple point addressing
by plant, location or other set attribute shall be possible both as methods of
interrogation and control. It shall be possible to easily establish the highest/lowest
temperature in a group of similarly labelled sensors, or the widest position of a
group of valves. Attributes shall be assigned, amended either locally or via the
network from a user terminal. Typical applications for these forms of multiple
monitoring/control are Heat pump/boiler demand control, VAV terminals/AHU
inter-control, lighting and energy monitoring.

________________________________________________________________________________
B - 46
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

D.6 Original Equipment Manufacturer (OEM) Supplied Components


a) Where outstations are supplied as dedicated controllers and mounted within OEM
supplied packaged plant (A/C Units, AHUs, Fan Coils etc.), the BMS specialist
shall complete all the necessary work to connect into the networks, commission
the communications and provide the necessary displays. OEM suppliers shall
supply the colour graphical displays compatible with their equipment and all
supporting documentation for inclusion in the O and M manuals.

D.7 Operator Interfaces


a) Operator stations shall comprise IBM or compatible desktop PCs complete with
printer and peripherals as below. Other interfaces at motor control panels shall be
provided by local keypads with LCD displays. Operator interfaces shall be
available in the following formats:

i. Main Operator Stations, main user facilities, IBM PC compatible type


complete with LCD colour screen, Winchester Disk storage, printers,
generally giving access to whole system.
ii. The operator workstation software shall provide context-sensitive help menus
and instructions for each operation and/or application currently being
performed.
iii. All controller software operating parameters shall be displayed on graphics
or user pages for the operator to view/modify from the operator workstation.
These include: setpoints, alarm limits, time
iv. Delays, PID tuning constants, run-times, point statistics, schedules, etc.
v. Portable versions of above for both desk-top and outstation local
interrogation.

b) A web server interface shall be provided that allows building users to access their
BMS data via the internet or intranet using standard browser software. This
interface shall use HTML-based pages to send and receive data from a BMS
system server to a web browser. Two local laptop computers shall be provided
and commissioned for facilities management staff to use for offsite relay of alarms
and simple diagnostic information.
c) The software shall service Microsoft Internet Explorer (8.0 or higher) and the
Firefox (3.0 or higher) browsers.
d) The interface shall provide four levels of user access. Users shall range from
read-only access to BMS data (level 4) to having complete access to view and
modify BMS data and user accounts (level 1).
e) The interface shall provide a user account utility, complete with a user profile
database that includes user ID, encrypted password, access level, and language
preference. Operators with the appropriate access level shall be able to add,
modify, and delete users within the user profile database, as well as change
users’ access levels.

________________________________________________________________________________
B - 47
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

f) The interface shall provide a means by which the user can collect items (BMS
data points) into “summary” groups. This functionality shall allow authorized users
to perform actions ranging from viewing summary groups, to adding items to or
deleting items from groups, to creating new summary groups.
g) The web-based interface shall provide full functionality for user friendly monitoring
and remote fault diagnosis.
h) The interface shall provide navigation tools for easy and intuitive moving between
systems views. In addition, it shall provide tools for gaining access to help and for
logging out of the system.

D.8 Operator Interfaces Facilities


a) Each workstation shall receive and process alarms sent to it by the control
system. The alarm management portion of the operator workstation software
shall, at the minimum, provide the following functions:
i. Log date and time of alarm occurrence.
ii. Generate a “Pop-Up” window informing an operator that an alarm has been
received.
iii. Allow an operator, with the appropriate security level, to acknowledge, delete,
or disable an alarm.
iv. Provide an audit trail for alarms by recording operator acknowledgement,
deletion, or disabling of an alarm. The audit trail shall include the name of the
operator, the alarm, the action taken on the alarm, and a time/date stamp.
v. Record all alarms received at an operator’s workstation to that workstation’s
hard drive.
vi. Allow the operators to view/manage the alarm data archived to hard disk.
Selection of a single menu item or tool bar button shall allow the user to
acknowledge, disable, delete, or print the selected alarm.
vii. Alarms shall be generated by the operator workstation for any controller that
is “off-line” and is not communicating, or that does not have an active control
program loaded.
viii. Changes made to alarm set points from the Operator Workstation shall
directly download to modify the controller alarm management database.
ix. Selection of a single menu item or tool bar button shall print any displayed
alarm report on the system printer for use as a building management and
diagnostics tool.
x. All valve and damper positions, fan and pump data and all intermediate
process temperatures shall be monitored and displayed on the BMS
supervisor graphics to assist fault diagnosis. Alarms shall be generated for all
significant temperature deviations and plant faults. All sensor readings and all
control actions shall be trend logged for commissioning and maintenance
purposes.

________________________________________________________________________________
B - 48
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

b) Reports shall be generated and directed to one of the following: workstation


displays, printers, or disk. As a minimum, the system shall provide the following
reports:

i. All points in the network.


ii. All points in a specific controller.
iii. A listing of a user-defined group of points in the network. There shall be no limit
to the number of user- defined group.
iv. All points currently in alarm.
v. All points in hardware override.
vi. All disabled points.
vii. All weekly schedules.
viii. All or selected point attributes, including, but not limited to:
1) Measurement Values
2) Set points
3) Alarm Limits set to a maximum excursion of +/- 10% of measured value
from set point.
4) Statistics
5) Run Times
6) All programmed holidays and associated schedules.
7) All disabled alarms.
8) All active, unacknowledged alarms.
9) All active, acknowledged alarms.
10) Any and all other controller operating parameters.

c) Reports shall be provided for specific point types, for each logical point group, for
user-defined groups, or for the entire facility.
d) The system shall allow for the creation of custom report point groups that shall be
capable of including points from multiple controllers.

1) The number of custom reports or display groups shall be limited by the


amount of available system memory.
2) Selection of a single menu item, tool bar item, or tool bar button shall
print any displayed report on the system printer for use as a building
management and diagnostics tool.

e) A time schedule programme facility for time-of-day scheduling and override


scheduling of building operations shall be provided. As a minimum, the following
time schedules shall be provided:

1) Weekly schedules.
2) Temporary override schedules.
3) Special Holiday schedules
4) Monthly calendars.
5) Holiday scheduling system.
________________________________________________________________________________
B - 49
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

6) Weekly schedules shall be provided for each piece of equipment with a


specific time use schedule. Each schedule shall include columns for each
day of the week, as well as holiday and special day columns for alternate
scheduling on user-defined days. Equipment scheduling shall be
accomplished by simply inserting use and non-use times into appropriate
information blocks on the spreadsheet.

f) Schedules shall be provided for each system or sub-system in the facility. Each
schedule shall include all points residing within the system. Each point may have
a unique schedule of operation relative to the system use schedule, allowing for
sequential starting and control of equipment within the system. Scheduling and
rescheduling of points shall be accomplished easily via the system schedule
spreadsheets.
g) Monthly calendars for a 12-month period shall be provided that allow for simplified
scheduling of holidays and special days in advance. Holidays and special days
shall be user-selected with the pointing device or keyboard, and shall
automatically reschedule equipment operation as previously defined on the
weekly schedules.

D.9 Main Operator Station


a) BMS Operator Station shall be provided within the Facilities Management (FM)
office, within the FM Pavilion building C3.
b) The operator station equipment manufacturer shall be the latest available and as
recommended by the BMS manufacturer. Alarms shall be relayed out of hours to
an alarm printer at one of any of the manned security desks at desks on the other
levels as designated by the end user. Future relocation to the other locations shall
be supported by the installed network infrastructure. The alarms shall also be
relayed to the laptop computers which are used by the operators. The operator
stations shall be supplied with suitable UPS back-up.
c) The BMS Operator Stations shall provide full facilities as follows:

1 Direct connect to Plant processors


2 User friendly graphics package
3 Storage of trend and data history
4 Transfer of data storage to data-manipulation package
5 Broad band Modem capability over PSTN or VPN profile facility through
WAN.
6 Multi-user capability

d) The Operator Stations provided shall be an Intel Pentium processor with the
necessary RAM extended memory and hard disk storage to provide adequate
operating speed and data archiving to suit the system requirements. The
components shall comprise the following:
e) PC Hardware – The personal computers shall be configured as follows:

________________________________________________________________________________
B - 50
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

1 Hard drive backup system


2 Network interface
3 DVD RW Drive
4 LCD screens
5 Motherboard: With 8 integrated USB 2.0 ports, integrated Intel Pro 10/100
(Ethernet), integrated audio, bios, and hardware monitoring.
6 Processor: Intel Core i7-4700MQ.
7 Random-Access Memory: 32GB.
8 Graphics: Video adapter, minimum 1600 x 1200pixels, 64MB video
memory, with TV out.
9 Each LCD – 19” XWGA Monitor 1600 x 1200 NI resolution minimum; .26 or
better dot pitch and 72 Hz. minimum vertical refresh rate or max resolution;
365k colours, 64MB video memory.
10 Hard-Disk Drive: 500GB.
11 DVD-ROM Read/Write Drive: 48x24x48.
12 Keyboard: QWERTY, 105 keys in ergonomic shape.
13 Microsoft three button optical bus mouse.
14 Uninterruptible Power Supply: 2 kVa.
15 Operating System: Microsoft Windows 10 Professional with high-speed
Internet access.
i. ASHRAE 135 Compliance: Workstation shall use ASHRAE 135
protocol and communicate using ISO 8802-3 (Ethernet)
datalink/physical layer protocol.
ii. LonWorks Compliance: Control units shall use LonTalk protocol and
communicate using EIA/CEA 709.1 datalink/physical layer protocol.
iii. BACNet Compliance: Control units shall use BACNet protocol and
communicate using appropriate datalink/physical layer protocol.

f) Peripheral Hardware

i. Alarm printers (one per BMS supervisor workstation and user


designated security desk):
a) Printer Make – Epson or equal
b) Printing Method –Minimum 24-Pin Impact Dot Matrix, line feed.
c) Print Speed – at least 270 Characters Per Second, Per Line
d) Buffer – not less than 256 K Input Print Buffer
ii. Reports printer (one per BMS supervisor workstation):
a) Printer Make – Hewlett Packard DeskJet or equal
b) Print Speed – not less than 600 DPI Black, 300 DPI Colour
c) Buffer – at least 256 K Input Print Buffer
d) Colour Printing – Include Colour Kit

g) Application Software:

i. I/O capability from operator station.

________________________________________________________________________________
B - 51
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

ii. System security for each operator via software password and access
levels.
iii. Automatic system diagnostics; monitor system and report failures.
iv. Database creation and support.
v. Automatic and manual database save and restore.

________________________________________________________________________________
B - 52
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

vi. Dynamic colour graphic displays with up to 20 screen displays at once.


vii. Custom graphics generation and graphics library of HVAC equipment
and symbols.
viii. Alarm processing, messages, and reactions.
ix. Trend logs retrievable in spreadsheets and database programs.
x. Alarm and event processing.
xi. Object and property status and control.
xii. Automatic restart of field equipment on restoration of power.
xiii. Data collection, reports, and logs. Include standard reports for the
following:

a) Current values of all objects.


b) Current alarm summary.
c) Disabled objects.
d) Alarm lockout objects.
e) Logs.
f) Custom report development.
g) Utility and weather reports.
h) Workstation application editors for controllers and schedules.
i) Maintenance management.

h) Custom Application Software:

i. English language oriented.


ii. Full-screen character editor/programming environment.
iii. Allow development of independently executing program
modules with debugging/simulation capability.
iv. Support conditional statements.
v. Support floating-point arithmetic with mathematic functions.
vi. Contains predefined time variables.
i) Diagnostic Terminal Unit: Portable notebook-style, PC-based microcomputer
terminal capable of accessing system data by connecting to system network with
minimum configuration as follows:

i. System: With four integrated USB 2.0 port, integrated Intel Pro
10/100 (Ethernet), integrated audio, bios, and hardware
monitoring.
ii. Processor: Intel Core i7-4700MQ.
iii. Random-Access Memory: 8GB.
iv. Graphics: Video adapter, minimum 1024 x 768 pixels, 64MB
video memory.
v. Monitor: 17 inches, LCD colour.
vi. Keyboard: QWERTY 105 keys.
________________________________________________________________________________
B - 53
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

vii. Hard-Disk Drive: 300GB.

viii. DVD-ROM Read/Write Drive: 48x24x48.


ix. Pointing Device: Touch pad or other internal device.
x. WiFi wireless LAN adaptors: Intel 7260
xi. Battery: 100Wh

D.10 Software
a) All operator station software shall run under the latest compatible Microsoft
operating system with facility of pre-emptive multi-tasking operating system
allowing other facilities programmes to run concurrently with the BMS. When
other software is operational, the software shall be configured to allow BMS
alarms to come to the front end. BMS software shall be modular and standard to
the manufacturer and supplied as a complete package with back-up copies,
manuals and operators instructions. The specialist contractor shall
supply the original software with all licences, permissions, warranties etc. required
for the full operation of the BMS. The workstation computer shall have the
following characteristics and functionality:

i. Allow generic components to be used and shared with other OPC-


compliant clients and systems.
ii. Serve as the “translation service” for the various languages used by
the diverse systems with which it communicates.
iii. Support multiple clients running on both local and remote machines in
the network.
iv. Control the interaction and communication between workstation
applications (on clients) and the BMS by providing standard methods
for sharing and exchanging data between the BMS and other systems.
v. Compatible anti-virus software.

b) The BMS terminal software shall provide the following facilities:

i. Colour graphics displays (see under).


ii. Dynamic text displays (see under).
iii. Setpoint and Manual overrides with individual password levels.
iv. Alarm annunciation/acknowledgement.
v. Alarm history file.
vi. Trend graphs with up to 4 overlays with intuitive and easy to use
operator scaling and colour options.
vii. Instantaneous data plots of any chosen analogue parameter with
choice of time interval (not necessarily trend logged).
viii. Operator manning schedules and alarm re-transmission.
ix. Time schedules, global/local incorporating holidays/special days.

________________________________________________________________________________
B - 54
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

x. Multilevel Password access, controls and set-up.


xi. Printer/Plotter control to allow printer to log alarms/password entry/exit
and the plotter for printing graphs/displays.
xii. Automatic Archive/re-display of trend graphs, display pages and plant
condition.
xiii. Data analysis and costing programmes.
xiv. Automatic configured Direct Data Exchange to third party software
such as Excel and ODBC for compatible software.
xv. Engineer’s Utility giving access to outstation and operator terminal
configuration.

c) The Building Management System shall be configured to provide, but not be


limited to, power monitoring reports, tenant billing reports, maintenance
scheduling and management reports; and display information through commonly

compatible language driven software.) as agreed with the end


user during the design development and submittal process.

d) Colour Graphic Diagrams:

1 Shall be supplied displaying the following features:

a) Each and every connected point, status conditions (Running/Stopped


etc.), analogue Values with engineering parameters ('F, %RH, 1/s
etc.), Output positions (% open, rpm etc.). Units shall be displayed
where trend data is graphed or displayed.
b) All valve and damper positions, fan and pump data and all
intermediate process temperatures shall be monitored and displayed
on the BMS supervisor graphics to assist fault diagnosis. Alarms shall
be generated for all significant temperature deviations and plant
faults. All sensor readings and all control actions shall be trend logged
for commissioning and maintenance purposes.
c) All calculated parameters as dictated by the controls specification,
(average, highest, lowest etc.).
d) Selected optimiser switching times, (start, stop).
e) Adjustable set points and overrides.
f) Current sequences in operation.
g) Energy/efficiency calculations.
h) Alarm conditions, shown high-lighted.
i) Click-boxes to gain text panels, pre-configured graphs and other
displays.
j) To select pre-configured control actions.
k) Real time data
l) Customised control panel
________________________________________________________________________________
B - 55
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

m) Use of graphic formats


n) 3D symbol library
o) Sketches/diagrams showing the lay-outs and menu forms shall be
supplied prior to data entry for comment by the Engineer, end users
and Employer. The graphics and supporting controller software shall
allow an operator to make simple changes such as manual override
of status, set point adjustment and valve position subject to a suitable
level of password authorization. This shall allow simple basic system
diagnostic checks without recourse to engineering mode.
p) Generally colour displays shall be supplied on the basis of one per
plant, with main and cross indexing/paths to allow movement between
the displays in a logical manner. An exit to the head/index page shall
be available from each display.
q) The correct performance of the displays shall form part of the plant
commissioning procedures.
r) An engineer utility allowing new displays to be created and changes
made to those formatted shall be supplied. The use of this
programme shall be considered for ease of use and its operation shall
be incorporated in the engineers training.

e) Dynamic Text Pages - Text pages shall be configured associated with each item
of plant. The page shall display the current state, hours run, number of starts etc.
and other conditional data. It shall also record basic data relating to the plant,
manufacturer and model number. Editing the text data shall be by a simple word
processor package. Text pages shall have click-pad facilities to select moves to
other pages, reset counters and adjust operating overrides in the same manner as
for the colour graphics.
f) Operation from graphics – It shall be possible to change values (set points) and
states in system controlled equipment by any of the following methods of operator
interaction:

i. Pick points –Any object shall be configurable as a pick point. In such


cases specific actions can be associated with selecting the object with
either the left, middle, or right mouse button:
ii. Load a specific graphic.
iii. Drag/Drop to load a graphic in a selected window.
iv. Link forward or backward to another graphic.
v. Change or toggle the value of an object.
vi. Launch an executable application.
vii. In addition to pick points certain methods of changing set points shall
be available and other analogue values shall be configurable implicitly
as part of a graphic.

________________________________________________________________________________
B - 56
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

viii. Graphic editing tool – A graphic editing tool shall be provided that
allows for the creation and editing of graphic files. The graphic editor
shall be capable of performing all drawing functions, defining all
ix. calculations to be executed as part of the graphic, defining all
animations, and defining all runtime
x. binding. It is not acceptable for separate programs to be required to do
these various functions.
xi. Basic drawing functions – In addition to the ability to create / edit any
of the objects listed above, the following basic drawing manipulation
functions shall be provided as a minimum:
1. Group
2. Ungroup
3. Move object to back
4. Move object to front
5. Free rotate object
6. Align objects
7. Space object
8. Copy
9. Paste
10. Duplicate

g) The BMS system shall be provided with a very complete symbol library containing
all of the basic symbols used to represent HVAC, FIRE, P&D, ELECTRIC and
SECURITY components of a typical BMS system.
h) Symbols shall be able to be added to any graphic display being constructed by
simply dragging the symbol from the library to the graphic under construction.
i) The user shall be able to add any number of new symbols to the symbol library.
Symbol generation shall include all of the abilities described for the graphic editor.
j) Any drawing—including all objects contained therein, and all animation definitions,
and all action definitions—shall be able to be grouped and saved into the symbol
library for re-use in graphic displays. Symbols shall be able to include implicit
bindings or relation bindings, as described in the following section.
k) Trend and change of value data shall be stored within the controller and then
uploaded to the trend database(s). Uploads shall occur based upon one of the
following: user-defined interval, manual command, or when the local trend buffers
are full.
l) Alarm Management - Alarms generated by any outstation shall be processed by a
main operator’s terminal to sort into at least 100 alarm priorities. Each type may
have any combination of the following parameters selected by the operator:

1 Alarm general/critical, outstation group, point label, location.


2 Retransmission destinations with operator time schedule.
3 Call associated plant display.
4 Store associated plat parameters on initiation.

________________________________________________________________________________
B - 57
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

5 Select print action.


6 Select audible alarm.
7 Log to alarm file.
8 Password level for acknowledgement.

D.11 Outstation Local User Interface/Keypads


a) Keypads shall provide local displays of point conditions on outstation within each
motor control panel, and allow local set-point adjustment and manual override.
Any changes shall be protected by the password system. Keypads shall be
available either as pocket portable or mounted at the outstation or control panel.
Keypads shall be supplied as follows:
b) 5 portable keypads shall be issued to the Employer at hand-over.
c) The BMS subcontractor shall provide a 2 no portable operator terminal. This
terminal shall be provided for full command entry, information management,
network alarm management, and database management functions. The terminal
shall be configured as follows:

1 Personal Laptop Computer Manufacturer – DELL, Compaq, or Toshiba.


2 16 GB RAM (minimum) – Microsoft Windows 7 Professional with BMS
software system.
3 2.1 GHz or Faster Clock Speed Pentium Intel Core 2 Duo Microprocessor.
4 PnP compliant Intel motherboard.
5 300 GB Hard Drive.
6 (1) DVD-R/RW Drive,
7 (1) Serial (8) USB and (1) Parallel Ports.
8 1 Keyboard with 83 keys (minimum).
9 Integral 2 button Track Point or Track Ball.
10 15.6” WXGA 1366 x 768 resolution high definition WLED display with 512
KB memory.
11 Two PCMCIA Type II or one Type III card slot.
12 ADSL or broad band Modem access interface
13 Complete operator workstation application software package, including any
hardware.
14 Original printed manuals including DVDs for all software and peripherals.
15 Original installation DVDs for all software, device drivers, and peripherals.
16 Software registration cards for all included software shall be provided to the
Employer.
17 Carrying case.
18 Spare battery.
19 External power supply/battery charger

D.12 Remote Printer

________________________________________________________________________________
B - 58
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

a) A remote A4 size line feed printer shall be provided. It shall be fitted with fan-fold
paper with a complete box of spare paper provided at hand-over. The printer
shall record all out-of-hours critical and system alarms and print the event type,
time and date along with text commands for action when alarms are re-
transmitted by a main operator terminal. An audible alarm with reset button to
silence shall be provided.

D.13 Autodial Modem


a) Not required on this Project
b) If remote access is required and access to an IP address is not available directly
then autodial modems shall be provided to allow communication over the
(PSTN/Private) network between the Site and the BMS specialists Local Office.
The autodialler hardware and its operative software shall meet Local Telephone
Authority approval, with pulse and tone dialling ability. The approval number,
Ringer Equivalence Number and line/gain specification required is to be included
in the works by the BMS subcontractor.
c) The modem with its controller and network interface shall be mounted within each
PC. The unit shall be battery backed to allow both the retention of the
programmed numbers and communication in the event of a mains failure. Should
a connection attempt fail more than 5 times the modem controller shall send an
alarm to a specified user terminal.
d) The BMS subcontractor shall fully configure and commission the auto-dialler(s)
adding telephone numbers for all dialled first and default addresses for reports,
faults and system alarms.

D.14 Fire Detection/BMS System Connection


a) Adequate interface connections shall be provided by the BMS subcontractor for
the requirements for each part of the building. The fire alarm system shall be hard
wired to the field devices, BMS network controllers/ control panels and smoke
dampers to provide the fire alarm, fireman’s override and reset signals for each
equipment fire alarm and discrete fire zone or compartment of the building.
b) The BMS subcontractor shall include for taking these signals and arranging the
software such that each system controlled by the BMS shall operate as defined
within this Specification.
c) Power supplies for the fire and smoke dampers shall be controlled by inputs from
the fire alarm system.

D.15 Building System Controllers


a) Sufficient direct digital controllers (DDC) shall be provided to meet the site
requirements.
b) The controller shall be a fully user-programmable, supervisory controller. The
DDC controller shall monitor the network of any distributed application-specific

________________________________________________________________________________
B - 59
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

controllers, provide global strategy and direction, and communicate on a peer-to-


peer basis with other DDC Controllers.
c) The DDC controller shall be IP addressable and reside on the first tier of any
network. Each DDC shall support a sub-network of a minimum of 64 controllers on
the second tier network.
d) Each integration controller shall have the ability to connect to third party control
systems. All programming required to implement the interface shall reside solely
within the controller and the associated device.
e) Controllers shall be microprocessor-based with a minimum word size of 24 or 32
bits and a minimum program scan rate of 1 second. They shall be multi-tasking,
multi-user, and real-time digital control processors. Controller size and capability
shall be sufficient to fully meet the requirements of this Specification.
f) Each controller shall have sufficient memory to support its own operating system,
databases, and control programs, and to provide supervisory control for all
second-tier controllers.
g) The controller shall have an integrated, hardware-based, real-time clock.
h) The network communication controller shall provide at least RS-232 serial data
communication port or USB connections for operation of operator I/O devices,
such as industry-standard printers, operator terminals, modems, and portable
operator’s terminals. Controllers shall allow temporary use of portable devices
without interrupting the normal operation of permanently connected modems,
printers, or terminals.
i) Controller shall continuously perform self-diagnostics, communication diagnosis,
and diagnosis of all panel components. The network controller shall provide both
local and remote annunciation of any detected component failures, low battery
conditions, or repeated failures to establish communication.

j) In the event of the loss of normal power, there shall be an orderly shutdown of all
controllers to prevent the loss of database or operating system software. Non-
volatile memory shall be incorporated for all critical controller configuration data,
and battery backup shall be provided to support the real-time clock and all volatile
memory for a minimum of 72 days.
k) During a loss of normal power a UPS system shall be provided to support each
safety critical controller and PC unit connected to or controlling the BMS system.
The UPS system shall be designed to allow the normal operating functions to be
maintained for a period of 3 hours. After this time the control sequences shall go
to the normal system shutdown conditions.
l) Upon restoration of normal power and after a minimum off-time delay, the
controller shall automatically resume full operation without manual intervention
through a normal soft-start sequence.
m) The DDC controller shall provide the essential role of supervising all interactions
between the connected management station and the processes which are
controlled and monitored at the lower levels of the system. At the same time, the
DDC controller shall manage the functions associated with the global operation of
________________________________________________________________________________
B - 60
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

the building electrical and mechanical services, coordinating the direct inter-
process communication for this purpose.
n) Encompassed in the above role are the real-time monitoring, data gathering and
storage functions which enable the performance of the system and its connected
processes to be evaluated, as well as providing the earliest warning of detected
faults and breakdowns.
o) Controller Functions

1 The system controller shall be programmed using software block


technology. This method shall work on the principle that each block is
dedicated to a precisely defined function or "sub-function", such that the
overall utility of the controller is totally flexible, and can be customized to
specific requirements by simply defining and linking the blocks together in
the appropriate way.
2 An overview of the general scope of the function blocks which shall be
implemented is given below.
3 INPUT OUTPUT POINTS: - Software blocks shall be used to define the
physical and virtual points in the upper levels of the system where they can
be subsequently accessed for operational and management purposes.
Failure of sensors and selection of possible default actions shall be
incorporated.
4 TIME CLOCK FUNCTIONS - Various blocks shall be available for defining
additional time schedules at the system controller level based on daily,
weekly and yearly events including holiday and exception.
5 INTERLOCKING AND CONTROL - The following logical functions shall be
implemented as blocks for additional interlocking functions at the system
controller level:
6 AND, NAND, OR, NOR, "invert", "toggle/latch" - These shall be
supplemented by time delay blocks for programmable ON and OFF
delays, as well as blocks for supplementary control functions such as:

a Analogue signal selection


b Linear conversion
c T hreshold detection

7 MATHEMATICAL FUNCTIONS - The following mathematical functions shall


be implemented as standard software routines for programming calculations
to be performed at the system controller level:
a +, -, /, x, MIN, MAX, AVG, SUM, ABS VAL, LOG, LN, SIN, COS, TAN,
SQR,
ROOT,
8 DATA STORAGE - Two distinct types of application shall be covered by
blocks of this nature:
a. Totalization, which can be performed on analogue points for integrating
________________________________________________________________________________
B - 61
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

measurements over their time base giving total quantities, as well as digital
points for run time accumulation.
b. Historical data gathering.
9 ALARM AND EVENT REPORTING - As this function is best described in
an overall context which includes the management level, a complete
overview is provided in "Alarm Management".
10 NERGY MANAGEMENT FUNCTIONS - The following standard software
routines shall be implemented for energy management functions at the
system controller level:

a) Adaptive Optimum start/stop control


b) Duty cycle operation
c) Heating/cooling dead band of 3ºC (excluding exhibition areas)

d) Optimum stop start algorithms for heating and cooling systems


e) Occupant sensing with manual run on timed override.
f) Sequencing of humidification and de-humidification with dead band
(excluding exhibition areas)
g) User adjustable hot water storage set point.
h) Minimum hot water system temperature protection with adjustable time
schedule.

11 GLOBAL INTERLOCKING AND SHARING - Blocks shall be available


which allow the direct transfer of data between system controllers on the
same network on a peer-to-peer basis. These are foreseen for global
interlocking and sensor sharing purposes.

p) Network Controller Specification

1 Hardware Specification:
a) Power 24 VAC +/-15%, 30VA, 50/60 Hz
b) Ambient Operating

 Temperatures 0 to 40 º C
 Transportation 0 to 40 ºCF
 Battery back-up 2 years power fail back up, 8 years normal service
life

D.16 Outstations

a) All outstations types shall be of standard designs and have a common protocol for
user configurable control and monitoring algorithms. No control/monitoring
devices without soft algorithms shall be supplied. All shall include the following
features:

1 Able to operate in complete stand-alone mode.


________________________________________________________________________________
B - 62
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

2 Include such programmable functions as scaling, calculations, and point,


override and control action text identifiers.
3 All Inputs/Outputs shall be constructed to give protection against mains
input voltages causing damage to other than that I/O channel.
4 Automatic restoration to full operation following a mains supply failure
without recourse to any data- files held elsewhere. Have sufficient on-
board battery support for on-board clock and all RAM functions to hold for
at least 6 months of total power down time.
5 Standalone lockable steel enclosures sealed to IP55 standard. All locks
shall have a common key.
6 Mechanical structure shall be modular to allow ease of service.
7 Satisfactory operation from 240Vac +10/-15%, 47-53Hz 1ph power supply.

b) Digital Inputs shall have the following facilities:

1 Capable of monitoring change of state or events from plant having volt-free


contacts with a resistance as high as 4kOhm.
2 Capable of monitoring pulse outputs from metering equipment monitoring
changes in volt-free contacts to at least 25Hz.
3 Status annunciation by LED.

c) Analogue inputs shall have the following facilities:

1 Capable of monitoring signals directly with or without additional hardware.


2 0-10vdc (ii) 4-20mA (iii) 0-10,000 Ohms (iv) Digital input as volt-free
contact.
3 ADC resolution of 8 bits or better.

d) Digital Outputs shall have the following facilities:

1 Relay contacts output s.p.c.o. rated at 240V AC, 5A resistive or 24V DC.
2 Status annunciation by LED or other.

e) Analogue Outputs shall have the following facilities:

1 Output 0 - 10vdc (500 Ohms minimum load) or 0-20 mA.


2 DAC resolution 8 bit or better.

f) Control and Monitoring Configuration:

1 The standard software residing in ROM (firmware) at the outstations shall


be structured so that users without computer programming knowledge can
configure and modify the control and monitoring strategies, (see training).
A user should be able to make simple temporary set point and time
schedule changes from graphics or user pages to perform simple
diagnostic checks on plant performance without entering engineering or
software configuration mode. An engineer’s utility programme shall enable
________________________________________________________________________________
B - 63
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

the engineer via a high level of password access to add/edit the strategies.
The firmware shall be capable of the following:

a) Comparators for I/O functions including delay times for match/miss-


match.
b) Analogue input scaling and parameter identification, high/low limit
alarm levels with adjustable time hysteresis and signal linearisation
and inversion for thermistor characteristic inputs.
c) Manual overrides ON/OFF and adjustments of setpoints and analogue
constants (see passwords).
d) Mathematical operations including multiplication, division, square root,
average, maximum, minimum, greater/lesser than, and logarithmic
calculations and shall typically be capable of calculating efficiency,
mass flow and enthalpy.
e) Counting operations providing outputs of rate and totals over selected
periods.
f) Boolean Logic, AND, OR, NAND, NOR functions.
g) Timer operations, advance and delay operations.
h) Control function modules incorporating proportional, integral and
derivative action and having manual override to set a default output.
i) Output switching to raise/lower, analogue, time proportion and binary
switch actuators. Adjustments shall be available to change hysteresis,
respond speed, max/min levels and signal inversion.
j) Optimum Start/Stop for both heating and cooling applications. This
programme shall accept variables for space temperature (calculated
or direct), outside temperature, supply medium temperature and
space temperature offsets, and calculate the optimum ON and OFF
times for the connected plant. The programme shall have a self-
adaptive algorithm to adjust the on/off time characteristic in line with
calculated gain/loss constants and incorporate a self-damping feature
to discount step changes after an initial settlement period. Reports
shall be available indicating the conditions at any of the key event
periods, start of run-up etc. A pre-start limit shall be incorporated to
prevent optimization automatically starting plant very early due to
system failure without alarm.
k) A minimum of 5 independent time schedules at each outstation, each
capable of 3 switching periods per day. Time schedules shall be
capable of set-up as stand-alone or via global instruction in common
with others. To speed set-up, facilities shall allow standard periods to
be copied to each other. It shall be possible to program a full years’
time schedule operations including holidays, special days, and special
events. The real-time clock shall have automatic clock adjustment
and be regularly synchronized with the LAN/system master.

________________________________________________________________________________
B - 64
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

l) Alarm history file, used for local fault finding, shall include all plant and
system alarm records. Alarms shall be generated for variables
exceeding set limits, field input transducers out of range, control
outputs over set limits, internal operational faults.
m) History logs to record direct or calculated internal analogue values.
Time between recordings shall be selectable so that values can be
recorded at intervals ranging from 15 seconds up to daily readings. A
chart of all trend logs currently recording shall be available at each
outstation showing the plot identify and recording interval.

2 Hardware Override Monitoring – DDC panels shall monitor the status or


position of all overrides, and include this information in logs and
summaries to inform the operator that automatic control has been
inhibited. DDC panels shall also collect override activity information for
daily and monthly reports.
3 Local Status Indicator Lamps – The DDC panel shall provide local status
indication for each binary input and output for constant, up-to-date
verification of all point conditions without the need for an operator I/O
device.
4 Surge and Transient Protection – Isolation shall be provided at all network
terminations, as well as all field point terminations, to suppress induced
voltage transients consistent with IEEE Standard 587-1980.

g) Outstation sizing and capacity

1 The BMS specialist shall submit a points schedule with his tender showing
the physical points to be connected at each outstation site, their totals and
the capacity of each I/O type available. The point schedule shall show the
point(s) identifier, I/O type and input/output field device. The target
installed spare capacity of I/O and software shall be 20% or better for each
point type. All points required for a fully functional system to achieve the
intent of the performance described in this specification shall be allowed by
the specialist.
2 The inputs and outputs shown on the schedules and drawings are
indicative of the general level of monitoring requirements and control
operation of the system. The tenderer shall add any additional inputs and
outputs required and detail the controls and interfaces to achieve the
demands of the performance specification and all BMS equipment he
proposes to supply to achieve the control performance required. A
schedule of outstations shall be submitted showing the points connected to
each indicating the I/O capacity supplied and the spare capacity available
for future additions. The target spare capacity of I/O and software shall be
20% or better for each point type at all outstations not regarded as terminal
controllers (FCUs).
________________________________________________________________________________
B - 65
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

h) Field Devices - A schedule of field devices shall be submitted, cross referenced


to the points schedule showing the total number and specification of the device to
be supplied, which shall comprise the manufacturer, model, range, accuracy, flow
characteristics, working operating and static pressure ranges, all applicable to the
transducer or actuator. The BMS subcontractor shall be responsible for the
correct output, sensitivity and positioning of sensors. Where notional sensor
positions are indicated on drawings, he shall advise any corrections required for
the correct operation of his detailed design and configuration to the engineer at
an early stage of the project.

D.17 Plant Control Processors


a) Main Plant Control Processors

1. The main plant controllers shall be microprocessor based, fully software


programmable, multi- algorithmic, three term DDC processors housed in the
various motor control panels.
2. The processors shall be in universal (analogue or digital) input/output units of
varying capacity enabling each processor location to be customised for the
designed point requirements for that location plus spare capacity as required
and detailed elsewhere.
3. All processors shall be fully interchangeable whatever their point capacity is
such that a unit with a larger point capacity may be fitted into the same base
and housing as a smaller capacity unit and vice versa.
4. The processors shall be able to be fitted directly adjacent to each other with this
arrangement automatically providing the necessary communications bus
connections.
5. Each processor shall have output override facilities available directly through
that unit, and via the communications bus, stored in EPROM. These facilities
shall be built in, access guarded and not require user definition.
6. Each processor shall contain its own time base and switch times with switch
time adjustment and automatic bus synchronization between processors and
between BMS and the processor bus. The time base shall be stored in EPROM
and shall be maintained within each processor such that failure of the
communications link, other processors or the BMS shall not affect the timed
operations contained within any one unit.
7. The processors shall contain basic control, logic and energy selective functions.
Such functions shall be resident within individual processors and selected or
combined to provide strategies for the various control loops. They shall
comprise of the following:
8. Control Functions not limited to:

a) Universal set point calculation.

________________________________________________________________________________
B - 66
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

b) Single, two and three term control. (P, PI and PID)


c) Two and three point digital control.
d) D to A, and A to D conversion.
e) Curve plotting with adaptable axis.
f) High, low and average signal selection.
g) Stepped output with delay on and off functions
h) Hysteresis control.
i) Second and third term control component limiters.
j) Fully adjustable term parameters.
k) Fully definable output blocks with in-built delay, override and interlock
functions.

9. Logic Functions not limited to:

a) Multiple input AND, OR, NAND, NOR and EXOR blocks.


b) Digi-analogue switching blocks.
c) Multiple output ring counters.
d) Delay on, off and pulse timers.
.
10. Energy Control Functions not limited to:
a) Self-adaptive optimization.
b) Enthalpy selection.
c) Duty cycling.
d) Air quality control.
e) Demand reset control.
f) 8 independent channel, 24 hour, 7 day timeclock. g
g) Yearly switch functions.
h) Automatic clock synchronization.
i) Run time totalization.

b) Main Plant Controller minimum technical specification, or equivalent and approved.

1 Processor memory capacity 32 bit/64 bit structure


2 EPROM for operating system and function library 2 to 4 Mbytes
3 RAM for temporary data > 512 kbytes
4 Resolution A/D, D/A converter 24 bit
5 Supply voltage 24 VAC +/- 10%
6 Frequency 50-60 Hz
7 Control accuracy 0.5% (of UeO-10V)
8 Maximum update time at least 1000ms
9 Transmission rate between modules and high order systems > 2 MB baud
10 Number of connectable modules at least 16 modules per bus

________________________________________________________________________________
B - 67
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

11 Data storage during power failure structures and parameters 10 years time
7 days
12 Radio interference protection accordance with VDE0871B
13 Protection class III
14 Protection standard IP00
15 Ambient temperatures - operation 10...50ºC, transport and operation -
25...70ºC
16 The processors, together with their associated field interfaces shall be so
designed as to provide maximum flexibility of input and output
configuration.
17 On Selection of any specific interface units the following shall be
considered as a minimum requirement:

a) Lamp indication shall be provided for all output signals both digital and
analogue. In the case of digital signals the lamp shall indicate the
current state of the output.
b) Lamp indication shall be provided for all digital input signals and active
analogue input signals. In the case of digital signals the lamp shall
indicate the current state of the input device connected. In the case of
the analogue signals the lamp shall vary in intensity to indicate the
magnitude of the signal received.
c) All output signals shall have the capability of individual manual override
to Hand/Off/Auto condition at interface level.
d) All output signals shall have provision for individual externally hardwired
override to maximum and minimum state. Such override to be
independent of, and have priority over, any software generated signal.

c) Energy metering

1 Metering of energy consumption shall be provided from the field metering


devices shown in the mechanical and electrical specifications and drawings
via dedicated input pulse units. The units shall connect directly to the meter
communication nodes in clusters via Mbus and MODbus and have the
ability to store pulse counts from the field metering devices on
communications failure. The meter communication controllers shall
communicate with the central system via Modbus/IP. Allow for full liaison
with the main MSI for the development and all software and hardware
needed to fully integrate with the master metering system for the
development.

d) Fan Coil Terminal Unit Controllers

1 The terminal unit controllers shall be microprocessor based, addressable,


processors housed at each terminal fan coil unit as detailed elsewhere in
the full project MEP specifications and drawings.
________________________________________________________________________________
B - 68
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

2 The controllers shall be supplied, together with all associated unit mounted
equipment free issue to the terminal unit manufacturer. The terminal unit
manufacturer shall permanently fix and wire the supplied equipment to each
unit in an order specified by the controls supplier and in full accordance with
the latest IEE regulations. The terminal unit manufacturer shall address and
label the controllers as required and specified by the controls supplier.
Finally the terminal unit manufacturer shall works test the unit prior to
shipment and provide test record documentation to the contract. The
controls specialist sub- contractor shall allow for the installation of individual
wall mounted set point adjustment, commissioning and setting to work of
the units on site following installation.
3 The controllers shall have both analogue and digital inputs and outputs to
suit any individual terminal unit requirements.
4 The controllers shall contain basic control, logic and energy selective
functions. Such functions shall be resident within individual controllers and
selected or combined to provide strategies for the individual fan coil units.
They shall comprise of the following:

a) 0-10V dc or 0-20 V dc modulating outputs


b) Cooling only or heating/cooling
c) Individually adjustable heating and cooling setpoints
d) Comfort, stand-by and energy hold-off modes with the following
features:
e) All 3 modes operated by singular and group communications over
communication bus where networked or pre-configured locally.
f) Energy hold-off mode operated by direct digital occupancy input at
any individual controller.
g) Energy hold-off mode cooling set point adjustable individually and
independently at each controller and over communication bus if
required.
h) Optional sensor only, sensor/set point and fan on/off and speed
control via room control unit.
i) nless indicated elsewhere, transmission of cooling energy demand to
the main plant controllers and BMS where networked.

e) Terminal Unit Controllers Technical Specification or equivalent and approved.

i. Protection standard - IP30 to IEC529 (DIN 40050)


ii. Protection class III to IEC 5180
iii. Noise emission - None.

f) Processing, Communications and Data Definition - DDC controller must have the
following additional functions:

________________________________________________________________________________
B - 69
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

1) Free selection of range and unit (dimension) of all signals (measured


values, accumulated values, calculated values etc).
2) Free definition of manual override priorities (software) from operator
terminal and/or management station (if included)
3) Graphic documentation of application programs in function plants
(structure diagrams). The signal paths must be clearly identifiable for
operators without special programming knowledge. (see training)
4) The processing speed must ensure precise and non-oscillating control
of all common building services processes.
5) A self-monitoring of the processor and self-test or correct functioning
of the functions must be automatic.
6) If - for any reason - the communication between the control modules
should be interrupted by wire breaks, disconnection etc, then each
control module shall be able to continue to function autonomously to
provide all functions including time of day based routines.
7) Each control module shall have a real time clock with sufficient time
channels which are day and date programmable to effect the control
required. The clocks shall be self-synchronizing when connected
together on the control system communications network, thus only
one clock needs setting for the whole system.
8) The clock shall be capable of clock adjustment on the basis of either
manual intervention or automatic time programme.
9) The main plant system shall be capable of two way communication
with intelligent terminal unit controllers. This shall allow transmission
of time, morning boost, purge and summer/winter compensation
signals from main plant to the terminal unit controls. Conversely the
terminal unit controls shall be capable of resetting the main plant
controls by transmission of heating/cooling demand signals.
10) The transmission of signals from the process interface must be
carried out via universal (analogue or digital) and digital in/outputs.
11) The connection of all the DDC units to the data bus must be provided
as standard.
12) Local operation. Each DDC unit and communication and control unit
for individual room controllers where installed must be connectable to
an operator terminal directly and/or remotely via a data bus. The
operation must be menu driven and interactive via an intuitive and
easy-to-understand keyboard and alphanumeric display.
13) The operating concept must be structured such that data can be
accessed at individual operating levels in accordance with the
associated access authority.
14) Terminal Unit Controllers
15) Each Unit Controller shall operate as a standalone controller capable
of performing its specified control responsibilities independently of

________________________________________________________________________________
B - 70
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

other controllers in the network. Each Unit Controller shall be a


microprocessor-based, multi-tasking, real-time digital control
processor.
16) Point types – Each Unit Controller shall support the following types of
point inputs and outputs:
17) Analogue inputs shall monitor the following analogue signals:
18) 0-10 VDC Sensors
19) 1000ohm RTDs
20) PTC Thermistors
21) Binary inputs shall monitor dry contact closures. Input shall provide
filtering to eliminate false signals resulting from input “bouncing.”
22) Counter inputs shall monitor dry contact pulses with an input
resolution of one HZ minimum.
23) Analogue outputs shall provide the following control outputs:
24) 0-10 VDC
25) Binary outputs shall provide SPDT output contacts rated for 2 amps at
24 VAC. Surge and noise suppression shall be provided on all pilot
relays. Inductive loads (i.e. solenoids) shall be controlled by pilot
relays.
26) TriState outputs shall be paired binary outputs for use as Power
Close/Power Open control output contacts rated for 2 amps at 24
VAC. Surge and noise suppression shall be provided on all pilot
relays.
27) Terminal Unit Controllers shall have a library of control routines and
program logic to perform the sequence of operations specified in the
controls narrative portion of this Specification.
28) Terminal Unit Controllers shall directly support the temporary use of a
portable user terminal that can be connected to the unit via a space
temperature sensor or directly at the controller.
29) All system set points, proportional bands, control algorithms, and any
other programmable parameters shall be stored such that a power
failure of any duration does not necessitate reprogramming the unit

________________________________________________________________________________
B - 71
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

D.18 FIELD PERIPHERAL EQUIPMENT


A. The field control equipment shall have the following minimum performance and
physical specification and shall be mounted in positions to measure representative
parameters:

1. Temperature Control Sensors

a) Sensors and transmitters shall be provided, as outlined in the sequence of


operations, drawings and specification and as required to meet the intent of the
performance controls specification.
b) The temperature sensor shall be of the resistance type, and shall be two-wire
1000 ohm nickel RTD, two-wire 1000 ohm platinum RTD or PTC/NTC
Thermistors to suit the application.
c) The following point types (and the accuracy of each) are required, and their
associated accuracy values include errors associated with the sensor, lead wire,
site installation and A to D conversion:
Point Type Accuracy
Chilled Water + 0.2 C.
Room Temp + 0.2 C.
Duct Temperature + 0.2 C.
Relative Humidity (%) + 1.0 %
All Others + 0.2 C.

2. Room temperature:
a) The unit shall be manufactured from white ABS plastic to IP30 and shall have a
de-mountable sensor housing/baseplate arrangement. The unit shall have a
multi-terminal push in connector block on the baseplate to facilitate easy initial
wiring and easy room unit interchange for set point/fan selector units.
b) Storage limits shall be 0 to 40 C.
c) Connections shall be non-polarity conscious.
d) The sensing element shall be a re-active 0-10V DC device. The power source to
be either supplied locally or from the processor concerned.
e) The sensor shall be suitable for operation between 0 and 100 C ambient and
have a linear voltage to temperature characteristic of 10 mV/K (50mV/K re-
active). Set point reset providing a +3 degree (adjustable) range.
f) Individual heating/cooling set point slide switches.
g) Tolerance shall be matched to room condition criteria.
h) Equipment finish and appearance shall be coordinated and compatible with
architectural finish.
i) Samples shall be submitted to the architect for comment.

________________________________________________________________________________
B - 72
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

3. External temperature:
a) As above but with clamp cable connections, housing to IP55 and suitable for
ambient temperature - 0 to 70 C. Outside air sensors shall be designed to
withstand the environmental conditions to which they shall be exposed.
b) The sensors shall also be provided with a solar shield. A perforated plate that
surrounds the sensor element shall shield sensors exposed to wind velocity
pressures.
c) Temperature transmitters shall be of NEMA 3R construction and rated for
ambient temperatures.

4. Duct temperature:
a) The sensor housing shall be to IP43. The unit shall be supplied as sensor and
mounting plate such that the sensor may be de-mounted and replaced in service.
b) Ambient operating temperature -0 to 70 C.
c) Electrical operation and characteristics to be as previous sensors above.
d) Duct mount sensors shall mount in an electrical box through a hole in the duct,
and be positioned so as to be easily accessible for repair or replacement.

5. Terminal Unit temperature:


a) The sensor shall be provided with flying lead connections and fittings for
mounting in ½ to ¾ inch diameter orifice.
b) Electrical operation and characteristics to be as previous sensors above.

6. Immersion temperature:

a) The sensor housing shall be to IP43. The unit shall be supplied as sensor and
immersion pocket enabling removal of sensor without requiring drain down.
b) All sensor pockets in Chilled Water applications shall be stainless steel, suitable
for local system pressure. The pocket shall be parallel.
c) Pockets shall enable immersion into the medium of no less than 60mm. Heat
conducting compound shall be used to ensure accurate transfer of process
temperature to the instrument.
d) Electrical operation and characteristics to be as previous sensors above.

7. Clamp on temperature sensors:


a) Clamp-on temperature sensors shall only be installed in applications as agreed
with the engineer. Sensor heads shall be PT100 accuracy, and suitable for
lagging over with the flying lead connecting to the electrical/junctions box.

8. Immersion sensors
a) The sensor and pocket shall be supplied as a complete assembly with the sensor
unit de-mountable in service.

________________________________________________________________________________
B - 73
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

b) Pockets shall be pressure rated and selected in accordance with the system
working pressure.
c) Pockets shall be mounted in a 1/2” BSP stabbing and allow easy access to the
sensor for repair or replacement.
d) Pockets shall be constructed of 316 stainless steel or brass to suit application,
ensure compatibility with materials that are in contact.
e) Heat conducting compound shall be used to ensure accurate transfer of process
temperature to the instrument.

9. Averaging Sensors

a) For ductwork greater in any dimension that 1.5 metre and/or where air
temperature stratification exists, an averaging sensor with multiple sensing points
shall be used.
b) For plenum applications, such as mixed air temperature measurements, a string
of sensors mounted across the plenum shall be used to account for stratification
and/or air turbulence. The averaging string shall have a minimum of 4 sensing
points per 4m long segment.
c) Capillary supports at the sides of the duct shall be provided to support the
sensing string.

B. Relative Humidity Control Sensors

1. Duct relative humidity:

a) The sensor shall be a solid state type, relative humidity sensor of the capacitive
Polymer Design. The sensor element shall resist service contamination. The unit
shall be identical in construction and protection to the room temperature sensor
detail given above.
b) The unit shall be an active 0-10V DC device. The power source to be either
supplied locally or from the processor concerned.
c) The range shall not be less than 20-90% RH with an accuracy of not less than +/-
1% RH (+/- 0.6% RH where required to meet room condition tolerances of < +/-
5%).
d) Where measurement of both RH and temperature is required one sensor capable
of providing both measured conditions shall be provided. Vaisala HMD60Y or
equal and approved.
e) Duct type sensing probes shall be constructed of 304 stainless steel, and shall
be equipped with a neoprene grommet, bushings, and a mounting bracket.

2. Room relative humidity:

________________________________________________________________________________
B - 74
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

a) The unit shall be identical in construction and protection to the duct temperature
sensor detail given above.
b) The unit shall be an active 0-10V DC device. The power source to be either
supplied locally or from the processor concerned.
c) The range shall not be less than 20-90% RH with an accuracy of not less than +/-
1% RH. (+/- 0.6% RH where required to meet room condition tolerances of < +/-
5%).
d) Where measurement of both RH and temperature is required one sensor capable
of providing both measured conditions shall be provided. Vaisala HMW60Y or
equal and approved.

C. Differential pressure sensors

1 The unit shall be manufactured from ABS plastic to IP54.


2 The unit shall be an active 0-10V DC inductive coupling device with a linear
voltage to pressure characteristic. The power source to be either supplied
locally or from the processor concerned.
3 The sensor and connections shall be suitable for ambient operating
temperatures between-0 and 70 C.

D. Differential pressure switches (air)

1 The unit shall be manufactured from ABS plastic to IP54.


2 The unit shall be a switching device with a SPDT 240V AC rated contact for
minimum 1A resistive duty.
3 The individual unit measuring range shall be selected to suit the application.
4 The switch and connections shall be suitable for ambient operating
temperatures between -0 and 70 C.

E. Low Differential Air Pressure Applications (0 to 1.25 kPa)

1 The differential pressure transmitter shall be of industrial quality and transmit


a linear, 0-10 VDC or 4 to 20 mA output in response to variation of
differential pressure or air pressure sensing points.
2 The differential pressure transmitter shall have non-interactive zero and
span adjustments that are adjustable from the outside cover and meet the
following performance specifications:
3 4-20 mA/0-10 VDC output.
4 Maintain accuracy up to 20 to 1 ratio turndown.
5 Reference Accuracy: +0.2% of full span.

F. Medium Differential Air Pressure Applications 1.25 -5kpa)

1 The pressure transmitter shall be similar to the Low Air Pressure


Transmitter, except that the performance specifications are not as severe.

________________________________________________________________________________
B - 75
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

Differential pressure transmitters shall be provided that meet the following


performance requirements:
2 The panel shall be constructed to NEMA 1 standards. The transmitter shall
be installed in the panel with high and low connections piped and valved. Air
bleed units, bypass valves, and compression fittings shall be provided.

G. Differential pressure switches (water)

1 The unit shall be manufactured to IP65 minimum and capable of


withstanding a system pressure of up to 16 bar.
2 The unit shall be a switching device with a SPDT 240V AC rated contact for
minimum 5A resistive duty. Pressure transmitters shall be constructed to
withstand 100% pressure over-range without damage, and to hold calibrated
accuracy when subject to a momentary 40% over-range input. Pressure
transmitters shall transmit a 0 to 5 VDC, 0 to 10 VDC, or 4 to 20 mA output
signal.
3 The individual unit measuring range shall be selected to suit the application.
Differential pressure transmitters used for flow measurement shall be sized
to the flow sensing device, and shall be supplied with Tee fittings and shut-
off valves in the high and low sensing pick-up lines to allow the balancing
Contractor and Employer permanent, easy-to-use connection.
4 The switch and connections shall be selected to cope with the ambient static
pressures experienced in such a high rise building.

H. Low Differential Water Pressure Applications (0-5kPa.)

1 The differential pressure transmitter shall be of industrial quality and transmit


a linear, 0-10 VDC or 4 to 20 mA output in response to variation of flow
meter differential pressure or water pressure sensing points.
2 The differential pressure transmitter shall have non-interactive zero and
span adjustments that are adjustable from the outside cover and meet the
following performance specifications.
3 0.1-5kPa input differential pressure range.
4 4-20 mA /0-10 VDC output.
5 Maintain accuracy up to 20 to 1 ratio turndown.
6 Reference Accuracy: +0.2% of full span.
7 The sensor and connections shall be selected to cope with the ambient
static pressures experienced in such a high-rise building.

I. Medium to High Differential Water Pressure Applications (Over 5kPa)

1 The differential pressure transmitter shall meet the low pressure transmitter
specifications with the following exceptions:
2 Differential pressure range 2.5kPa to 3000 kPa.

________________________________________________________________________________
B - 76
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

3 Reference Accuracy: +1% of full span (includes non-linearity, hysteresis,


and repeatability).
4 Standalone pressure transmitters shall be mounted in a bypass valve
assembly panel. The panel shall be constructed to NEMA 1 standards. The
transmitter shall be installed in the panel with high and low connections
piped and valved. Air bleed units, bypass valves, and compression fittings
shall be provided. The sensor and connections shall be selected to cope
with the ambient static pressures experienced in such a high-rise building.

J. Flow switches (water)

1 The unit shall be manufactured to IP65 minimum and capable of


withstanding a system pressure of 175 psi and media temperature of 2000
F.
2 The unit shall be a switching device with a SPDT 240V AC rated contact for
minimum 15A resistive duty.
3 The individual unit measuring range shall be selected to suit the application.
4 The switch and connections shall be selected to cope with the ambient static
pressures experienced in such a high-rise building.

K. Remote Adjustment Potentiometers

1 Where these are supplied for local override of set-point, they shall not be
scaled. The scaling and range shall be achieved in software so as to allow
the Employer to adjust to his design. RAP's may be mounted integrally with
space temperature sensors or in their own enclosure as dictated by the
specification.

L. Carbon Dioxide and Air Quality Sensors

1 Carbon Dioxide (CO2) sensors shall be mounted in the measured space at


a height between 0.9m and 1.8m from the floor and provide an output in
parts per million (ppm). Range 0-2000ppm. The unit shall be manufactured
to IP30 minimum and capable of operating between 0 and 50 C.
2 Carbon Dioxide sensors shall provide 0-10V or 4-20mA output. Accuracy +/-
30ppm. Repeatability +/- 20ppm. Response time <60s 90% step change.
The power source shall be supplied locally or from the processor concerned.
3 The sensor shall employ automatic baseline calibration techniques to
preserve calibration for 5 years.

M. Liquid Level Switches

1 Floating type. Suitable for contents of tank.

________________________________________________________________________________
B - 77
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

N. Light Level Sensors


1 Outside light sensors shall have a range of 10-2000 Lux with an output of 4-
20mA and be mounted in an IP67 enclosure. The sensor shall be mounted in
an open position not subject to shade.

O. Current Switches

1 Current switches shall be supplied as control panel mounted split core solid
state current sensor.
2 The unit shall be a switching device with a SPDT 240V AC rated contact for
minimum resistive duty.
3 The individual unit measuring range shall be selected to suit the application.
P. Fan Velocity Sensor
1 The unit shall comprise a multiple point, flow traverse probe, located in the
inlet core of the centrifugal fan.
2 The unit shall be an active 0-10VDC device. The power supply to be either
supplied locally or from the processor concerned.
3 Where double width, double inlet fans are utilized a set of the fan inlet
airflow traverse probes shall be mounted in each of the two fan inlets and
interconnected by signal tubing.
Q. Hydraulic Flow Rate and Direction Sensors

1 The unit shall comprise a flow tube using Faradays Law to sense the voltage
induced by the rate of water flow through a magnetic field.
2 The unit shall be an active 0-10VDC device. The power supply to be either
supplied locally or from the processor concerned.
3 Water flow meters shall be electromagnetic type with integral
microprocessor-based electronics. The meter shall have an accuracy of
0.25%.
R. Duct Mounted Air Flow Sensors

1 Duct mounted air flow sensors shall be installed to provide a grid of velocity
readings across the whole area of the duct.
2 The velocity pressure readings shall be averaged and the velocity sensor
shall convert the flow probe average velocity pressure into a linear volume
flow rate and provide a 0 - 10V or 4 - 20mA signal.
3 The velocity transmitter shall have the following specification:

a) Electronic velocity pressure transducer with square rooted and


differential pressure signal output.
b) Low zero drift characteristic
c) High repeatability in low ranges
d) Standard output signals 0 - 10V 4 - 20mA
e) IP54 enclosures
________________________________________________________________________________
B - 78
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

f) Option of 24V and 220V AC power supply


g) User calibratable
h) LCD - Display scaled in m/s or m3/s

D.19 Field Output Devices


A. Actuators

1 Damper and valve actuators shall be electronic. Electronic damper actuators


shall be direct shaft mount.
2 Modulating and two-position actuators shall be provided as required by the
sequence of operations. Damper sections shall be sized based on actuator
manufacturer’s recommendations for face velocity, differential pressure and
damper type.
3 The actuator mounting arrangement and spring return feature shall permit
normally open or normally closed positions of the dampers, as required. All
actuators (except terminal units) shall be furnished with mechanical spring
return and fail safe in fire mode and on power failure unless otherwise
specified in the sequences of operations. All actuators shall have external
adjustable stops, to limit the travel in either direction, and a gear release
mechanism to allow manual positioning.
4 Modulating actuators shall accept 24 VAC or VDC power supply and
consume no more than 15 VA. The control signal shall be 2-10 VDC or 4-20
mA.
5 Two-position or open/closed actuators shall accept 24 or 240 VAC power
supply. Isolation, smoke, exhaust fan, and other dampers, as specified in
the sequence of operations, shall be furnished with adjustable end switches
to indicate open/closed position or be hard wired to start/stop associated
fan. Two-position actuators, as specified in sequences of operations as
“quick acting,” shall move full stroke within 20 seconds. In addition all fire
smoke damper actuators shall be quick acting.
6 All power supplies to essential life safety fire smoke dampers shall be run in
halogen free fire resistant cables compliant with BS 7846 and BS 6387
Category CWZ and the standard details of the electrical specification for this
project. Fire performance shall conform to EN 60332-1-2 : 2004 and EN
60332-3- 24:2009. E.g. Pirelli type FP400 or equal and approved.

B. Electronic Valve Actuators

1 Electronic valve actuators shall be manufactured by the valve manufacturer.


Each actuator shall have current limiting circuitry incorporated in its design
to prevent damage to the actuator.
2 Modulating and two-position actuators shall be provided as required by the
sequence of operations. Actuators shall provide the minimum torque
________________________________________________________________________________
B - 79
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

required for proper valve close-off against the system pressure for the
required application. The valve actuator shall be sized based on valve
manufacturer’s recommendations for flow and pressure differential. All
actuators shall fail in the last position unless specified with mechanical
spring return in the sequence of operations. The spring return feature shall
permit normally open or normally closed positions of the valves, as required.
All direct shaft mount rotational actuators shall have external adjustable
stops to limit the travel in either direction.
3 Modulating Actuators shall be 24 VAC powered. The control signal shall be
0-10 VDC or 4-20 mA.
4 Two-position or open/closed actuators shall accept a 24 or 240 VAC power
supply. Butterfly isolation and other valves, specified in the sequence of
operations, shall be furnished with adjustable end switches to indicate
open/closed position or be hard wired to start/stop the associated pump or
chiller.

C. Control Valves

1 All automatic control valves shall be fully proportioning and provide near
linear heat transfer control. The valves shall be quiet in operation and fail-
safe open, closed, or in their last position. All valves shall operate in
sequence with another valve when required by the sequence of operations.
All control valves shall be sized by the control manufacturer, and shall be
guaranteed to meet the heating and cooling loads, as specified.
2 All control valve/actuator assemblies shall be suitable for the system flow
conditions and close against the differential pressures involved. The fan coil
two port valve/actuator assemblies shall be selected by the BMS
subcontractor to shut off against the maximum differential pressure in the
particular section of the distribution in which they are installed, generally the
maximum associated pump head. Body pressure rating and connection type
(screwed, or flanged) of the valves selected by the specialist contractor shall
conform to the information in the MEP schedules and drawings elsewhere in
the MEP Specification and, in particular, be adequate to cope with the high
static pressures due to the nature of high rise building design and
construction.
3 Chilled water control valves shall be modulating plug, ball, and/or butterfly,
as required by the specific application. Modulating water valves shall be
sized and selected by the specialist as per manufacturer’s recommendations
for the given application. In general, 2 way valves serving variable flow air
handling
unit coils shall be sized to give a valve authority of 0.3 to 0.7 based on the
actual pressure drop through the local controlled variable circuit at maximum
demand. Valves (3-way and 4-way) serving constant water flow air handling
unit coils shall, in general, be sized for a valve authority of 0.5 or greater,
________________________________________________________________________________
B - 80
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

which means a notional pressure drop shall approximately equal or greater


than 100% of the coil pressure drop.
4 Mixing valves (3-way) serving secondary water circuits shall be sized for a
pressure drop of no less than 5 psi. Valves for terminal coils shall be sized
for a notional 2 psi pressure drop, but no more than a 35 kPa drop, subject
always to maintaining the authority required in the paragraph above.
5 Modulating plug and seat water valves of the single-seat type with equal
percentage flow characteristics shall be used for all hot and chilled water
applications, except those described hereinafter. The valve discs shall be
composition type. Valve stems shall be stainless steel. Diverting valves shall
not be single seat.
6 Ball valves shall be acceptable for water terminal reheat coils, radiant
panels, unit heaters and package air conditioning units.
7 Butterfly valves shall be acceptable for modulating large flow applications
greater than modulating plug valves can control, and for all two-position,
open/close applications. In-line and/or three-way butterfly valves shall be
heavy-duty pattern with a body pressure rating comparable to the local
ambient pipe system pressure rating, replaceable lining suitable for
temperature of system, and a stainless steel vane.
8 Valves for modulating service shall be controlled in such a manner that the
valve does not suffer from drift of actual controlled position over time or
during power outage. All modulating valves shall employ physical and
software components that detect any drift or error and restore true valve
position to within 2% of control position automatically, for instance by
resetting datum on a sufficiently regular basis to prevent lack of control by
position drift. Valves for isolation service shall be the same size as the pipe.
Valves in the closed position shall be bubble-tight.

D. Electric Damper Actuators

1 All motorized dampers shall be provided as part of the ductwork installation.


2 The BMS specialist shall provide the correct number of suitable actuators for
each motorized damper.
3 The BMS specialist shall be responsible for determining the power and
number of actuators required for each and every motorized damper.
4 All modulating damper actuators shall be self-stroking and have position
indictors and manual override facilities.
5 Each two position damper actuator shall have an end switch provided
indicting the safe condition for interlock of the plant and for monitoring by the
BMS.
6 All two position actuators shall be spring return and set up to fail safe in fire
mode on power failure.

________________________________________________________________________________
B - 81
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

7 All actuators shall be supplied complete with all necessary mounting


brackets and linkages. The BMS installer shall mount and stroke the
actuators.
8 All power supplies to essential life safety fire smoke dampers shall be run in
halogen free fire resistant cables compliant with BS 7846 and BS 6387
Category CWZ and the standard details of the electrical specification for this
project. Fire performance shall conform to EN 60332-1-2 : 2004 and EN
60332-3-24 : 2009..E.g. Pirelli type FP400 or equal and approved.

E. Motor Speed Controllers

1 The BMS specialist shall be responsible for interfacing the system outputs to
the motor speed controllers, supplying any transducers or interface circuits
as required. Fan-out Modules
2 Where voltage driven output control modules are used to provide single or
multiple switched outputs, they shall be DIN rail mounted within motor
control panels, outstation cubicles or local panels to IP55 standard.

________________________________________________________________________________
B - 82
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

D.20 Metering
A. Flow Meters

1 Types proposed shall be chosen to suit the application, static pressure and
pressure drop. The meter range and turn-down ratio shall be chosen such that
the full anticipated flow range is measured within an accuracy of +/-2% or better.
No positive displacement types shall be employed where safety is jeopardized
by lack of flow. Flow meters shall supply a pulse output (max 25Hz at full rated
flow) or 4- 20mA. All flow metering devices shall be supplied complete with any
output transducers and supplied with individual over-all calibration chart. The
BMS subcontractor shall advise the engineer and mechanical contractor of any
isolating valves or by-pass circuits thought necessary for instrument service
and maintenance of flow. Air flow measurement shall be by means of
Veloprobe type pitot static averaging tubes with integrated and calibrated
electronic transmitters. Accuracy shall be better than +/-
5% of design minimum flow rate.

B. Local Control Panels

1 All control panels shall be factory constructed, incorporating the BMS


manufacturer’s standard designs and layouts. Control panels shall be fully
enclosed, with sub-panel, hinged door, and key-locking latch.
2 In general, the control panels shall consist of the DDC controller(s), display
module, and I/O devices— such as relays, transducers, and so forth—that are
not required to be located external to the control panel due to function. The
display module shall be flush mounted in the panel face unless otherwise noted.
3 All I/O connections on the DDC controller shall be extended to a numbered,
colour-coded, and labelled terminal strip for ease of maintenance and expansion.
Wiring to I/O devices shall be made from this terminal strip.
4 All other wiring in the panel, internal and external, shall be made to additional
line or low voltage colour-coded and labelled terminal strips. Low and line
voltage wiring shall be segregated. All terminal strips and wiring shall be UL
listed, 300-volt service and provide adequate clearance for field wiring.
5 All wiring for every control panel shall follow a common colour-coded format. All
terminal strip colour coding and numbering shall follow a common format. All
wiring shall be neatly installed in plastic trays or tie-wrapped.
6 A convenience 240 VAC RCD protected socket shall be provided in each
enclosure, fused on/off power switch, and required transformers.

C. Power Supplies

1 DC power supplies shall be sized for the connected device load. Total rated
load shall not exceed 75% of the rated capacity of the power supply.

________________________________________________________________________________
B - 83
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

2 Input: 240 VAC +10%, 50Hz.


3 Output: 24 VDC.
4 Line Regulation: +0.05% for 10% line change.
5 Load Regulation: +0.05% for 50% load change.
6 Ripple and Noise: 1 mV rms, 5 mV peak to peak.
7 An appropriately sized fuse and fuse block shall be provided and located next to
the power supply.
8 A power disconnect switch shall be provided next to the power supply.

________________________________________________________________________________
B - 84
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

D.21 Documentation
A. Wiring Diagrams

1 The appointed BMS subcontractor shall prepare wiring diagrams, physical and
fascia layout, field wiring installation drawings and details, drawings which,
when completed, shall be forwarded through the contract for comment.
2 The wiring diagrams shall indicate the cable type and the number of cores
required for each item.
3 Wiring diagrams shall be produced in sufficient time to enable the wiring to be
implemented within the building programme.
4 The BMS subcontractor should note that no manufacture of equipment shall
commence until written comments have been given by the Engineer.

B. Control Strategy Design Intent

1 The BMS Specialist shall prepare a written detailed description of the proposed
control strategy for each system, including control, logging, graphics and alarm
parameters, before application software is commenced, for comment by the
Employer.

C. Operating and Maintenance Manuals

1 The manuals shall include the following information:

a) Wiring and fascia diagrams. Wiring diagrams must include terminal


numbers on connected plant, whether supplied as part of mechanical
works or by others. In addition, to ease reading of wiring drawings the
terminals on relays and contractors should be 'grid referenced' to the area
of the drawing showing the circuit through those terminals.
b) Field wiring installation drawings, showing routing and destination of all
wiring.
c) Local Area Network (LAN) schematic.
d) Control strategy document.
e) Control logic diagrams
f) Location of all panels, outstations and control devices.
g) Control, alarm and limit for each control device.
h) Alarm schedules, destinations of alarms.
i) Copies of all demonstration, monitored/trend logs.
j) All test/calibration certificates.
k) Technical details of all panel equipment, outstations, controllers, control
sensors, etc.
l) Suggested spares list.
m) Copies of BMS system graphics as a record of the as installed schematics

________________________________________________________________________________
B - 85
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

n) A simple user guide, specific to this project, which shall explain simply and
clearly in layman’s not engineering or technical language how to use the
controls and in particular the use of interfaces/controls. The document
shall be in English and Arabic and shall enable a non-technical occupant
to set the system up easily to achieve desired conditions. A summary with
basic tips for successful operation and very basic troubleshooting
guidance shall be included. The aim is to enable an occupant to get the
best from the system and the room controls in particular and rectify simple
faults such as (but not exclusively) power off, set point too high too low
etc. without external help.

D. Application Software

1 Two copies of the as installed application software on compact disk shall be


handed over at Practical Completion. One hard copy print of software. Any
changes during the next 12 months shall be recorded and updated copies shall
be provided.

E. Updating

1 The installer shall allow for the full updating of the O&M Manuals at the end of
the 12 months after Practical Completion, following any modifications to the
control systems required and for providing two further copies of the revised
application software.

________________________________________________________________________________
B - 86
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

D.22 Software and Equipment Maintenance and Updates


A. The BMS subcontractor shall provide software maintenance for one year after
handover.
B. The BMS subcontractor shall provide a guarantee that the systems and equipment
that he provides shall either continue to be produced and/or be maintainable for a
period of at least 10 years. Elemental equipment substitution is accepted for
peripheral items, but not for the microprocessor based equipment.
C. The BMS subcontractor shall provide maintenance of the complete controls
installation for one year after handover. Include in the tender for maintenance to
include:

1 Help desk back-up for the user.


2 Call out service.
3 Regular service visits.
4 Re-tuning of control loops to cope with seasonal and occupancy changes.
5 Re-calibration of panel components every 6 months.
6 Re-calibration of field sensors and actuators every 6 months.
7 Replacement of all defective equipment during the maintenance period.
8 Software updates.

________________________________________________________________________________
B - 87
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

PART 'E' : EXECUTION

E.1 Installation of HVAC Control System Wiring


A. All conduit, wiring, accessories and wiring connections required for the installation of
the Building Management System, as herein specified, shall be provided by the BMS
subcontractor unless specifically shown as provided otherwise on the Electrical
Drawings. The electrical installation, both power and controls wiring, shall be
performed in accordance with the full electrical installation particular and general
specifications for this project and all local and national installation advisory and
statutory regulations applicable at the time of construction.
B. All analogue input wiring shall be twisted shielded pair or multi-core minimum
0.55mm² csa or as specified by the BMS equipment manufacturer. All system
analogue output wiring shall be twisted shielded pair/3- wire as required, minimum
0.55mm² csa or as specified by the BMS equipment manufacturer. All internal panel
device wiring for binary outputs and pilot relay shall be minimum 16 gauge wire.
C. All field control wiring shall be installed within a dedicated trunking/conduit system or
armoured cables routed on a dedicated tray. Similarly all power wiring is to be routed
in a tray system or contained within a trunking system.

1 ELV wiring not installed in conduit shall be supported every 150mm from the
building structure utilizing metal hangers designed for this application. Wiring
shall be installed neatly and tidily in parallel to the building structural lines. All
wiring shall be installed in accordance with local code requirements. Exposed
wiring shall only be allowed in concealed accessible locations.
2 ELV control wiring and 24VAC can be run in the same conduit and if allowed by
manufacturer of specific equipment used. Power wiring 240VAC and greater
must be in a separate conduit.
3 All wiring in plant rooms shall be in conduit and trunking. Minimum control
wiring conduit size 20mm.
4 Visible wiring and equipment in occupied spaces shall be coordinated and
conform to architectural requirements.
5 All power supplies to essential life safety fire smoke dampers shall be run in
halogen free fire resistant cables compliant with BS 7846 and BS 6387
Category CWZ and the standard details of the electrical specification for this
project. Fire performance shall conform to BS EN 60332-1-2:2004 and BS EN
60332-3-24 : 2009. E.g. Pirelli type FP400 or equal and approved.

E.2 Location of Equipment


A. All equipment shall be sited in such a position that it can be easily maintained with
adequate access. Control panels are not to be sited adjacent to escape routes.
Ensure that a minimum of 1000mm is provided for access at the front of each control
panel.

________________________________________________________________________________
B - 88
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

E.3 Equipment Identification


A. All items of automatic control equipment are to be identified. Use engraved laminate
labels (black lettering on white background). BMS subcontractor to provide a
complete schedule of control devices with the proposed coherent and unique
labelling, system and item number, for comment by the Engineer.

B. Identification Standards

1 All controllers shall be identified by a plastic engraved nameplate securely


fastened to the outside of the controller enclosure.
2 All local control panels shall be identified by a plastic engraved nameplate
securely fastened to the outside of the controller enclosure.
3 All field devices shall be identified by a typed (not handwritten) securely
attached tag label.
4 All internal panel devices shall be identified by a typed label securely fastened
to the backplate of the local control panel.
5 All power and control wiring shall be identified by a number, as referenced to the
associated control diagram, at each end of the conductor or cable. Identification
number shall be permanently secured to the conductor or cable and shall be
typed.

C. Digital Controller Systems

1 Each system shall be provided with its own dedicated direct digital controller or
application specific controller. Mechanical systems such as AHUs, VAVs or
Packaged system shall not be controlled from more than 1 application specific
controller.
2 Systems that use second tier controllers as point expansion for system
controllers shall only be allowed under when the I/O points are directly
controlled by the CPU of the local application specific controller.
D. Input Devices

1 All Input devices shall be installed as per the manufacturer’s recommendations.


The mechanical contractor shall install all in-line devices such as temperature
wells, pressure taps, duct smoke detectors, air flow stations, etc.
2 Low Differential Air Pressure Applications (Under 0.2 psi) Differential pressure
transmitters used for flow measurement shall be sized to the flow sensing
device and shall be supplied with Tee fittings and shut- off valves in the high
and low sensing pick-up lines to allow the balancing contractor and Employer
permanent easy-to-use connection. Provide a minimum of a NEMA 1 housing
for the transmitter. Locate transmitters in accessible local control panels
wherever possible. Except on VAV box applications.
3 Medium Differential Air Pressure Applications (0.2 to 0.75 psi.) Mount stand-
alone pressure transmitters in a bypass valve assembly panel. The panel shall
be constructed to NEMA 1 standards. The transmitter shall be installed in the

________________________________________________________________________________
B - 89
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

panel with hi and low connections piped and valved. Air bleed units, bypass
valves and compression fittings shall be provided.
4 Medium to High Differential Water Pressure Applications (Over 0.75 psi): Mount
stand-alone pressure transmitters in a bypass valve assembly panel. The panel
shall be constructed to NEMA 1 standards. The transmitter shall be installed in
the panel with hi and low connections piped and valved. Air bleed units, bypass
valves and compression fittings shall be provided.
5 Building Differential Air Pressure Applications (-0.04psi to +0.04): Mount
pressure transmitter in the local control panel. Transmitter’s exterior sensing tip
shall be installed with a shielded static air probe to reduce pressure fluctuations
caused by wind. The interior tip shall be inconspicuous and located within a
representative central space.
6 Air Flow Measuring Stations: Where the stations are installed in insulated
ducts, the airflow passage of the station shall be the same size as the inside
airflow dimension of the duct. Station flanges shall be two inch to three inch to
facilitate matching connecting ductwork. Stations shall be installed in strict
accordance with the manufacturer’s published requirements. Air flow
measurement shall be by means of Veloprobe type pitot static averaging tubes
with integrated and calibrated electronic transmitters. Accuracy shall be better
than +/- 5% of design minimum flow rate.
7 Water Flow Monitoring Stations: Water Flow Monitoring Stations shall be
installed in strict accordance with the manufacturer’s published requirements.
8 Outside Air Humidity Sensors: Outside air relative humidity sensors shall be
installed with a rain proof, perforated cover. The transmitter shall be installed in
a NEMA 3R enclosure with sealtite fittings and stainless steel bushings.
9 Outside Air Sensors: Outside air sensors shall be mounted on the North wall to
minimize solar radiant heat impact or located in a continuous intake flow
adequate to monitor outside air temperatures accurately. Sensors exposed to
solar radiation must be installed with adequate solar shields or sufficient other
protection to prevent solar gain distorting the values measured. Sensors
exposed to wind velocity pressures shall be shielded by a perforated plate
surrounding the sensor element.
10 Duct Temperature Sensors: Duct mount sensors shall mount in an electrical
box through a hole in the duct and be positioned so as to be easily accessible
for repair or replacement. The sensors shall be insertion type and constructed
as a complete assembly including lock nut and mounting plate. For ductwork
greater in any dimension that 48 inches and/or air temperature stratification
exists such as a mixed air plenum, utilize an averaging sensor with multiple
sensing points.
11 The sensor shall be mounted to suitable supports using factory approved
element holders. For large plenum applications such as mixed air temperature
measurements, utilize a string of sensors mounted across the plenum to
account for stratification and/or air turbulence. The averaging string shall have
a minimum of 4 sensing points per 3 mh long segment.

________________________________________________________________________________
B - 90
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

12 Space Temperature Sensors: Shall be mounted at 60 inches above the finished


floor. Temperature sensors installed in public areas shall be provided with
lockable covers to prevent tampering.
13 Low Temperature Limit Switches: Mount element horizontally across duct in a
serpentine pattern insuring each square metre of coil is protected by 36 inches
of sensor. For large duct areas where the sensing element does not provide full
coverage of the air stream, provide additional switches as required to provide
full protection of the air stream.
14 Differential Pressure Status Switches: Provide complete installation kit
including; static pressure tops, tubing, fittings and air filters. Provide appropriate
scale range and differential adjustment for intended service.

E. All output devices shall be installed per the manufacturers’ recommendation. The
mechanical contractor shall install all in-line devices such as control valves, dampers,
etc.
F. All control actuators shall be sized capable of closing against the maximum system
shut-off pressure, for two port valves the appropriate pump head. The actuator shall
modulate in a smooth fashion through the entire stroke. When any pneumatic
actuator is sequenced with another device, pilot positioners shall be installed to allow
for proper sequencing.
G. Control Valves shall be sized for proper flow control authority of 0.4 to 0.6 for the
controlled circuit and with equal percentage valve plugs. The maximum pressure
drop for water applications shall be 5 psi. The maximum pressure drop for steam
applications shall be 0.725 psi. All valves shall be selected to withstand the static
pressure of the circuits in which they shall be installed.
H. Electronic Signal Isolation Transducers: Whenever an analogue output signal from
the Building Management System is to be connected to an external control system as
an input (such as a chiller control panel), or is to receive as an input a signal from a
remote system, provide a signal isolation transducer. Signal isolation transducer shall
provide ground plane isolation between systems. Signals shall provide optical
isolation between systems

________________________________________________________________________________
B - 91
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

E.4 Field Quality Control


A. Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect, test, and adjust field-assembled components and equipment installation,
including connections, and to assist in field testing. Report results in writing.
B. Perform the following field tests and inspections and prepare test reports:

1 Operational Test: After electrical circuitry has been energized, start units to
confirm proper unit operation. Remove and replace malfunctioning units and
retest.
2 Test and adjust controls and safeties.
3 Test calibration of electronic controllers by disconnecting input sensors and
stimulating operation with compatible signal generator.
4 Test each point through its full operating range to verify that safety and
operating control set points are as required.
5 Test each control loop to verify stable mode of operation and compliance with
sequence of operation. Adjust PID actions.
6 Test each system for compliance with sequence of operation.
7 Test software and hardware interlocks.

C. DDC Verification:

1 Verify that instruments are installed before calibration, testing, and loop or leak
checks.
2 Check instruments for proper location and accessibility.
3 Check instrument installation for direction of flow, elevation, orientation,
insertion depth, and other applicable considerations.
4 Check instrument tubing for proper fittings, slope, material, and support.
5 Check installation of air supply for each instrument.
6 Check flow instruments. Inspect tag number and line and bore size, and verify
that inlet side is identified and that meters are installed correctly.
7 Check pressure instruments, piping slope, installation of valve manifold, and
self-contained pressure regulators.
8 Check temperature instruments and material and length of sensing elements.
9 Check control valves. Verify that they are in correct direction.
10 Check air-operated dampers. Verify that pressure gages are provided and that
proper blade alignment, either parallel or opposed, has been provided.
11 Check DDC system as follows:

i. Verify that DDC controller power supply is from emergency power


supply, if applicable.
ii. Verify that wires at control panels are tagged with their service
designation and approved tagging system.
iii. Verify that spare I/O capacity has been provided.
iv. Verify that DDC controllers are protected from power supply surges.
12 Replace damaged or malfunctioning controls and equipment and repeat testing
procedures.

________________________________________________________________________________
B - 92
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

E.5 Warranty
a) Material: The BMS Control System shall be free from defects in material and
workmanship under normal use and service. If within three years from the date of
practical completion in whole or in part any of the equipment herein described proves
defective in operation, workmanship or materials, it shall be replaced, repaired or
adjusted at the option of the BMS subcontractor free of charge.
b) Installation: The Control System shall be free from defects in installation
workmanship for a period of one year from the date of practical completion in whole or
in part. The BMS subcontractor shall, free of charge, correct any defects in
workmanship within one week of notification in writing by the Engineer.

E.6 Commissioning
a) The BMS subcontractor shall be responsible for the full checking and commissioning
of his system and any other controls equipment supplied by him. Pre-commissioning
documentation with individual signatures recording the proving of each input and
output on the BMS shall be prepared and published prior to commissioning.
b) All safety interlocks, overrides and fail-safe conditions are to be operational prior to
starting the plant. Demonstrate as approved by the Engineer prior to starting plant in
BMS auto mode.
c) Fault conditions for all critical alarms, safety devices and control interlocks shall be
simulated and proved effective as soon as practical once BMS control mode is
selected.
d) Sensors shall be checked to ascertain accuracy within limits, pressure switches
checked for switch points and hysteresis. Humidity sensors shall be checked for
accuracy using a wet/dry bulb thermometer. Alarm thresholds shall be set up for all
measured variables. Initially set to maximum +\- 10% for all measured variables
unless specified tighter elsewhere in the specification.
e) All the necessary test equipment and materials used in commissioning shall be
supplied by the BMS subcontractor. All test equipment shall have valid test
certificates.
f) Trend graphs shall be provided to demonstrate the stable control of all of the plant.
Changing control set points or if necessary simulated inputs shall be employed to
check stability over the design environmental range.
g) The BMS subcontractor shall allow for sufficient additional full day returns, minimum
but not limited to six days, by his commissioning engineer to revisit, check and re-tune
the system at a later date (6 months and 11 months after hand-over) or other time
agreed with the Engineer. He shall check and adjust operational parameters, and re-
tune any control as maybe required by change in the seasonal load conditions or
bedding-in of the plant to restore correct functionality.
h) The BMS subcontractor shall include in his tender an allowance for sufficient return
visits to site for system tuning and to check correct operation of all plants which may
exhibit changes in stability due to settling in or seasonal conditions.
i) Detailed commissioning documentation and schedules shall be submitted for
comment by the Engineer during the design phase showing each plant item, input

________________________________________________________________________________
B - 93
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

and output point, interlock and control algorithms, and the stages of checks and
commissioning required. Each cleared item to have date and engineer reference.
Completed copies shall be submitted to the Engineer for comment prior to
acceptance testing. A complete set of the commissioning documentation is to form
part of the system documentation.
j) Once any item of plant is commissioned and left running to the dictates of the BMS,
appropriate documentation showing the overrides, control and software configuration
shall be available on site at all times.

E.7 Adjusting
a) Calibrating and Adjusting:

1 Calibrate instruments.
2 Make three-point calibration test for both linearity and accuracy for each
analogue instrument.
3 Calibrate equipment and procedures using manufacturer's written
recommendations and instruction manuals. Use test equipment with accuracy
at least double that of instrument being calibrated.
4 Control System Inputs and Outputs:

a) Check analogue inputs at 0, 50, and 100 percent of span.


b) Check analogue outputs using milli-ampere meter at 0, 50, and 100
percent output.
c) Check digital inputs using jumper wire.
d) Check digital outputs using ohmmeter to test for contact making or
breaking.
e) Check resistance temperature inputs at 0, 50, and 100 percent of span
using a precision-resistant source.

5 Flow:
a) Set differential pressure flow transmitters for 0 and 100 percent values with
3-point calibration accomplished at 50, 90, and 100 percent of span.
b) Manually operate flow switches to verify that they make or break contact.

6 Pressure:

a) Calibrate pressure transmitters at 0, 50, and 100 percent of span.


b) Calibrate pressure switches to make or break contacts, with adjustable
differential set at minimum.

7 Temperature:

a) Calibrate resistance temperature transmitters at 0, 50, and 100 percent of


span using a precision- resistance source.
b) Calibrate temperature switches to make or break contacts.

________________________________________________________________________________
B - 94
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

8 Stroke and adjust control valves and dampers without positioners, following
the manufacturer's recommended procedure, so that valve or damper is 100
percent open and closed.
9 Stroke and adjust control valves and dampers with positioners, following
manufacturer's recommended procedure, so that valve and damper is 0, 50,
and 100 percent closed.
10 Provide diagnostic and test instruments for calibration and adjustment of
system.
11 Provide written description of procedures and equipment for calibrating each
type of instrument. Submit procedures review and approval before initiating
startup procedures.
12 Adjust initial temperature and humidity set points.
13 Occupancy Adjustments: When requested within 12 months of date of
Substantial Completion, provide on-site assistance in adjusting system to suit
actual occupied conditions. Provide up to three visits to Project during other
than normal occupancy hours for this purpose.

________________________________________________________________________________
B - 95
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

E.8 Demonstrations and Operation Trials


a) Engage a factory-authorized service representative to train Owner's maintenance
personnel to adjust, operate, and maintain HVAC instrumentation and controls. Refer
to "Demonstration and Training."
b) General

1 In addition to Engineer demonstrations and commissioning works, the


following shall be monitored (by use of the BMS trend logging facility and
where necessary by electronic data loggers) on a 15-minute interval basis (or
more frequently if required to show compliance with the specified performance
in specific spaces) 24 hours/day for a 7 day operational week both for winter
and summer periods.

i. Outdoor air temperature and humidity.


ii. Supply and return air temperature and humidity for the following:
 All AHUs
 All FCUs
 Cooling water flow and return temperatures (all primary and
secondary circuits). All space temperature, humidity and air
quality sensor values.
 All air volume supply rates.

2 Schedule the operating parameters and time schedules that have been set
into the control systems during the two trial periods to enable the data log
results to be analyzed.
3 Print out on a daily basis, graphs of all points monitored and mark-up these
graphs with the control set points and design limits where applicable and
submit all of these graphs and schedules to the Engineer and Employer for
comment.
4 Enclose the data log graphs and operating parameters scheduled as part of
the
5 O&M Manual at handover of the buildings. It is accepted that at handover,
only one of the two trial periods shall have been completed and consequently
that the second set of results shall be recorded and enclosed at a later date.
Retain on site a qualified engineer with knowledge of the project until such
time as the O&M Manual is available and training delivered.
6 The object of the trials is to demonstrate that the monitored systems perform
as required, including scheduled starts and stops, for a 7 day period without
requiring adjustment of any control set points or changing of any equipment. It
follows, therefore, that sufficient pre-trials test runs must be carried out by the
installer, such that they are confident that the systems and their controls shall
operate satisfactorily during the trails periods.
________________________________________________________________________________
B - 96
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

7 Should any part of the system or its controls fail during the trial or require
adjustment the Engineer shall decide whether the trial shall be void and
restarted.
8 The benefit to the BMS subcontractor of successfully carrying out the above
detailed trial is that he shall have proved that the systems work as required.
9 It is necessary to check the calibration of all sensors prior to starting the trial to
prevent abortive work.
10 A signed certificate detailing the calibration check results for each sensor shall
be provided by the BMS subcontractor.
11 Copies of calibration certificates for all test equipment used shall also be
provided.
12 The position of each data logger around the building shall be agreed in
advance of the trials commencement with the Engineer. Notwithstanding the
above, all data loggers must be placed at working plane level (35 inches from
finished floor level) and be sited away from the influence of draughts or direct
solar gain.
13 The complete set of graphs shall be referenced, indexed and included as part
of the handover documentation in their own clearly identified ring file. All
sensors and test equipment calibration Certificates shall also be included in
this document.
14 Compact disk(s) containing all of the trial data shall be included with the
handover documentation.
15 Should any part of the system require alteration or adjustment during the trial
then the period shall be extended to provide the required time after the
alteration/adjustment.
16 Any compromise to that trial period extension shall be at the discretion of the
Engineer.
17 The controls contractor shall issue a report based on a sampling of the FCU
controller calculated loop performance metrics. The report shall indicate
performance criteria, include the count of conforming and non-conforming
boxes, list the non-conforming boxes along with their performance data, and
shall also include graphical representations of performance. The sampling shall
take place after completion of Test and Balance, when design cooling and
heating media have been available and occupied conditions approximated for
five consecutive days.

c) Supervisors

1 Demonstrate to the satisfaction of the Engineer that alarms handling,


passwords, acknowledgements, peripherals, graphics, automatic data storage,
back door access, alarm and graphics report times and alarm masking are all
set up and function correctly at each Building System Operating Station.

________________________________________________________________________________
B - 97
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

d) Repeatability Test

1 Comprehensively repeat and test transmission of alarms to supervisors and


generate alarm faults to demonstrate to the satisfaction of the Engineer that
the communications system is reliable.
2 The object of this test is to demonstrate that the communication system
operates without fault at handover. The benefit to the BMS subcontractor of
successfully carrying out the above test is that he shall have proved that the
system did work as required. Notwithstanding the above, the BMS
communications network is the sole responsibility of the BMS subcontractor
and he shall immediately rectify any faults which are detected during the
defects liability period.

________________________________________________________________________________
B - 98
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
__________________________________________________________________________

E.9 Operating Training and Maintenance


a) The BMS subcontractor shall provide a suitable member of the site BMS installation
and commissioning staff and the project BMS and Planned Preventative Maintenance
(PPM) system engineer, to attend the site and assist the Employer in the operation of
the BMS system for a period of two weeks after system handover, and for a further
period of one month to be arranged during the first year after system handover.
b) The BMS subcontractor shall arrange and allow for all associated costs, for the
selected representatives (allow for five number staff) to undertake training in the use
of BMS.
c) The training shall be phased to ensure a full understanding of the system.
d) The first phase shall be the provision of a basic set of literature on the principles of
the BMS method of control, specifically for the manufacturers’ equipment, BMS set-up
and PPM capabilities.
e) The second phase shall be the provision of all of the manuals by the BMS
subcontractor in the word processed format, together with the drawings and methods
of operation to allow the representatives to familiarize themselves with the features of
the system installed.
f) The third phase shall be a course each provided with simulator terminals and with
hands on adjustment and appraisal of the control elements used within the
manufacturers works or other suitable location as agreed with the Engineer and
Client. The course content shall include:

1 System hardware.
2 System software.
3 The operator interface.
4 Access routines
5 System hierarchy and structure.
6 Communications.
7 Alarms.
8 Trend logging.
9 Graphics creation and editing.
10 Programming language.
11 Hard and soft points.
12 Control loop.
13 Edit facilities.
14 Network theory and equipment.
15 Outstation programming.

________________________________________________________________________________
B - 99
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________

16 BMS input and manipulation.


17 PPM programming and interfacing to the BMS.

g) The fourth phase of the training shall be Site based with a familiarization tour of all the
BMS and PPM facilities that are unique. This shall be undertaken with the "as
installed" information and final manuals and incorporate any field adjustment and
maintenance activities that are required.
h) The final phase of the training shall be on Site with all user activities being
demonstrated and with each representative having a keyboard tour of the Site
facilities with opportunity provided to have supervised access to all of the system
functions.
i) In order to support good facilities management sufficient training shall be provided to
enable a trained operator to, as a minimum:

1 View equipment status


2 View and acknowledge alarms
3 Adjust optimized time clocks and calendars
4 Adjust set points, alarm tolerances and control parameters. Alarm thresholds
initially set to maximum +\- 10% for all measured variables unless tighter
values specified.
5 Investigate calculated values
6 View plant hours run data
7 Chart energy usage from the meters
8 Create tenant utility bills
9 Create and view long term trend Logs of controlled parameters in particular
the temperature and humidity in areas.

j) The Contractor shall allow for 2 No additional full day presentations and/or training
days for new users of the system within a one-year period after handover.
k) Provide costs within the tender for maintenance options for the control system for
one, three and five years.
l) Allow for adequate visits to achieve service in line with HVAC Standard Maintenance
Specification.
m) Allow for local on-site call out attendance response within 24 hours.

________________________________________________________________________________
B - 100
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

PART 'F' : BMS POINTS SCHEDULE I/O

F.1 AIR CONDITIONING & VENTILATION SYSTEM

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


1 Air Cooled Water Chillers (Both System) 10
1 Chiller enable 10 VFC to Panel
2 Chiller run status 10 VFC from Panel
3 Chiller fault status 10 VFC from Panel
4 Integral primary CHW pump enable 10 VFC to Panel
5 Integral primary CHW pump run status 10 VFC from Panel
6 Integral primary CHW pump fault status 10 VFC from Panel
7 Motorized Valve Open / Close Status 10 VFC from Panel
8 CHW flow sensing 10 Flow Meter
9 CHW static water pressure 10 Water Pressure sensor
10 CHW flow temperature 10 Immerssion Temp Sensor
11 CHW return temperature 10 Immerssion Temp Sensor
2 Secondary CHW Pumps (Both System) 8
1 Secondary CHW pump enable 8 VFC to Panel
2 Secondary CHW pump run status 8 VFC from Panel
3 Secondary CHW pump fault status 8 VFC from Panel
4 Secondary CHW pump speed 8 0-10V Signal to VSD (VSD by others)
5 Secondary CHW pump VSD status 8 0-10V Signal from VSD
3 Chilled Water Pressurisation Unit(Both System) 2

____________________________________________________________________________________________________________________________________
B - 101
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


1 Pressurisation unit enable 2 To pressurisation unit control panel
2 Pressurisation unit run status 2 From pressurisation unit control panel
3 Pressurisation unit fault status 2 From pressurisation unit control panel
4 Pressurisation unit low pressure alarm 2 From pressurisation unit control panel
5 Pressurisation unit high pressure alarm 2 From pressurisation unit control panel
6 System static water pressure 2 Water Pressure sensor
Recirculation Air Handling Units with (TFA) (All
4 21
Applicable Blocks)
1 OA motorised damper 21 Modulating Damper Actuator
2 EA motorised damper 21 Modulating Damper Actuator
3 Recirc motorised damper 21 Modulating Damper Actuator
4 Supply fan start/stop 21 VFC to Panel
5 Supply fan speed 21 0-10V Signal to VSD (VSD by others)
6 Supply run status 21 Air DP Switch
7 Supply fan fault status 21 VFC from Panel
8 Supply fan airflow (m3/s) 21 Air DP Sensor
9 AHU emergency stop 21 VFC from Panel
10 RA air filter pressure drop 21 Filter DP Sensor
0-10V Signal to Cooling Coil Control Valve
21
11 Cooling control valve Actuator
12 Cooling Coil entering Temp/Humidity 42 Duct Temp/Humidity Sensor
13 Cooling Coil leaving Temp/Humidity 42 Duct Temp/Humidity Sensor
14 RA Temp/Humidity 42 Duct Temp/Humidity Sensor
15 RA CO2 21 CO2 Sensor

____________________________________________________________________________________________________________________________________
B - 102
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


16 Air Duct Pressure 21 Air Pressure Sensor
17 Supply air temperature (downstream of AHU) 21 Duct Temp Sensor
Recircular with Direct FA Air Handling Unit (All
5 15
Applicable Blocks)
1 OA motorised damper 15 Modulating Damper Actuator
2 EA motorised damper 15 Modulating Damper Actuator
3 Supply fan start/stop 15 VFC to Panel
4 Exhaust fan start/stop 15 VFC to Panel
5 Supply fan speed 15 0-10V Signal to VSD (VSD by others)
6 Exhaust fan speed 15 0-10V Signal to VSD (VSD by others)
7 Supply fan status 15 VFC from Panel
8 Exhaust fan status 15 VFC from Panel
9 Supply fan fault status 15 VFC from Panel
10 Exhaust fan fault status 15 VFC from Panel
11 Supply fan airflow (m3/s) 15 Air DP Sensor
12 AHU emergency stop 15 VFC from Panel
13 OA air filter pressure drop 15 Filter DP Sensor
0-10V Signal to Cooling Coil Control Valve
15
14 Cooling control valve Actuator
15 AHU Supply OA Temp/Humidity 30 Ambient Temp/Humidity Sensor
16 Supply air side LADB /LARH 30 Duct Temp/Humidity Sensor
17 Exhaust air side LADB /LARH 30 Duct Temp/Humidity Sensor
18 Cooling Coil leaving Temp/Humidity 30 Duct Temp/Humidity Sensor
19 Supply air temperature (downstream of AHU) 15 Duct Temp Sensor

____________________________________________________________________________________________________________________________________
B - 103
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


20 RA Temp/Humidity 15 Duct Temp/Humidity Sensor
21 RA CO2 15 CO2 Sensor
22 Air Duct Pressure 15 Air Pressure Sensor
Recircular with Air Handling Unit (All Applicable
6 7
Blocks) - No FA
1 Supply fan start/stop 7 VFC to Panel
2 Exhaust fan start/stop 7 VFC to Panel
3 Supply fan speed 7 0-10V Signal to VSD (VSD by others)
4 Exhaust fan speed 7 0-10V Signal to VSD (VSD by others)
5 Supply fan status 7 VFC from Panel
6 Exhaust fan status 7 VFC from Panel
7 Supply fan fault status 7 VFC from Panel
8 Exhaust fan fault status 7 VFC from Panel
9 Supply fan airflow (m3/s) 7 Air DP Sensor
10 AHU emergency stop 7 VFC from Panel
0-10V Signal to Cooling Coil Control Valve
7
11 Cooling control valve Actuator
12 Cooling Coil leaving Temp/Humidity 14 Duct Temp/Humidity Sensor
13 Supply air temperature (downstream of AHU) 7 Duct Temp Sensor
14 RA Temp/Humidity 7 Duct Temp/Humidity Sensor
15 RA CO2 7 CO2 Sensor

7 Air Pressure Sensor


16 Air Duct Pressure
7 Thermal Wheel Air Handling Unit (All Applicable 27

____________________________________________________________________________________________________________________________________
B - 104
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


Blocks)
1 OA motorised damper 27 Modulating Damper Actuator
2 EA motorised damper 27 Modulating Damper Actuator
3 Supply fan start/stop 27 VFC to Panel
4 Exhaust fan start/stop 27 VFC to Panel
5 Supply fan speed 27 0-10V Signal to VSD (VSD by others)
6 Exhaust fan speed 27 0-10V Signal to VSD (VSD by others)
7 Supply fan status 27 VFC from Panel
8 Exhaust fan status 27 VFC from Panel
9 Supply fan fault status 27 VFC from Panel
10 Exhaust fan fault status 27 VFC from Panel
11 Supply fan airflow (m3/s) 27 Air DP Sensor
12 Exhaust fan airflow (m3/s) 27 Air DP Sensor
13 AHU emergency stop 27 VFC from Panel
14 OA air filter pressure drop 27 Filter DP Sensor
15 EA filter pressure drop 27 Filter DP Sensor
0-10V Signal to Cooling Coil Control Valve
27
16 Cooling control valve Actuator
17 Thermal wheel enable 27 VFC to Panel
18 Thermal wheel speed 27 0-10V Signal to VSD (VSD by others)
19 Thermal wheel fault status 27 VFC from Panel
20 Thermal Wheel supply air side LADB /LARH 54 Duct Temp/Humidity Sensor
21 Thermal Wheel exhaust air side LADB/LARH 54 Duct Temp/Humidity Sensor
22 Cooling Coil leaving Temp/Humidity 54 Duct Temp/Humidity Sensor

____________________________________________________________________________________________________________________________________
B - 105
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


23 Supply air temperature (downstream of AHU) 27 Duct Temp Sensor
24 RA Temp/Humidity 54 Duct Temp/Humidity Sensor
25 EA Temp/Humidity 54 Duct Temp/Humidity Sensor
26 RA CO2 27 CO2 Sensor
27 EA CO2 27 CO2 Sensor
28 Air Duct Pressure 54 Air Pressure Sensor
8 Classroom & Staff IAQ Controls 499
1 Room CO2 499 CO2 Sensor
9 Substation Cooling 6
1 ACU enable 6 VFC to Panel
2 ACU run status 6 VFC from Panel
3 ACU fault status 6 VFC from Panel
4 LV Room Temp 1 Room Temp Sensor
10 Underground Plant Room 1
1 Fresh Air Itake Motorized damper Open / Close 2 VFC to Panel
2 Plant room Exhaust fan enable 1 VFC to Panel
3 Plant room Exhaust fan run status 1 VFC from Panel
4 Plant room Exhaust fan fault status 1 VFC from Panel
5 FCU enable 2 VFC to Panel
6 FCU run status 2 VFC from Panel
7 FCU fault status 2 VFC from Panel
8 Room temperature 2 Room Temp Sensor

____________________________________________________________________________________________________________________________________
B - 106
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


11 Extract Fan Twin 25
1 Exhaust fan start/stop 25 VFC to Panel
2 Exhaust fan speed 25 0-10V Signal to VSD (VSD by others)
3 Exhaust run status 25 Air DP Switch
4 Exhaust fan fault status 25 VFC from Panel
12 Extract Fan Single 33
1 Exhaust fan start/stop 33 VFC to Panel
2 Exhaust fan speed 33 0-10V Signal to VSD (VSD by others)
3 Exhaust run status 33 Air DP Switch
4 Exhaust fan fault status 33 VFC from Panel
13 Crub Mounted Fan 2
1 Exhaust fan start/stop 2 VFC to Panel
2 Exhaust fan speed 2 0-10V Signal to VSD (VSD by others)
3 Exhaust run status 2 Air DP Switch
4 Exhaust fan fault status 2 VFC from Panel
14 Plant Room Wall Mounted Fan 2
1 Exhaust fan start/stop 2 VFC to Panel
2 Exhaust fan speed 2 0-10V Signal to VSD (VSD by others)
3 Exhaust run status 2 Air DP Switch
4 Exhaust fan fault status 2 VFC from Panel
15 Smoke Extract Fan (All Applicable Blocks) 18
1 Motorised fire smoke damper (MFSD) open 18 MSFD (by others)
2 MFSD status 18 VFC from Panel

____________________________________________________________________________________________________________________________________
B - 107
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

AIR CONDITIONING & VENTILATION SYSTEM


3 Exhaust fan start/stop 36 VFC to Panel
4 Exhaust fan speed 36 0-10V Signal to VSD (VSD by others)
5 Exhaust run status 36 Air DP Switch
6 Exhaust fan fault status 36 VFC from Panel
7 FA Intake Open / Close 18 Open / Close Actuator
Smoke Extract Fan Wall Mounted (All Applicable
16 3
Blocks)
1 Motorised fire smoke damper (MFSD) open 3 MSFD (by others)
2 MFSD status 3 VFC from Panel
3 Exhaust fan start/stop 6 VFC to Panel
4 Exhaust fan speed 6 0-10V Signal to VSD (VSD by others)
5 Exhaust run status 6 Air DP Switch
6 Exhaust fan fault status 6 VFC from Panel
7 FA Intake Open / Close 3 Open / Close Actuator
TOTAL BMS POINTS I/O ALL BLOCKS 1531 648 473 306

F.2 PLUMBING / DRAINAGE / FIREFIGHTING SYSTEM

____________________________________________________________________________________________________________________________________
B - 108
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl. PERIPHERAL EQUIPMENT &
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY
No AI DI AO DO REMARKS

PLUMBING / DRAINAGE / FIREFIGHTING SYSTEM


BLOCK C1, C2 and All External
1 Potable Cold Water Storage Tank 2
1 High level alarm 2 Level Switch
2 Low level alarm 2 Level Switch
3 Water temperature 2 Immerssion Temp Sensor
2 Potable Cold Water Domestic Booster Pumpset 3
1 Booster pumpset enable 3 VFC to Panel
2 Booster pump run status 3 VFC from Panel
3 Booster pumpset alarm 3 VFC from Panel
4 System Pressure 3 Water Pressure sensor
3 Potable Water Chlorine Dioxide Disinfection 1
1 Chlorine Dioxide disinfection unit enable 1 VFC to Panel
2 Chlorine Dioxide disinfection unit status 1 VFC from Panel
3 Chlorine Dioxide disinfection unit fault 1 VFC from Panel
4 Potable Cold Water Booster Transfer Pumpset 2
1 Booster pumpset enable 2 VFC to Panel
2 Booster pump run status 2 VFC from Panel
3 Booster pumpset alarm 2 VFC from Panel
4 System Pressure 2 Water Pressure sensor
5 Irrigation Plant Irrigation water storage tank & booster Pumpset 1
1 Water storage tank high level alarm 1 Level Switch
2 Water storage tank low level alarm 1 Level Switch
3 Irrigation system enable 1 VFC to Panel
4 Irrigation system common alarm 1 VFC from Panel

____________________________________________________________________________________________________________________________________
B - 109
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl. PERIPHERAL EQUIPMENT &
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY
No AI DI AO DO REMARKS

PLUMBING / DRAINAGE / FIREFIGHTING SYSTEM


5 Irrigation booster pump run status 2 VFC from Panel
6 Irrigation booster pumpset alarm 2 VFC from Panel
7 Submersible sump pump status 2 VFC from Panel
8 Submersible simp pump alarm 2 VFC from Panel
8 Submersible Pumpset fault 2 VFC from Panel
6 Electric Domestic Water Storage Calorifiers System 4
1 Water heater enable 4 VFC to Panel
2 Water heater fault status 4 VFC from Panel
3 HWS storage temperature 2 Immerssion Temp Sensor
4 DHW circulation pump enable 2 2 VFC to Panel
5 DHW circulation pump status 2 2 VFC from Panel
6 DHW circulation pump fault 2 2 VFC from Panel
7 Swimming Pool Water Pant Monitoring (Learning + Competetion) 2
0-10V Signal to Cooling Coil Control
2
1 CHW control valve Valve Actuator
2 Pool water cooling /Heating entering water temperature 2 Immerssion Temp Sensor
3 Pool water cooling /Heating leaving water temperature 2 Immerssion Temp Sensor
0-10V Signal to Cooling Coil Control
2
4 LTHW control valve Valve Actuator
5 Pool water treatment system enable 2 VFC to Panel
6 Pool water treatment system status 2 VFC from Panel
7 Pool water treatment system common alarm 2 VFC from Panel
8 Heat Pump enable 2 VFC to Panel
9 Cooling enable 2 VFC to Panel

____________________________________________________________________________________________________________________________________
B - 110
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl. PERIPHERAL EQUIPMENT &
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY
No AI DI AO DO REMARKS

PLUMBING / DRAINAGE / FIREFIGHTING SYSTEM


10 Heating enable 5 VFC to Panel
11 Heat Pump run status 5 VFC from Panel
12 Heat Pump fault status 5 VFC from Panel
13 Circulation pump enable 2 VFC to Panel
14 Circulation pump run status 2 VFC from Panel
15 Circulation pump fault status 2 VFC from Panel
16 Water flow sensing 2 Flow Meter
17 Water static water pressure 2 Water Pressure sensor
18 Pool Water flow temperature 2 Immerssion Temp Sensor
19 Pool Water return temperature 2 Immerssion Temp Sensor
20 Pool Water flow sensing 2 Flow Meter
21 Pool Water pressure 2 Water Pressure sensor
22 Pool Water flow temperature 2 Immerssion Temp Sensor
23 Pool Water return temperature 2 Immerssion Temp Sensor
8 Stormwater Pumps for Irrigation 4
1 Stormwater Pump Enable 4 4 VFC to Panel
2 Storm water Pump lum Status 4
3 Storm water Pump Slop Status 4
4 Storm water Pump Fault Status 4
5 Instant water Heater enable 232
6 Instant water Heater Fault Status 232
9 Stormwater Sump Pump 4
1 Submersible Pump Enable 4

____________________________________________________________________________________________________________________________________
B - 111
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl. PERIPHERAL EQUIPMENT &
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY
No AI DI AO DO REMARKS

PLUMBING / DRAINAGE / FIREFIGHTING SYSTEM


2 Submersible Pump Status 4
3 Submersible Pump Fault 4
10 Firefighting System
1 Jockey Pump Enable 1 VFC from Fan
2 Jockey Pump Start / Stop Status 1
3 Jockey Pump Fault Alarm 2
4 Electric Pump Enable 1
5 Electric Pump Start / Stop Status 1
6 Diesel Engineering Start / Stop Status 2
7 Firefighting System Pressure 2
8 firefighting System 1
9 Firefighting Zone control valve Open / Close 28 28
TOTAL BMS POINTS I/O ALL BLOCKS 523 94 8 27

F.3 ELECTRICAL SYSTEM

____________________________________________________________________________________________________________________________________
B - 112
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
1 BLOCK S1 : SECONDARY
Electrical (KWH) Metering -
LVS1/00/01 10 Pulse Output from Power Meter
Future allowance
LV supply failure LVS1/00/01 1
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Central Battery System Central Battery 1
LCP OF DB/S1/00/01/L 1
Lighting Control system
LCP OF DB/S1/01/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
LIFT-STATUS LIFT 1
2 BLOCK S2 : SECONDARY
UPS STATUS UPS ICT HUB- FOR ICT 2
UPS STATUS UPS ICT HUB-FOR CCTV 2
LCP OF DB/S2/00/01/L 1
Lighting Control system
LCP OF DB/S2/01/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1

____________________________________________________________________________________________________________________________________
B - 113
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
3 BLOCK S3 : SECONDARY
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/S3/00/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
4 BLOCK S4 : SECONDARY
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/S4/00/01/L 1
LCP OF DB/S4/01/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1

Disabled Alarm DAP 1

5 BLOCK S5 : SECONDARY
Electrical (KWH) Metering -
ACCP/S5/FF/01 5
Future allowance
SMDB/S5/UPS 8

____________________________________________________________________________________________________________________________________
B - 114
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
UPS ICT SERVER- FOR
UPS STATUS 2 ON/OFF/TRIP/HEALTHY
SERVER
Lighting Control system LCP OF DB/S5/00/01/P 1
LCP OF DB/S5/01/01/P 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
6 BLOCK S6 : SECONDARY
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/S6/00/01/L 1 ON/OFF/TRIP/HEALTHY
LCP OF DB/S6/01/01/L 1 ON/OFF/TRIP/HEALTHY
DB/S6/00/01/EXT 33 ON/OFF/TRIP/HEALTHY
DB/S6/00/01/EXT 33 SWITCHING
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
7 BLOCK H1 : CENTRAL HUB
Electrical (KWH) Metering -
LVS/H1/00/01 13
Future allowance
ACCP/H1/FF/01 7

____________________________________________________________________________________________________________________________________
B - 115
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
ACCP/H1/FF/02 11
ACCP/H1/FF/03 11
ACCP-SF/H1/GF/01 2
SMDB/H1/00/01 16
EMDB/H1/00/01 16
SMDB/H1/00/01/CB 7
LV supply failure LVH1/00/01 1
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Central Battery System Central Battery 1
Lighting Control system LCP OF DB/H1/00/01/L 1
LCP OF DB/H1/00/02/L 1
LCP OF DB/H1/00/01/TL
1
(AUTDITORIUM LCP)
DB/H1/00/01/EXT 1 ON/OFF/TRIP/HEALTHY
DB/H1/00/01/EXT 1 SWITCHING
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
LIFT-STATUS LIFT 1
8 BLOCK P1 : PRIMARY

____________________________________________________________________________________________________________________________________
B - 116
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
Electrical (KWH) Metering -
ACCP/P1/GF/01 16
Future allowance
ACCP-SF/P1/GF/01 5
SMDB/P1/00/01 4
SMDB/P1/00/02 KITCHEN 17
SMDB/P1/UPS 6
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/P1/00/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
9 BLOCK P2 : PRIMARY
Electrical (KWH) Metering -
ACCP/P2/GF/01 4
Future allowance
ACCP/P2/FF/01 13
ACCP-SF/P2/GF/01 1
SMDB/P2/00/01 16
SMDB/P2/00/02 5
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY

____________________________________________________________________________________________________________________________________
B - 117
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
Lighting Control system LCP OF DB/P2/00/01/L 1
LCP OF DB/P2/00/02/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
LIFT-STATUS LIFT 1
10 BLOCK P3 : PRIMARY
Electrical (KWH) Metering -
ACCP/P3/GF/01 3
Future allowance
SMDB/P3/00/01 3
ACCP/P3/GF/01 5
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/P3/00/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
11 BLOCK P4 : PRIMARY
Electrical (KWH) Metering -
ACCP/P4/GF/01 2
Future allowance
SMDB/P4/00/01 5

____________________________________________________________________________________________________________________________________
B - 118
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
ACCP/P4/GF/01 2
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/P4/00/01/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
12 BLOCK P5 : PRIMARY
Electrical (KWH) Metering -
ACCP/P5/GF/01 4
Future allowance
ACCP/P5/FF/01 12
ACCP-SF/P5/GF/01 1
SMDB/P5/00/01 5
SMDB/P5/00/01 5
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Lighting Control system LCP OF DB/P5/00/01/L 1
LCP OF DB/P5/00/02/L 1
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1

____________________________________________________________________________________________________________________________________
B - 119
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
LIFT-STATUS LIFT 1
13 BLOCK C1 : PRIMAR SPORTS BLOCK
Electrical (KWH) Metering -
LVC1/00/01 3
Future allowance
LVC1/00/02 7
ACCP/C1/FF/01 12
ACCP-SF/C1/GF/01 1
SMDB/C1/00/01 4
SMDB/BS/01 7
EMDB/C1/00/01 11
SMDB/C1/00/01/CB 3
LV supply failure LVSC1/00/01 1
LVSC1/00/01 1
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Central Battery System Central Battery 1
Lighting Control system LCP OF DB/C1/00/01/L 1
DB/C1/00/01/EXT 1 ON/OFF/TRIP/HEALTHY
DB/C1/00/01/EXT 1 SWITCHING
Fire Alarm System Interface FACP 1
PAVA PAVA 1

____________________________________________________________________________________________________________________________________
B - 120
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
Disabled Alarm DAP 1
14 BLOCK C2 : SECONDARY SPORTS BLOCK
Electrical (KWH) Metering -
LVS/C2/00/01 6
Future allowance
LVS/C2/00/02 4
LVS/C2/00/03 7
ACCP/C2/GF/01 21
ACCP/C2/FF/01 16
ACCP/C2/RF/P/01 7
ACCP/C2/RF/P/02 7
ACCP/C2/RF/S/01 4
ACCP/C2/RF/S/02 4
ACCP/-SF/C2/GF/01 4
SMDB/C2/00/01 10
LV supply failure LVS/C2/00/01 1
LVS/C2/00/02 1
LVS/C2/00/03 1
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Central Battery System Central Battery 1
Lighting Control system LCP OF DB/C2/00/01/L 1

____________________________________________________________________________________________________________________________________
B - 121
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
LCP OF DB/C2/01/01/L 1
DB/C2/00/01/EXT 1 ON/OFF/TRIP/HEALTHY
DB/C2/00/01/EXT 1 SWITCHING
Fire Alarm System Interface FACP 1
PAVA PAVA 1
Disabled Alarm DAP 1
LIFT-STATUS LIFT 1
15 BLOCK C3 : FACILITY MANAGEMENT (FM)
Electrical (KWH) Metering -
LVS/C3/00/01 7
Future allowance
ACCP/C3H1/FF/01 8
ACCP-SF/C3/GF/01 1
SMDB/C3/00/01 16
EMDB/C3/00/01 16
LV supply failure LVS/C3/00/01 1
UPS STATUS UPS ICT HUB- FOR ICT 2 ON/OFF/TRIP/HEALTHY
UPS STATUS UPS ICT HUB-FOR CCTV 2 ON/OFF/TRIP/HEALTHY
Central Battery System Central Battery 1
Lighting Control system LCP OF DB/C3/00/01/L 1
DB/C3/00/01/EXT 1 ON/OFF/TRIP/HEALTHY
DB/C3/00/01/EXT 1 SWITCHING

____________________________________________________________________________________________________________________________________
B - 122
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
Fire Alarm System Interface FACP - C3 1
FACP - MAIN 1
PAVA PAVA - C3 1
PAVA - MAIN 1
Disabled Alarm DAP 1
16 Electrical Interface (For Applicable Blocks) 11
From the ECC LV Switchpanel
From ECC Standby Generator control
11 panel
From ECC Standby Generator control
LV supply failure panel
Standby generator run status 5 Pulse output from power meter
Standby generator fault status 5 Pulse output from power meter
17 Diesel Fuel Transfer System for all Generators 5
via AOM control switch on FTS control
5
Fuel transfer pump enable panel
Fuel transfer pump run status 5 on FTS control panel
Fuel transfer pump fault status 5 on FTS control panel
Overflow tank level 5 on FTS control panel
Overflow tank high level alarm 5 via FTS control panel
Diesel fuel leak detection system status 5 on FTS control panel
Diesel fuel leak detection system alarm 5 on FTS control panel

____________________________________________________________________________________________________________________________________
B - 123
DOHA COLLEGE B.M.S Specification
AL WAJBA QATAR
(QEA-924)
_______________________________________________________________________________________________________________

INPUT OUTPUT
Sl.
EQUIPMENT & CONTROL FUNCTION DESCRIPTION QTY PERIPHERAL EQUIPMENT & REMARKS
No AI DI AO DO

ELECTRICAL SYSTEM
18 External Gate Barrier 8
Gate Barrier ON/OFF/NORMAL STATUS 8
TOTAL BMS POINTS I/O ALL BLOCKS 5 779 11

****************************************************

____________________________________________________________________________________________________________________________________
B - 124

You might also like