DATE : 01/03/2016 REV : 0

DESIGN CRITERIA &


HYDRAULIC CALCULATIONS

•FOAM WATER DELUGE SYSTEM


HIGH EXPANSION FOAM FOR
WAREHOUSE (NO.09)

… for

AL JABR TALKE MULTI USER


LOGISTICS FACILITY
WAREHOUSE (NO.09)
DESIGN CRITERIA & CALCULATIONS
AL JABR TALKE MULTI USER
LOGISTICS FACILITY
WAREHOUSE (NO.09)

FOAM WATER DELUGE SYSTEM

HIGH EXPANSION FOAM FOR

WAREHOUSE (NO.09)

HYDRAULIC CALCULATION
REPORT
DESIGN CRITERIA & CALCULATIONS
AL JABR TALKE MULTI USER
LOGISTICS FACILITY
WAREHOUSE (NO.09)

Design Criteria for Deluge Foam System

DESCRIPTION Calculation

1 Room / Area Name WAREHOUSE (NO.09)

2 Design Standard NFPA - 11

3 Type of System Foam – Water Deluge System


Minimum Flow Rate Required (243 gpm)
4 Per Foam Generator. (Manufacturer recommended)
Total number of Foam
5 Generator 15 nos.
Minimum End Head Pressure 6.20 bar
6 Required (Manufacturer recommended)
7 Pressure Setting of the PRV 9.0 bar (130 psi)
Minimum Foam Discharge
8 Duration 15 minutes
Foam Concentrate Type and
9 Percentage AR -AFFF, 2%
Friction Loss Coefficient
10 Galvanized = 120
(Hazen-Williams Value, C)

CALCULATION SUMMARY

Total Flow at Point of Connection : (2429 gpm)

Pressure at connection point :9.0 bar

Foam Generator min residual pressure : 6.2 bar

(manufacture recommended)

Foam Minimum Discharge Duration : 15 mins

FOAM QUANTITY :2429X0.02X15min : 729 gallons

Bladder Tank Capacity : 900 gallons


AL JABR TALKE MULTI USER
Fire Hose System Reports

for

WAREHOUSE (NO.09)

Prepared By:

ACTIVE

2/27/2016
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 2

General Project Data Report

General Data
Project Title: AL JABR TALKE MULTI USER Project File Name: WARE HOUSE .09..fiw
Designed By: ACTIVE Date: 2/27/2016
Code Reference: NFPA 11 Approving Agency:
Client Name: WAREHOUSE (NO.09) Phone:
Address: City, State Zip Code:
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: Building Owner:
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Ex. Haz. Gp. 1 Hose System Type: Wet
Design Area Of Water Application: 21528 ft² Maximum Area Per Hose: 2153 ft²
Default Hose K-Factor: 25.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Hose Specifications
Make: TOP ROOF Model: FOAM GENERATOR
Size: 2" Temperature Rating: 0 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 2429.39 gpm Calculated Inflow Residual Pressure: 130.66 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 89.92 psi Minimum Desired Flow Density: 0.10 gpm/ft²
Number Of Active Nodes: 36
Number Of Active Pipes: 35 Number Of Inactive Pipes: 0
Number Of Active Hoses: 1 Number Of Inactive Hoses: 0

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 3

Fire Hose Input Data

Node Input Data


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Hose ---- 25.60 89.92 33.79 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 90.32 33.79 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 93.18 27.89 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 88.00 38.39 243.00


4
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 88.40 38.39 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 93.33 27.89 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 87.22 41.67 243.00


7
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 87.62 41.67 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 94.04 27.89 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 90.93 36.75 243.00


10
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 91.33 36.75 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 95.52 27.89 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 94.95 33.46 243.00


13
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 95.35 33.46 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 98.06 27.89 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 103.56 27.89 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 94.68 33.46 243.00


17
---- 0.000 0.0 ---- 0.0 0.00

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 4

Fire Hose Input Data

Node Input Data (cont'd)


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 95.10 33.46 0.00


18
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 97.81 27.89 0.00


19
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 90.67 36.75 243.00


20
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 91.08 36.75 0.00


21
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 95.27 27.89 0.00


22
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 86.95 41.67 243.00


23
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 87.37 41.67 0.00


24
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 93.78 27.89 0.00


25
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 87.73 38.39 243.00


26
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 88.15 38.39 0.00


27
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 93.08 27.89 0.00


28
---- 0.000 0.0 ---- 0.0 0.00

Fixed ---- N/A 89.65 33.79 243.00


29
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 90.07 33.79 0.00


30
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 92.93 27.89 0.00


31
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 105.54 27.89 0.00


32
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 121.36 1.64 0.00


33
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 126.34 1.64 0.00


34
---- 0.000 0.0 ---- 0.0 0.00

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 5

Fire Hose Input Data

Node Input Data (cont'd)


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 129.56 -3.28 0.00


35
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 130.66 -3.28 0.00


36
---- 0.000 0.0 ---- 0.0 0.00

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 6

Fire Hose Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 2 SCHED 40 WET STEEL 4.000 0 21.33 0.00 21.33 120

2 3 SCHED 40 WET STEEL 4.000 0 E 5.91 10.00 15.91 120

3 6 SCHED 40 WET STEEL 6.000 0 E 45.93 14.00 59.93 120

4 5 SCHED 40 WET STEEL 4.000 0 21.33 0.00 21.33 120

5 6 SCHED 40 WET STEEL 4.000 0 E 10.50 10.00 20.50 120

6 9 SCHED 40 WET STEEL 6.000 0 T 45.93 30.00 75.93 120

7 8 SCHED 40 WET STEEL 4.000 0 21.33 0.00 21.33 120

8 9 SCHED 40 WET STEEL 4.000 0 E 13.78 10.00 23.78 120

9 12 SCHED 40 WET STEEL 6.000 0 T 45.93 30.00 75.93 120

10 11 SCHED 40 WET STEEL 4.000 0 21.33 0.00 21.33 120

11 12 SCHED 40 WET STEEL 4.000 0 E 8.86 10.00 18.86 120

12 15 SCHED 40 WET STEEL 6.000 0 T 45.93 30.00 75.93 120

13 14 SCHED 40 WET STEEL 4.000 0 21.33 0.00 21.33 120

14 15 SCHED 40 WET STEEL 4.000 0 E 5.58 10.00 15.58 120

15 16 SCHED 40 WET STEEL 6.000 0 ET 64.96 44.00 108.96 120

29 30 SCHED 40 WET STEEL 4.000 0 21.98 0.00 21.98 120

30 31 SCHED 40 WET STEEL 4.000 0 E 5.91 10.00 15.91 120

31 28 SCHED 40 WET STEEL 6.000 0 E 45.93 14.00 59.93 120

26 27 SCHED 40 WET STEEL 4.000 0 21.98 0.00 21.98 120

27 28 SCHED 40 WET STEEL 4.000 0 E 10.50 10.00 20.50 120

28 25 SCHED 40 WET STEEL 6.000 0 T 45.93 30.00 75.93 120

23 24 SCHED 40 WET STEEL 4.000 0 21.98 0.00 21.98 120

24 25 SCHED 40 WET STEEL 4.000 0 E 13.78 10.00 23.78 120

25 22 SCHED 40 WET STEEL 6.000 0 T 45.93 30.00 75.93 120

20 21 SCHED 40 WET STEEL 4.000 0 21.98 0.00 21.98 120

21 22 SCHED 40 WET STEEL 4.000 0 E 8.86 10.00 18.86 120

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 7

Fire Hose Input Data

Pipe Input Data (cont'd)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

22 19 SCHED 40 WET STEEL 6.000 0 T 45.93 30.00 75.93 120

17 18 SCHED 40 WET STEEL 4.000 0 21.98 0.00 21.98 120

18 19 SCHED 40 WET STEEL 4.000 0 E 5.58 10.00 15.58 120

19 16 SCHED 40 WET STEEL 6.000 0 ET 69.88 44.00 113.88 120

16 32 SCHED 40 WET STEEL 8.000 0 T 6.56 35.00 41.56 120

32 33 SCHED 40 WET STEEL 8.000 0 EGC 26.25 67.00 93.25 120

33 34 SCHED 40 WET STEEL 8.000 0 EGC 37.07 67.00 104.07 120

34 35 SCHED 40 WET STEEL 8.000 0 E 4.92 18.00 22.92 120

35 36 SCHED 40 WET STEEL 8.000 0 E 4.92 18.00 22.92 120

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 8

Fire Hose Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -242.78 242.75 0.00 0.00 89.92

2 1 0 242.78 0.00 0.00 0.00 90.32 0.07910


2 3 0 -242.70

3 2 0 242.70 0.00 0.00 0.00 93.18 0.00421


3 6 0 -242.70

4 5 0 -242.95 0.00 243.00 0.00 88.00 0.05126

5 4 0 242.95 0.00 0.00 0.00 88.40 0.00565


5 6 0 -242.94

6 3 0 242.70 0.00 0.00 0.00 93.33 -0.02837


6 5 0 242.94
6 9 0 -485.67

7 8 0 -242.95 0.00 243.00 0.00 87.22 0.04969

8 7 0 242.95 0.00 0.00 0.00 87.62 -0.00889


8 9 0 -242.96

9 6 0 485.67 0.00 0.00 0.00 94.04 -0.01705


9 8 0 242.96
9 12 0 -728.64

10 11 0 -242.97 0.00 243.00 0.00 90.93 0.03420

11 10 0 242.97 0.00 0.00 0.00 91.33 -0.00024


11 12 0 -242.97

12 9 0 728.64 0.00 0.00 0.00 95.52 0.00675


12 11 0 242.97
12 15 0 -971.60

13 14 0 -242.97 0.00 243.00 0.00 94.95 0.03420

14 13 0 242.97 0.00 0.00 0.00 95.35 -0.00061


14 15 0 -242.97

15 12 0 971.60 0.00 0.00 0.00 98.06 0.01138


15 14 0 242.97
15 16 0 -1214.56

16 15 0 1214.56 0.00 0.00 0.00 103.56 -0.01964


16 19 0 1214.80
16 32 0 -2429.38

17 18 0 -242.97 0.00 243.00 0.00 94.68 0.03426

18 17 0 242.97 0.00 0.00 0.00 95.10 -0.00067

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 9

Fire Hose Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
18 19 0 -242.97

19 16 0 -1214.80 0.00 0.00 0.00 97.81 0.01180


19 18 0 242.97
19 22 0 971.85

20 21 0 -242.97 0.00 243.00 0.00 90.67 0.03426

21 20 0 242.97 0.00 0.00 0.00 91.08 -0.00030


21 22 0 -242.97

22 19 0 -971.85 0.00 0.00 0.00 95.27 0.01481


22 21 0 242.97
22 25 0 728.90

23 24 0 -242.94 0.00 243.00 0.00 86.95 0.05778

24 23 0 242.94 0.00 0.00 0.00 87.37 -0.00021


24 25 0 -242.94

25 22 0 -728.90 0.00 0.00 0.00 93.78 -0.07637


25 24 0 242.94
25 28 0 485.88

26 27 0 -242.95 0.00 243.00 0.00 87.73 0.05134

27 26 0 242.95 0.00 0.00 0.00 88.15 -0.00020


27 28 0 -242.95

28 25 0 -485.88 0.00 0.00 0.00 93.08 0.02102


28 27 0 242.95
28 31 0 242.95

29 30 0 -242.95 0.00 243.00 0.00 89.65 0.05134

30 29 0 242.95 0.00 0.00 0.00 90.07 -0.00088


30 31 0 -242.95

31 28 0 -242.95 0.00 0.00 0.00 92.93 -0.00183


31 30 0 242.95

32 16 0 2429.38 0.00 0.00 0.00 105.54 0.01522


32 33 0 -2429.37

33 32 0 2429.37 0.00 0.00 0.00 121.36 0.00204


33 34 0 -2429.37

34 33 0 2429.37 0.00 0.00 0.00 126.34 -0.02864


34 35 0 -2429.39

35 34 0 2429.39 0.00 0.00 0.00 129.56 -0.00005


35 36 0 -2429.39

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 10

Fire Hose Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

36 35 0 2429.39 0.00 0.00 -2429.39 130.66

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 11

Fire Hose Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 25.60 33.79 242.75 89.92 4.00 242.75 0.01888 21.33 0.403


2 0.00 33.79 0.00 90.32 4.026 242.78 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.33 0.403

2 0.00 33.79 0.00 90.32 4.00 0.00 0.01886 5.91 0.300


3 0.00 27.89 0.00 93.18 4.026 242.70 E 10.00 2.557
SCHED 40 WET STEEL 120 6.12 0 15.91 2.857

4 0.00 38.39 243.00 88.00 4.00 243.00 0.01890 21.33 0.403


5 0.00 38.39 0.00 88.40 4.026 242.95 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.33 0.403

3 0.00 27.89 0.00 93.18 6.00 0.00 0.00256 45.93 0.154


6 0.00 27.89 0.00 93.33 6.065 242.70 E 14.00 0.000
SCHED 40 WET STEEL 120 2.70 0 59.93 0.154

5 0.00 38.39 0.00 88.40 4.00 0.00 0.01890 10.50 0.387


6 0.00 27.89 0.00 93.33 4.026 242.94 E 10.00 4.546
SCHED 40 WET STEEL 120 6.12 0 20.50 4.933

7 0.00 41.67 243.00 87.22 4.00 243.00 0.01890 21.33 0.403


8 0.00 41.67 0.00 87.62 4.026 242.95 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.33 0.403

6 0.00 27.89 0.00 93.33 6.00 0.00 0.00925 45.93 0.703


9 0.00 27.89 0.00 94.04 6.065 485.67 T 30.00 0.000
SCHED 40 WET STEEL 120 5.39 0 75.93 0.703

8 0.00 41.67 0.00 87.62 4.00 0.00 0.01890 13.78 0.449


9 0.00 27.89 0.00 94.04 4.026 242.96 E 10.00 5.967
SCHED 40 WET STEEL 120 6.12 0 23.78 6.416

10 0.00 36.75 243.00 90.93 4.00 243.00 0.01890 21.33 0.403


11 0.00 36.75 0.00 91.33 4.026 242.97 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.33 0.403

9 0.00 27.89 0.00 94.04 6.00 0.00 0.01960 45.93 1.488


12 0.00 27.89 0.00 95.52 6.065 728.64 T 30.00 0.000
SCHED 40 WET STEEL 120 8.09 0 75.93 1.488

11 0.00 36.75 0.00 91.33 4.00 0.00 0.01890 8.86 0.356


12 0.00 27.89 0.00 95.52 4.026 242.97 E 10.00 3.836
SCHED 40 WET STEEL 120 6.12 0 18.86 4.192

13 0.00 33.46 243.00 94.95 4.00 243.00 0.01890 21.33 0.403


14 0.00 33.46 0.00 95.35 4.026 242.97 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.33 0.403

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 12

Fire Hose Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

12 0.00 27.89 0.00 95.52 6.00 0.00 0.03338 45.93 2.535


15 0.00 27.89 0.00 98.06 6.065 971.60 T 30.00 0.000
SCHED 40 WET STEEL 120 10.79 0 75.93 2.535

14 0.00 33.46 0.00 95.35 4.00 0.00 0.01890 5.58 0.294


15 0.00 27.89 0.00 98.06 4.026 242.97 E 10.00 2.415
SCHED 40 WET STEEL 120 6.12 0 15.58 2.709

15 0.00 27.89 0.00 98.06 6.00 0.00 0.05045 64.96 5.497


16 0.00 27.89 0.00 103.56 6.065 1214.56 ET 44.00 0.000
SCHED 40 WET STEEL 120 13.49 0 108.96 5.497

19 0.00 27.89 0.00 97.81 6.00 0.00 0.05047 69.88 5.748


16 0.00 27.89 0.00 103.56 6.065 1214.80 ET 44.00 0.000
SCHED 40 WET STEEL 120 13.49 0 113.88 5.748

17 0.00 33.46 243.00 94.68 4.00 243.00 0.01890 21.98 0.416


18 0.00 33.46 0.00 95.10 4.026 242.97 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.98 0.416

18 0.00 33.46 0.00 95.10 4.00 0.00 0.01890 5.58 0.294


19 0.00 27.89 0.00 97.81 4.026 242.97 E 10.00 2.415
SCHED 40 WET STEEL 120 6.12 0 15.58 2.709

22 0.00 27.89 0.00 95.27 6.00 0.00 0.03340 45.93 2.536


19 0.00 27.89 0.00 97.81 6.065 971.85 T 30.00 0.000
SCHED 40 WET STEEL 120 10.79 0 75.93 2.536

20 0.00 36.75 243.00 90.67 4.00 243.00 0.01890 21.98 0.416


21 0.00 36.75 0.00 91.08 4.026 242.97 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.98 0.416

21 0.00 36.75 0.00 91.08 4.00 0.00 0.01890 8.86 0.356


22 0.00 27.89 0.00 95.27 4.026 242.97 E 10.00 3.836
SCHED 40 WET STEEL 120 6.12 0 18.86 4.192

25 0.00 27.89 0.00 93.78 6.00 0.00 0.01962 45.93 1.489


22 0.00 27.89 0.00 95.27 6.065 728.90 T 30.00 0.000
SCHED 40 WET STEEL 120 8.09 0 75.93 1.489

23 0.00 41.67 243.00 86.95 4.00 243.00 0.01890 21.98 0.415


24 0.00 41.67 0.00 87.37 4.026 242.94 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.98 0.415

24 0.00 41.67 0.00 87.37 4.00 0.00 0.01890 13.78 0.449


25 0.00 27.89 0.00 93.78 4.026 242.94 E 10.00 5.967
SCHED 40 WET STEEL 120 6.12 0 23.78 6.416

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 13

Fire Hose Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

28 0.00 27.89 0.00 93.08 6.00 0.00 0.00926 45.93 0.703


25 0.00 27.89 0.00 93.78 6.065 485.88 T 30.00 0.000
SCHED 40 WET STEEL 120 5.40 0 75.93 0.703

26 0.00 38.39 243.00 87.73 4.00 243.00 0.01890 21.98 0.415


27 0.00 38.39 0.00 88.15 4.026 242.95 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.98 0.415

27 0.00 38.39 0.00 88.15 4.00 0.00 0.01890 10.50 0.387


28 0.00 27.89 0.00 93.08 4.026 242.95 E 10.00 4.546
SCHED 40 WET STEEL 120 6.12 0 20.50 4.933

31 0.00 27.89 0.00 92.93 6.00 0.00 0.00257 45.93 0.154


28 0.00 27.89 0.00 93.08 6.065 242.95 E 14.00 0.000
SCHED 40 WET STEEL 120 2.70 0 59.93 0.154

29 0.00 33.79 243.00 89.65 4.00 243.00 0.01890 21.98 0.415


30 0.00 33.79 0.00 90.07 4.026 242.95 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.12 0 21.98 0.415

30 0.00 33.79 0.00 90.07 4.00 0.00 0.01890 5.91 0.301


31 0.00 27.89 0.00 92.93 4.026 242.95 E 10.00 2.557
SCHED 40 WET STEEL 120 6.12 0 15.91 2.858

16 0.00 27.89 0.00 103.56 8.00 0.00 0.04778 6.56 1.986


32 0.00 27.89 0.00 105.54 7.981 2429.38 T 35.00 0.000
SCHED 40 WET STEEL 120 15.58 0 41.56 1.986

32 0.00 27.89 0.00 105.54 8.00 0.00 0.04778 26.25 4.456


33 0.00 1.64 0.00 121.36 7.981 2429.37 EGC 67.00 11.365
SCHED 40 WET STEEL 120 15.58 0 93.25 15.820

33 0.00 1.64 0.00 121.36 8.00 0.00 0.04778 37.07 4.973


34 0.00 1.64 0.00 126.34 7.981 2429.37 EGC 67.00 0.000
SCHED 40 WET STEEL 120 15.58 0 104.07 4.973

34 0.00 1.64 0.00 126.34 8.00 0.00 0.04778 4.92 1.095


35 0.00 -3.28 0.00 129.56 7.981 2429.39 E 18.00 2.131
SCHED 40 WET STEEL 120 15.58 0 22.92 3.226

35 0.00 -3.28 0.00 129.56 8.00 0.00 0.04778 4.92 1.095


36 0.00 -3.28 0.00 130.66 7.981 2429.39 E 18.00 0.000
SCHED 40 WET STEEL 120 15.58 0 22.92 1.095

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 14

Fire Hose Output Data

Overall Hose Output Data


Flowing Node Residual Flowing Hose
Area Group Hose Flowing Area
Hose Node Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
No. (feet) (psi) (gpm/ft²) (gpm)

1 25.60 33.79 89.92 2152.78 0.113 242.75


Sub Totals For Non-Group 2152.78 0.113 242.75

Totals For All Groups 2152.78 0.113 242.75

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 15

Fire Hose Output Summary

Hydraulically Most Demanding Hose Node


HMD Hose Node Number: 1
HMD Actual Residual Pressure: 89.92 psi
HMD Actual GPM: 242.75 gpm

Hose Summary
Hose System Type: Wet
Specified Area Of Application: 21527.83 ft²
Minimum Desired Density: 0.100 gpm/ft²
Application Average Density: 0.011 gpm/ft²
Application Average Area Per Hose: 21527.83 ft²
Hose Flow: 242.75 gpm
Average Hose Flow: 242.75 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 35 - 36 ) 15.58 ft/sec
Maximum Velocity Pressure ( In Pipe 35 - 36 ) 1.63 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0071 psi
Actual Average Nodal Pressure Imbalance: 0.0013 psi
Actual Maximum Nodal Flow Imbalance: 0.0791 gpm
Actual Average Nodal Flow Imbalance: 0.0210 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 35
Number Of Flowing Hoses: 1

Pipe System Water Volume: 1163.24 gal

Hose Flow: 242.75 gpm


Fixed Flow: 2187.00 gpm

Minimum Required Residual Pressure At System Inflow


130.66 psi
Node:
Demand Flow At System Inflow Node: 2429.39 gpm

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr AL JABR TALKE MULTI USER
Hell Page 16

Fire Hose Output Data

Hydraulic Supply/Demand Graph

200

180

160

140
131
Pressure psi

120

100

80

60

40

20

0
3 6 9 12 15 18 21 24 27 30
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 130.66 psi
Calculated Flow Rate: 2429.39 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 16.05 psi

C:\Users\prjdsgn2\Desktop\WARE HOUSE .09..fiw Tuesday, March 01, 2016, 12:47 PM

You might also like