CAPACITOR SIZE CALCULATIONS
APPD
Contractor's Consultants CODE REV.
DOCUMENT No. KKSIL/SINIGURALI/STP-11/3A/E03
R0
Unique Consultants

RELEASED FOR P PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION


: DOCUMENT NO REV DATE
PROJECT 11 MLD STP AT SINGURALI
KKSIL/SINGURALI/STP-11/E-03 R0 04/11/2018
: PREPARED CHECKED APPROVED SHEET
TITLE Capacitor Size Calculations
AD AB

1 Total load on transformer in kW = 484.04 kW

2 Total load on transformer in kVA = 408.60 KVA

3 System power factor (Cos Ø1 = kW/kVA)) = 0.80

4 Reactive power absorbed (kVA x sin Ø1) = 245.16 KVAr1

5 Improved power factor (Cos Ø2) = 0.98

6 Reactive power at improved power factor (kW x tan Ø2) = 98.29 KVAr2

7 Capacitor bank required (KVAr1-kVAr2) = 146.87 kVAr

Selected capacitor bank = 150.00 kVAr