You are on page 1of 140

Low Voltage

Prisma iPM
system L
Wall mounted switchboards up to 630A

Catalogue
2018
Illustrated table of contents of
Index of commercial numbers A-2 Standards A-11

Overview A-8 Prisma iPM a tested A-18


switchboard

Functional unit description B-2 B-4 B-12 B-16

Compact NSX 100 / 630 A EasyPact CVS 100 / 630 A Easypact EZC 100/400/630A

B-18

Interpact INS 250 / 630 A

B-20

Fupact INF

B-28 B-30 B-32 B-33

Industrial and control devices Human / Machine interface Other devices Reserve space

Distribution description C-2 C-5 C-6 C-14

Multi-stage busbars Rear busbars Distribution blocks

Enclosure description D-2 D-4 D-5 D-6

IP30 / 40 PAK wall mounted enclosures IP30 / 31 wall mounted enclosures IP40 wall mounted enclosures

Spare parts E-2 Mechanical characteristics E-8

Electrical characteristics E-3 Environment E-12

Assembling recommendations F-2

Assembling tips F-8


Prisma iPM system L

presentation
Wall mounted system L A-24 Commercial reference A-30

Index and
Tools and services A-28

Circuit breakers

B-24 B-24

Multi 9 modular devices NG125 modular device


Switch-disconnectors

Functional units
Fusegear

Other

B-34

Functional units accessories


Distribution

Distribution
C-16 C-19

Accessories Partitioning
PAK and wall mounted
enclosures

Enclosures
D-7 D-8 D-10

IP54 wall mounted enclosures IP30 / 31 / 40 / 54 enclosure accessories Dimensions


Characteristics
Recommendations
A-4
Index and presentation Contents
System L

Index A-2
Index of catalogue numbers A-2

Presentation A-6
Overview A-8
Standards A-13
Prisma iPM a tested switchboard A-18
Wall mounted system L up to 630 A A-24
Tools and services A-28

Commercial reference A-30


Commercial reference numbering system A-30
Determining the commercial number A-31

A-1
Index and presentation Index of catalogue numbers
System L

Index

Com. no. Designation Page Com. no. Designation Page


03180 20 M4 clip-nuts for slotted mounting plates B-32 04751 Insulated flexible bar 32x5mm, L=1800mm C-16

03181 20 M5 clip-nuts for slotted mounting plates B-32 04753 Insulated flexible bar 32x8mm, L=1800mm C-16

03182 20 M6 clip-nuts for slotted mounting plates B-32 08903 12 adhesive label holders, H=24mm, W=432mm B-35

03183 20 M5 self-tapping screws for functional upright B-5 08913 12 clip-on labels, 18x35mm B-35
mounting B-7
08940 Barrel lock no. 405 D-9
B-9
B-11 08945 DIN double bar insert D-9
B-13
08946 Screwdriver slot insert D-9
B-15
B-17 08963 Adhesive drawing holder D-9
B-19
B-21 LSL58033A Door spare parts for system L E-2
B-25 LSL58104A IP30-IP54 plain door W600 H300 4M D-4
B-27 D-5
B-29 D-6
B-32 D-7
D-4
D-5 LSL58108A Plain door W600 H500 8M D-4
D-6 D-5
D-7 LSL58112A Plain door W600 H700 12M D-4
03581 2 universal angle brackets B-34 D-5

04029 Conn.200A multiclip/rear BB C-6 LSL58116A Plain door W600 H900 16M D-4
C-9 D-5
C-15 LSL58120A Plain door W600 H1100 20M D-4
04031 Polybloc distribution block, 1P, 160A C-15 D-5

04033 Polybloc distribution block, 3P, 250A C-15 LSL58124A Plain door W600 H1300 24M D-4
D-5
04034 Polybloc distribution block, 4P, 250A C-15
LSL58128A Plain door W600 H1600 28M D-5
04045 Distribloc 125A B-25
B-27 LSL58132A Plain door W600 H1800 32M D-5
C-15 LSL58149A IP54 plain door W600 H500 8M D-6
04171 4 bars with threaded holes, 160A, L=1400mm C-12 D-7
C-13 LSL58150A IP54 plain door W600 H700 12M D-4
04172 4 bars with threaded holes, 250A, L=1400mm A-33 D-6
C-12 D-7
C-13 LSL58151A IP54 plain door W600 H900 16M D-4
04173 4 bars with threaded holes, 400A, L=1400mm C-12 D-6
C-13 D-7

04174 4 bars with threaded holes, 630A, L=1400mm C-12 LSL58152A IP54 plain door W600 H1100 20M D-4
C-13 D-6
D-7
04195 40 M6x16mm screws for bars with threaded holes, A-33
less than 630A C-13 LSL58153A IP54 plain door W600 H1300 24M D-4
C-18 D-6
D-7
04197 Busbar power supply barrier, 630A A-31
C-13 LSL58154A IP54 plain door W600 H1600 28M D-6
D-7
04198 Rear busbar barrier C-13
LSL58155A IP54 plain door W600 H1800 32M D-6
04226 Modular device rail, L=1600mm B-29 D-7
B-32
LSL58157T IP54 transparent door W600 H900 16M D-4
04239 12 horizontal cable straps A-33 D-6
B-25 D-7
B-27
C-17 LSL58158T IP54 transparent door W600 H1100 20M D-4
D-6
04243 4 covers for horizontal cable straps A-33 D-7
B-25
B-27 LSL58159T IP54 transparent door W600 H1300 24M D-4
C-17 D-6
D-7
04255 12 horizontal trunking supports B-25
LSL58160T IP54 transparent door W600 H500 8M D-6
B-27
D-7
C-18
LSL58161T IP54 transparent door W600 H700 12M D-4
04742 Insulated flexible bar 20x2mm, L=1800mm C-16
D-6
04743 Insulated flexible bar 20x3mm, L=1800mm C-16 D-7

A-2
Index and presentation Index of catalogue numbers
System L

Index

Com. no. Designation Page Com. no. Designation Page


LSL58162T Transparent door W600 H500 8M D-4 LSL58274A 2 additional lifting / fixing rings D-8
D-5
LSL58275A Assembly kit IP54 D-7
LSL58163T Transparent door W600 H700 12M D-4
LSL58276A L IP40 accessories + gasket kit 2000mm D-4
D-5
D-6
LSL58164T Transparent door W600 H900 16M D-4
LSL58279V L vertical partition 28M 32M C-19
D-5
LSL58280V L vertical partition 4M to 24M C-19
LSL58165T Transparent door W600 H1100 20M A-33
D-4 LSL58281H L horizontal partition W500 D235 C-19
D-5
LSL58282H L horizontal partition W500 D305 C-19
LSL58166T Transparent door W600 H1300 24M D-4
D-5 LSL58293A 4 wall mounted cable tie supports, W=300mm A-33
D-9
LSL58167T Transparent door W600 H1600 28M D-5
LSL58296A 4 wall mounted cable tie supports, W=600mm A-33
LSL58168T Transparent door W600 H1800 32M D-5 D-9
LSL58169T IP54 transparent door W600 H1600 28M D-6 LSL58328A IP30 WM enclosure W600 D305 H1600 28M D-5
D-7 D-6
LSL58170T IP54 transparent door W600 H1800 32M D-6 LSL58329A Pak WM enclosure W600 D305 H1600 28M D-4
D-7
LSL58332A IP30 WM enclosure W600 D305 H1800 32M D-5
LSL58204A IP30 WM enclosure W600 D235 H300 4M D-5 D-6
D-6
LSL58333A Pak WM enclosure W600 D305 H1800 32M D-4
LSL58205A PAK WM enclosure W600 D235 H300 4M D-4
LSL58336A IP30 WM enclosure + door W300 D305 H1600 28M D-5
LSL58208A IP30 WM enclosure W600 D235 H500 8M D-5 D-6
D-6
LSL58337A IP30 WM enclosure + door W300 D305 H1800 32M D-5
LSL58209A PAK WM enclosure W600 D235 H500 8M D-4 D-6
LSL58212A IP30 WM enclosure W600 D235 H700 12M D-5 LSL58504A IP54 WM enclosure W600 D235 H300 4M D-7
D-6
LSL58508A IP54 WM enclosure W600 D235 H500 8M D-7
LSL58213A PAK235 WM enclosure W600 D235 H700 12M D-4
LSL58512A IP54 WM enclosure W600 D235 H700 12M D-7
LSL58216A IP30 WM enclosure W600 D235 H900 16M D-5
D-6 LSL58516A IP54 WM enclosure W600 D235 H900 16M D-7

LSL58217A PAK235 WM enclosure W600 D235 H900 16M D-4 LSL58520A IP54 WM enclosure W600 D235 H1100 20M D-7

LSL58220A IP30 WM enclosure W600 D235 H1100 20M A-33 LSL58524A IP54 WM enclosure W600 D235 H1300 24M D-7
D-5 LSL58528A IP54 WM enclosure W600 D305 H1600 28M D-7
D-6
LSL58532A IP54 WM enclosure W600 D305 H1800 32M D-7
LSL58221A PAK235 WM enclosure W600 D235 H1100 20M D-4
LSL58541A IP54 WM enclosure + door W300 D235 H500 8M D-7
LSL58224A IP30 WM enclosure W600 D235 H1300 24M D-5
D-6 LSL58542A IP54 WM enclosure + door W300 D235 H700 12M D-7

LSL58225A PAK235 WM enclosure W600 D235 H1300 24M D-4 LSL58543A IP54 WM enclosure + door W300 D235 H900 16M D-7

LSL58231A IP30 WM enclosure + door W300 D235 H500 8M D-5 LSL58544A IP54 WM enclosure + door W300 D235 H1100 20M D-7
D-6 LSL58545A IP54 WM enclosure + door W300 D235 H1300 24M D-7
LSL58232A IP30 WM enclosure + door W300 D235 H700 12M D-5 LSL58546A IP54 WM enclosure + door W300 D305 H1600 28M D-7
D-6
LSL58547A IP54 WM enclosure + door W300 D305 H1800 32M D-7
LSL58233A IP30 WM enclosure + door W300 D235 H900 16M D-5
D-6 LSL58604A System L front plate support 4M D-4

LSL58234A IP30 WM enclosure + door W300 D235 H1100 20M A-33 LSL58608A System L front plate support 8M D-4
D-5
LSL58612A Front plate support 12M D-4
D-6
LSL58616A Front plate support 16M D-4
LSL58235A IP30 WM enclosure + door W300 D235 H1300 24M D-5
D-6 LSL58620A Front plate support 20M D-4

LSL58266A L IP31/41 canopy, D=235mm, W=620mm D-8 LSL58624A Front plate support 24M D-4

LSL58267A L IP31/41 canopy, D=235mm, W=300mm D-8 LSL58628A System L front plate support 28M D-4

LSL58268A L IP31/41 canopy extension, D=235mm, W=600mm D-8 LSL58632A System L front plate support 32M D-4

LSL58269A L IP31/41 canopy, D=300mm, W=620mm D-8 LSL58801A L modular device rail A-33
B-24
LSL58270A L IP31/41 canopy, D=300mm, W=300mm D-8
B-32
LSL58271A L IP31/41 canopy extension, D=300mm, W=600mm D-8
LSL58272A Flush-mount kit up to 24 modules D-8
LSL58273A 4 assembly kit IP30/31/40/41 D-5
D-6

A-3
Index and presentation Index of catalogue numbers
System L

Index

Com. no. Designation Page Com. no. Designation Page


LSL58802A L adjustable modular device rail B-11 LSX58053A Multiclip 200A 3P A-33
B-24 B-25
B-26 B-27
B-32 C-15
D-10
D-11 LSX58054A Multiclip 200A 4P B-25
D-12 B-27
D-13 C-15
LSL58803V L mounting plate EZC100 3P4P / 250 3P vertical B-17 LSX58070A Cu earth  /  neutral bar 24M A-33
LSL58804H L mounting plate EZC100 horizontal B-17 C-17

LSL58805H L mounting plate EZC250 3P horizontal B-17 LSX58080A Rear busbars support C-13

LSL58806V L mounting plate EZC250 4P vertical B-17 LSX58082A Multi-stage busbars support A-33
C-13
LSL58807H L mounting plate EZC250 4P horizontal B-17
LSX58621A Blanking strip modular device L1000 B-25
LSL58810V L mounting plate fupact INF D160 vertical front B-21 B-27
direct B-32
B-34
LSL58814H L mounting plate NSX-INS250 horizontal toggle B-7
B-15 LSX58751A Blanking strip CVS/NSX250 L148 B-7
B-15
LSL58815H L mounting plate NSX-INS250 horizontal toggle A-33
B-7 B-29
B-15 B-34
B-19 LSX58752A Blanking strip EZC250 L1000 B-17
LSL58816V L mounting plate NSX-INS250 vertical toggle A-31 B-34
B-7
LSX58776A Front plate hinge kit B-29
B-15
B-19 B-34
B-29 E-2

LSL58820V L mounting plate NSX-INS630 vertical toggle B-5 LSX58777A 4 front plate lead-sealable screws B-34
B-13
LSX58883A Front plate modular device 3M B-25
B-19
B-29
LSL58824A L slotted mounting plate 4M B-29 B-32
B-32
D-10 LSX58884A Front plate modular device 4M A-33
D-11 B-25
D-12 B-27
D-13 B-29
LSL58825A L slotted mounting plate 12M B-29 B-32
B-32 LSX58885A Front plate modular device 5M B-25
D-10 B-27
D-11
B-32
D-12
D-13 LSX58886V Front plate EZC100 vertical B-17
LSL58826A L plain mounting plate 4M B-32 LSX58887H Front plate EZC100 horizontal B-17
D-10
D-11 LSX58888H Front plate EZC250 3P horizontal B-17
D-12 LSX58889V Front plate 3 / 4 EZC250 vertical B-17
D-13
LSX58890H Front plate EZC250 4P horizontal B-17
LSL58827A L plain mounting plate 12M B-32
D-10 LSX58892V Front plate EZC400 3P vertical B-17
D-11
D-12 LSX58893H Front plate NSX250 horizontal B-7
D-13 B-15

LSL58828H L mounting plate NSXm160 3/4P horizontal B-9 LSX58895V Front plate 4 FUPACT INFD32 / 40 3P vertical B-21

LSL58829V L mounting plate NSXm160 3/4P vertical B-9 LSX58896V Front plate 3 FUPACT INFD63 3P vertical B-21

LSL58959V L front plate NSXm160 3P vertical DRH B-9 LSX58897V Front plate 2 FUPACT INFD100 / 160 3P vertical B-21
LSX58030A 20 front plate screws+nuts B-35 LSX58901H Front plate INS250 horizontal B-19
E-2
LSX58902V Front plate 3 / 4 CVS-NSX-INS250 vertical toggle B-7
LSX58031A Prisma iPM spare parts handle E-2
B-15
LSX58052A Multiclip 200A 2P B-25
B-29
C-15
LSX58903V Front plate 3 / 4 CVS-NSX-INS250 vertical toggle B-7
B-15

A-4
Index and presentation Index of catalogue numbers
System L

Index

Com. no. Designation Page


LSX58904H Front plate NSX250 horizontal B-7
B-15

LSX58905V Front plate INS250 vertical A-33


B-19

LSX58914V Front plate INS630 vertical B-19

LSX58921V Front plate NSX630 vertical vigi B-5


B-13
B-17

LSX58931A Plain front plate 1M A-33


B-5
B-7
B-13
B-15
B-17
B-19
B-25
B-27
B-29
B-33

LSX58932A Plain front plate 2M A-33


B-5
B-7
B-13
B-15
B-17
B-19
B-21
B-33

LSX58933A Plain front plate 3M B-5


B-13
B-19
B-29
B-33

LSX58934A Plain front plate 4M B-5


B-13
B-29
B-33

LSX58935A Plain front plate 5M B-33

LSX58936A Plain front plate 6M B-29


B-33
C-13

LSX58955A Metal front plate with cut-outs, 3 modules B-31


(for four 96 x 96 mm devices)

LSX58956A Metal front plate with cut-outs, 3 modules B-31


(for six 72 x 72 mm devices)

LSX58958H Front plate NSXm160 3/4P horizontal toggle B-9

LSX58960A Blanking plate (for 96 x 96 mm hole) B-31

LSX58961A Blanking plate (for 72 x 72 mm hole) B-31

LSX58961V Front plate NSXm160 4P vertical DRH B-9

LSX58962H Front plate NSXm160 3/4P horizontal DRH B-9

LSX58964T Transparent front plate 4M B-29


B-33

LSX58966T Transparent front plate 6M B-29


B-33

A-5
Let’s pool our
energies for building
dependability

Ensuring the dependability Prisma iPM, a dependable,


of electrical installations simple, innovative solution
of tertiary and industrial for LV electrical distribution
buildings: continuity of and control switchboards.
service and safety of life
and property.

A-6
100% dependable
switchboards
Seize the Prisma iPM opportunity when assembling switchboards
that are optimised, tested and compliant with the IEC 61439-1 standard.
Prisma iPM is a prefabricated, modular solution unique in the market,
that is reliable and upgradeable.
You control your costs and deadlines. Buildings run perfectly.
Users work efficiently and safely.

Make the most of your energy

A-7
Let’s develop installation
dependability

As building market professionals, you are faced with growing demands


for electrical installation continuity of service, safety of life and property
and deadline and cost control.

A-8
Prisma iPM
> An innovative solution based on the
experience, expertise and switchgear
offerings from the global specialist in
energy management.

> Quality production certified ISO 9001.

Using our Prisma iPM solution, you can easily


design, implement and operate low voltage
electrical distribution and control switchboards
that are dependable, because they are optimised,
tested and compliant with the IEC 61439 -1
standard.

Improve the Ensure the Control


continuity of safety of life deadlines
service and property and costs

A-9
Dedicating ourselves
to safe, simple low
voltage switchboards
Prisma iPM, a modular and prefabricated solution based on a complete
system in kit form, that fully integrates Schneider Electric switchgear offerings.

Energy is available 3
in the buildings
2
The Prisma iPM solution perfectly integrates 1
Schneider Electric switchgear and includes our
distribution systems and enclosures.
These quality components have been designed 4
to operate together with optimised performances:
mechanical electrical and communications 5
consistency are ensured.
Switchboards designed and manufactured with
the Prisma iPM solution have all the qualities
needed to ensure energy availability. They
are organised by function and by zone, which
improves reliability and facilitates design,
installation, operation and upgrading.
All switchboard architectures are factory tested
> Example of 28 modules wall mounted switchboard
in line with specifications that go well beyond
the IEC 61439-1 standard.
1 A cable connection 3 A zone for current 4 IPXXB front plates for
The same continuity of service is ensured area with complete distribution with innovative protecting people from
throughout the switchboard’s entire accessibility. busbars. The multistage any direct access to live
current distribution brings parts and circuits opening
life cycle.
2 A zone for functional lightness, ergonomics, and closing.
units* dedicated to each and easy front access.
application in the building 5 Attractive finish to fit
(lighting, HVAC, lifts, etc). into any facility.

* A functional unit includes


switchgear, mounting plate, front
plate and connections.

> Example of floor standing switchboard > Example of 16 modules wall


mounted switchboard

A-10
Energy management
has never been simpler
Simple-to-install Smart Panels connect your building to real savings
in 3 steps

Measure
Embedded and stand-
alone metering & control
capabilities

Connect Save
> Integrated communication > Data-driven energy efficiency
interfaces actions
> Ready to connect to energy > Real time monitoring and control
management platforms > Access to energy and site
information through on-line services

A-11
MEASURE
"Smart Panels" mean
visible information
Grouping most of the electrical protection,
command and metering components, the
switchboards are now significant sources
CLOUD of data locally displayed and sent via
communication networks.

CONNECT
… and ready to be linked
to expertise
Smart Panels use reliable, simple to install
and use displays, and Ethernet and Modbus
interfaces on the Enerlin’X communication
system.
Information is safely transmitted through the
most efficient networks:
• Modbus SL inside switchboards, between
components
• Ethernet, on cable or WiFi, inside the
building and connecting switchboards,
computers,
• Ethernet on DSL or GPRS, for access to
on-line services by Schneider Electric.
Energy experts, wherever they are, are
now able to provide advises based on
permanently updated data of the building.

SAVE

CLOUD

On-site real time


monitoring and control
On a touch screen display connected
to Ethernet
• s hows essential electrical information and
On-line Energy
alarms concerning the electrical network, Management services
•a  llows control (open, close, reset…) of
StruXureWare Energy Operation
various equipments.
automates data collection via an open,
This touch screen is well appreciated for real scalable, and secure energy management
time value checking and control, directly on information system.
the front panel of the main switchboard.
With the help of the Schneider Electric energy
On a PC display with common browser
management services team, data is then
• s hows monitoring web pages hosted into turned into actionable information to enable
the local Ethernet interface, customers to understand their facilities’
•a  larm events generate automatic email performance on an ongoing basis.
notifications,
Energy Operation leverages companies’
•a  llows control (open, close, reset…) of current investments in their existing systems,
various equipments. and can be used to communicate advanced
Data displayed on graphics or recorded into results and performance to a broad audience
files are of a great interest for optimizing for a shared understanding throughout an
the use of energy in the building. organization.
As an example, they definitely help validating
the change of temperature settings, time
scheduling in a Building Management System
or other automated devices.

A-12
Compact NSXm circuit breaker

Last generation well fitting within your Prisma iPM

• From 16 up to 160A
• From 16 KA up to 70 KA
• Thermal magnetic
• Everlink power connections
• Dual plate & DIN rail built-in
• Auxiliary externally visible
• Embedded earth leakage protection

I design an electrical solution I build an electrical solution


“Obtain more projects and provide the best solution “Make the business more profitable...”
for your customers...” • save up to 40% mounting & cabling time (DIN rail,
• enhance power availability thanks to great everlink & spring connections...)
discrimination • optimize the space within your panel (power
• improve panel cost thanks to cascading connection & built-in Vigi)
• high secure design using the power connections • easy to select using the Schneider on-line tools
everlink

A-13
A-14
Index and presentation Standards
International electrotechnical standards
System L

Presentation

IEC international standards The IEC (International Electrotechnical Commission) is a worldwide organisation for
standardisation comprising all national electrotechnical committees (IEC National
IEC member countries Committees).
South Africa Japan
Germany Luxemburg
Argentina Malaysia The object of the IEC is to promote international cooperation on all questions
Australia Mexico concerning standardisation in the electrical and electronic fields.
Austria Norway To that end, the IEC publishes International Standards.
Belarus New Zealand Their preparation is entrusted to technical committees and any IEC National
Belgium Pakistan Committee interested in the subject dealt with may participate in the preparatory
Brazil Netherlands
Bulgaria Poland work.
Canada Portugal
China Rumania
Korea (Rep. of) United Kingdom
Croatia Russia
Denmark Singapore
Egypt Slovakia
Spain Slovenia
Finland Sweden
France Switzerland
Greece Czech Rep.
Hungary Thailand
India Turkey
Iran Ukraine
Indonesia United States
Ireland Yugoslavia
Israel
Italy

National standards In Europe


The IEC documents are first studied by CENELEC, which establishes:
bb either a European standard (EN), often identical to the IEC standard, which then
DD382009

becomes the applicable national standard in all the member countries


bb or, if problems arise, a harmonisation document (HD).
Other IEC member countries
Each country is autonomous and can accept the IEC standard as the national
standard, with or without modifications.
Even though they are IEC members, countries such as Japan and the United States
continue to develop their own standardisation systems.
Countries without a standardisation system
It is possible to refer to an IEC standard in the framework of a project.

CEI / IEC
International Electrotechnical Commission
CENELEC
European Committee for Electrotechnical Standardisation
UTE
Union Technique de l’Électricité (French electrotechnical
standardisation organisation)
VDE
Verband der Elektrotechnik, Elektronik und Informationstechnik
e.v. (German electrotechnical, electronics and computer
technology standardisation organisation)
BSI
British Standards Institution
CCC
China Certification Center

A-15
Index and presentation Standards
Tools for quality assurance
System L

Presentation

The different types of standards There are different types of standards, including:
bb management standards,
bb installation standards,
bb product standards.

Management standards
DD381775

DD381776

ISO 9004: Quality management system - guidelines for performance improvement.


Used in setting up quality management systems.

ISO 9001: Quality management system - requirements. Used for certification audits.

ISO 14004: Environmental management system - major guidelines on the principles.


Design and manufacture. Switchgear assemblies. Systems and techniques implemented.

ISO 14001: Environmental management system - specification with guidance for


DD381777

DD381778

use.

A majority of Schneider Electric development centres and factories are certified


ISO 9001 and ISO 14001.

Installation standards
The set of IEC 60364-X standards defines the main principles and rules on:
Switchgear devices. Installation.
bb assessment of general characteristics of installations,
bb protection,
bb selection and erection of equipment,
bb verification and maintenance of installations.

Product standards
They apply to LV switchgear devices or LV switchgear assemblies, where the
purpose is to ensure the correct operation and safety of the concerned products.
bb standards on switchgear devices:
v IEC 60947-1: general rules,
v IEC 60947-2: circuit breakers,
v IEC 60947-3: switches and disconnectors,
v IEC 60947-4: contactors,
v IEC 62208 / EN 50298: empty enclosures.

bb standards on switchgear assemblies:


v IEC 61439-1: General rules
v IEC 61439-2: Power switchgear and controlgear ASSEMBLIES (PSC-
ASSEMBLIES)
v IEC 61439-3: Distribution boards (to supersede IEC 60439-3)
v IEC 61439-4: ASSEMBLIES for construction sites (to supersede IEC 60439-4)
v IEC 61439-5: ASSEMBLIES for power distribution (to supersede IEC 60439-5)
v IEC 61439-6: Busbar trunking systems (to supersede IEC 60439-2).

Regulations The regulations in a given country may make certain standards legally binding and
may also create additional safety requirements.

Quality assurance In addition to providing proof of the conformity of its quality management system, a
product manufacturer can demonstrate the quality of products by providing proof
that their design and manufacture comply with the requirements in the applicable
standard.
Proof of conformity may be a declaration by the manufacturer or a certificate supplied
by an independent organisation.

A-16
Index and presentation Standards
Standards IEC 61439-1
System L

Presentation

All elements making up the electrical switchboard are concerned.


The object of standard IEC 61439-1 is to lay down the definitions and to state the
service conditions, construction requirements, technical characteristics and tests for
low-voltage switchgear and controlgear assemblies (U < 1000 V).
The standard defines a low-voltage switchgear and controlgear assembly (the
electrical switchboard) as “a combination of one or more low-voltage switching
devices together with associated control, measuring, signalling, protective,
regulating equipment, etc., completely assembled under the responsibility of the
manufacturer with all the internal electrical and mechanical inter-connections and
structural parts”.

Standard IEC 61439-1 These tests ensure the conformity of the electrical switchboard and are intended to
check switchboard characteristics.
b tests are carried out on typical configurations
b routine tests are carried out on the completely finished switchboard. Their purpose
is the check that the characteristics validated by the type tests were not altered
during the manufacturing operations.

The 12 design points tested by 1 - Strength of materials and parts


schneider electric The mechanical, electrical and thermal capability of constructional materials and
parts of the assembly shall be deemed to be proven by verification of construction
and performance characteristics.
where an empty enclosure in accordance with IEC 62208 is used, and it has not
been modified so as to degrade the performance of the enclosure, no repetition of
the enclosure testing is required.

2 - Degree of protection of assemblies


The degree of protection shall be verified in accordance with IEC 60529; the test
may be carried out on a representative equipped assembly. Where an empty
enclosure in accordance with IEC 62208 is used, and no external modification has
been carried out that may result in a deterioration of the degree of protection, no
further testing is required.

3 - Clearances and creepage distances


For dimensioning clearances and creepage distances between separate circuits, the
highest voltage ratings shall be used (rated impulse withstand voltage for clearances
and rated insulation voltage for creepage distances).
The clearances and creepage distances apply to phase to phase, phase to neutral,
and except where a conductor is connected directly to earth, phase to earth and
neutral to earth.

4 - Protection against electric shock and integrity of protective


circuits
b Effectiveness of the protective circuit
b Effective earth continuity between the exposed conductive parts of the assembly
and the protective circuit
b Short-circuit withstand strength of the protective circuit

5 - Incorporation of switching devices and components


Compliance with the design requirements, the incorporation of switching devices
and components shall be confimed by inspection and verified to the requirements of
this standard.
b Electromagnetic compatibility

6 - Internal electrical circuits and connections


7 - Terminals for external conductors
Compliance with the design requirements for terminals for external conductors shall
be confirmed by inspection.

8 - Dielectric properties
All the electrical equipment of the assembly shall be connected, except those items
of apparatus which, according to the relevant specifications, are designed for a lower
test voltage; current-consuming apparatus (e.g. windings, measuring instruments,
voltage surge suppression devices) in which the application of the test voltage would
cause the flow of a current, shall be disconnected. Such apparatus shall be
disconnected at one of their terminals unless they are not designed to withstand the
full test voltage, in which case all terminals may be disconnected.

A-17
Index and presentation Standards
Standards IEC 61439-1
System L

Presentation

9 - Verification of temperature rise


b Verification by testing with current
b Derivation of ratings for similar variants
b Verification by calculation

10 - Short-circuit withstand strength


The short-circuit withstand strength declared by the originalmanufacturer shall be
verified. Verification may be by the application of design rules, by calculation or by
test as specified.
b Circuits of assemblies which are exempted from the verification of the short-circuit
withstand strength
b Verification by the application of design rules
b Verification by comparison with a reference design
b Verification by test

11 - Electromagnetic compatibility(EMC)
b Assembles not incorporating electronic circuits
b Assembles incorporating electronic circuits

12 - Mechanical operation
This verification test shall not be made on such devices of the assembly which have
already been type tested according to their relevant product standard unless their
mechanical operation is impaired by their mounting.
For parts, which need verification by test, satisfactory mechanical operation shall be
verified after installation in the assembly. The number of operating cycles shall be
200.

Routine Verification Series of test under responsibility of the assemblers that must be performed for each
LV assembly.

1 - Degree of protection of enclosures


2 - Clearances and creepage distances
3 - Protection against electric shock and integrity of protective
circuits
4 - Incorporation of built-in components
5 - Internal electrical circuits and connections
6 - Terminals for external conductors
7 - Mechanical operation
8 - Dielectric properties
9 - Wiring, operational performance and function

A-18
Index and presentation Standards
Enclosure standards
System L
IEC 62208 and EN 50298
Presentation

Standards IEC 62208 and EN 50298 General rules for empty enclosures
Empty enclosures for low-voltage switchgear and Standards IEC 62208 and EN 50298 lay down definitions, classifications,
controlgear assemblies characteristics and test requirements for the enclosures used for assemblies.
They apply to empty enclosures before installation of the devices by the panel
builder, as supplied by the manufacturer.
They apply to one-piece enclosures and to enclosures supplied in kit form.

Type tests 1 - Static load


2 - Hoisting
3 - Axial loads of metal inserts
4 - IK code
5 - IP code
6 - Thermal stability
7 - Resistance to heat
8 - Resistance to abnormal heat and to fire
9 - Dielectric strength
10 - Protective-circuit continuity
11 - Weather resistance
12 - Corrosion resistance
13 - Marking.

A-19
Index and presentation Prisma iPM a tested switchboards
System L

Presentation

A switchboard must comply with the requirements in standard IEC 61439-1 to


guarantee the safety and reliability of the installation.
Managers of installations, fully aware of the professional and legal liabilities weighing on their
company and on themselves, demand a high level of safety for the electrical installation.
What is more, the serious economic consequences of prolonged halts in production
mean that the electrical switchboard must provide excellent continuity of service,
whatever the operating conditions.

The Schneider Electric solution bb Specify switchboards that comply with standard IEC 61439-1.
bb Guarantee a level of safety that has been 100% tested, from the day the
switchboard is installed and throughout its service life.
bb Ensure the return on investment through easy upgrading of the installation in
compliance with the standard.
bb Guarantee that the switchboard complies with the technical specifications.

Prisma iPM tested switchboards The conformity of the switchboard has been tested and proven.
A Prisma iPM switchboard is:
bb made up of Schneider Electric low-voltage devices and components that all
comply with the applicable standards,
bb based on configurations in the Schneider Electric catalogue,
bb made up of Prisma iPM mechanical and electrical components that have been
subjected to the twelve tests required by the standard,
bb mounted and wired by a panel builder in compliance with professional standards,
bb subjected to the nine routine verifications required by the standard.
Schneider Electric makes available to the panel builder everything required to create
tested Prisma iPM switchboards, including the basic configurations in the
low-voltage distribution catalogue, all the documentation for switchboard design and
mounting, calculation and design software, etc.
The panel builder can easily demonstrate conformity with standard IEC 61439-1 by
presenting the declarations or certificates of conformity concerning the type tests carried
out by independent laboratories (CCC, ASEFA) and supplied by Schneider Electric.
The panel builder is responsible for the three routine tests and delivers the
corresponding declarations of conformity.

Certifications

A-20
Index and presentation Standards
System M

Presentation

e marking e marking is a regulatory symbol attributed under the sole responsibility of the
manufacturer and intended for the verification authorities of the European countries
that enforce the European regulations.
It allows free circulation of a product in the European Union and certifies that it
complies with the basic requirements in all the applicable European directives.
e marking is not a quality symbol and does not indicate conformity with a standard.

The e declaration is intended exclusively for the authorities in charge of verifying


compliance with the applicable regulations and it is drafted, signed and held for
presentation to the authorities by the manufacturer.
For the Prisma iPM range, the declaration is the respons bility of the Schneider
Electric unit that has designed and developed the product.
For LV switchboards, the declaration is the responsibility of the panelbuilder.

The following products receive e marking:


bb all products that are liable to endanger the safety of persons, animals and property
(LV directive)
bb all products likely to emit electromagnetic disturbances above a standardised
threshold or to be disturbed during operation (EMC directive).

Consequences:
bb the Prisma iPM range falls under the LV directive only
bb LV switchboards are covered by the LV directive and may also fall under the EMC
directive, depending on the type of devices incorporated.

e
For the Prisma iPM range, e marking is applied:
bb on the packing of “mechanical” components
bb on the product itself for “electrical” components.
For the LV assemblies created by the panelbuilder, e marking is applied:
bb on the packing
bb on the rating plate (if applicable)
bb on one of the documents accompanying the switchboard when it is shipped.

A-21
Presentation
IEC 61439 standard

The switchboard,
central to the electrical installation
Both the point of arrival of energy and a device for distribution
to the site applications, the LV switchboard is the intelligence of
the system, central to the electrical installation.
It plays an essential role in the availability of electric power, while meeting the needs of personal and property safety.
Its definition, design and installation are based on precise rules; there is no place for improvisation. The IEC 61439 standard
aims to better define ‘‘low-voltage switchgear and controlgear assemblies’’, ensuring that the specified performances are
reached. It specifies in particular:
> the responsibilities of each player, distinguishing those of the original equipment manufacturer; the organization that per-
formed the original design and associated verification of an assembly in accordance with the standard, and of the assem-
bly manufacturer - the organization taking responsibility for the finished assembly;
> the design and verification rules, constituting a benchmark for product certification.
All the component parts of the electrical switchboard are concerned by the IEC 61439-2 standard. Equipment produced in
accordance with the requirements of this switchboard standard ensures the safety and reliability of the installation.

A switchboard must comply with the Prisma iPM tested switchboards


equirements of standard IEC 61439-1 and 2
to guarantee the safety and reliability of the The conformity of the switchboard has been
installation. Managers of installations, fully tested and proven.
aware of the professional and legal liabilities A Prisma iPM switchboard is:
weighing on their company and on themselves, > made up of Schneider Electric low-voltage
demand a high level of safety for the electrical devices and components that all comply with
installation. the applicable standards;
What is more, the serious economic > based on configurations in our catalogue;
consequences of prolonged halts in production > made up of Prisma iPM mechanical and elec-
mean that the electrical switchboard must trical components that have been subjected to
provide excellent continuity of service, whatever the verification of original equipment manufac-
the operating conditions. turer;
> mounted and wired by a panelbuilder in com-
pliance with professional standards;
> subjected to the individual verification.
Schneider Electric makes available to the
The Schneider Electric solution panelbuilder everything required to create tested
> Specify switchboards that comply with Prisma iPM switchboards, including the basic
standard IEC 61439-1 and 2. configurations in the low voltage distribution
> guarantee a level of safety that has been catalogue, all the documentation for switchboard
100% tested, from the day the switchboard is design and mounting, calculation and design
installed and throughout its service life. software, etc.
> ensure a lasting investment through easy Panelbuilders can demonstrate conformity with
upgrading of the installation in compliance standard IEC 61439-1 and 2 by presenting the
with the standard. declarations or certificates of conformity for type
> guarantee that the switchboard complies with tests carried out by independent laboratories
the technical specifications. (ASEFA, ASTA, KEMA, etc.) and supplied by
Schneider Electric. The panelbuilder is
responsible for the individual routine verification
and delivers the corresponding declarations of
conformity.

A-22
Presentation
IEC 61439 standard

Original Manufacturer and Assembly Manufacturer:


Both involved
in tested assemblies
Standard IEC 61439 clearly defines
the type of verifications that must be conducted
by both organisations involved in final conformity of
the solution: the Original Manufacturer, guaranteeing
assembly system design and the Assembly
Manufacturer, responsible for the final conformity
of the switchboard.

Specifier
> Specifies the needs and
constraints for design,
tion*
installation, operation and
upgrading of the complete
cifica
system.
> Checks that its
ct spe

requirements have been


fully integrated by the
Assembly Manufacturer.
Proje

Depending on the
application, the specifier
could be the end-user or a
design office.

Tes
ted
stem As
ly Sy Assembly sem
bly
mb
A sse Manufacturer
(Panel builder)
The organisation (whether
or not the same as the OM)
responsible for the
completed assembly.

Original He is responsible for End-User


‘‘Routine verifications’’
Should ask for a certified
Manufacturer on each panel produced,
according to the standard. LV switchboard.
The organisation that has By systematically requesting
If he derivates from the routine verifications,
carried out the original design
instructions of the original he ensures that the
and the associated
manufacturer he has to carry assembly system used is
verification of an assembly
out again design verifications. compliant.
system.
He is responsible for the
‘‘Design verifications’’ listed by
IEC 61439-2 including many
electrical tests.

A-23
Presentation
IEC 61439 standard

The main 10 functions


of standard IEC 61439
For each of the following 10 functions, the standard IEC 61439 requires design veri-
fications from the system manufacturer - mainly through type-tests - and routine
verifications on each panel from the Panel Builder to achieve 3 basic goals:
safety, continuity of service and compliance with end-user requirements.

Safety
Voltage stresses withstand capability
To withstand long term voltages, and transient and temporary overvoltages according to the insulation coordination principles and
requirements.
Current-carrying capability
To protect against burns and to withstand temperature rise:
> when any circuit is continuously loaded, alone, to the specified current
> when the assembly is loaded to the specified current according to the specified load pattern (between circuits and/or as a
function of the time).
Short-circuit withstand capability
To withstand the stresses resulting from the prospective short-circuit current and from the associated data (High forces between
conductors, temp. rise in a very short time, air ionization, overpressure).
Protection against electric shock
> Hazardous-live-parts not to be accessible (basic protection)
> Accessible conductive parts not to become hazardous-live (fault protection).
Protection against risk of fire or explosion
> Resistance to internal glowing elements
> Note: Protection of persons, and optional protection of the assembly, against arcing due to internal fault can be specified
through a ‘‘special test’’ according to IEC 61641.

Continuity of service
Maintenance and modification capability
Capability to preserve continuity of supply without impairing safety during assembly maintenance or modification
> Electrical condition of the assembly or various circuits
> Speed of exchange of the functional units
> Test facilities…
Electro-Magnetic compatibility
To properly function (immunity) and not to generate EM disturbances (emission) in specified environmental conditions:
> Industrial networks or locations (Environment A)
> Domestic, commercial, and light industrial locations (Environment B).

Compliance with end-user requirements


Capability to operate the electrical installation
To properly function, according to:
> The electrical diagram of the overall system and related information (voltages, coordination…)
> The specified operating facilities (e.g. free or restricted access to Man Machine Interfaces, isolation of the outgoing circuits, …).
Capability to be installed on site
> To withstand handling, transport, storage… and installation constraints
> Capability to be erected and connected (type of enclosure, type, material and cross sectional areas of external conductors).
Protection of the assembly against mechanical and atmospheric environmental conditions
> Presence of water or solid foreign bodies (IP according to IEC 60529)
> External mechanical impacts (optional IK according to IEC 62262)
> Indoor or outdoor installation (humidity, UV).

A-24
Presentation
IEC 61439 standard

IEC 61439-1 paragraph 11.4

Standard individual
Protection against electric shocks
and integrity of protection circuits
The following should be checked visually:
> Presence of protective shields against direct and
indirect contacts on live parts;
> Presence of the PE conductor.
The continuity of protection circuits is ensured by
check sheet
compliance with the assembly instructions delivered
with each product.
in accordance with the IEC 61439-1
and 2 standard from the assembly
manufacturer (panelbuilder)
IEC 61439-1 paragraph 11.5
Integration of incorporated
components
The assembly manufacturer must comply
with the instructions of the original equipment Job No.:
manufacturer for installation Switchboard No.:
and wiring of the components used. Drawing No./Rev. No.:

IEC 61439-1 paragraph 11.6 Chapter Verified


Internal electric circuits Degrees of protection provided by enclosures 11.2 v
and connections Insulation clearances and creepage distances 11.3 v
Schneider Electric recommends marking Protection against electric shocks and integrity of
the nut with a tinted acrylic lacquer, indelible 11.4 v
protection circuits
and temperature-resistant.
This allows: Integration of incorporated components 11.5 v
> not only self-checking to check effective tightening
Internal electric circuits and connections 11.6 v
to torque;
> but also identification of any loosening. Terminals for external conductors 11.7 v
Mechanical operation 11.8 v
Dielectric properties 11.9 v
IEC 61439-1 paragraphe 11.9
Wiring, operating performance and function 11.10 v
Dielectric properties
The main circuits, and the auxiliary and control circuits
connected to the main circuit, shall be subjected to the
test voltage in accordance. Date of verification:
/ /
Verifications performed by:
IEC 61439-1 paragraph 11.10
Wiring, operating performance
and function
Verification of wiring and marking conformity with the
drawings, parts list and diagram.

A-25
Index and presentation Wall mounted system L
System L up to 630 A
Presentation

Incoming feeders and main LV


switchboards
DD800462

Currents up to 6300 A.

Currents up to 4000 A.

Power distribution
and loads

Currents up to 4000 A.

Currents up to 630 A.

Currents up to 250 A.

A-26
Index and presentation Wall mounted system L
System L up to 630 A
Presentation

Main characteristics
In-door wall mounted system

Electrical characteristics
Nominal rated current (A) 630
Rated insulation voltage Ui 1000
(V AC)
Rated operation voltage 690
(V AC)
Rated impulse withstand 8
voltage (KV)
Frequency (Hz) 50 / 60
Main busbar rated current 630
max. Ie (A)
Rated short-time withstand 25
current Icw (KA / 1 s.)
Rated peak withstand 53
current Ipk (KA)
Neutral network TNC v TNS v IT v TT v
Enclosure characteristics (dimensions, IP, …)
Overall height (mm) 300 500 700 900 1100 1300 1650 1850
Number of vertical modules 4 8 12 16 20 24 28 32
DD800162

(functional height)
1 module = 50 mm
Depth (mm) 235 305
Width of enclosure for 600
devices (mm)
Width of cable duct (mm) 300
Partitioning 1
IP 30 / 31 / 40 / 54
IK 07 / 08
Aplicable standards
Type test IEC61439-1
IP class IEC60529
Insulation materials inside IEC60695
of enclosures
Environment conditions
Operation indoor
Altitude max. (m) 2000
Temperature average max. 35
(˚C)
Temperature max. (˚C) 45
Temperature min. (˚C) 0
Environmental conditions Environment B
Degree of pollution 3
Others
Enclosure materials sheet metal
Painting epoxy resin powder electrostatic sprayed
Colour RAL 7047 (enclosure) and RAL 9022 (functional unit)
Insulation materials inside high-temperature withstand, combustion self-prevent
of enclosure

A-27
Index and presentation Wall mounted system L
System L up to 630 A
Presentation

Configuration

DD800332
Vigi
PD800069

PD800071

Functional Overall
height in height in
modules mm

Application This configuration is adapted for lighting, HVAC, lift, etc… in tertiary and industrial
buildings.

A-28
Index and presentation Wall mounted system L
System L up to 630 A
Presentation

Configuration

DD800333
NSX400 3P

PD800066

Functional
height in
modules Overall
height
in mm

Application This configuration is adapted for lighting, HVAC, lift, etc… in tertiary and industrial
buildings.

A-29
Index and presentation Tools and services
System L

Presentation

Schneider Electric provides a large range of tools and


services to support you all along the life cycle of the
product. Design, order
For futher information, please consult us or see bb Catalogue
Schneider Electric website: bb Technicial guide for Pnb
www.schneider-electric.com. Software
bb Thermal calculation
Technical information
bb AutoCAD library
bb Bars drawings library
bb Derating tables
On-line support
bb Customer Care Center

Design &
implementation

Order

Advice, order
bb Catalogue
Software
bb Bom tool
On-line support
bb Customer Care Center

Promotional Training
bb Promotional leaflets bb Training sessions
bb Posters, videos
Specifications bb Customer conferences
& tendering Advice, order
bb Catalogue
Specifications
bb Type tested conference
bb New IEC conference
bb Specification forms
Software
bb Flash quotation

A-30
Index and presentation Tools and services
System L

Presentation

DD800163
Operation
Commissioning & recycling

Assembling

Operation
Guides bb Technical guide for Pnb
bb Technical guide for Recycling
Pnb bb Product Environmental
Profile
Guides
bb Technical guide for Pnb
bb Mounting leaflets library
bb Busbar drawings
PD800039

A-31
Index and presentation Commercial reference
System L numbering system
Commercial reference

Commercial-number composition

L S p 5 p p p p p
bb One letter designating the voltage.
Voltage Code
Low L

bb One letter designating the product.


Type Code
Switchboard S

bb One letter designating the family.


Type Code
Floor-standing system M
Wall mounted system L
Common X

bb One number designating the brand.


Brand Code
Prisma iPM 5

bb Four numbers designating the reference.

bb One number indicating characteristics specific to the


component.
Characteristic Code
Drawout D
Fixed F
Non-significant A
Horizontal H
Transparent T
Vertical V
Rear connection R

Five-figure commercial Some products have 5-figure commercial numbers. These products are sold in other
Schneider Electric product ranges and are totally compatible with Prisma iPM
numbers electrical switchboard range.

A-32
Index and presentation Determining the commercial
System L number
Commercial reference

Using the circuit diagram

DD800137
Draw up the list of devices to be installed grouping
them together in families.

And using the commercial


number tables
Reminder: 1 module = 50 mm

DD800006
Circuit Mounting Front plates No. of
breaker plate cut-out upstream downstream vertical
The selection of the functional unit is done after module
selectioning the electrical devices (circuit breakers, INS 250 LSL58816V LSX58905V LSX58931A LSX58932A 8
modular switchgears, etc.).

1 For the incoming unit, if it is not installed in the duct,


determine:
bb the number of vertical modules required;

DD800019
Set of Busbar Front Mounting
bb the commercial numbers for mounting plate and 4 drilled bars support barrier hardware
front plates. 04172 4 x LSX58082A 04197 04195

Determine the connection and its width so as to


connect the incoming unit to the busbars, or the
distribution block and its width.

2 For the outgoing units, determine:

DD800138
Circuit breaker Mounting plate Front plate No. of vertical
bb the number of vertical modules required, module
bb the commercial numbers for the modular rail and the
front plate, NSX 100 LSL58815H LSX58904H 5
LSX58931A
bb the distribution block: Multiclip, comb, etc.

DD800139
Modular Modular Front plate Additional No. of vertical
devices rail front plate module
1 row LSL58801A LSX58884A LSX58931A 5
Multi 9(1)
(1) 48 x 9 mm.

Distribution block Quantity Com. no.


Multiclip 200 A, 3P 1 LSX58053A

Module total = 18

3 Add-up the number of modules required. Height of the corresponding enclosure = 20

4 Based on the degree of protection IP, on the number


DD800140

Enclosure Com. no.


of modules required, choose the enclosure. IP30 /  wall mounted enclosure W = 600 mm, LSL58220A
D = 235 mm, H = 1100 mm, 20 modules
IP30 /  wall mounted enclosure with door W = 300 mm, LSL58234A
D = 235 mm, H = 1100 mm, 20 modules
Transparent door W = 600 mm, H = 1100 mm, LSL58165T
20 modules

5 If the devices to be installed do not occupy the whole


DD381583

Plain front plate Com. no.


enclosure, complete the front panel with an extra plain 20 - 18 = 2 modules LSX58932A
front plate.

6 Determine the necessary accessories: Description Com. no.


bb for distribution, 12 cable straps for horizontal cables 04239
bb for cable running, 4 covers for horizontal cable straps L = 430 mm 04243
bb for the overall installation. 4 wall mounted cable tie supports, W = 300 mm LSL58293A
4 wall mounted cable tie supports, W = 600 mm LSL58296A
Cu earth / neutral bar, 24 modules LSX58070A

A-33
B-2
Functional units Contents
System L

Description B-2
Functional units up to 630 A B-2

Commercial numbers B-4


Compact NSX 400 to 630 A B-4
Compact NSX 100 to 250 A B-6
Compact NSXm 160 B-8
EasyPact CVS 400 to 630 A B-12
EasyPact CVS 100 to 250 A B-14
Easypact EZC from 100 to 630 A B-16
Interpact INS 250 to 630 A B-18
Fupact INF 32 to 160 A B-20
Widths of modular devices B-22
Multi 9/Acti 9 ≤ 63 A B-24
NG 125, C120 B-24
INS 40 / 160 switch disconnectors B-26
Industrial and control devices B-28
Human / Machine interface B-30
Other devices B-32
Reserve space B-33
Functional unit accessories B-34

B-1
Functional units Functional units up to 630 A
System L

Description

The functional unit is defined in the IEC 61439.1 standard as


followed:
“A part of an assembly comprising all the mechanical and electrical
elements that contribute to the fulfilment of the same function.”
Each device is part of a functional unit comprising:
bb a dedicated mounting plate for device installation,
bb a front plate to block direct access to live parts,
bb the device connections or distribution solutions,
bb systems for on-site connections and running of auxiliary wires.
The functional units are modular and are arranged rationally, one on top of another,
within the enclosure.
The system includes everything required for functional unit mounting, supply and on
site connection.
The components of the Prisma iPM functional units have been designed and tested
taking into account device characteristics.
This design approach ensures a high degree of reliability in system operation and
optimum safety for people.
PD800003

Mounting plates The devices are mounted on a mounting plate. The space occupied by the mounting
plate corresponds to the device dimensions: optimization of the occupied space.
DD800432

Prisma iPM offers a complete range of mounting plates for each type of devices up
to 630 A:
bb EasyPact CVS and Compact NSX,
bb Interpact INS,
bb Easypact EZC,
bb modular devices,...

Plain or slotted mounting plates are available for other devices.

The mounting plates have threaded holes for direct mounting from the front.
The fixing screws of the mounting plate are supplied with.

The mounting plates have slots for tightening power cable and auxiliary connection.

It is front connected, without nuts, using thread-forming screws.


The use of thread-forming screws is mandatory to ensure electrical continuity
between exposed conductive parts.

B-2
Functional units Functional units up to 630 A
System L

Description

Modular rails The modular rails are supplied ready for mounting with screws.
The symmetrical rail is made of an aluminium alloy and is very rigid.
DD800123

The supports are factory mounted (crimped on the rails) and screw to the functional
uprights using two thread-forming, captive screws that also ensure the electrical
continuity of the exposed conductive parts.
The ends of the supports overrun the edge of the rails to act as a stop for the
modular devices.
Different type of rails:
bb modular devices rail
bb adjustable rail
bb rail for direct mounting on the functional uprights.

Rails can be fitted with devices, modular distribution blocks, contactors,


transformers, various auxiliary devices and terminal blocks and all cable-running
accessories such as straps and trunking supports, as well as the supports for
earth-neutral bars.

Front plates For more safety, the front plates only allow access to the device setting and control
devices. It ensures the IPxxB protection degree.
Each device has its own front plate with the appropriate cut-outs.
DD800279

Prisma iPM offers a complete range of front plates for each type of devices up to 630
A:
bb EasyPact CVS and Compact NSX,
bb Interpact INS,
bb Easypact EZC,
bb modular devices,
bb 72 x 72 and 96 x 96 mm measurement devices, ...

The various front plates are coloured in grey aluminium RAL 9022.
There are blanking strips (L = 1000 mm) to blank off the unused space on the
cut-out front plate. Also available in the catalogue are labels that fit on the front plate
or may be screwed to a door or front plate.

Plain and transparent front plates are also available in the catalogue.

Each front plate is front mounted on the supports by captive screws and nuts.
Electrical continuity of exposed conductive parts is ensured by the studs of the nuts
and the fixing screws (supplied).

The front plates are mounted on a front frame. It enables to assemble the front plates
at the workshop and to mount it on the wall mounted enclosure at the worksite. All
the front plates can be removed in one operation, as they are fixed on the frame.

Reserve space Plain front plates are available in the catalogue to blank off empty areas.
DD800465

B-3
Functional units Compact NSX 400 to 630 A
Selection table
System L

Commercial numbers

Vertical installation
Circuit breaker Front connection Control Type No. of pole

NSX400 direct by cables toggle/direct rotary handle fixed 3 / 4P


DD800023

NSX630 direct by cables toggle/direct rotary handle fixed 3 / 4P


Vigi NSX400 direct by cables toggle/direct rotary handle fixed 3 / 4P
Vigi NSX630 direct by cables toggle/direct rotary handle  fixed 3 / 4P

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

Distribution solutions For the distribution solutions, see page C-2~C-4.


DD800002
DD800001

Rear busbars Multi-stage busbars

B-4
Functional units Compact NSX 400 to 630 A
Selection table
System L

Commercial numbers

No. of vertical Mounting plate Front plate screw Long terminal


modules cut-out + upstream + downstream shield
(1 module = 50 mm)
DD800178

DD800179

DD800180

DD800181

DD384035
11 LSL58820V 9 modules LSX58921V 1 modules LSX58931A 1 modules LSX58931A 03183 b
14 LSL58820V 9 modules LSX58921V 2 modules LSX58932A 3 modules LSX58933A 03183 b
13 LSL58820V 9 modules LSX58921V 2 modules LSX58932A 2 modules LSX58932A 03183 b
16 LSL58820V 9 modules LSX58921V 3 modules LSX58933A 4 modules LSX58934A 03183 b

Mandatory.
Optional.

B-5
Functional units Compact NSX 100 to 250 A
Selection table
System L

Commercial numbers

Horizontal installation
Circuit breaker Duct Incoming No. of devices Front Control
per row connection

NSX100/160 1 x 3P direct by cables toggle/direct rotary


1 x 4P handle 
DD800025

NSX250 b 1 x 3P direct by cables toggle/direct rotary

DD800183
1 x 4P handle 

1 x 3P direct by cables toggle/direct rotary

DD800184
1 x 4P handle 

(1)
1 x 3P direct by cables toggle/direct rotary

DD800529
1 x 4P handle 

Vigi NSX100/160 1 x 3P direct by cables toggle/direct rotary


1 x 4P handle 
Vigi NSX250 b 1 x 3P direct by cables toggle/direct rotary

DD800183
1 x 4P handle 

1 x 3P direct by cables toggle/direct rotary


DD800184 handle 
1 x 4P

(1)
1 x 3P direct by cables toggle/direct rotary
DD800529

1 x 4P handle 

(1) Maximum size of connection cables: 70 mm².


For cable cross-sections greater than 70 mm², use of a cable duct is mandatory.

Vertical installation
Circuit breaker No. of devices Front Control Type
per row connection

NSX100 / 160 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed


DD800024

NSX250 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed


Vigi NSX100 / 160 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed
Vigi NSX250 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

Distribution For the distribution solutions, see page C-2~C-4.


DD800002
DD800001

DD800463

Rear busbars Multi-stage busbars Polybloc distribution block

B-6
Functional units Compact NSX 100 to 250 A
Selection table
System L

Commercial numbers

Type No. of pole No. of vertical Mounting Front plate screw


modules plate cut-out + upstream + downstream
(1 module = 50 mm)

DD800179

DD800180

DD800181

DD384035
DD800182
fixed 3P 4 LSL58814H 3 modules LSX58893H 1 module LSX58931A - - 03183
4P 5 LSL58815H 4 modules LSX58904H 1 module LSX58931A - - 03183
fixed 3P 5 LSL58814H 3 modules LSX58893H - - 2 modules LSX58932A 03183
4P 6 LSL58815H 4 modules LSX58904H - - 2 modules LSX58932A 03183

fixed 3P 5 LSL58814H 3 modules LSX58893H 2 modules LSX58932A - - 03183


4P 6 LSL58815H 4 modules LSX58904H 2 modules LSX58932A - - 03183

fixed 3P 7 LSL58814H 3 modules LSX58893H 2 modules LSX58932A 2 modules LSX58932A 03183


4P 8 LSL58815H 4 modules LSX58904H 2 modules LSX58932A 2 modules LSX58932A 03183

fixed 3P 4 LSL58814H 3 modules LSX58893H 1 module LSX58931A - - 03183


4P 5 LSL58815H 4 modules LSX58904H 1 module LSX58931A - - 03183
fixed 3P 5 LSL58814H 3 modules LSX58893H - - 2 modules LSX58932A 03183
4P 6 LSL58815H 4 modules LSX58904H - - 2 modules LSX58932A 03183

fixed 3P 5 LSL58814H 3 modules LSX58893H 2 modules LSX58932A - - 03183


4P 6 LSL58815H 4 modules LSX58904H 2 modules LSX58932A - - 03183

fixed 3P 7 LSL58814H 3 modules LSX58893H 2 modules LSX58932A 2 modules LSX58932A 03183


4P 8 LSL58815H 4 modules LSX58904H 2 modules LSX58932A 2 modules LSX58932A 03183

No. of No. of vertical Mounting plate Front plate screw Blanking


pole modules cut-out + upstream + downstream strip
(1 module = 50
mm)
DD800178

DD800179

DD800180

DD800181

DD384035
3 / 4P 6 LSL58816V 5 modules LSX58902V - 1 modules LSX58931A 03183 LSX58751A
3 / 4P 9 LSL58816V 5 modules LSX58902V 2 modules LSX58932A 2 modules LSX58932A 03183 LSX58751A
3 / 4P 8 LSL58816V 7 modules LSX58903V - 1 modules LSX58931A 03183 LSX58751A
3 / 4P 11 LSL58816V 7 modules LSX58903V 2 modules LSX58932A 2 modules LSX58932A 03183 LSX58751A

Mandatory.
Optional.

B-7
Functional units Compact NSXm 160
Selection table
System L

Commercial numbers

Horizontal installation
Circuit breaker No. of devices Front Control Type
per row connection

NSXm 160 1 x 3P direct by cables toggle Fixed


DD800601

NSXm 160 1 x 4P
NSXm Vigi 1 x 3P / 4P
(ELCB) 160
NSXm 160 1 x 3P direct rotary
handle
NSXm 160 1 x 4P

Vertical installation
Circuit breaker No. of devices Front Control Type
per row connection

NSXm 160 5 x 3P, 4 x 4P direct by cables toggle Fixed


DD800602

NSXm Vigi 4x 3P / 4P
(ELCB) 160
NSXm 160 5 x 3P direct rotary
handle
NSXm 160 4 x 4P

B-8
Functional units Compact NSXm 160
Selection table
System L

Commercial numbers

No. of pole No. of vertical Mounting plate Front plate screw


modules cut-out + upstream + downstream
(1 module =

DD800603

DD800179

DD800180

DD800181

DD384035
50 mm)

3P 4 LSL58828H 3 modules LSX58958H 1 module LSX58931A - - 03183


4P 4 3 modules LSX58958H 1 module LSX58931A - - 03183
3P / 4P 4 3 modules LSX58958H 1 module LSX58931A - - 03183

3P 4 3 modules LSX58962H 1 module LSX58931A - - 03183


4P 4 3 modules LSX58962H 1 module LSX58931A - - 03183

No. of pole No. of vertical Mounting plate Front plate screw Blanking
modules cut-out + upstream + downstream strip
(1 module =
DD800604

DD800179

DD800180

DD800181

DD384035
50 mm)

3P / 4P 6 LSL58829V 5 modules LSX58885A - - 1 module LSX58931A 03183 LSX58621A


3P / 4P 6 LSL58829V 5 modules LSX58885A - - 1 module LSX58931A 03183 LSX58621A

3P 6 LSL58829V 5 modules LSL58959V - - 1 module LSX58931A 03183 LSX58621A


4P 6 LSL58829V 5 modules LSX58961V - - 1 module LSX58931A 03183 -

Mandatory.
Optional.

B-9
Functional units Compact NSXm 160
Modular devices
System L
Selection table
Commercial numbers

Vertical installation
Circuit breaker No. of Horizontal Front connection No. of pole
modules per row

NSXm 160 5 x 3P, 4 x 4P direct by cables 3P / 4P


DD800607

NSXm Vigi (ELCB) 160 4x 3P / 4P direct by cables 3P / 4P

B-10
Functional units Compact NSXm 160
Modular devices
System L
Selection table
Commercial numbers

No. of vertical Modular device Front plate screw Blanking strip


modules rail cut-out + upstream + downstream
(1 module =

DD800179

DD800180

DD800181

DD384035
50 mm)

6 LSL58802A 5 modules LSX58885A - - 1 module LSX58931A 03183 LSX58621A


6 LSL58802A 5 modules LSX58885A - - 1 module LSX58931A 03183 LSX58621A

Mandatory.
Optional.

B-11
Functional units EasyPact CVS 400 to 630 A
Selection table
System L

Commercial numbers

Vertical installation
Circuit breaker Front connection Control Type No. of pole

CVS400 direct by cables toggle/direct rotary handle  fixed 3 / 4P


DD800000

CVS630 direct by cables toggle/direct rotary handle  fixed 3 / 4P


Vigi CVS400 direct by cables toggle/direct rotary handle  fixed 3 / 4P
Vigi CVS630 direct by cables toggle/direct rotary handle   fixed 3 / 4P

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

Distribution solutions For the distribution solutions, see page C-2~C-4.


DD800001

DD800002

Rear busbars Multi-stage busbars

B-12
Functional units EasyPact CVS 400 to 630 A
Selection table
System L

Commercial numbers

No. of vertical modules Mounting plate Front plate screw Long terminal
(1 module = 50 mm) cut-out + upstream + downstream shield

DD800181

DD384035
DD800178

DD800179

DD800180
11 LSL58820V 9 modules LSX58921V 1 module LSX58931A 1 module LSX58931A 03183 b
14 LSL58820V 9 modules LSX58921V 2 modules LSX58932A 3 modules LSX58933A 03183 b
13 LSL58820V 9 modules LSX58921V 2 modules LSX58932A 2 modules LSX58932A 03183 b
16 LSL58820V 9 modules LSX58921V 3 modules LSX58933A 4 modules LSX58934A 03183 b

Mandatory.
Optional.

B-13
Functional units EasyPact CVS 100 to 250 A
System L
Selection table

Commercial numbers

Horizontal installation
Circuit breaker Duct Incoming No. of devices Front Control
per row connection

CVS100/160 1 x 3P direct by cables toggle/direct rotary


handle 
DD800003

1 x 4P
CVS250 b 1 x 3P direct by cables toggle/direct rotary

DD800183
1 x 4P handle 

1 x 3P direct by cables toggle/direct rotary

DD800184
1 x 4P handle 

1 x 3P direct by cables toggle/direct rotary

DD800529
(1)

1 x 4P handle 

Vigi CVS100/160 1 x 3P direct by cables toggle/direct rotary


1 x 4P handle 
Vigi CVS250 b 1 x 3P direct by cables toggle/direct rotary

DD800183
1 x 4P handle 

DD800184 1 x 3P direct by cables toggle/direct rotary


1 x 4P handle 

(1)
1 x 3P direct by cables toggle/direct rotary
DD800529

1 x 4P handle 

(1) Maximum size of connection cables: 70 mm².


For cable cross-sections greater than 70 mm², use of a cable duct is mandatory.

Vertical installation
Circuit breaker No. of devices Front Control Type
per row connection

CVS100 / 160 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed


DD800004

CVS250 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed


Vigi CVS100 / 160 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed
Vigi CVS250 4 x 3P, 3 x 4P direct by cables toggle/direct rotary handle  fixed

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

Distribution For the distribution solutions, see page C-2~C-4.


DD800002
DD800001

DD800463

Rear busbars Multi-stage busbars Polybloc distribution block

B-14
Functional units EasyPact CVS 100 to 250 A
System L
Selection table

Commercial numbers

Type No. of No. of vertical Mounting plate Front plate screw


pole modules cut-out + upstream + downstream
(1 module = 50 mm)

DD800182

DD800179

DD800181

DD384035
DD800180
fixed 3P 4 LSL58814H 3 modules LSX58893H 1 module LSX58931A - - 03183
4P 5 LSL58815H 4 modules LSX58904H 1 module LSX58931A - - 03183
fixed 3P 5 LSL58814H 3 modules LSX58893H - - 2 modules LSX58932A 03183
4P 6 LSL58815H 4 modules LSX58904H - - 2 modules LSX58932A 03183

fixed 3P 5 LSL58814H 3 modules LSX58893H 2 modules LSX58932A - - 03183


4P 6 LSL58815H 4 modules LSX58904H 2 modules LSX58932A - - 03183

fixed 3P 7 LSL58814H 3 modules LSX58893H 2 modules LSX58932A 2 modules LSX58932A 03183


4P 8 LSL58815H 4 modules LSX58904H 2 modules LSX58932A 2 modules LSX58932A 03183

fixed 3P 4 LSL58814H 3 modules LSX58893H 1 module LSX58931A - - 03183


4P 5 LSL58815H 4 modules LSX58904H 1 module LSX58931A - - 03183
fixed 3P 5 LSL58814H 3 modules LSX58893H - - 2 modules LSX58932A 03183
4P 6 LSL58815H 4 modules LSX58904H - - 2 modules LSX58932A 03183

fixed 3P 5 LSL58814H 3 modules LSX58893H 2 modules LSX58932A - - 03183


4P 6 LSL58815H 4 modules LSX58904H 2 modules LSX58932A - - 03183

fixed 3P 7 LSL58814H 3 modules LSX58893H 2 modules LSX58932A 2 modules LSX58932A 03183


4P 8 LSL58815H 4 modules LSX58904H 2 modules LSX58932A 2 modules LSX58932A 03183

No. of No. of vertical Mounting plate Front plate screw Blanking


pole modules cut-out + upstream + downstream strip
(1 module = 50 mm)
DD800180

DD800181

DD384035
DD800178

DD800179

3 / 4P 7 LSL58816V 5 modules LSX58902V - - 2 modules LSX58932A 03183 LSX58751A


3 / 4P 9 LSL58816V 5 modules LSX58902V 2 modules LSX58932A 2 modules LSX58932A 03183 LSX58751A
3 / 4P 9 LSL58816V 7 modules LSX58903V - - 2 modules LSX58932A 03183 LSX58751A
3 / 4P 11 LSL58816V 7 modules LSX58903V 2 modules LSX58932A 2 modules LSX58932A 03183 LSX58751A

Mandatory.
Optional.

B-15
Functional units Easypact EZC from 100 to 630 A
System L
Selection table

Commercial numbers

Horizontal installation
Circuit breaker Duct Incoming No. of Front Control Type
devices connection
per row

EZC100 1 x 3P direct by cables toggle fixed


DD800036

EZC250 b 1 x 3/4P direct by cables toggle fixed

DD800183
1 x 3/4P direct by cables toggle fixed

DD800184
(1)
1 x 3/4P direct by cables toggle fixed

DD800529
(1) Maximum size of connection cables: 70 mm².
For cable cross-sections greater than 70 mm², use of a cable duct is mandatory.
(2) If EZC100 connected to rear busbars, add a 2 modules front plate LSX58932A.

Vertical installation
Circuit breaker No. of devices Front Control Type No. of pole
per row connection

EZC100 5 x 3P, 3 x 4P direct by cables toggle fixed 3 / 4P


EZC250 4 x 3P direct by cables toggle fixed 3P
3 x 4P direct by cables toggle fixed 4P
DD800007

Circuit breaker Front connection Control Type No. of pole

EZC400 direct by cables toggle/ fixed 3 / 4P


DD800000

direct rotary
handle
EZC630 direct by cables toggle/ fixed 3 / 4P
direct rotary
handle

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

B-16
Functional units Easypact EZC from 100 to 630 A
System L
Selection table

Commercial numbers

No. of pole No. of vertical Mounting Front plate screw


modules plate cut-out + upstream + downstream
(1 module = 50 mm)

DD800181

DD384035
DD800180
DD800179
DD800038
3P 3 LSL58804H 2 modules LSX58887H 1 module LSX58931A (2) - 03183
3P 5 LSL58805H 3 modules LSX58888H - 2 modules LSX58932A 03183

4P 6 LSL58807H 4 modules LSX58890H 2 modules LSX58932A 03183

3P 5 LSL58805H 3 modules LSX58888H 2 modules LSX58932A - - 03183

4P 6 LSL58807H 4 modules LSX58890H 2 modules LSX58932A - - 03183

3P 7 LSL58805H 3 modules LSX58888H 2 modules LSX58932A 2 modules LSX58932A 03183

4P 8 LSL58807H 4 modules LSX58890H 2 modules LSX58932A 2 modules LSX58932A 03183

No. of vertical Mounting plate Front plate screw Blanking strip


modules cut-out + downstream L = 1000 mm
(1 module = 50 mm)
DD800038

DD800179

DD800181

DD384035
7 LSL58803V 5 modules LSX58886V 2 modules LSX58932A 03183 LSX58752A
9 LSL58803V 9 modules LSX58889V - - 03183 LSX58752A
9 LSL58806V 9 modules LSX58889V - - 03183 LSX58752A
03183

No. of vertical Mounting plate Front plate screw Long terminal


modules cut-out + upstream + downstream shield
(1 module = 50 mm)
DD800178

DD800179

DD800180

DD800181

DD384035

11 LSL58820V 7 modules LSX58921V 1 module LSX58931A 1 module LSX58931A 03183 b

14 LSL58820V 7 modules LSX58921V 2 modules LSX58932A 3 modules LSX58933A 03183 b

Mandatory.
Optional.

Distribution solutions For the distribution solutions, see page C-2~C-4.


DD800001

DD800002

Rear busbars Multi-stage busbars

B-17
Functional units Interpact INS 250 to 630 A
System L
Selection table

Commercial numbers

Horizontal installation
Circuit breaker Duct Incoming Front Control No. of pole
connection

INS250 ■ direct by cables direct front 3 / 4P

DD800183
DD800005

rotary handle

direct by cables direct front 3 / 4P

DD800184
rotary handle

(1)
direct by cables direct front 3 / 4P

DD800529
rotary handle

(1) Maximum size of connection cables: 70 mm².


For cable cross-sections greater than 70 mm², use of a cable duct is mandatory.

Vertical installation
Circuit breaker No. of device per Front Control No. of pole
row connection

INS250 3x3P, 3x4P direct by cables direct front 3 / 4P


rotary handle
DD800006

INS320 / 400 1x3P, 1x4P direct by cables direct front 3 / 4P


rotary handle
INS500 / 630 1x3P, 1x4P direct by cables direct front 3 / 4P
rotary handle

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

Distribution solutions For the distribution solutions, see page C-2~C-4.


DD800001

DD800002

DD800463

Rear busbars Multi-stage busbars Polybloc distribution block

B-18
Functional units Interpact INS 250 to 630 A
System L
Selection table

Commercial numbers

No. of vertical Mounting plate Front plate screw


modules cut-out + upstream + downstream
(1 module = 50 mm)

DD800181

DD384035
DD800182

DD800179

DD800180
6 LSL58815H 4 modules LSX58901H - 2 modules LSX58932A 03183

6 LSL58815H 4 modules LSX58901H 2 modules LSX58932A - - 03183

8 LSL58815H 4 modules LSX58901H 2 modules LSX58932A 2 modules LSX58932A 03183

No. of vertical Mounting plate Front plate screw Long terminal


modules cut-out + upstream + downstream shield
(1 module = 50 mm)

DD800181

DD384035
DD800178

DD800179

DD800180

8 LSL58816V 5 modules LSX58905V 1 module LSX58931A 2 modules LSX58932A 03183 b

10 LSL58820V 6 modules LSX58914V 2 modules LSX58932A 2 modules LSX58932A 03183 b

12 LSL58820V 6 modules LSX58914V 3 modules LSX58933A 3 modules LSX58933A 03183 b

Mandatory.
Optional.

B-19
Functional units Fupact INF 32 to 160 A
System L
Selection table

Commercial numbers

Vertical installation
Circuit breaker No. of devices Front Control No. of pole
per row connection

INF32 / 40 4 x 3P direct by cables front control 3P


DD800144

INF63 3 x 3P direct by cables front control 3P


INF100 / 160 2 x 3P direct by cables front control 3P

Fupact INF32 / 40
DD800145

Fupact INF100 / 160

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

T
LIGH

B-20
Functional units Fupact INF 32 to 160 A
System L
Selection table

Commercial numbers

No. of vertical modules Mounting plate Front plate screw Long terminal
(1 module = 50 mm) cut-out + downstream shield

DD800181

DD384035
DD800185

DD800179
4 LSL58810V 4 modules LSX58895V - - 03183 -
5 LSL58810V 5 modules LSX58896V - - 03183 b
7 LSL58810V 5 modules LSX58897V 2 modules LSX58932A 03183 b

Mandatory.
Optional.

B-21
Functional units Widths of modular devices
System L

Commercial numbers

All the devices listed below can be mounted on:


bb modular device rail,
bb adjustable modular rail ,
bb modular rail, length =1600 mm.
Modular, plain or transparent front plates are available in this catalogue.

Widths of Multi 9/Acti 9 devices (in number of 9 mm modules)


Description Width in 9 mm
1P 1P + N 3P 4P
2P 3P + N
Alarm, ATo4x technical 8
Ammeter, AMP analogue 8
Ammeter, multi-rating 4
Ammeter, AMP digital 4
Auxiliaries, for ID, C60, C120 1-2-4
Auxiliaries, for C32H-DC 1-2
Auxiliaries, NO / NF 2
Auxiliaries, ACTp and ACT for contactor 2
Auxiliaries, ACTo+f for contactor 1
Auxiliaries, NTVo and TTVo for remote dimmer 2
Bell or buzzer 2
Circuit breaker D’clic, D’clic XE 2
Circuit breaker D’clic Vigi 4
Circuit breaker DT40, DT40N 2 6
Circuit breaker DT40 Vigi 4
Circuit breaker C32H-DC 4
Circuit breaker C60, iC60 / N / H / L / LMA, iK60N 2 4 6 8
Circuit breaker C120 / N / H 3 6 9 12
Circuit breaker NG125 3 6 9 12
Auxiliary 2 OF or OF + SD 1
Auxiliary MX + OF or MN 2
Auxiliary MN s 4
Circuit breaker NG125 Vigi s 11 18 21
Circuit breaker NG125 Vigi I / S / R 11 20 23
Circuit breaker P25 M 5
Auxiliary MN 1
Auxiliaries MX + OF 2
Circuit breaker, Reflex, XC40 8 10 12
Contactor, CT 16 / 25 A 2 2 4 4
Contactor, CT 40 / 63 / 100 A 4-6 4-6 6-12
Contactor, ACTc auxiliary 2
Contactor, CDS 1-ph load shedder 10
Contactor, CDSc 1-ph load shedder 16
Contactor, CDS 3-ph load shedder 16
Contactor, CT+ silent 2
Cooling spacer 1
Counter, CI pulse 4
Counter, CH time 4
Dimmer, Vo1000 10
Extension , ETL for TL impulse relay 2
Extension, ERL 2
Frequency meter, FREQ 4
Impulse relay, TL 16 A and 32 A, ETL 16 and 32 A 2 2
Impulse relay, TLI 16 A andTLc 2
Impulse relay, TLm and TLs 2
Impulse relay auxiliaries, ATLc+c and ATLc+s 2
Impulse relay auxiliaries, ATLt and ATLz 2
Impulse relay auxiliaries, ATL4 4
Impulse relay, TL+ silent 2
Insulation monitor, SM21 8
Kilowatt-hour meter, CE, CEr 12
Load shedder, DSE’clic 2-channel 6
Load shedder, DSE’clic 4-channel 8
Multimeter PM9 8
Optical repeater, RPo 2+2
Power socket, PC, 10 A and 16 A 5
Power socket, PC, 20 A 8

B-22
Functional units Widths of modular devices
System L

Commercial numbers

Widths of Multi 9/Acti 9 devices (in number of 9 mm modules)


Description Width in 9 mm
1P 1P + N 3P 4P
2P 3P + N
Pushbuttons 2
Rccb, ID’clic 4
Rccb, ID’clic XE 4
Regulator, REGad1 / REGad2 12
Relay, RBN low level 2
Switch disconnector, INS 40 to 80 A 10 10
Switch disconnector, INS 100 to 160 A 15 15

B-23
Functional units Multi 9/Acti 9 ≤ 63 A
System L NG 125, C120
Modular devices
Commercial numbers Selection table
Vertical installation
Circuit breaker No. of horizontal Fr connection No. of No. of Modular device
modules per row pole vertical rail (1)
modules

DD800040
(1 module
= 50 mm)
Multi 9 ≤ 63 A 48 direct by cables 1P 3 LSL58801A
DD800008

Acti 9 ≤ 63 A 2P 3 LSL58801A
3P 3 LSL58801A
4P 3 LSL58801A

by multiclip 2P 4 LSL58801A
by distribloc
3P 4 LSL58801A
4P 4 LSL58801A

NG125 48 direct by cables 1P 4 LSL58802A


C120 2P 4 LSL58802A
DD800009

3P 4 LSL58802A
4P 4 LSL58802A
by distribloc 1P 5 LSL58802A
2P 5 LSL58802A
3P 5 LSL58802A
4P 5 LSL58802A

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

IERE
LUM

Distribution solutions For the distribution solutions, see page C-2~C-4.


DD800002
DD800001

Rear busbars Multi-stage busbars


DD381308

Distribloc distribution block

B-24
Functional units Multi 9/Acti 9 ≤ 63 A
System L NG 125, C120
Modular devices
Commercial numbers Selection table

Front plate Blanking strip screw Upstream connection Distribution accessories(4)


cut-out L=1000 mm 12 horizontal 4 covers 12 trunking

DD384035

DD800187
cable straps L = 430 mm supports
DD800186

Multiclip 200 A(2) or Distribloc(3)


3 modules LSX58883A LSX58621A 03183 - - 04239 04243 04255
3 modules LSX58883A LSX58621A 03183 - - 04239 04243 04255
3 modules LSX58883A LSX58621A 03183 - - 04239 04243 04255
3 modules LSX58883A LSX58621A 03183 - - 04239 04243 04255

LSX58621A 03183 LSX58052A 04045 04239 04243 04255


4 modules LSX58884A

4 modules LSX58884A LSX58621A 03183 LSX58053A 04045 04239 04243 04255


4 modules LSX58884A LSX58621A 03183 LSX58054A 04045 04239 04243 04255

4 modules LSX58884A LSX58621A 03183 - - 04239 04243 04255


4 modules LSX58884A LSX58621A 03183 - - 04239 04243 04255
4 modules LSX58884A LSX58621A 03183 - - 04239 04243 04255
4 modules LSX58884A LSX58621A 03183 - - 04239 04243 04255
5 modules LSX58885A LSX58621A 03183 - 04045 04239 04243 04255
5 modules LSX58885A LSX58621A 03183 - 04045 04239 04243 04255
5 modules LSX58885A LSX58621A 03183 - 04045 04239 04243 04255
5 modules LSX58885A LSX58621A 03183 - 04045 04239 04243 04255

Mandatory.
Optional.
Note:
(1) Capacity of modular rail: 48 Multi 9/Acti 9 modules (1 Multi 9/Acti 9 modules = 9 mm).
(2) Add 1 upstream plain plate (LSX58931A) when a modular row with a 200 A Multiclip
distribution block is positioned:
b directly below a non-modular mounting plate (Compact, Interpact, etc);
b at the top of a switchboard.
Add one vertical module (i.e. 4+1) = 5 M.
(3) When NG125 circuit breaker is incomer.
(4) See page C-16~C-18.

B-25
Functional units INS 40 / 160 switch disconnectors
System L
Modular devices
Selection table
Commercial numbers

Vertical installation
Circuit breaker No. of Front No. of No. of Adjustable device rail
horizontal connection pole vertical

DD800039
modules modules
per row (1 module
= 50 mm)
INS 40 / 63 / 80 48 direct by cables 3P 3 LSL58802A
DD800010

4P 3 LSL58802A
by multiclip 3P 4 LSL58802A
4P 4 LSL58802A
INS 100 / 125 / 160 48 direct by cables 3P 4 LSL58802A
4P 4 LSL58802A
by multiclip 3P 5 LSL58802A
by distribloc 4P 5 LSL58802A

Accessories For the functional unit accessories, see page B-34~B-35.


DD383974

IERE
LUM

Distribution solutions For the distribution solutions, see page C-2~C-4.


DD800001

Rear busbars Multi-stage busbars


DD381308

Distribloc distribution block

B-26
Functional units INS 40 / 160 switch disconnectors
System L
Modular devices
Selection table
Commercial numbers

Front plate Blanking strip screw Upstream connection Distribution accessories Long
L=1000 mm 12 trunking terminal

DD384035

DD800187
cut-out 12 4 covers
horizontal L = 430 mm supports shield
DD800186

cable straps
Multiclip 200 A(1) or Distribloc
3 modules LSX58883A LSX58621A 03183 - - 04239 04243 04255 -
3 modules LSX58883A LSX58621A 03183 - - 04239 04243 04255 -
4 modules LSX58884A LSX58621A 03183 LSX58053A - 04239 04243 04255 -
4 modules LSX58884A LSX58621A 03183 LSX58054A - 04239 04243 04255 -
4 modules LSX58884A LSX58621A 03183 - - 04239 04243 04255 -
4 modules LSX58884A LSX58621A 03183 - - 04239 04243 04255 -
5 modules LSX58885A LSX58621A 03183 LSX58053A 04045 04239 04243 04255 b
5 modules LSX58885A LSX58621A 03183 LSX58054A 04045 04239 04243 04255 b

Mandatory.
Optional.
Note:
(1) Add 1 upstream plain plate (LSX58931A) when a modular row with a 200 A
Multiclip distribution block is positioned:
b directly below a non-modular mounting plate (Compact, Interpact, etc);
b at the top of a switchboard.
Add one vertical module (i.e. 4+1) = 5 M.

B-27
Functional units Industrial and control devices
Motor control up to 15kw
System L
LV/LV tranformers
Commercial numbers Selection table
Vertical installation
Circuit breaker + Contactors up to 45kw NO. of vertical modules
(1 module=50mm)

NSX100-MA 6
DD800521

TeSys D / EasyPact TVS contactors <=95A NO. of vertical modules


(1 module=50mm)
TeSys D / EasyPact TVS contactor ≤ 40A 3
DD800522

(Side by side)

TeSys D / EasyPact TVS contactor ≤ 95A 4


(Side by side)
4

TeSys D GV2 / EasyPact TVS circuit breakers NO. of vertical modules


(1 module=50mm)
TeSys D GV2 circuit breakers (≤ 40A) 3
DD800523

(Side by side)
EasyPact TVS GZ1E ≤ 32A
(Side by side)

TeSys D GV2 / EasyPact TVS circuit breaksers + Series D contactor NO. of vertical modules
(1 module=50mm)
TeSys D GV2 + LC1D (≤ 40A) 5
DD800041

EasyPact TVS GZ1E + LC1E ( ≤ 32A)

Soft starter up to 11kw NO. of vertical modules


(1 module=50mm)

ATS48D17 ATS48D22 ATS48D32 8


DD800525
DD800524

ATS48D38 ATS48D47
8

ATS48D62 ATS48D75 8
ATS48D88 ATS48C11

LV/LV transformers NO. of vertical modules


(1 module=50mm)

LV/LV transformers 4
DD800526

12

Accessories For the function unit and front plate accessories, see page B-34~B-35.
DD800527

T
LIGH

B-28
Functional units Industrial and control devices
Motor control up to 15kw
System L
LV/LV tranformers
Commercial numbers Selection table
Vertical installation
Mounting plate Front plate screw Optional Comments

DD384035
LSL58816V LSX58902V + LSX58931A 03183 LSX58751A Number of device 4x3P or 3x4P

Mounting plate Front plate Optional Comments

04226 (1) LSX58933A 04226 rail, cut by customer

04226 (1) LSX58934A


04226 (1) LSX58964T Transparent front plate

Mounting plate Front plate Optional Comments

04226 LSX58883A

Mounting plate Front plate Optional Comments

04226 (1) LSX58964T + LSX58931A 04226 rail, cut by customer


Transparent front plate

04226 (1) LSX58884A + LSX58931A 04226 rail, cut by customer, add front plate
hinge kit Ref. LSX58776A

Mounting plate Front plate screw Optional Comments


DD384035

2xLSL58824A 2xLSX58931A + LSX58966T 03183 only for 305mm depth cubicle

2xLSL58824A 2xLSX58934 03183 only for 305mm depth cubicle, add front plate
hinge kit Ref. LSX58776A
2xLSL58824A 03183 only for 305mm depth cubicle, without front
plate

Mounting plate Front plate screw Optional Comments


DD384035

LSL58824A LSX58934A 03183

2xLSL58824A 2xLSX58934A 03183

LSL58825A 2xLSX58936A 03183

(1)Capacity of modular rail: 48 Multi9 modules (1 Multi 9 module=9mm).

B-29
Functional units Human / Machine interface
System L
72 x 72 and 96 x 96 mm devices
Presentation
Commercial numbers

Dedicated front plates are available for 72 x 72 mm and 96 x 96 mm devices.


Presentation It is installed in the device zone.

Blanking plate are available to blank off any unused locations.


They have knock-outs to fit lights, push-buttons, etc..

72 x 72 mm and 96 x 96 mm devices can be directly adapted on plain door: cut-out to


be made by the customer.

The degree of protection for installed devices is IP30.


To maintain the IP54 degree of protection, the devices must be installed behind a
transparent door.

DD800012

Front plate of 72x72 mm diameter for 6 devices.


DD800013

Front plate of 96x96 mm diameter for 4 devices.

B-30
Functional units Human / Machine interface
System L
72 x 72 and 96 x 96 mm devices
Presentation
Commercial numbers

72 x 72 mm measurement devices Designation Com. no.


Metal front plate with cut-outs, 3 modules (for six 72 x 72 mm devices) LSX58956A
DD381689

Blanking plate (for 72 x 72 mm hole) LSX58961A

DD382637
The blanking plates have knock-outs:
bb 3 holes, 22 mm diameter,
bb 1 hole, 45 x 45 mm.

96 x 96 mm measurement devices
Designation Com. no.
Metal front plate with cut-outs, 3 modules (for four 96 x 96 mm devices) LSX58955A
DD381711

DD382637

Blanking plate (for 96 x 96 mm hole) LSX58960A


The blanking plates have knock-outs:
bb 3 holes, 22 mm diameter,
bb 1 hole, 45 x 45 mm,
bb 1 hole, 72 x 72 mm.

B-31
Functional units Other devices
System L
For all type of device
Selection table
Commercial numbers

Installation on modular rail Designation Depth behind Useful length Com. no.
front plate (mm) (mm)
DD800393

Adjustable modular device rail 47 to 114 432 LSL58802A


2 modular device rails 144 1600 04226
L modular device rail 49 432 LSL58801A

Adjustable modular device rail (LSL58802A).


DD800394

Modular rail, L=1600 mm (04226).

Installation on slotted plate Designation No. of vertical modules Depth behind front Com. no.
(1 module = 50 mm) plate (mm)
DD800044

Slotted mounting plate 4 141.5 LSL58824A


12 122 LSL58825A

Clip-nuts for slotted mounting plates (for device fixing)


Designation Com. no.
20 M4 clip-nuts for slotted mounting plate 03180
20 M5 clip-nuts for slotted mounting plate 03181
20 slotted mounting plate clip-nuts M6 03182
20 M5 self-tapping screws for functional upright mounting 03183
DD381312

Installation on plain plate Designation No. of vertical Depth behind Fixing screw Com. no.
modules (1 front plate (mm)
module = 50 mm)
DD800042

Plain mounting plate 4 141.5 03183 LSL58826A


12 116 03183 LSL58827A

Cut-out front plate for modular Designation No. of vertical modules Com. no.
(1 module = 50 mm)
devices Front plate for modular devices 3 LSX58883A
4 LSX58884A
DD800161

5 LSX58885A

Blanking strip (for blanking off unused locations)


Designation Com. no.
Blanking strip modular device, L = 1000 mm LSX58621A
DD380805

B-32
Functional units Reserve space
System L
Selection table

Commercial numbers

Plain front plate Designation No. of vertical modules (1 module = 50 mm) Cat. no.
Plain front plate 1 LSX58931A
DD381583

2 LSX58932A
3 LSX58933A
4 LSX58934A
5 LSX58935A
6 LSX58936A

Transparent front plate Designation No. of vertical modules (1 module = 50 mm) Cat. no.
Transparent front plate 4 LSX58964T
DD381582

6 LSX58966T

B-33
Functional units Functional unit accessories
System L
Selection table

Commercial numbers

The angle brackets are used for:


Universal angle bracket bb vertical mounting of the earth / neutral bar in the duct,
bb mounting of the modular rail L = 1600 mm (com. no. 04226).
DD800390

Designation Com. no.


2 universal angle brackets 03581

DD381577

Blanking strip The blanking strips are used to fill the space on the cut-out front plates.
Designation Com. no.
DD380805

Blanking strip modular device, L = 1000 mm LSX58621A


Blanking strip CVS/NSX250/INS250, L = 148 mm LSX58751A
Blanking strip EZC250, L = 1000 mm LSX58752A

Hinge kit Designation Com. no.


Front plate hinge kit LSX58776A
DD800015

For restricted access, the front plate can be sealed as visual checking.
Lead-sealable screws
Designation Com. no.
DD800014

4 front plate lead-sealable screws LSX58777A

B-34
Functional units Functional unit accessories
System L
Selection table

Commercial numbers

The labels are used on front plates for the identification of the outgoings.
Identification labels
Designation Com. no.
DD381715

12 adhesive label holders, W = 432 mm, H = 24 mm 08903


12 clip-on labels 18 x 35 08913

bb The clip-on support is supplied with a paper label and a transparent cover.
bb It clips onto the front plate horizontally or vertically and can be screwed to any
support (plain door, plain front plate, etc.).

Adhesive label.
DD383974

T
LIGH

Clip-on label.

Front plate accessory Designation Com. no.


20 front plate screws + nuts LSX58030A
DD800561

20 front plate screws + nuts

B-35
C-2
Distribution Contents
System L

Description C-2
Overview of distribution solutions C-2
Different type of distribution solutions C-4
Busbars C-5
Multi-stage busbars C-5
Rear busbars C-6
Distribution blocks C-7
Distribloc distribution block C-7
Polybloc distribution block C-8
Multiclip distribution block C-9
Multi-stage current distribution blocks C-10
Comb busbars C-11

Commercial numbers C-12


Busbars from 160 to 630 A C-12
Distribution blocks C-14
Distribution accessories C-16
Partitioning C-19

C-1
Distribution Overview of distribution
System L solutions
Description

For incoming devices

160 to 630 A multi-stage busbar

bb Traditional, highly versatile solution.


bb Installation position:
v horizontal in the 600 mm wide enclosure,
v vertical in the cable duct.

160 to 400 A rear busbar

bb Traditional, highly versatile solution.

C-2
Distribution Overview of distribution
System L solutions
Description

For rows of modular devices

125 A Distribloc
bb Spring terminals for
electrical connections
that stay tight.
bb Front designed to
integrate perfectly with
modular devices.
DD800158

200 A Multiclip
bb Reliable spring-
terminal connections
requiring no maintenance
bb Fast installation.
bb Easy upgrades through
replacement or addition
of devices.
bb Easy balancing of
phases.

80 to 125 A comb busbars


bb Fast and direct
connections, adaptable to
all needs.
bb Fast, economical
connections.

C-3
Distribution Different type of distribution
System L solutions
Description

Prisma iPM enclosures provide you with distribution solutions adapted to your
requirements.

Centralised distribution Centralised distribution consists of a distribution block that redistributes electricity to
the various switchboard feeders. It is placed as close as possible to the incomer and
is simple and easy to install.
DD800157

The splitter or distribution block is perfectly suited to medium-sized electrical


switchboards and is used as a sub-distribution block.
It can be used with all types of switchgear making it suitable for industrial control
applications.
Prisma iPM centralised distribution solutions
No. of Distribution Rating (A) Devices
connection
points
6 to 16 Distribloc distribution block 125 Multi 9
Multi-stage current distribution 125 Multi 9
block
9 per phase Polybloc distribution block 160 and 250 EasyPact CVS,
Interpact INS
13 per phase horizontal multi-stage busbars 160, 250 and 400 EasyPact CVS,
Interpact INS
> 15 rear busbar or busbar in duct (see split distribution)

Split distribution Split distribution consists of distributing the current from the incomer to the
enclosure’s various feeders by providing connection points as close as possible to
the feeders.
DD800398

The current is distributed via a full-height rear busbar or side mounted busbar that is
as close as possible to the devices. The busbars, made up of offset and stepped
bars, allow direct and easy front access to all the connection points.

Split distribution is suited to large electrical switchboards and offers:


bb a nominal current rating of 125 to 630A,
bb a high connection capacity,
bb connections that can be added and changed at any time,
bb the possibility of having more than 10 feeder groups.

It is also ideal for the electrical distribution between 2 switchboards when enclosures
are combined.

With split distribution, you have the guarantee of a tested solution.

Prisma iPM split distribution solutions


Busbar Rating (A) Implantation
Rear busbar 160, 250 and 400 in device area
Vertical multi-stage busbar 160, 250, 400 and 630 in duct

Sub-distribution for modular Sub-distribution consists of either a 200A Multiclip distribution block or a comb
busbar connected directly to the centralised distribution block or the busbar. They
switchgears thus feed each row of modular devices.
Prisma iPM sub-distribution solutions
Devices Distribution blocks
DD800397

All type of devices Distribloc distribution block


Multi-stage current distribution block
Polybloc distribution block
Dedicated to one type of Multi 9 device 200 A multiclip distribution block
Comb busbar
Multi-stage current distribution block
Easypact 100 A Comb busbar

C-4
Distribution Busbars
Multi-stage busbars
System L

Description

Multi-stage busbar presentation The multi-stage busbars can be installed:


bb horizontally in a 600 mm wide enclosures in the device zone. They have
13 outgoers per phase, max. 50 mm2,
DD800047

bb vertically in the 300 mm wide duct. They are particularly useful for distribution to
2 enclosures on each side of the duct. All connection points are easily accessible
from the front. The inclination of the bars facilitates connections and improves cable
running.
They are valid for three and four-pole versions with ratings from 160 to 630 A.
Available in one length, 1400 mm, they can be cut as needed.

Composition
Flat, copper bars with threaded M6 holes every 25 mm for connection along the
entire length of the busbars. There are 8.2 mm diameter holes at each end for
supply. The staggered supports are made of an insulating material.
An optional, front barrier is available to protect against direct contact from the front
(IPxxB degree of protection).
Electrical characteristics
Horizontal multi-stage busbar installed in a 600 mm wide bb Rated current :160A,250A,400A,630A.
enclosure. bb Rated insulation level Ui : 750V.
bb Impulse withstand voltage Uimp: 8kV.
DD800019

Busbar supports
Horizontal multi-stage busbar in 600 mm wide enclosure
2 supports are needed.
DD800028

Vertical multi-stage busbar in 300 mm wide duct


The table below indicates:
bb the size of the bars to be used, depending on the permissible current level in the
busbars,
bb the number of supports depends on the rated short-time withstand current (Icw),
Vertical multi-stage busbar installed in a 300 mm wide duct. bb the distance between supports, depending on the rated short-time withstand
current (Icw).
Rating (A) Size of a bars (mm) Distance between support centres (mm)
Icw (kA rms / 1 s.)
10 13 15 20 25
160 15 x 5
250 20 x 5
400 32 x 5 450 300 300(1)
630 32 x 8
(1) Icw (kA rms / 0.6 s.).
DD800027

C-5
Distribution Busbars
Rear busbars
System L

Description

Rear busbars presentation The rear busbar is installed in a 600 mm wide enclosures and is mounted directly on
the uprights of the frameworks.
It is valid for three or four-pole versions with ratings from 160 to 400 A.
DD800018

Available in one length, 1400 mm, the bars can be cut as needed.
The connection with a Compact or Interpact incoming device occupies two vertical
modules ( 50 mm each).
Composition
Flat, copper bars with threaded M6 holes every 25 mm for connection along the
entire length of the busbars.
The insulating supports can receive a fifth bar, 15 x 5 mm or 20 x 5 mm, to create an
earth bar.
Installation
The busbars are mounted directly on the functional uprights of a 600 mm wide
enclosure.
Connection
bb 16 mm2 to 50 mm2 flexible cables, with crimped lugs,
bb insulated flexible bars.
Rear busbar installed in a 600 mm wide enclosure. Electrical characteristics
bb Rated peak withstand current Ipk (kÂ)
v 30 k for 160 A busbars,
v 40 k for 250 A busbars,
v 55 k for 400 A busbars.
bb Rated insulation level Ui = 1000 V.

Busbar calculation Busbar size and distance between supports


The table below indicates:
bb the size of the bars to be used, depending on the permissible current level in the
busbars,
bb the distance between supports, depending on the rated short-time withstand
current (Icw).
Rating (A) Size of a bars (mm) Distance between support centres(1) (mm)
Icw (kA rms / 1 s.
10 13 15 20 25
160 15 x 5
250 20 x 5 450
400 32 x 5 300 250
(1) Multiclip 200 A distribution blocks equipped with connections (04029) can be used as
intermediate supports (200 mm max. distance between centres) in addition to the top and bottom
supports.

C-6
Distribution Distribution blocks
Distribloc distribution block
System L

Description

Distribloc distribution block The Distribloc distribution block is particularly suited to small and medium-sized
enclosures. It gives lots of flexibility when there are few feeders. It provides safety
presentation and makes maintenance easy.
It has been optimised for enclosures containing mainly modular devices. It can be
DD800464

used equally as a main or sub-distribution block, or for industrial control applications.


It is easily installed by simply clipping it onto the modular rail. It can also be fixed to
the backplate for industrial control applications.

The Distribloc distribution block provides you with:


bb safety
v IPxxB protection of live conductors,
v tightening quality guaranteed by spring terminals,
v electrical performance levels adapted to your needs,
bb simplicity
v easy installation and wiring,
Distribloc distribution block supplying the modular devices. v simple choice depending on device rating,
bb flexibility
v selection of combinations,
v possibility of adding and changing feeders.

Dimensions Composition
The four-pole distribution block is made up of:
DD381609
DD381608

bb a fully insulated, one-piece distribution block complying with the degree of


protection IPxxB (protection against direct contacts),
bb a modular cover.
The design of the front (45 mm nose) blends perfectly into a row comprising modular
devices.
Electrical characteristics
bb Rated insulation level: Ui = 750 V.
bb Rated operational current Ie (40°C):
v 125 A for the 125 A Distribloc,
bb Short-circuit withstand current: the reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained. The worst-case situations have been
tested.
bb Complies with the low-voltage device standard IEC 60947.7.1 and / or
IEC 61439.1
bb Impulse withstand voltage Uimp = 8 kV.
Supply
bb Tunnel terminal on 125 A Distribloc 125 for 6 to 35 mm2 flexible cables (10 to
35mm2 rigid cables).
Distribution
bb Spring terminals:
v 2 outgoers from 1 to 10 mm2, flexible or rigid,
v 3 outgoers from 1 to 6 mm2, flexible or rigid,
v 7 outgoers from 1 to 4 mm2, flexible or rigid.
bb Tunnel terminals:
v 1 outgoer from 4 to 16 mm2, flexible (4 to 25 mm2 rigid).
Supply
bb An identification label.
bb Adhesive labels for phase identification.
Installation
bb Clipped onto a modular rail.
bb Width occupied is 12 modules (9 mm each).
bb Screwed to plain or slotted backplate. Distances between centres = 100 x 75 mm.

The spring terminals Downstream circuits are connected from the front, to spring terminals.
Contact pressure automatically adapts to the size of the conductor. It does not
depend on the operator.
DD381399

Contacts are insensitive to vibrations and thermal variations.


Only one cable (flexible or rigid, without a metal ferrule) can be inserted in a spring
terminal.
Degree of protection: IPxxB.
Advantages
bb A reliable electrical connection, no maintenance required (tightness guaranteed
over time).
bb Very fast connection.
bb Easy phase balancing.
bb Rewiring is very easy if the switchboard is expanded or modified.

C-7
Distribution Distribution blocks
Polybloc distribution block
System L

Description

Polybloc distribution block The Polybloc distribution block is particularly suited to small and medium-sized
enclosures. It gives lots of flexibility when there are few feeders. It provides safety
presentation and makes maintenance easy.
It has been optimised for enclosures containing mainly modular devices. It can be
used equally as a main or sub-distribution block.
DD800441

The Polybloc is available in two versions :


bb the 250 A Polybloc distribution block is designed for installation directly
downstream of Compact circuit breakers and Interpact switch-disconnectors devices
up to 250 A. It can be rapidly mounted in the vertical position. Electrical connections
are made directly to the device terminals. The connection terminals are slanted to
facilitate cable entry and not exceed the bending radius of the flexible and rigid
cables,
bb the 160 A Polybloc is made up of individual elements that can be used alone or
with others to make two-pole, three-pole or four-pole distribution blocks.
Mounting is very fast. It clips onto a modular rail and is supplied by cables via a tunnel
terminal. The connection spring terminals are slanted to facilitate cable entry and
bending of the flexible and rigid cables. It is supplied with a cover that also guides the
cables.
Electrical characteristics
bb Rated insulation level Ui = 750 V.
250 A Polybloc distribution block installed bb Short-circuit withstand current: the reinforced breaking capacity due to cascading
in a 600 mm wide enclosure. in circuit-breaker combinations is maintained. The worst-case situations were tested.
bb Impulse withstand voltage Uimp = 8 kV.
Supply
bb 250 A Polybloc distribution block:
DD800147

v directly to the terminals of the Compact NSX and Interpact INS devices up to
250 A.
bb 160 A Polybloc distribution block:
v direct to a tunnel terminal, for cables up to 70 mm2.
Distribution
bb 250 A Polybloc distribution block:
v via cables, up to six 10 mm2 cables and three 16 mm2 cables per phase.
bb 160 A Polybloc distribution block:
v via cables, up to six 16 mm2 cables.
160 A Polybloc distribution block installed Installation
in a 600 mm wide enclosure. bb 250 A Polybloc distribution block:
bb It is mounted downstream of vertically mounted Compact NS100 / 250 and
NSX100 / 250 and Interpact INS250 devices in the enclosures. The Polybloc is
mounted on the modular device rail (LSL58801A).
bb 160 A Polybloc distribution block:
v the blocks clip onto a modular rail.
Dimensions

70

95

38

250 A Polybloc distribution block 160 A Polybloc distribution block

The spring terminals Downstream circuits are connected from the front, to spring terminals.
Contact pressure automatically adapts to the size of the conductor. It does not
depend on the operator.
Contacts are insensitive to vibrations and thermal variations.
DD381399

Only one cable (flexible or rigid, without a metal ferrule) can be inserted in a spring
terminal.
Degree of protection: IPxxB.
Advantages
bb A reliable electrical connection, no maintenance required (tightness guaranteed
over time).
bb Very fast connection.
bb Easy phase balancing.
bb Rewiring is very easy if the switchboard is expanded or modified.

C-8
Distribution Distribution blocks
Multiclip distribution block
System L

Description

200 A Multiclip distribution block The 200A Multiclip distribution block has been optimised to feed rows of modular
devices. It is easily installed by simply clipping it onto the modular rail, either above
presentation or below the row of devices. Its flexibility means it can be fitted before or after the
devices have been mounted.
DD383483

Its dimensions have been kept to a minimum to ensure the best possible integration
into the switchboard.

To ensure compatibility with all installation types, we recommend you connect the
supply to the distribution block at its centre.
The 200A Multiclip distribution block provides you with:
bb flexibility
v compatibility with all types of switchgear,
v possibility of mixing all types of modular devices,
v distribution blocks with different numbers of available poles,
bb safety
v insulation of upstream terminal pads,
v flawless connection reliability thanks to its spring terminals,
v full protection (IPxxB) against direct contact,
bb protection degree
v a protective cover on the busbar ensures IPxxB from the front,
bb easy modifications
v increased connection capacity (number of points and cross-section),
v possibility of adding or changing feeders, whatever type of device is to be added,
v continuity of service.

Application
Distribution over full rows of modular devices.
The distribution block is generally supplied by busbars in enclosures.
Electrical characteristics
bb Rated insulation level Ui = 750 V.
bb Impulse withstand voltage Uimp = 8 kV.
DD800048

bb Short-circuit withstand current: the reinforced breaking capacity due to cascading


in circuit-breaker combinations is maintained. The worst-case situations have been
tested.
bb 200 A Multiclip distribution blocks:
v 10 mm2 cable outgoer: Imax = 50 A,
v two 10 mm2 cables: Imax = 63 A.
Supply
bb Direct to terminals:
v 50 mm2 cables with crimped lugs,
v 20 x 3 mm flexible bars.
bb From busbars in the rear of a wall mounted enclosure (04029).
Busbar connection
The Multiclip distribution block is supplied by the rear busbar through a connection
(04029).
No. of poles H (mm) Distribution
2P 24 bb 200 A Multiclip, 2P and 3P (LSX58052A and LSX58053A):
3P 44 v 12 connection points for phase and neutral.
bb 200 A Multiclip, 4P (LSX58054A):
4P 52
v 12 connection points for each phase,
v 18 connection points for the neutral.
Each connection point can receive a single 10 mm2 cable, either flexible or rigid.
Installation
bb Clipped onto the rear of modular rail.
bb Screwed to plain or slotted backplate.
Supplied with:
bb 100 mm long, bared 10 mm2 copper connections:
v 200 A Multiclip, 2P, 3P and 4P (LSX58052A, LSX58053A and LSX58054A): 2 sets
of 12 connections.
bb Protection covers for the supply terminals (IPxxB).
bb The hardware required for the supply terminals.

The spring terminals See previous page.

C-9
Distribution Distribution blocks
Multi-stage current distribution blocks
System L

Description

Multi-stage current distribution The multi-stage current distribution block is easy to install and can be either clipped
onto the modular rail or fixed to a solid or perforated mounting plate.
block presentation Electrical characteristics
bb Rated operating current: Ie (40 °C) = 125 A.
DD382813

bb Rated insulation level Ui = 500 V.


bb Rated short-time withstand current Icw = 3.5 kA rms / 1 s.
bb Peak withstand current Ipk = 20 kÂ.
bb Impulse withstand voltage Uimp = 8 kV.
Supply
bb Connected with flexible or rigid cable with or without crimped lugs.
Installation
bb Clipped onto the modular rail.
bb Screwed to plain or slotted backplate.
Supplied with:
bb transparent, insulating cover,
bb mounting hardware.

Dimensions
E19453

C-10
Distribution Distribution blocks
Comb busbars
System L

Description

Comb busbars presentation The comb busbars are used for the distribution over full rows of modular devices.
They may be supplied by either the incoming device fitted on the row or via
connectors.
E40638

They can be cut to length. The cutting locations are marked on the copper bar and on
the insulation.
They are fully insulated.
Markers can be fitted for circuit identification.
The tooth-caps ensure the IPxxB protection. The unused teeth may be insulated by
fitting tooth-caps.

Comb busbars for C60 devices


Description
bb Range of comb busbars for 18 mm spacing.

The insulated connectors are firmly clipped onto insulated


Electrical characteristics
parts of comb busbars. bb Rated insulation level Ui:
v 250 V for 1P + N and 3P + N comb busbars,
v 500 V for 1P, 2P, 3P and 4P comb busbars.
bb Rated operational current Ie (40°C) :
v 80 A with 1 central supply point for 1P, 2P, 3P and 4P comb busbars only,
E40637-32

E40639-32

v 100 A with 1 central supply point for 1P + N and 3P + N comb busbars and
2 central points for 1P, 2P, 3P and 4P comb busbars,
MERL
IN GERIN
NG125
v 125 A with 2 supply points for 1P + N and 3P + N comb busbars only.
MERL
IN GERIN
NG125
I . ON
bb short circuit withstand capacity compatible with the breaking capacities of
I . ON
Schneider modular circuit breakers.
Connection
bb Can be supplied by the rear busbar through insulated connectors.
Picture N°1. Picture N°2. bb Direct connection to a device terminals.
The tooth-caps may be fitted to insulate unused teeth of the Supplied with:
comb busbar for the C60 devices (picture n°1) or the bb two IP2 end caps.
NG125 devices (picture n°2).
Comb busbars for NG125 devices
Description
bb Range of 1P, 2P, 3P and 4P comb busbars for 27 mm terminal spacing.
bb Length:
v 432 mm (16 x 27 mm) for 1P, 2P and 4P comb busbars,
v 405 mm (15 x 27 mm) for 3P comb busbar.
Electrical characteristics
bb Rated insulation level Ui: 690 V.
bb Rated operating current Ie (40°C) = 125 A.
bb Maximum rated current per outgoing circuit = 63 A.
bb Rated impulse withstand voltage Uimp = 8 kV.
bb short circuit withstand capacity compatible with the breaking capacities of
Merlin Gerin modular circuit breakers.
Connection
bb Supply by cables with a maximum cross-section of 50 mm2, directly in the tunnel
terminals of the device.
bb To supply the comb busbar from a busbar set located at the rear of the enclosure,
use a 100 A connection.
Supplied with:
bb 8 tooth-caps + 2 end-caps for 2P comb busbar.
bb 4 tooth-caps + 2 end-caps for 3P and 4P comb busbars.

C-11
Distribution Busbars from 160 to 630 A
Selection table
System L

Commercial numbers

Rear busbar for enclosures W = 600 mm


Rating (A) Length (mm) Size of bars (mm)

160 1400 15 x 5
DD3800018

250 1400 20 x 5
400 1400 32 x 5

Vertical multi-stage busbar for enclosures W = 300 mm


Rating (A) Length (mm) Size of bars (mm)

160 1400 15 x 5
DD800019

250 1400 20 x 5
400 1400 32 x 5
630 1400 32 x 8

Horizontal multi-stage busbar for enclosures W = 600 mm


Rating (A) Length (mm) Size of bars (mm) Set of 4 drilled bars
with threaded holes
160 1400 15 x 5 04171
DD800047

250 1400 20 x 5 04172


400 1400 32 x 5 04173
630 1400 32 x 8 04174

Accessories For the distribution accessories, see page C-16~C-18.


DD381398

C-12
Distribution Busbars from 160 to 630 A
Selection table
System L

Commercial numbers

Set of 4 drilled bars Busbar support Barrier Mounting hardware


with threaded holes 40 M6 x 16 screws + 40 washers for threaded bars
04171 LSX58080A 04198 04195
04172 LSX58080A 04198 04195
04173 LSX58080A 04198 04195

Set of 4 drilled bars Busbar support(1) Barrier Mounting hardware


with threaded holes 40 M6 x 16 screws + 40 washers for threaded bars
04171 LSX58082A 04197 04195
04172 LSX58082A 04197 04195
04173 LSX58082A 04197 04195
04174 LSX58082A 04197 04195

(1) The number of supports depends on the rated short-time withstand current (Icw), see the
table in “Busbar calculation”.

Busbar support Barrier Plain front plate, 6 modules Mounting hardware


40 M6 x 16 screws + 40 washers for threaded bars
2 x LSX58082A 04197 LSX58936A 04195
2 x LSX58082A 04197 LSX58936A 04195
2 x LSX58082A 04197 LSX58936A 04195
2 x LSX58082A 04197 LSX58936A 04195

C-13
Distribution Distribution blocks
Selection table
System L

Commercial numbers

Designation No. of Rating Rated Rated impulse Rated Rated short-time


poles insulation withstand voltage operational withstand current Icw
voltage Ui Uimp current Ie (40°C)
Distribloc distribution block - 125 A 750 V 8 kV 125 A depending on
connected device
DD381660

Polybloc distribution block 1P 160 A 750 V 8 kV 160 A depending on


connected device
DD382981

3P 250 A 750 V 8 kV 160 A depending on


connected device

4P 250 A 750 V 8 kV 160 A depending on


connected device

Multi-stage current distribution 2P 125 A 500 V 8 kV 125 A 3.5 kA rms / 1 s.


block
DD382813

4P 125 A 500 V 8 kV 125 A 3.5 kA rms / 1 s.

200 A Multiclip distribution block 2P 200 A 750 V 8 kV 200 A depending on


connected device
DD381672

3P 200 A 750 V 8 kV 200 A depending on


DD381670

connected device

4P 200 A 750 V 8 kV 200 A depending on


DD381671

connected device

C-14
Distribution Distribution blocks
Selection table
System L

Commercial numbers

Rated peak Connection capacity Com. no. Installation / comments


withstand current upstream downstream
Ipk
depending on tunnel terminals for 6 to 35 mm2 b spring terminals 04045 b modular rail
connected device flexible cables (10 to 35 mm2 rigid v 2 outgoers from: 1 to 10 mm2, flexible or rigid b plain or slotted backplate
cables) v 3 outgoers from: 1 to 6 mm , flexible or rigid
2

v 7 outgoers from: 1 to 4 mm2, flexible or rigid


b tunnel terminals
v 1 outgoer from: 4 to 16 mm2, flexible or rigid
(4 to 25 mm2 rigid)

depending on tunnel terminal, for cables up to via cables, up to six 16 mm2 cables. 04031 b modular rail
connected device 70 mm2 b plain or slotted backplate

depending on directly to the incoming device: b spring terminals 04033 b directly downstream of the incoming
connected device EasyPact CVS 100 / 250 and v 6 x 10 mm2 + 3 x 16 mm2, flexible or rigid device:
Compact NSX 100 / 250, Interpact v EasyPact CVS 100 / 250 and
INS250 Compact NSX 100 / 250, Interpact
INS250
b modular rail
depending on directly to the incoming device: b spring terminals 04034 b directly downstream of the incoming
connected device EasyPact CVS 100 / 250 and v 6 x 10 mm2 + 3 x 16 mm2, flexible or rigid device:
Compact NSX 100 / 250, Interpact v EasyPact CVS 100 / 250 and
INS250 Compact NSX 100 / 250, Interpact
INS250
b modular rail
20 k via flexible or rigid cable with or via flexible or rigid cable with or without See b 2 x13 holes:
without crimped lugs crimped lugs Schneider 1 x 8.5 mm2 + 2 x 7 mm2 + 5 x 5.5 mm2
corresp. + 5 x 4.4 mm2
b clipped onto modular rail
b screwed to plain or slotted backplate
20 k via flexible or rigid cable with or via flexible or rigid cable with or without See b 4 x13 holes:
without crimped lugs crimped lugs Schneider 1 x 8.5 mm2 + 2 x 7 mm2 + 5 x 5.5 mm2
corresp. + 5 x 4.4 mm2
b clipped onto modular rail
b screwed to plain or slotted backplate
See b 4 x17 holes:
Schneider 1 x 8.5 mm2 + 2 x 7 mm2 + 7 x 5.5 mm2
corresp. + 7 x 4.4 mm2
b clipped onto modular rail
b screwed to plain or slotted backplate
depending on b via connection from rear busbar b supplied flexible cables: LSX58052A b clipped onto rear of modular rail
connected device b 50 mm2 cables with crimped lugs b 10 mm2 b screwed to plain or slotted backplate
b 20 x 3 mm flexible bars b the Multiclip distribution block is
supplied by the rear busbar through a
connection (04029).

depending on b via connection from rear busbar b supplied flexible cables: LSX58053A b clipped onto rear of modular rail
connected device b 50 mm2 cables with crimped lugs b 10 mm2 b screwed to plain or slotted backplate
b 20 x 3 mm flexible bars

depending on b via connection from rear busbar b supplied flexible cables: LSX58054A b clipped onto rear of modular rail
connected device b 50 mm2 cables with crimped lugs b 10 mm2 b screwed to plain or slotted backplate
b 20 x 3 mm flexible bars

C-15
Distribution Distribution accessories
Selection table
System L

Commercial numbers

Insulated flexible bars The insulated flexible bars are tested in a type-tested switchboard environment.
Their design takes into account the switchboard architecture where they are often in
close proximity to a protection device (circuit breaker or fuse) with significant heat
DD381659

losses.
In-depth knowledge of switchboard architecture and the connected devices led to
the establishment of a selection table based on the type of device.
Flexible bars are 1800 mm long and made of copper with an insulating sheath.
Rated insulation level Ui = 1000 V.
The sizes for the flexible bars indicated below take into account the heat losses of
Schneider devices in a Prisma iPM switchboard.

Connection between device and busbars


The flexible bars are determined taking into account the connected device, whatever
the internal temperature of the switchboard.
The bar sizes indicated below take into account the derating curves of devices.
Device Size (mm) Com. no.
NSX100 20 x 2 04742
NSX160 / 250 20 x 3 04743
NSX400 32 x 5 04751
NSX630 32 x 8 04753
NS100 20 x 2 04742
NS160 / 250 20 x 3 04743
NS400 32 x 5 04751
NS630 32 x 8 04753
EZC100 20 x 2 04742
EZC160 / 250 20 x 3 04743
EZC400 32 x 5 04751
INS125 / 160 20 x 2 04742
INS250 20 x 3 04743
INS400 32 x 5 04751
INS630 32 x 8 04753
200 A Multiclip 20 x 3 04743

Connection between busbars


Flexible bars are designed for connections between busbars taking into account the
following characteristics:
bb a maximum temperature of 60°C inside the switchboard. This corresponds to the
average temperature inside a switchboard for an ambient temperature of 35°C,
bb the maximum withstand temperature for the insulating material is 125°C.
Ie max. (A) Size (mm) Com. no.
200 20 x 2 04742
250 20 x 3 04743
520 32 x 5 04751
660 32 x 8 04753
DD382008

C-16
Distribution Distribution accessories
Selection table
System L

Commercial numbers

Earth / neutral bar The earth bar (450 mm long) is equipped with 40 clamps with captive screws.
It is supplied with 1 connector for rigid or semi-rigid cable 35 mm2, 2 insulating
spacers for use on a neutral bar and mounting hardware.
DD800020

It is directly installed in horizontal position on functional uprights.


The neutral bar is created by inserting 2 insulating spacers (supplied) behind the
earth bar.
Designation Com. no.
Cu earth / neutral bar, 24 modules LSX58070A

E56846

E56845
Neutral bar. Earth bar.

Horizontal cable straps Designation Com. no.


12 cable straps for horizontal cables 04239
DD381618

Horizontal cable straps have the same capacity as 60 x 30 mm trunking.


DD800021

Cover for horizontal cable Designation Com. no.

straps 4 covers for horizontal cable straps L = 430 mm 04243


DD381621

DD800029

C-17
Distribution Distribution accessories
Selection table
System L

Commercial numbers

Horizontal trunking support For cable trunking, height = 60 or 80 mm.


Designation Com. no.
DD381626

12 horizontal trunking supports 04255

DD800016

Mounting hardware Designation Com. no.


Set of 40 M6 x 16 screws (40 screws + 40 contact washers) 04195
DD381398

C-18
Distribution Partitioning
Selection table
System L

Commercial numbers

Horizontal partition The partition is a metal barrier installed in a wall mounted enclosure or a 300 mm
wide enclosure.
It is used to:
DD800051

bb separate the functional units from one another,


bb create a physical separation between devices and a terminal block, for example.
It is mounted directly on the functional uprights.
Lateral and rear knock-outs are available for cable running or the installation of
busbars at the rear of the switchboard.
Designation Com. no.
Horizontal partition W = 500 mm D = 235 mm LSL58281H
D = 305 mm LSL58282H

Vertical partition The metal partition creates a physical separation between the device compartment
and the 300 mm wide duct of a wall mounted enclosure.
It is used to:
DD800052

bb separate the devices from busbars or a distribution block installed in the duct,
bb set up a special zone for terminal blocks in the duct.
There are knock-outs for cable running.
Vertical partitioning It can be cut to length every 150 mm and can be used for
partitioning up to 32-module in wall mounted enclosure (H = 1850 mm).
Designation Com. no.
Vertical partition 4 to 24 modules LSL58280V
28 and 32 modules LSL58279V

C-19
D-2
Enclosures Contents
System L

Description D-2
IP30/31/40/41/54 in-door enclosures D-2

Commercial numbers D-4


IP30/31/40/41 PAK wall mounted enclosures D-4
IP30/31 wall mounted enclosures D-5
IP40/41 wall mounted enclosures D-6
IP54 wall mounted enclosures D-7
IP30/31/40/41/54 enclosures accessories D-8

Dimensions D-10

D-1
Enclosures IP30/31/40/41/54 in-door
System L enclosures
General information
Description

Wall mounted enclosures PAK Full kit

DD800467
DD800466

IP IP30/31/40/41 IP30/31/40/41/54

In up to 630 A

IK 07 (without door), 08 (IP30/31/40/41/54 door)

Functional height
DD800162

(1 module = 50 mm) 4 8  12 16 20 24 28 32 4 8  12 16 20 24 28 32

Overall height (mm) 300 500 700 900 1100 1300 1650 1850 300 500 700 900 1100 1300 1650 1850

Overall depth (mm) 235 305 235 305

Enclosure color RAL 7047


Same plain or transparent doors

Same front frame


DD800468

and plain door or


transparent door

Association no yes yes


vertically and horizontally vertically
and
horizontally

Cable duct no yes yes


(width = 300 mm)
DD800469

DD800470

DD800471

Installation flush mounted or surface surface flush mounted or surface surface


mounted mounted mounted mounted
DD800474

DD800474
DD800472

DD800472

D-2
Enclosures IP30/31/40/41/54 in-door
System L enclosures
General information
Description

Enclosure description 1 The enclosure


Enclosure size is determined simply according to the switchgear installed, the
DD800054

connection method and positioning and the required free rows.


The enclosures can be flush mounted or surface mounted.
Pre punch-outs at the wall mounted enclosure back are provided for rear cable
insertion.
Square holes every 50 mm make it easy to count modules.
The 600 mm wide wall mounted enclosures are dedicated for functional unit area.
The 300 mm wide duct is dedicated to the cables and busbar area.
The panelling is assembled after mounting devices and cabling to maintain complete
accessibility in the switchboard during its implementation.

2 Removable chassis
It enables to install the empty enclosure on site; then to assemble and cable the
devices on the removable frame at the workshop and to mount it in the PaK
enclosure at the worksite.

3 Front frame/Front Plate support


The Front frame/Front Plate support is supplied with the full kit enclosures. It enables
the mounting of the front plates.
It can be removed for fast, direct access to all the devices, with all the front plates
mounted on.

4 Doors
Both plain and transparent doors are reversible and designed for quick and easy left
or right-hand mounting by a single person.
A handle is only available on the 600 mm wide doors. The 300 mm wide duct is
dedicated to the professional staff. For greater safety, it is closed with screws.
A range of locks are available for the “push and pull” handle.

Enclosure combination The wall mounted enclosures must have the same depth to be combined each other
horizontally and vertically.
DD800032

The 28-module and 32-module height enclosures can be horizontally combined only.
An assemby kit is supplied with the 300 mm wide duct.
For other combinations than 600 + 300 mm wide enclosures, assembly kits are
available in option.
The degrees of protection are maintained.

Side-by-side combination
It ensures the mechanical connection between the wall mounted enclosures and the
duct.

Vertical combination
A combination kit ensures the mechanical connection between the two functional
unit wall mounted enclosures.

“L” shape combination


The “L” shape is created by combining two enclosures (extension or duct) with a
600 mm wide enclosure.

Square combination
The square shape is created by combining three enclosures (extension or duct) with
a basic enclosure.
Square combinations are only possible with enclosures that have the same number
of vertical modules.

Enclosure fixing IP30/31/40/41 wall mounted enclosures


bb From 4 to 24 modules, switchboards is mounted on a wall through the holes at the
DD800473

rear of the switchboard. It is possible to mount the switchboards on a wall by using


external wall mounted fixing rings (2 x LSL58274A).
bb From 28 to 32 modules, switchboards is mounted on a wall by using external wall
mounted fixing rings (LSL58274A).

IP54 wall mounted enclosures


bb Switchboards is mounted on a wall by using external wall mounted fixing rings
(supplied).

D-3
Enclosures IP30/31/40/41 PAK
System L wall mounted enclosures
Selection table
Commercial numbers

PAK The enclosures can be flush mounted or surface mounted.

IP30/31

DD800548

DD800546

DD380623

DD380624

DD384035
DD800545

Overall Functional Overall Enclosure Front plate Door Fixing


depth height height W = 600 support plain or transparent screw
(mm) (1 module (mm) mm
= 50 mm)
235 4 300 LSL58205A LSL58604A LSL58104A - -
8 500 LSL58209A LSL58608A LSL58108A LSL58162T -
12 700 LSL58213A LSL58612A LSL58112A LSL58163T -
16 900 LSL58217A LSL58616A LSL58116A LSL58164T -
20 1100 LSL58221A LSL58620A LSL58120A LSL58165T -
24 1300 LSL58225A LSL58624A LSL58124A LSL58166T -
305 28 1650 LSL58329A LSL58628A LSL58128A LSL58167T 03183
32 1850 LSL58333A LSL58632A LSL58132A LSL58168T 03183
For the flush mounting kit and enclosure accessories, see page D-8~D-9.

Enclosure weight
Empty weight
No. of vertical modules Weight (kg)
(1 module = 50 mm) Enclosure W = 600 mm
Without door With door
4 6 11
8 9 13
12 12 17
16 14 21
20 15 24
24 17 27
28 37 50
32 39 54

PAK The enclosures can be flush mounted or surface mounted.

IP40/41
DD800548

DD800546

DD380623

DD380624
DD800545

Overall Functional Overall Enclosure Front plate Door


depth height height W = 600 mm support plain or transparent
(mm) (1 module (mm)
of 50 mm)
235 4 300 LSL58205A LSL58604A LSL58104A -
8 500 LSL58209A LSL58608A LSL58149A LSL58160T
12 700 LSL58213A LSL58612A LSL58150A LSL58161T
16 900 LSL58217A LSL58616A LSL58151A LSL58157T
20 1100 LSL58221A LSL58620A LSL58152A LSL58158T
24 1300 LSL58225A LSL58624A LSL58153A LSL58159T
305 28 1650 LSL58329A LSL58628A LSL58154A LSL58169T
32 1850 LSL58333A LSL58632A LSL58155A LSL58170T

Gasket kit Com. no.


L IP40/41 accessories + gasket kit 2000mm LSL58276A
For the flush mounting kit and enclosure accessories, see page D-8~D-9.

Enclosure weight
Empty weight
No. of vertical modules Weight (kg)
(1 module = 50 mm) Enclosure W = 600 mm
Without door With door
4 6 11
8 9 13
12 12 17
16 14 21
20 15 24
24 17 27
28 37 50
32 39 54

D-4
Enclosures IP30/31
System L wall mounted enclosures
Selection table
Commercial numbers

Full kit The enclosures 4-24M can be flush mounted or surface mounted.
The enclosures 28-32M can be surface mounted.
To ensure compliance with the degree of protection IP31, the addition of a canopy
DD800054

with a gasket is needed.

DD800478

DD800057

DD380623

DD380624

DD384035
Overall Functional Overall Enclosure Duct with Door Fixing
depth height Height W = 600 mm door plain or transparent screw
(mm) (mm) W = 300 mm
235 4 300 LSL58204A - LSL58104A - -
8 500 LSL58208A LSL58231A LSL58108A LSL58162T -
12 700 LSL58212A LSL58232A LSL58112A LSL58163T -
16 900 LSL58216A LSL58233A LSL58116A LSL58164T -
20 1100 LSL58220A LSL58234A LSL58120A LSL58165T -
24 1300 LSL58224A LSL58235A LSL58124A LSL58166T -
305 28 1650 LSL58328A LSL58336A LSL58128A LSL58167T 03183
32 1850 LSL58332A LSL58337A LSL58132A LSL58168T 03183
(1) Mandatory for front plate mounting.
For the flush-mount kit and enclosure accessories, see page D-8~D-9.

Enclosure weight
Empty weight
No. of vertical Weight (kg)
modules Enclosure W = 600 mm Enclosure + door W = 300 mm
(1 module = 50 mm)
Without door With door With door
4 10 13 -
8 13 17 10
12 15 21 12
16 18 25 15
20 20 29 17
24 22 33 19
28 33 46 26
32 35 50 28

Assembly kit An assembly kit is supplied with the 300 mm wide duct in standard.
Designation Cat. no.
DD800088

4 assembly kit IP30/31/40/41 LSL58273A

Combinations possibilities
DD800058

DD800061
DD800060

Vertical combination Vertical and horizontal Horizontal combination of


with 1 x LSL58273A combination with 2 enclosures W = 600 mm
2 x LSL58273A with 1 x LSL58273A
DD800062

DD800063

DD800064

Horizontal combination of Horizontal combination of Square combination of


3 enclosures W = 600 + 300 + 2 enclosures W = 600 + 300 mm 4 enclosures W = 600 mm with
600 mm with 1 x LSL58273A with 1 x LSL58273A 4 x LSL58273A

D-5
Enclosures IP40/41
System L wall mounted enclosures
Selection table
Commercial numbers

Full kit

DD800478

DD800057

DD380623

DD380624

DD384035
DD800054

Overall Functional Overall Enclosure Duct with Door


depth height Height W = 600mm door plain or transparent
(mm) (1 module (mm) W = 300mm
= 50 mm)
235 4 300 LSL58204A - LSL58104A - -
8 500 LSL58208A LSL58231A LSL58149A LSL58160T -
12 700 LSL58212A LSL58232A LSL58150A LSL58161T -
16 900 LSL58216A LSL58233A LSL58151A LSL58157T -
20 1100 LSL58220A LSL58234A LSL58152A LSL58158T -
24 1300 LSL58224A LSL58235A LSL58153A LSL58159T -
305 28 1650 LSL58328A LSL58336A LSL58154A LSL58169T 03183
32 1850 LSL58332A LSL58337A LSL58155A LSL58170T 03183
(1) Mandatory for front plate mounting.
To ensure the degree of protection IP40/41, the gasket kit 2000mm (LSL58276A) is needed.
For enclosure accessories,see page D-8~D-9.

Enclosure weight
Empty weight
No. of vertical Weight (kg)
modules Enclosure W = 600 mm Enclosure + door W = 300 mm
(1 module = 50 mm)
Without door With door With door
4 10 13 -
8 13 17 10
12 15 21 12
16 18 25 15
20 20 29 17
24 22 33 19
28 33 46 26
32 35 50 28

Assembly kit An assembly kit is supplied with the 300 mm wide duct in standard.
Designation Cat. no.
DD800088

4 assembly kit IP30/31/40/41 LSL58273A

Combinations possibilities
DD800058

DD800060

DD800061

Vertical combination Vertical and horizontal Horizontal combination of


with 1 x LSL58273A combination with 2 enclosures W = 600 mm
2 x LSL58273A with 1 x LSL58273A
DD800064
DD800062

DD800063

Horizontal combination of Horizontal combination of Square combination of


3 enclosures W = 600 + 300 + 2 enclosures W = 600 + 300 4 enclosures W = 600 mm with
600 mm with 1 x LSL58273A mm with 1 x LSL58273A 4 x LSL58273A

D-6
Enclosures IP54
System L wall mounted enclosures
Selection table
Commercial numbers

Full kit

DD800478

DD800057

DD380623

DD380624

DD384035
DD800054

Overall Functional Overall Enclosure Duct with Door


depth height Height W = 600 door
plain or transparent
(mm) (vertical (mm) mm W = 300
modules mm
of 50 mm)
235 4 300 LSL58504A - LSL58104A - -
8 500 LSL58508A LSL58541A LSL58149A LSL58160T -
12 700 LSL58512A LSL58542A LSL58150A LSL58161T -
16 900 LSL58516A LSL58543A LSL58151A LSL58157T -
20 1100 LSL58520A LSL58544A LSL58152A LSL58158T -
24 1300 LSL58524A LSL58545A LSL58153A LSL58159T -
305 28 1650 LSL58528A LSL58546A LSL58154A LSL58169T 03183
32 1850 LSL58532A LSL58547A LSL58155A LSL58170T 03183
For enclosure accessories, see page D-8~D-9.

Enclosure weight
Empty weight
No. of vertical Weight (kg)
modules Enclosure W = 600 mm Enclosure + door W = 300 mm
Without door With door With door
4 10 13 -
8 13 17 10
12 15 21 12
16 18 25 15
20 20 29 17
24 22 33 19
28 33 46 26
32 35 50 28

Assembly kit An assembly kit is supplied with the 300 mm wide duct in standard.
Designation Cat. no.
Assembly kit IP54 LSL58275A
DD800118

Combinations possibilities
DD800091

DD800090
DD800089

Vertical combination Vertical and horizontal Horizontal combination of


with 1 x LSL58275A combination with 2 enclosures W = 600 mm
2 x LSL58275A with 1 x LSL58275A
DD800092

DD800093

DD800094

Horizontal combination of Horizontal combination of Square combination of


3 enclosures 2 enclosures 4 enclosures W = 600 mm
W = 600 + 300 + 600 mm W = 600 + 300 mm with with 4 x LSL58275A
with 1 x LSL58275A 1 x LSL58275A

D-7
Enclosures IP30/31/40/41/54 enclosures
System L accessories
Commercial numbers

The addition of a canopy over a wall mounted enclosure equipped with a door
Canopy (IP31/41) ensures compliance with the degree of protection IP31/41.
Designation Com. no.
DD800026

IP31 canopy D = 235 mm W = 620 mm LSL58266A


W = 300 mm LSL58267A
D = 300 mm W = 620 mm LSL58269A
W = 300 mm LSL58270A
IP31 canopy extension D = 235 W = 600 mm LSL58268A
D = 300 W = 600 mm LSL58271A
Dimensions of combined wall mounted enclosures with canopies

DD800126

DD800121
15 15

Combination of 600 mm and 300 mm Combination of 2 x 600 mm wide wall mounted


wide wall mounted enclosures. enclosures.

DD800189
15 15

Combination of 600 mm + 300 mm + Combination of more than three 600 mm wide


600 mm wide wall mounted enclosures. wall mounted enclosures.

20 20
580

Ø7
Ø12
30

LSL58266A / LSL58269A

20 20
580

30

LSL58266A / LSL58269A

20 20 20 20
560 260

30 30
LSL58268A / LSL58271A LSL58267A / LSL58270A

Flush-mount kit (IP30 / 31) When the enclosure is embedded into the wall, a flush-mounted kit is mandatory to
fix it and to hide free spaces.
The flush-mounted enclosure exceeds of 63 mm from the wall.
DD381256

Designation Com. no.


Flush-mount kit up to 24 modules LSL58272A

Lifting / fixing rings Designation Com. no.


2 additional lifting / fixing rings LSL58274A
DD800491

IP30/31/40/41 wall mounted enclosures


bb From 4 to 24 modules, switchboards is mounted on a wall through the holes at the
rear of the switchboard. It is possible to mount the switchboards on a wall by using
external wall mounted fixing rings (2 x LSL58274A).
bb From 28 to 32 modules, switchboards is mounted on a wall by using external wall
mounted fixing rings (LSL58274A).
IP54 wall mounted enclosures
bb Switchboards is mounted on a wall by using external wall mounted fixing rings
(supplied).

D-8
Enclosures IP30/31/40/41/54 enclosures
System L accessories
Commercial numbers

Barrel lock and insert Designation Com. no.


Barrel lock no. 405 08940
DD800122

DIN double bar insert 08945


Screwdriver slot insert 08946

08940
08945

08946

Cable tie supports Designation Fixing screw Com. no.


4 wall mounted cable tie W = 300 mm 03183 LSL58293A
DD800141

supports W = 600 mm 03183 LSL58296A

Drawing holder Designation Com. no.


Adhesive drawing holder, colour RAL 9001 08963
DD381208

D-9
Enclosures IP30/31/40/41 PAK
System L wall mounted enclosures
Dimensions

Wall mounted enclosures Door Aperture


From 4 to 24 modules From 28 to 32 modules

DD800410
DD800095

DD800545_00

DD800479
H

DD800477

150
DD800476

235/305 450 250/320


600

No of modules
4 8 12 16 20 24 28 32
H 300 500 700 900 1100 1300 1500 1700

Wall mounting
From 4 to 24 modules From 28 to 32 modules
Fixing hole diameters
DD800538

DD800546_00

100
DD800077

DD800278
100

Fixing to floor for 28 and 32-module


enclosures
DD800547_00

225

No of modules
4 8 12 16 20 24 28 32
A 400 600 800 1000 1200 1400 1700 1900 23 554

A’ 200 400 600 800 1000 1200 1600 1800

Top cable entry


DD800547

105

320

527

Depth behind front plate


Functional uprights Adjustable device rail Slotted mounting plates Plain mounting plate
DD800618
DD800617
DD800109

DD800115

49 141.5 141.5
93

LSL58802A LSL58824A LSL58826A


DD800548_00

DD800117
DD800116

243

62
LSL58825A LSL58827A

D-10
Enclosures IP30 / 31
System L wall mounted enclosures
Dimensions

Wall mounted enclosures Door


From 4 to 24 modules From 28 to 32 modules 300 mm wide duct

DD800097_01
82.5 82.5

DD800100

DD800102
150

165
DD800095

40 x 40

165

150

150

450
600
DD800066

DD800101

DD800103
No of modules Aperture
4 8 12 16 20 24 28 32

DD800410
H 300 500 700 900 1100 1300 1500 1700

Wall mounted enclosures


From 4 to 24 modules From 28 to 32 modules
DD800149

DD800076

Fixing hole diameters 100


DD800077

DD800278

100

Fixing to floor for 28 and 32-module


enclosures
DD800108

No of modules 225
4 8 12 16 20 24 28 32
A 400 600 800 1000 1200 1400 1700 1900 Ø11
A’ 220 420 620 820 1020 1220 1600 1800
23 554 46 254 23

Top cable entry Cable entry for base frame


DD800104

DD800105

137.8 202.8

Depth behind front plate


Functional uprights Adjustable device rail Slotted mounting plates Plain mounting plate
DD800109-1

DD800115

DD800618
DD800617

174.5
49 141.5 141.5
62 93

LSL58802A LSL58824A LSL58826A


DD800480

DD800117
DD800116

239.5
301.5
62

LSL58825A LSL58827A

D-11
Enclosures IP40/41
System L wall mounted enclosures
Dimensions

Wall mounted enclosures Door


From 4 to 24 modules From 28 to 32 modules 300 mm wide duct
DD800097_01
82.5 82.5

DD800100

DD800102
150

165
DD800095

40 x 40

165

150

150

450
600
DD800066

DD800101

DD800103
No of modules Aperture
4 8 12 16 20 24 28 32

DD800410
H 300 500 700 900 1100 1300 1500 1700

Wall mounted enclosures


From 4 to 24 modules From 28 to 32 modules
DD800149

DD800076

Fixing hole diameters 100


DD800077

DD800278

100

Fixing to floor for 28 and 32-module


enclosures
DD800108

No of modules 225

4 8 12 16 20 24 28 32
A 400 600 800 1000 1200 1400 1700 1900 Ø11
A’ 220 420 620 820 1020 1220 1600 1800
23 554 46 254 23

Top cable entry Cable entry for base frame


DD800104

DD800105

137.8 202.8

Depth behind front plate


Functional uprights Adjustable device rail Slotted mounting plates Plain mounting plate
DD800115
DD800109-1

DD800618
DD800617

174.5 49 141.5 141.5


93
62
LSL58802A LSL58824A LSL58826A
DD800480

DD800117
DD800116

239.5
301.5
62

LSL58825A LSL58827A

D-12
Enclosures IP54
System L wall mounted enclosures
Dimensions

Wall mounted enclosures Door


From 4 to 24 modules From 28 to 32 modules 300 mm wide duct

DD800097_01
82.5 82.5

DD800100

DD800102
150

165
DD800095

40 x 40

165

150

150

450
600

DD800103
DD800066

DD800101

No of modules Aperture
4 8 12 16 20 24 28 32

DD800410
H 300 500 700 900 1100 1300 1500 1700

Wall mounted enclosures


From 4 to 24 modules From 28 to 32 modules
DD800150

DD800106

Fixing hole diameter


100
DD800278

100

Fixing to floor for 28 and 32-module


enclosures
DD800108

No of modules 225

4 8 12 16 20 24 28 32
A 400 600 800 1000 1200 1400 1700 1900 Ø11

23 554 46 254 23

Top cable entry Cable entry for base frame


DD800104

DD800105

141.5

Depth behind front plate


Functional uprights Adjustable device rail Slotted mounting plates Plain mounting plate
DD800109-1

DD800618
DD800617
DD800115

174.5 49 141.5 141.5


93
62
LSL58802A LSL58824A LSL58826A
DD800480

DD800117
DD800116

239.5
301.5
62

LSL58825A LSL58827A

D-13
E-2
Characteristics Contents
System L

Spare parts E-2

Electrical characteristics E-3


Designing Prisma iPM power circuits E-3
Designing connections y 630 A E-4
Designing connections with cables E-6
Designing the PEN conductor E-7

Mechanical characteristics E-8


Degree of protection E-8
Properties of metal enclosure E-10

Environment E-12
Environmental profile of Prisma iPM switchboards E-12

E-1
Characteristics Spare parts
System L

Spare parts

Door accessories Wall mounted enclosure Com. no.


Door spare parts for system L LSL58033A
20 front plate screws + nuts LSX58030A
DD800560_01

Prisma iPM spare parts handle LSX58031A

Door spare parts for system L


DD800561

20 front plate screws + nuts


DD800556

Prisma iPM spare parts handle

Hinge kit Designation Com. no.


Front plate hinge kit LSX58776A
DD800015

E-2
Characteristics Designing Prisma iPM
System L power circuits
Presentation and approach
Electrical characteristics

The Prisma iPM system takes into account the In the following pages you will find a number of examples, validated for Prisma iPM
installation and connection conditions of Schneider switchboards, intended to assist in determining the busbars as well as the upstream
Electric devices. and downstream connections for the installation.
The entire installation complies with standard IEC The examples assume that the devices have already been selected.
61439-1. The result is a type tested switchboard. A complete process involves a number of steps before making final choices
(transformer, conductors, protection, etc.).
Schneider Electric offers a number of tools to assist in designing a complete
installation (technical guides, software).
PD800010

PD800000

Busbar sizing The factors that must be taken into account in determining the size of busbars
include:
bb the diversity factor.
Not all the loads supplied by a set of busbars are used at full rated load or at the
same time. The diversity factor is the means to determine the maximum load current
used to size the busbars.
Standard IEC 61439-1.
Number of circuits Diversity factor
2 and 3 0.9
4 and 5 0.8
6 to 9 0.7
10 and more 0.6
bb the degree of protection IP.
For information on defining the necessary degree of protection IP.
bb the ambient temperature around the switchboard.

E-3
Characteristics
Designing connections y 630 A
System L Device connections

Electrical characteristics

Insulated flexible copper bars Switchboards that comply with standard IEC 61439-1
It is imperative to use the values indicated below that have been validated for the
installation of devices in Prisma iPM switchboards.
The parameters determining the size of flexible bars are:
bb the environment in which the devices are installed:
v position in the enclosure,
v dimensions of other conductors in the circuit,
v ambient temperature around the switchboard,
bb the characteristics of the connected devices:
v device heat losses,
v the type of installation (horizontal or vertical),
v the type of device (fixed or withdrawable).

Only the equipment manufacturer with in-depth knowledge on:


bb the characteristics of the installed devices
the configuration of the installation in the enclosure can provide the correct sizes of
flexible bars for a given permissible current. Insulated, flexible bars make for easy,
fast and flexible implementation up to 630 A, but higher ratings require sizes that
cancel these advantages.
For high Isc values, it is advised to use rigid bars which require fewer supports.

Insulated flexible bars are better than cables, they offer:


bb flexible copper bars with an insulating sheath,
bb better insulation temperature withstand (125°C for bars, 105°C for cables) and a
larger exchange surface for an equivalent size, i.e. a smaller size for a given current,
bb greater rigidity offering better electrodynamic characteristics for short-circuit
currents,
bb no intermediate parts (lugs) for a direct connection between the device and the
busbars therefore less temperature rise and less risk of error,
bb fast implementation of prefabricated connections already cut to length, formed and
drilled.
Technical characteristics
bb thickness of the insulation: variable depending on the bar size, 2 mm on average,
bb rated insulation level Ui = 1000 V,
bb impulse withstand voltage Uimp = 12 kV,
bb maximum withstand temperature of insulating material = 125°C.

Connection In all cubicles with IP y 54


bb the switchboard internal temperature is 60°C,
bb the withstand temperature of the insulating material is 125°C.
If the withstand temperature of the insulation is only 105°C, use the next largest
flexible bar.
The bar sizes indicated below take into account the derating curves of devices.

Connection of devices and distribution blocks to busbars


Device INS125 (1) INS160 (1) INS250 (1) INS320 (1) INS500 (1) NS100(1) NS160(1)
INS400 (1) INS630 (1)
S (mm) 20 x 2 20 x 2 20 x 3 32 x 5 32 x 8 20 x 2 20 x 3
Device NS250(1) NS400(1) NS630 (1) NSX100 (1) NSX160 (1) NSX250 (1) NSX400 (1)

S (mm) 20 x 3 32 x 5 32 x 8 20 x 2 20 x 3 20 x 3 32 x 5
Device NSX630 (1) EZC100 (1) EZC160 (1) EZC250 (1) EZC400 (1)
S (mm) 32 x 8 20 x 2 20 x 3 20 x 3 32 x 5
(1) The values for circuit breakers apply to contactors with the same ratings.

Device Multiclip distribution


block (200 A)
S (mm) 20 x 3

Disconnectors, terminal blocks, connections, busbars to


busbars
I max. (60 °C) 200 A 250 A 400 A 400 A 480 A 520 A 660 A
S (mm) 20 x 2 20 x 3 24 x 5 24 x 5 24 x 6 32 x 5 32 x 8

Note: The values indicated above have been validated for Prisma iPM switchboards.

E-4
Characteristics
Designing connections y 630 A
System L Compact circuit breakers
NSX100 to NSX630
Electrical characteristics

Compact NSX100 to NSX630


Insulated flexible copper bars
Devices Permissible current (A)
Device Type Protection Vigi Size per Average ambient temperature around the switchboard
IP y 55 phase 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C

Fixed TMD No 20 X 2 100 97.5 95 92.5 90 85


Fixed TMD Yes 20 X 2 100 97.5 95 92.5 90 85
Withdrawable TMD No 20 X 2 100 97.5 95 92.5 90 85
Withdrawable TMD Yes 20 X 2 100 97.5 95 92.5 90 85
Fixed Micrologic 2.2/5.2/6.2 No 20 X 2 100 100 100 100 100 100
NSX100
Fixed Micrologic 2.2/5.2/6.2 Yes 20 X 2 100 100 100 100 100 100
Withdrawable Micrologic 2.2/5.2/6.2 No 20 X 2 100 100 100 100 100 100
Withdrawable Micrologic 2.2/5.2/6.2 Yes 20 X 2 100 100 100 100 100 100
Fixed Micrologic 4.2/7.2 No 20 X 2 100 100 100 100 100 100
Withdrawable Micrologic 4.2/7.2 No 20 X 2 100 100 100 100 100 100
Fixed TMD No 20 X 3 160 156 152 147 144 140
Fixed TMD Yes 20 X 3 160 156 152 147 144 140
Withdrawable TMD No 20 X 3 160 156 152 147 144 140
Withdrawable TMD Yes 20 X 3 145 140 135 132 129 126
Fixed Micrologic 2.2/5.2/6.2 No 20 X 3 160 160 160 160 160 160
NSX160
Fixed Micrologic 2.2/5.2/6.2 Yes 20 X 3 160 160 160 160 160 160
Withdrawable Micrologic 2.2/5.2/6.2 No 20 X 3 160 160 160 160 160 160
Withdrawable Micrologic 2.2/5.2/6.2 Yes 20 X 3 144 144 144 144 144 144
Fixed Micrologic 4.2/7.2 No 20 X 3 160 160 160 160 160 160
Withdrawable Micrologic 4.2/7.2 No 20 X 3 160 160 160 160 160 160
Fixed TMD No 20 X 3 250 244 238 231 225 198
Fixed TMD Yes 20 X 3 250 244 238 231 225 198
Withdrawable TMD No 20 X 3 250 244 238 231 225 198
Withdrawable TMD Yes 20 X 3 225 219.6 214.2 207.9 202.5 178.2
Fixed Micrologic 2.2/5.2/6.2 No 20 X 3 250 250 237.5 237.5 225 225
NSX250
Fixed Micrologic 2.2/5.2/6.2 Yes 20 X 3 250 250 237.5 237.5 225 225
Withdrawable Micrologic 2.2/5.2/6.2 No 20 X 3 250 250 237.5 237.5 225 225
Withdrawable Micrologic 2.2/5.2/6.2 Yes 20 X 3 215 215 205 205 195 190
Fixed Micrologic 4.2/7.2 No 20 X 3 245 245 237.5 230 225 220
Withdrawable Micrologic 4.2/7.2 No 20 X 3 220 215 210 200 195 190
Fixed Micrologic 2.3/5.3/6.3 No 32 X 5 400 400 400 390 380 370
Fixed Micrologic 2.3/5.3/6.3 Yes 32 X 5 400 390 380 370 360 350
Withdrawable Micrologic 2.3/5.3/6.3 No 32 X 5 400 390 380 370 360 350
NSX400
Withdrawable Micrologic 2.3/5.3/6.3 Yes 32 X 5 388 378.3 368.6 358.9 349.2 339.5
Fixed Micrologic 4.3/7.3 No 32 X 5 395 390 380 370 360 350
Withdrawable Micrologic 4.3/7.3 No 32 X 5 385 375 365 355 345 335
Fixed Micrologic 2.3/5.3/6.3 No 32 X 8 630 615 600 585 570 550
Fixed Micrologic 2.3/5.3/6.3 Yes 32 X 8 570 550 535 520 505 490
Withdrawable Micrologic 2.3/5.3/6.3 No 32 X 8 570 550 535 520 505 490
NSX630
Withdrawable Micrologic 2.3/5.3/6.3 Yes 32 X 8 513 495 481.5 468 454.5 441
Fixed Micrologic 4.3/7.3 No 32 X 8 560 545 530 515 500 485
Withdrawable Micrologic 4.3/7.3 No 32 X 8 470 457 444 420 405 385

E-5
Characteristics Designing connections with
System L cables
Electrical characteristics

Cables Practical guidelines


Schneider Electric provides cabling recommendations according to the rating of the
circuit breaker.
The size of cables must be selected according to:
bb the level of current,
bb the ambient temperature around the conductors,
bb the degree of protection for the switchboard.

The tables below take into account the installation conditions for each type of device
(permissible temperature at connection terminals, etc.).
They follow the temperature derating values for installed devices in all cubicles with
cover panels rated IP y 55.
bb switchboard internal temperature 60°C,
bb connections using copper cables.
For wall mounted enclosures, the volumes, ratings and connection lengths are low.
Select the values in the “Cables tied together” column, according to the IP.

Supply of devices Flexible copper bars with an insulating cover.


To determine the required sizes for flexible bars, see the tables starting on, which
for outgoers y 630 A indicate the correct size for each type of connected device.
bb an insulated flexible bar (not connected) must meet standards IEC 60243-1
(dielectric) and IEC 60332-1 (fire),
bb a flexible bar connected to a device in an enclosure must comply with standard
IEC 61439-1 (see explanations on).
Cables
To determine the cables required, see the table on.
They can be used to determine:
bb the size of cables as a function of:
v the circuit breaker rating,
v the current,
v the ambient temperature around the switchboard,
bb the permissible current for individually tied cables or touching cables as a function
of:
v the size of the cables,
v the degree of protection for the switchboard.

Connection of circuit breakers Size of Permissible current (A)


cables Cables tied individually Cable tied together
(mm²) IP y 31 IP > 31 IP y 31 IP > 31
1.5 16 14 14 12
2.5 25 25 22 20
4 32 29 28 24
6 40 39 36 33
10 63 55 55 50
16 90 77 80 70
25 110 100 100 93
35 135 125 125 120
50 180 150
70 230 190
95 275 230
Note: Schneider Electric recommends connecting NSX400 / 630 circuit breakers with insulated flexible
bars or rigid bars.

Connection of other devices Size of Permissible current (A)


cables Cables tied individually Cable tied together
(mm²) IP y 31 IP > 31 IP y 31 IP > 31
1.5 13 12 12 10
2.5 23 21 20 19
4 28 26 25 22
6 36 35 32 30
10 55 50 50 46
16 80 70 72 63
25 100 90 90 84
35 120 115 110 103
50 165 135
70 210 176
95 250 210

E-6
Characteristics Designing the PEN conductor
Power circuit
System L

Electrical characteristics

Size of PEN protective conductor Practical guidelines


The size of the PEN is determined in the same manner as a neutral conductor, i.e.:
bb for copper single-phase circuits or sized y 16mm², it must be the same size as the
phase conductors
bb for copper three-phase circuits sized > 16 mm², it can be:
v the same size as the phase conductors,
v smaller on the condition that:
- the current likely to flow in the neutral during normal operation is less than the
permissible current for the conductor,
- the power rating of single-phase loads does not exceed 10% of the total rating.

The conductor must be accessible to enable connections both in the factory and on
site, as well as checks on the tightness of connections.

Implementing the PEN protective Practical guidelines


conductor According to standard IEC 61439-1, the practical guidelines for implementing the
PEN are the following:
bb at the entry to the assembly, the PEN connection must be next to the phase
connections,
bb within the assembly, the PEN does not need to be insulated from the exposed
conductive parts (except on sites where there is a risk of fire or explosion),
bb the size of the conductor must be at least equal to that of the neutral,
bb the size must remain constant throughout the main busbars,
bb the change from a TNC to a TNS system must take place at a single point in the
switchboard, via a marked neutral-disconnection bar that is accessible and can be
dismantled to facilitate the impedance measurement of the fault loop,
bb after the TNS creation point, it is forbidden to recreate a TNC system.
The PE and the neutral must meet their specific requirements.

E-7
Characteristics Degree of protection
General
System L

Mechanical characteristics

Standard IEC 60364-5-51 listed and codified a large number of external


influences to which electrical installations can be subjected, including the
presence of water, solid objects, shocks, vibrations, corrosive substances,
etc.

Degree of protection IP Standard IEC 60529 (IP code, February 2001) indicates the degrees of protection
provided by an enclosure for electrical devices against access to hazardous parts,
against penetration of solid foreign objects and against penetration of water.
These standards do not apply for the protection against the risks of explosion or
conditions such a humidity, corrosive vapour, fungus or vermin.
The IP code is made up of two characteristic numerals and can include an additional
letter when the actual protection for persons against access to the hazardous parts
is better than that indicated by the first numeral.
The first numeral characterises the protection provided against the ingress of solid
foreign objects and the protection of persons.
The second numeral characterises the protection provided against the ingress of
water with harmful effects.

1st numeral 2nd numeral


Protection of persons Protection against ingress of solid objects Protection against ingress of water

1 Protected against Protected against


1 Protected against

DD381966
DD381959

DD381959

access with back of solid foreign objects vertically falling water


hand larger than 50 mm drops (condensation)

2 Protected against Protected against


2 Protected against

DD381967
DD381960

DD381963

access with a finger solid foreign objects vertically falling water


larger than 12.5 mm drops when enclosure
tilted up to 15°

3 Protected against Protected against


3 Protected against
DD381968
DD381961

DD381961

access with a tool solid foreign objects spraying water up to


larger than 2.5 mm 60° from vertical

4 Protected against Protected against


4 Protected against
DD381962

DD381962

DD381969

access with a wire solid foreign objects splashing water from


larger than 1 mm all directions

5 Protected against Protected against dust


5 Protected against
DD381964
DD381962

DD381970

access with a wire (dust protected) water jets from all


directions

6 Protected against Dust tight


6 Protected against
DD381962

DD381965

DD381971

access with a wire powerful water jets


from all directions

7 Protected against the


DD381972

effects of temporary
immersion in water

8 Protected against the


DD381973

effects of continuous
immersion in water

E-8
Characteristics Degree of protection
General
System L

Mechanical characteristics

Additional letter (optional) Protection of persons against access to hazardous parts.


Designation Protection
A Protected against access with back of hand
B Protected against access with a finger
C Protected against access with a tool
D Protected against access with a wire
The additional letter is used only if the actual protection of persons is higher than that
indicated by the first characteristic numeral of the IP code.
If only the protection of persons is of interest, the two characteristic numerals are
replaced by “X”, e.g. IPxxB.
Example
Protected against solid foreign objects
larger than 2.5 mm

No protection
IP30D Protected against access with
a tool 1 mm in diameter

Remarks on the degree of bb the degree of protection IP must always be read and understood numeral by
numeral and not as a whole.
protection IP For example, an IP31 wall mounted enclosure is suitable for an environment that
requires a minimum degree of protection IP21. But an IP30 wall mounted enclosure
is not suitable.
bb the degrees of protection indicated in this catalogue are valid for the enclosures as
presented. However, the indicated degree of protection is guaranteed only when the
installation and device mounting are carried out in accordance with professional
standards.

Degree of protection against Standard IEC 62262 defines an IK code characterising the capacity of products to
resist mechanical impacts from all sides.
mechanical impacts IK
IK code Impact energy (joules(1))
01 0.14
02 0.2
03 0.35
04 0.5
05 0.7
06 1
07 2
08 5
09 10
10 20
(1)The SI derived unit used to measure energy or work. One joule is equal to the energy used to accelerate a
body with a mass of one kilogram using one newton of force over a distance of one meter. One joule is also
equivalent to one watt-second.

Recommendation
In terms of the risks of impacts, selection of the IK code can be summed up as
indicated below.
Site Recommended IK
No risk of major impact Technical rooms 07
Significant risk of impact that Hallways 08 (switchboard with door)
can damage devices
Maximum risk of impact that can Workshops 10
damage the switchboard

E-9
Characteristics Properties of metal enclosure
System L

Mechanical characteristics

Schneider Electric enclosures comply with standard EN 50298 for empty enclosures.
The sheet metal used for Schneider Electric enclosures receives a thermosetting,
polyester-resin-modified epoxy powder for colour and appearance.
This coat system provides excellent finish and corrosion protection.

Mechanical properties of powder Test conditions


coated surfaces

Adhesion (cross-hatch and pull-off) class 0 required (ISO 2409)


Impact strength (1) > 1 kg / 40 cm (ISO 6272)
Mandrel bending test (2) < 10 mm (ISO 6860)
Persoz hardness 300 s (ISO 1522)
(1) No cracking of the paint film after dropping a weight of one kilogram on the test piece from a height of
50 centimetres.
(2) Film cracks over a length of 10 millimetres maximum.

Artificial ageing test on powder Test conditions:


coating Two tests carried out on the same 1 mm thick steel sheet test piece.
bb cyclical damp-heat test:
v as per standard IEC 68-2-30,
- six 24-hour cycles at temperatures higher than 40°C,
bb continuous resistance to neutral salt mist:
v the tests were carried out over a period of 400 hours, far more than the 48 hours
required by the standard for indoor installations,
v as per standard IEC 68-2-11 and ISO 7253
- 400 hours without blistering for normal surface on test piece,
- 240 hours for a scratched surface.
Evaluation of corrosion as per ISO 4628:
bb adhesion: class y 1,
bb blistering: degree 1 dim.1,
bb rusting: Ri 1,
bb cracking: class 1,
bb flaking imp. 1 dim. 1.
propagation of corrosion under scratch with respect to the scratch axis: 3 mm
max.

E-10
Characteristics Properties of metal enclosure
System L

Mechanical characteristics

Chemical properties of Tests carried out at ambient temperature on phosphated test pieces coated
powder coating with a 150 to 200 micron film.

Test duration (months) 2 4 6 8 10 12


Acids Concentration
Acetic 20 %
Sulphuric 30 %
Nitric 30 %
Phosphoric 30 %
Hydrochloric 30 %
Lactic 10 %
Citric 10 %
Bases Soda 10 %
Ammonia 10 %
Water Distilled water
Seawater
Tap water
Diluted bleach
Solvents Petrol
High alcohols
Aliphatics
Aromatics
Ketones, esters
Tri-perchlorethylene

Film intact.

Film damaged (blisters, yellowing, loss of shine).

E-11
Characteristics Environmental profile of
System L Prisma iPM switchboards
Environment

Schneider Electric is committed to a Prisma iPM has reaped the benefits of an ecological design process which has
long-term environmental policy. improved its environmental performance.
Its intention is to promote respect of all natural This committed approach, aiming to integrate environmental protection right from the
resources and to work towards constant active design phase, has been a deciding factor on different aspects:
improvement of conditions for a clean environment for bb the choice of materials used to preserve natural resources,
the satisfaction of its customers, staff and the bb use of environmentally friendly manufacturing procedures,
communities in which it is based. bb a degree of product recyclability which is well over the environmental
recommendations.

For Schneider Electric, acting responsibly as a company with regard to the


environment and on a wider scale, to society in general, contributes to performance:
bb by obtaining ISO 14001 certification for all its sites,
bb by making pertinent decisions for the long term,
bb by encouraging all its partners, in particular its suppliers and customers, to support
the initiative.

Product design Use of high-performance tools has guided the designers in the choice of
materials and has enabled them to assess the impact of the product on the
environment throughout its life-cycle.
Published on 13th February 2003 and applicable as from 1st July 2006, directive
2002 / 95 / EC concerning the restriction of use of certain dangerous substances in
electrical and electronic equipment is more commonly known as the RoHS directive
(Restriction of Hazardous Substances).

Among these substances which are considered dangerous to the environment and
health we find lead, mercury, cadmium, hexavalent chromium, polybrominated
biphenyls(1) (PBB) and polybrominated diphenyl ethers(1) (PBDE).
These six substances are banned or restricted (if exemption) in the electrical and
electronic equipment listed in the WEEE directive and replaced by more
environmentally friendly substances.

Schneider Electric products are little or only indirectly affected by this


restriction. However all low voltage products will be subject to compliance as
from December 2008.

Production Production is an important phase in the switchboard life-cycle.


Schneider Electric has adopted a dynamic, ambitious environmental policy in its
PD395023

initiative to integrate environmental protection into its industrial processes, in


particular by obtaining ISO 14001 certification for all its sites.
PD395090

(1) They are self-timer of brominated flames.

E-12
Characteristics Environmental profile of
System L Prisma iPM switchboards
Environment

Distribution The concept of a switchboard delivered in kit form, combined with particularly well
thought-out packaging has made it possible to significantly reduce volumes and
therefore limit the risks and pollution caused by transport.
PD395122

A significant reduction

PD395096
in volumes transported
With the kit system, the
products are delivered
flat-packed and are easy
to store and handle.

Optimum use of packaging


Schneider Electric complies with the packaging directive. Published for the first time
on 31st December1994, directive 94 / 62 / EC concerning packaging and packaging
waste has since been updated many times.
This directive applies to all packaging put on the market and all waste produced by it
with the aim of reducing its impact on the environment.
The obligations mainly concern reducing the volume, weight and quantity of heavy
metals used in packaging, its reuse or recovery at the end of its life and
implementation of a system for collecting packaging waste.
PD395011

Switchboard use Use of the Prisma iPM electrical switchboard is a phase of the life-cycle which
can have a significant impact on the environment.
Prisma iPM contains products in compliance with the EUP directive. Published on
22nd July 2005, directive 2005 / 32 / EC relating to ecological design requirements to
be applied to energy consuming products is more commonly known as the EUP
(Energy Using Products) directive.
The aim of this directive is to achieve a high level of environmental protection by
reducing the impact of energy consuming products and fostering acceptance of the
concept of ecological design within companies.

As the switchboard consumes electricity, a certain number of criteria have been


taken into account:
bb reducing energy consumption in the usage phase to a minimum,
bb reducing leaks and release into the environment to a minimum
bb increasing product durability,
bb easier product maintenance and repair (product reliability, product modularity,
etc).

End-of-life Schneider Electric undertakes to comply with recycling rates and to recover the
products at the end of their life. The group meets the WEEE (Waste Electrical and
Electronic Equipment) directive. Published on 13th February 2003, directive
2002 / 96 / EC concerning electrical and electronic equipment waste is more
commonly known as the WEEE directive.
PD395051

An easily-dismantled product.
The product is in kit form. All components can be
removed, which facilitates sorting the different types of
materials.

E-13
Characteristics Environmental profile of
System L Prisma iPM switchboards
(Example)
Environment

Example with a 250 A switchboard:


Design:
bb functional units:
v incomer: fixed Compact NSX 250 A circuit breaker,
v feeders: 3 rows of Multi 9 devices,
bb current distribution
v Multiclip distribution block,
bb enclosure:
v 24 module enclosure,
v 24 module transparent door.

Technical characteristics:
bb product reference standard: IEC 61439 - 1,
bb rated insulation voltage for the main busbar: Ui up to 1000 V,
bb rated operating current: In up to 630 A,
bb rated short-time withstand current: Icw up to 25 kA rms / 1s.

1 Materials used in the switchboard.


The total weight of the enclosure is 29.4kg in the following proportions:
Material Weight (kg) Percentage of the total
weight (%)
Steel 28.5 96.9
Copper 0.14 0.5
Aluminium 0.6 2
Stainless steel 0.003 0.01
Brass 0.004 0.01
Zamak 0.014 0.01
Thermoplastic 0.15 0.5
Total 29.4 100

2 Energy consumption.
The electrical energy dissipated by the 250 A switchboard depends on the operating
conditions.
The following assumptions have been chosen to calculate energy consumption:
bb annual rate of load for the equipment (Tc): 30 %,
bb estimated length of use of the equipment (d): 20 years (equivalent to
175,200 hours),
bb energy consumption for the enclosure (E): 3322.6 kWh / 20 years.

Method of calculation
If P is the power dissipated in the enclosure, energy consumption is calculated using
the following formula:
E = P x Tc x d

Prisma iPM enclosures do not contain either storage cells or batteries.

3 Packaging.
Materials used in packaging:
Materials Weight (kg) Percentage of the total
weight (%)
Cardboard 2 84
PE polyethylene 0.18 8
EPE 0.19 8
PA66 0.01 0
Total 2.38 100

Every care is taken in collaboration with our services, suppliers and subcontractors
to ensure that the packaging does not contain any substances which are forbidden
under European regulations.

E-14
Characteristics Environmental profile of
System L Prisma iPM switchboards
(Example)
Environment

4 Switchboard end-of-life management.


At the end of their service lives, the enclosures can be either dismantled or crushed
in order to make best use of the various component materials. This can take the form
of recycling or incineration.

99 % of materials used in the 250 A switchboard can be recovered by


dismantling.
This percentage includes iron and non-iron materials used in the product.

0.5 % can be incinerated, which includes the thermoplastics and thermosetting


plastics, in the knowledge that they do not contain any brominated flame retarders.

No particular precautions must be taken before crushing or dismantling unless the


enclosure is fitted with a transparent door. The glass used for this door weighs
approximately 4 kg and must be recycled separately.
PD800004

E-15
F-2
Recommendations Contents
System L

Assembling recommendations F-2


Assembling sequences F-2

Assembling tips F-8


Assemble the wall mounted enclosure Install the busbars F-8
Install the mounting plates F-9
Run and cable the power circuits F-10
Route and cable the low power and auxiliary circuits F-11
Finish and fit the switchboard with panels F-12

F-1
Recommendations Assembling sequences
System L

Assembling recommendations

8 1 8 2 4 8 7 8 8
PD800067

3 6 2 2 5 9 9 10 10

F-2
Recommendations Assembling sequences
System L

Assembling recommendations

Chronology of the opposite switchboard configuration assembly:

1 - Wall mounted enclosure structure


bb Rear panel.

2 - Mounting plates and switchgears


bb Mounting plate with NSX 400
bb Mounting plate with Compact NSX100.
bb Modular device rails.
bb Multi9 and IC devices.

3 - Distribution blocks
bb 200 A Multiclip distribution block.

4 - Cable duct association


bb Cable duct.
bb Assembly kit.

5 - Busbars
bb Vertical multi-stage busbar.

6 - Wiring trunking
bb Trunking.
bb Tunking for the fine wiring.

7 - Power cables
bb Connection devices to busbar.
bb Terminal blocks.
bb Earth / neutral bar.
bb Connection devices to terminal blocks.

8 - Wall mounted enclosure covering


bb Pillars.
bb 2 side panels.
bb Top and bottom plates.
bb Front frame.

9 - Front plates
bb Front plates.

10 - Doors
bb Transparent door.
bb Plain door.

F-3
Recommendations Assembling sequences
System L

Assembling recommendations

Preparation of the rear panel

DD800494
Install the mounting plate with its circuit breaker
DD800490

Install the modular device rail


DD800488

Install the distribution block


DD800400

Install the modular devices


DD800487

F-4
Recommendations Assembling sequences
System L

Assembling recommendations

Install the cable duct

DD800486
DD800485

DD800401
DD800484

x2

DD800402

Install the selected busbar


DD800483
DD800403

F-5
Recommendations Assembling sequences
System L

Assembling recommendations

Wiring trunking

DD800528

Power cables
Neutral bar
E56846

Earth bar
E56845

F-6
Recommendations Assembling sequences
System L

Assembling recommendations

Wall mounted enclosure covering

DD800438

DD800437
DD800436

Install the front plates


DD800482

Install the doors


DD800481

F-7
Recommendations Assemble the wall mounted
System L enclosure Install the busbars
Assembling tips

Assemble the wall mounted bb The wall mounted enclosure must be assembled
horizontally on a table that is protected to ensure the
enclosure paintwork is not damaged.
NB
The cover panels
bb The assembly is quick and reliable.
are assembled
DD800413

once the internal


components have
been mounted and
cabled, thus
guaranteeing
100 % access to
components
throughout
assembly and
installation.

Couple the enclosures bb The mounting hardware must be carefully


associated with each wall mounted enclosure.
During storage, take measures to prevent damaging
DD800088

component paintwork.

bb Do not use the pillars to handle the rear panel of the


wall mounted enclosure.
Take care to ensure the enclosure rear panel remains
level during cabling operations.

IP30 / 31 / 40 combination kit.


DD800118

IP54 combination kit.

Install the busbar bb Busbar overall dimensions do not vary with current
strength. NB
If cutting oil is used,
DD800018

bb Whatever the busbar type, the order of the bars is the busbars must
always the same: from the front to the rear N, L1, L2 be cleaned prior to
and L3. assembly as oil
adversely affects
bb With the rear busbar, the Neutral is to the left, then insulation
L1, L2, L3. properties.

F-8
Recommendations Install the mounting plates
System L

Assembling tips

Install the mounting plates bb The order of assembly of the mounting plates and devices depends on the
technical features of the devices.
DD800414

bb To define the position of a mounting plate of a functional unit, you need to know the
overall dimensions of the functional unit (H), i.e. the number of modules
(1 module = 50 mm). This number is given in the functional unit pages catalogue.
The reference starting point for the installation of the mounting plate (b) is given in
the leaflets.

Assemble order bb Table showing the assembly order according to the device type:
Device Assembly order
EasyPact CVS and Compact NSX, Interpact bb Place the device on the mounting plate.
INS and Easypact EZC and EZC y 630 A bb Install the equipped mounting plate.
DD800415

Modular devices bb Install the rail system.


bb Place the modular devices on the rail.
DD800416

Checking switchgear position bb This operation allows operators inspection and prevents incorrect positioning of
the functional unit with respect to the front panel, before the wall mounted enclosure
has been cabled.
DD800495

F-9
Recommendations Run and cable the power circuits
System L

Assembling tips

Installing the secondary bb You need to comply with connection capacities, stripping lengths, the number of
cables connected and use the appropriate tools.
distribution blocks
bb Do not use ferrules with the spring loaded terminals. Each terminal may only take
a single wire.

bb On the Multiclip 200 A, cable entry is via the bottom only to allow assembly of the
insulating covers and production of cable straps.

bb Table showing the connections of the distribution blocks:


Type Connection capacity Connection principle
Distribloc(1) b Power supply

DD800421
DD800417

DD800420
b Distribution

DD800422
Polybloc b Distribution
DD800426
DD800427

DD800422
Multi-stage current distribution block b Power supply

DD800425
DD382813

Multiclip 200 A (1) b Power supply


DD800419
DD382235
DD800418

b Distribution
DD800423

Comb busbar b Power supply


DD800424

DD800428

(1) The downstream device connecting cables are delivered with the Multiclip and Distribloc.

F-10
Recommendations Route and cable the low power
System L and auxiliary circuits
Assembling tips

Install the devices on door or bb Human switchboard interface with 72 x 72 mm,


96 x 96 mm, diameter 22 mm, lighting, push-button,
front plate etc.
NB
The devices can be
installed on
DD800013

conventional plain
doors by making a
cut-out.

Cabling the auxiliary circuits bb We recommend that you use protection devices for
wiring through uprights or to doors
NB
DD800430

Thoroughly secure
bb Mark the wires to simplify on-site connection and
cables onto the
maintenance of wall mounted enclosures, thus
door to avoid
avoiding laborious switchboard reworking that could
disconnecting the
cause errors.
devices when
opening.
We recommend
you use protection
devices for wiring
through the front
panel or to the
doors.

F-11
Recommendations Finish and fit the switchboard
System L with panels
Assembling tips

Labelling and marking bb Device marking: this enables users of the system to
identify clearly the various circuits involved. Marking
should be fully legible, durable and properly attached to
DD800190

the device.

bb Inside the switchboard: marking identifies the NB


E20578

devices, thus avoiding all risk of confusion when Barriers preventing


working inside the switchboard access to live parts
should be marked
with a “DANGER”
sign.
DD382180

Fitting the switchboard bb When the doors are fitted, for safety reasons, ensure
that the door opening direction will not obstruct on site NB
access to an evacuation corridor or passageway. The
DD800431

Take care to
door must open in the direction of the evacuation. degrease surfaces
thoroughly before
bb It is advisable to install barrels and inserts before sticking on the
fitting the handle on the door and before installation on gaskets.
the wall mounted enclosure.

F-12
Notes

F-13
Notes

F-14
ART.838787 © 2018 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS


35, rue Joseph Monier As standards, specifications and designs change from time to time, please ask for confirmation
CS 30323 of the information given in this publication.
F - 92506 Rueil Malmaison Cedex
This document has been printed on ecological paper.
RCS Nanterre 954 503 439
Capital social 896 313 776 € Design: Schneider Electric
www.schneider-electric.com Photos: Schneider Electric
Publishing: Altavia Connexion

LVED210001EN 02-2018