Your system for fire detection, alarming, Application: complex building Application: extensive campus

and control: Cerberus PRO Network in a complex building, for example a university. Very large network spanning large distances, for example for a university campus.

Danger
Remote access management
with Cerberus- system from
Remote Customer network Ethernet Siemens

Security module
(firewall)
FN2009-A1

Security module
(firewall)
FN2009-A1

Ethernet switch
FN2008-A1 Backbone (C-WEB/LAN)
Ethernet switch Ethernet switch Ethernet switch
FN2008-A1 FN2008-A1 FN2008-A1

Manual call
point
FDM221

Alarm C-NET Fire control


sounder
FDS221 Fire control panel Fire control panel panel
FC722 FC722 FC724

Cluster (C-WEB/SAFEDLINK)
Sounder base Floor repeater Fire control panel
DBS720 terminal FT2010 FC726
Fire terminal
FT724

Heat detector
HI722 (max) Fault transmission

Input module
Alarm transmission FDCI222
Floor repeater
www.siemens.com/cerberus Smoke display FT2011
detector
OP720
Fire control panel Heat detector
C-NET ASA neural FC724 HI720

Cerberus PRO – panels, Alarm


sounder beacon
FDS229-R
Input/output
module
FDCIO222
Multi-sensor
fire detector
OH720
LaserFOCUS
fire detector
OOH740

ASA neural fire


(max + RoR)

Stub line
Description
In complex buildings, the fire safety system can
be adapted to the building structure. The control
Benefits
– Only one remote transmission to fire brigade
for entire system necessary
– Timely hand-over due to parallel commissioning
of individual panels or clusters
Description
A campus comprises different, independent
buildings. These have their own organization
Benefits
– Smartly arranged network structure with clear
clusters
– Distributed intelligence: A cluster maps entire
fire control; this enables ideal adaptation to
C-NET
network, and accessories
VLF-500 and CO detector panels as well as fire terminals are networked via – One interface to common pager system – Distributed intelligence: A cluster maps entire and structure that can be mapped ideally with – Only one control panel necessary to access structural and process conditions
OOHC740
clusters (C-WEB/SAFEDLINK) with each other. – Visibility of entire system from any, configured fire control; this enables ideal adaptation to a cluster of up to 16 panels. The backbone entire system with all subnets – Security personnel has entire campus in view
Smoke detector
DO1101A-Ex These clusters are connected via industrial LAN terminal structural as well as process requirements connects these clusters to a common, EN 54- – Backbone is EMC-protected and EN 54 conform – The right information at the right place:
Extinguishing Smoke technology per backbone (C-WEB/LAN) to an – Fiber-optic backbone with high immunity conform network. – Commissioning is possible at several places Predefined views can be displayed according
control unit XC10 detector Safety barrier Flame detector
OP720 SB3 FDF241-9
EN 54-conform overall system. against electromagnetic disturbances simultaneously (gain in time) to customer requirements over the entire
Planning Tool – System-wide EN 54-conform operation – Only one central connection to pager system
for entire system
system; all controls can be configured to spe-
cific requirements

ASA neural Multi-sensor Sinorix Manual call Input/output Linear Mimic


fire detector smoke detector extinguishing point module “transponder” smoke detector display driver
Manual release OOH740 OH320C solution FDM223 FDCIO223 FDL241-9 FT2001-A1

Backbone (C-WEB/LAN) Backbone (C-WEB/LAN)


Answers for infrastructure. Cluster (C-WEB/SAFEDLINK) Cluster (C-WEB/SAFEDLINK)

www.siemens.com/cerberus

Topology 1 Topology 2 Topology 3


Up to 16 panels can be networked in a cluster (C-WEB/SAFEDLINK) – if connected Up to 64 panels in one EN 54-conform system with different combinations Using a customer network to transmit relevant information from several localities
safe, and secure buildings and infrastructure.” of users. Also, our need for safety and security is constantly to a danger management system. Without a danger management system, even up to of clusters and backbone – and with connection to a danger management system to one central danger management station.
“We are the preferred partner for energy-efficient, In addition, we need to increase comfort for the well-being
has top priority – and not only where energy is concerned.
32 panels can be networked. via a customer network.
answers. warming, and resource shortages. Maximum efficiency
well they manage these challenges. Siemens has the in new ways: demographic change, urbanization, global
growing. For our customers, success is defined by how Our world is undergoing changes that force us to think Danger Danger
Answers for infrastructure. Remote access management management
with Cerberus- system from
Remote Customer network Ethernet Siemens
system from
Siemens

Danger
management
© Siemens Switzerland Ltd, 2011 • Order no. 0-92254-en • 0,551105 system from
Siemens
be specified in each individual case at the time of closing the contract.
which do not always have to be present in individual cases. The required features should therefore
Backbone (C-WEB/LAN)
The information in this document contains general descriptions of technical options available, Ethernet Ethernet
Customer network
Ethernet
Tel +41 41 724 24 24
Switzerland
6301 Zug Without connection to
a danger management
Gubelstrasse 22 system: up to 32 panels
International Headquarters can be networked in a
cluster.
Building Technologies Division
Industry Sector
Siemens Switzerland Ltd
Cluster Fault transmission
Cluster Cluster Cluster Cluster
(C-WEB/SAFEDLINK) (C-WEB/SAFEDLINK) (C-WEB/SAFEDLINK) (C-WEB/SAFEDLINK) (C-WEB/SAFEDLINK)
Alarm transmission

Fault transmission Fault transmission Fault transmission

Alarm transmission Alarm transmission Alarm transmission

Characteristics of topology example Key data Characteristics of topology example Key data Characteristics of topology example Key data
– Easy networking of panels – Max. number of networkable panels: 32 – EN 54-conform networking of up to 64 panels – Max. number of networkable panels – Connecting independent locations via IT – Max. number of networkable panels
– Operation of panels as stand-alone solution or – Max. number of networkable panels if via backbone incl. clusters (EN 54 conform): 64 network provided by your customer with a per cluster: 16
networked with a total length of up to 460 km connected to a danger management – Very large networks spanning long distances – Max. number of clusters: 14 danger management station
– Data rate can be adapted to line quality system: 16 – Highest system availability thanks to system- – Max. number of networkable panels – Reduced installation or maintenance costs The maximum number of additional clusters,
– Max. distance between panels with wide redundancy per cluster: 16 thanks to usage of customer networks panels or data points depends on the
copper cable: – Panels on different clusters can communicate – Number of panels with system-wide view: 5* – Autonomous clusters with their own remote management station.
• without repeater: 1,000 m with each other transmission to fire brigade (to fulfill EN 54
• with repeater: 2,000 m – Only one remote transmission to fire brigade * and more with respective system topology regulations)
– Max. distance between panels with over entire system necessary
fiber-optic cable: – Distributed building complexes can be ideally
• multi mode: 2,500 m protected
• single mode: 15,000 m – Backbone is realized with fiber-optic cable
– Max. number of panels with
system-wide view: 5
Cerberus PRO Planning Tool – panels, network, and accessories
Answers for infrastructure.

Danger management system Network components Housings Expansion options


The danger management system from Siemens is either directly
To enable remote operation with Cerberus-Remote, Customer network Ethernet connected to the backbone (via Ethernet switch) or via the customer Backbone Housing (Eco) FH7201-Z3 Loop extension (C-NET) FCI2003-A1
the PC has to be connected to an Ethernet switch of network by using additional security modules. Each station that is – Max. battery capacity: 2x7 Ah The loop extension makes it possible to double the
the backbone. Access to a certain panel in a cluster Security to be addressed by the danger management system must be released Security module (firewall) FN2009-A1 Ethernet switch FN2008-A1 – 430x398x80 mm (WxHxD) number of loops (e.g. from 2 loops to 4 loops or
will be granted by installing an L1 license key into module by means of the license key (L2). Protects devices and networks in auto- The Ethernet switch connects clusters – Optional: from 4 loops to 8 loops) while retaining a constant
this panel. (firewall) mation and industrial communication with the backbone. To answer special • Power supply kit (70 W) FP2003-A1 total number of addresses on the C-NET line card
FN2009-A1 with a combination of different security requirements regarding redundancy, • Event printer FTO2001-A1 (e.g. 2 loops with 126 addresses each or 4 loops
Remote access with measures such as firewall and VPN a cluster with a second panel and a • Operating add-on (2xLED-ind.) FCM7211-Y3 with 63 addresses each).
Cerberus-Remote (Virtual Private Network) via IPsec second switch to the backbone can be • Operating add-on (4xLED-ind.) FCM7212-Y3
Security Art. no.: A5Q00010136
module tunnel: added. Art. no.: S54400-B72-A1
(firewall) – data espionage For example for:
FN2009-A1 – data manipulation – Cluster with more than 512 detectors/ RS232 module (isolated) FCA2001-A1
– unauthorized access manual call points Housing (Standard) FH7202-Z3 This module is needed, for example, for operating
Art. no.: S54400-F95-A1 – Cluster with remote transmission in – Max. battery capacity: 2x26 Ah an event printer. It is plugged into the PMI main-
systems with more than 512 detectors – 430x398x160 mm (WxHxD) board. The RS232 module is not contained in the
Backbone Fire control panel FC724-ZA Fire control panel FC724-ZE Fire control panel FC722-ZZ Fire control panel FC722-YZ
The security module can be easily
integrated into a panel with: – Managed Ethernet switch – Optional:
• Power supply kit (70 W) FP2003-A1 or
set for the event printer.
– FHA2029-A1 (S54400-B79-A1) – 4x10/100 Mbit/s RJ45 connections Art. no.: A5Q00005327
(C-WEB/LAN) Ethernet switch
FN2008-A1 consisting of: consisting of: consisting of: consisting of: for housing (Comfort) – 2x100 Mbits/s multi-mode BFOC
– LED diagnosis
• Power supply kit (150 W) FP2004-A1 or
additional power supply (150 W) FP2005-A1
Control unit Control unit Control unit Control unit – FHA2030-A1 (S54400-B81-A1)
• Event printer FTO2001-A1 RS485 module (isolated) FCA2002-A1
Clusters can be networked via an Ethernet back- – Optional: – 48 display groups each with one – Optional: – 24 display groups each with for housing (Large Extension) Art. no.: S54400-F94-A1
• Operating add-on (2xLED-ind.) FCM7211-Y3 This is needed, for example, for operating the
bone, using industrial LAN technology. Siemens is • Event printer FTO2001-A1 red and one yellow LED • Event printer FTO2001-A1 one red and one yellow LED With a mounting kit, the Ethernet • Operating add-on (4xLED-ind.) FCM7212-Y3 following modules:
the first manufacturer who offers this as EN 54- • Key switch Kaba FTO2005-C1 – Optional: • Key switch Kaba FTO2005-C1 – Optional: key switch Kaba switch can be easily integrated into
approved solution. With this architecture that is • Operating add-on, 48 display groups • Event printer FTO2001-A1 FTO2005-C1 Art. no.: S54400-B70-A1 – Fire department display panel with integrated
Housing panels or additional housings:
standard in IT, building structures and organizational each with one red and one yellow • Key switch Kaba FTO2005-C1 fire department operating panel (FAT and FBF)
– Standard: 430x398x160 mm Housing – FHA2029-A1 (S54400-B79-A1)
processes can be ideally depicted. LED FCM7211-Y3 • Operating add-on, 96 display groups [DE & CZ]
(WxHxD) – Standard: 430x398x160 mm for housing (Comfort)
• Operating add-on, 96 display groups each with one red and Housing (Comfort) FH7203-Z3 – EVAC module [NL]
Characteristics of networking via backbone – 70 W power supply (WxHxD) – FHA2030-A1 (S54400-B81-A1)
each with one red and one yellow one yellow LED FCM7212-Y3 – Max. battery capacity: 2x26 Ah The RS485 module (isolated) is plugged into the
– Ethernet switch to connect a cluster to the – Max. battery capacity: 2x12 Ah – 70 W power supply for housing (Large Extension)
LED FCM7212-Y3 Housing – 430x796x160 mm (WxHxD) PMI mainboard.
backbone – Max. battery capacity: 2x12 Ah
Art. no.: S54400-C29-A5 – Optional:
– Redundant transmission thanks to circular wiring System-wide view Housing – Comfort: 430x796x160 mm (WxHxD) Art. no.: A5Q00009923
Art. no.: S54400-C29-A4 • Power supply kit (70 W) FP2003-A1 or
– Redundant connection possible due to two with the fire terminal – Comfort: 430x796x160 mm (WxHxD) – 150 W power supply
Cluster • Power supply kit (150 W) FP2004-A1 or
Ethernet switches FT724 – 150 W power supply – Max. battery capacity: 2x26 Ah
additional power supply (150 W) FP2005-A1 Sounder module FCA2005-A1
– Increased EMC protection thanks to fiber-optic – Max. battery capacity: 2x26 Ah Art. no.: S54400-C30-A3 Network module (SAFEDLINK) • Event printer FTO2001-A1 The sounder module has connections for 4 conven-
cabling FN2001-A1
Art. no.: S54400-C30-A2 • Operating add-on (2xLED-ind.) FCM7211-Y3
– Easily programmable, EN 54-conform system-wide tional sounder lines (primary lines; 4x up to 1 A,
With this module, the station can be • Operating add-on (4xLED-ind.) FCM7212-Y3
control max. 2 A total). The sounder module is screwed
Ethernet switch networked via the cluster. For this
– Configurable view of single panels Backbone (C-WEB/LAN) FN2008-A1 purpose it is necessary to install a
Art. no.: S54400-B71-A1 to the assembly plate FHA2007-A1.
– All panels can be used as router panel (for further network module. In case of additional Art. no.: A5Q00014866
information on FC726, please have a look into the requirements in terms of the degrade
separate documentation). Fire control panel FC726-ZA Housing (Large) FH7205-Z3
mode function, 2 network modules can
– Max. battery capacity: 2x100 Ah License key L1 FCA2012-A1
Key data consisting of: be installed.
– 430x796x260 mm (WxHxD) Activates the Cerberus-Remote function. For operat-
– Max. number of panels in EN 54 system: 64 Repeater (SAFEDLINK) For example for:
Control unit Housing – Optional ing Cerberus-Remote, only the station which is to
– Max. number of panels in a cluster: 16 FN2002-A1 – Networked panels with more than
– Optional: – Large: 430x796x260 mm • Power supply kit (70 W) FP2003-A1 act as the CAP needs to have an L1 installed.
– Max. number of networkable clusters: 14 Each FC726 control The repeater doubles the 512 C-NET devices
• Event printer FTO2001-A1 (WxHxD) In the basic version each FC724 • Power supply kit (150 W) FP2004-A1
– Number of panels placed directly on backbone: 4* panel contains:
control panel contains:
range between 2 C-WEB – Networked panel with connection to Art. no.: A5Q00018856
• Key switch Kaba FTO2005-C1 – 150 W power supply • Power supply kit (150 W) FP2005-A1
– Number of panels with system-wide view: 5* Alarm transmission
Alarm transmission
stations (from 1,000 m to remote transmission and with more
• Operating add-on, 48 display – Max. battery capacity: Fault transmission • Event printer FTO2001-A1
– Max. distance between clusters Fire controls
Fault transmission 2,000 m). A separate power than 512 C-NET devices
groups each with one red and 2x45 Ah Fire controls • Operating add-on (2xLED-ind.) FCM7211-Y3
(fiber optic: multi mode): 3,000 m Monitoring of 2 conven- supply is needed. License key L2 FCA2013-A1
one yellow LED FCM7211-Y3 Art. no.: S54400-C87-A1 tional sounder lines
Monitoring of 2 conven- Art. no.: A5Q00012851 • Operating add-on (4xLED-ind.) FCM7212-Y3
* and more with respective system topology • Operating add-on, 96 display tional sounder lines Art. no.: S24236-B2502-A1 Activates the Cerberus-Remote function and the
Art. no.: S54400-B86-A1 connection to the danger management system.
The following guidelines must be observed groups each with one red and
one yellow LED FCM7212-Y3 Every station that needs to be accessed by a manage-
– To fulfill the EN 54 norm, you need only 1 Ethernet
ment system must have L2 installed.
switch to connect control panels with less than Housing (Large Extension) FH7204-Z3
512 fire detectors to the backbone. Art. no.: A5Q00018857
– Max. battery capacity: 2x100 Ah
– 430x398x260 (WxHxD)
– Optional:
Power supply kit (70 W) FP2003-A1
• Power supply kit (150 W) FP2004-A1

Fire control panel Fire control panel FC724 (4-loop) Fire control panel Fire control panel • Power supply kit (150 W) FP2005-A1
• Event printer FTO2001-A1 Operating add-ons
• Operating add-on (2xLED-ind.) FCM7211-Y3
Cluster FC726 (modular) Description Technical data FC722 (2-loop) FC721 (1-loop) • Operating add-on (4xLED-ind.) FCM7212-Y3
Art. no.: S54400-B89-A1
(C-WEB/SAFEDLINK) Description Note: all extensions included
The FC724 is a compact 4-loop fire control
panel. It has the following features:
C-NET detector lines
– Number of addresses: max. 504 Description Description
Operating add-on (2xLED-ind.) FCM7211-Y3
This contains 48 display groups each with one red
FC726 is a modular fire control panel. – 4 C-NET loops – Number of loops/stubs: 4/8 The FC722 is a compact 2-loop fire control panel. The FC721 is a compact fire control panel. and one yellow LED. Any events can be allocated
Via the powerful cluster, up to 32 panels can be Flush mounting bezel one HU FHA2017-A1
It has the following features: – Integrated inputs/outputs for peripherals – Optionally with loop extension: to the LEDs; 427x200x25 (WxHxD)
networked (fire control panels and fire terminals).
It has the following features: Fire control panel FC721-ZZ It has the following features: Optional bezel for flush mounting
– 4 C-NET loops – Integrated control unit 8 loops/16 stubs – 2 C-NET loops – 1 C-NET loop Optional: event printer FTO2001-A1
consisting of: installation for all fire control panels
Characteristics of networking via the system bus – 5 slots for additional module bus cards – Integrated power supply Inputs and outputs – Integrated inputs/outputs for peripherals – Integrated inputs/outputs for peripherals Art. no.: S54400-F75-A1
and FT724 fire terminal;
– Wiring with two wires – Integrated inputs/outputs for peripherals – Automatic configuration – 1 relay output for RT alarm – Integrated control unit Control unit – Integrated control unit 530x500 mm (WxH)
– Redundant transmission thanks to circular wiring – Integrated control unit – Networkability via backbone (C-WEB/LAN), – 1 relay output for RT fault – Integrated power supply – Optional: key switch Kaba – Integrated power supply
– Increased safety due to degrade mode using a – Integrated power supply cluster (C-WEB/SAFEDLINK) or Ethernet FTO2005-C1 Art. no.: A5Q00024719
– 1 monitored alarm output – Automatic configuration – Automatic configuration Operating add-on (4xLED-ind.) FCM7212-Y3
second network module – Automatic configuration – 1 monitored fault output – Networkability via backbone (C-WEB/LAN), cluster Housing This contains 96 display groups each with one red
– No additional cabling necessary for degrade – Networkability via backbone (C-WEB/LAN), – 2 monitored sounder outputs (1 A each) (C-WEB/SAFEDLINK) or Ethernet – Eco: 430x398x80 mm (WxHxD) Technical data and one yellow LED. Any events can be allocated
mode; even for systems with more than 512 fire cluster (C-WEB/SAFEDLINK) or Ethernet Flush mounting bezel two HU FHA2015-A1
– 12 configurable inputs/outputs DC 24 V – 70 W power supply to the LEDs; 427x200x25 (WxHxD)
detectors C-NET detector lines Optional bezel for flush mounting
– 1 Ethernet connection (RJ45) Technical data – Max. battery capacity: 2x7 Ah Art. no.: S54400-F88-A1
– Configurable view of individual panels – Number of addresses: max. 126 installation for all fire control panels
Technical data – Optional: sounder module for Art. no.: S54400-C32-A2 – Number of integrated loops/stubs: 1/2 and FT724 fire terminal;
Key data splitting the sounder line output C-NET detector lines
Basic configuration – Number of addresses: max. 252 Inputs and outputs 530x886 mm (WxH)
– Max. number of networkable panels: 32 into 4 monitored outputs (2 A) Key switch Kaba FTO2005-C1
– Max. number of networkable panels – Number of loops/stubs: 4/8 – Number of loops/stubs: 2/4 – 1 relay output for RT alarm Art. no.: A5Q00024621
Kaba lock cylinder with installation accessories
if connected to a danger management – Optionally with loop extension: 8 loops/16 stubs – Optionally with loop extension: – 1 relay output for RT fault
and keys (Kaba 8 #100). Usable optionally for
system: 16 Modular extension 4 loops/8 stubs – 1 monitored alarm output
enabling operation.
– Max. distance between panels with – Additional line card for 252 C-NET devices each: Inputs and outputs – 1 monitored fault output 19“ mounting kit FHA2016-A1
– 1 monitored sounder output (1 A) Enables all fire control panels and fire terminals Art. no.: A5Q00010113
copper cable 20 loops/40 stubs – 1 relay output for RT alarm
• without repeater: 1,000 m – I/O card with 12 programmable inputs/outputs – 1 relay output for RT fault – 4 configurable inputs/outputs DC 24 V to be mounted in a 19‘‘ frame; 430x100x324 mm
• with repeater: 2,000 m – 1 monitored alarm output – 1 Ethernet connection (RJ45) (WxHxD)
Final configuration Key switch Nordic FTO2006-B1
– Max. distance between panels with – Number of addresses: max. 1,512 – 1 monitored fault output Art. no.: A5Q00020179
Key set with mounting accessories. Optimally
fiber-optic cable
• multi mode: 2,500 m
– Number of loops/stubs: 28/56
Inputs and outputs
Fire terminal FT724 – 1 monitored sounder output (1 A)
– 8 configurable inputs/outputs DC 24 V
applicable for operation clearance.
• single mode: 15,000 m – 1 Ethernet connection (RJ45) Art. no.: A5Q00010129
– 1 relay output for RT alarm
– Max. number of panels with Description Technical data – Optional: sounder module for splitting the
system-wide view: 5 – 1 relay output for RT fault
sounder line output into 4 monitored outputs (2 A)
– 1 monitored alarm output The FT724 has the following features: – DC 24 V system power supply Fire control panel FC721-YZ Event printer FTO2001-A1
– 1 monitored fault output – Integrated control unit – Alarm current: 130 mA consisting of:
Module bus cards for FC726 The event printer FTO2001-A1 is installed directly in
– 2 monitored sounder outputs (1 A each) – Separate DC 24 V supply input possible the control panel or in the terminal. It is a thermal
Control unit
– 12 configurable inputs/outputs DC 24 V – Redundant DC 24 V supply input printer which logs all events. An RS232 module
– 24 display groups each with one
– 1 Ethernet connection (RJ45) – Networkability via C-WEB/SAFEDLINK Line card (C-NET) FCL2001-A1 (isolated) FCA2001-A1 is required for operating the
red and one yellow LED
– Optional: sounder module for splitting the sounder or Ethernet For 252 C-NET devices on 4 loops or 8 stubs. event printer. This is not contained in the printer
– Optional: key switch Kaba
line output into 4 monitored outputs (2 A) In the basic version
Art. no.: A5Q00009875 set and must be ordered separately.
C-NET each FC722 control
panel contains:
FTO2005-C1
Housing Art. no.: A5Q00010126
Alarm transmission
Fault transmission – Eco: 430x398x80 mm (WxHxD)
The C-NET is a modern, multi-purpose bus system. I/O card (programmable) FCI2008-A1
Fire controls – 70 W power supply
It allows rapid, fail-safe communication between Monitoring of conven- 12 programmable inputs/outputs with defined Event printer DL3750+
– Max. battery capacity: 2x7 Ah
the Cerberus® PRO bus elements and the fire control
panel.
Cluster (C-WEB/SAFEDLINK) tional sounder line
Art. no.: S54400-C32-A3
behavior in degrade mode. Monitored external event printer for serial con-
nection or via Ethernet. Optional: RS232 module
Art. no.: S54400-A6-A1
Characteristics of networking via the detector bus (isolated) FCA2001-A1.
– Use of all cable types (shielded or unshielded) Art. no.: A5Q00023962
– Integration of star-shaped cable networks without
modifications to cable network
– Shielding not necessary
– 2-wire loop Fire terminal FT724-ZZ Fire control panel FC722-ZA Fire control panel FC722-ZE
– Power supply to all bus elements via the C-NET
(except transponder FDCIO223, LaserFOCUS,
consisting of: consisting of: consisting of: Power supply
Control unit Control unit Control unit
extinguishing control unit XC10) Floor repeater terminal FT2010-A1
– Optional: – Optional: – 48 display groups each with
Key data • Event printer FTO2001-A1 • Event printer FTO2001-A1 one red and one yellow LED Used for the display and control of
Power supply kit (70 W) FP2003-A1
– Up to 40 T-taps • Key switch Kaba FTO2005-C1 • Key switch Kaba FTO2005-C1 – Optional: messages from the monitored area
For the independent power supply of fire
– Up to 126 bus elements on one loop Housing • Operating add-on, 48 display groups • Event printer FTO2001-A1 Properties terminals such as FT724-ZZ.
– Cable lengths up to 3.3 km with up to 126 bus – Eco: 430x398x80 mm (WxHxD) each with one red and one yellow • Key switch Kaba FTO2005-C1 – Backlit display with plain text display
Art. no.: A5Q00016005
elements – Optional: LED FCM7211-Y3 • Operating add-on, 96 display groups (6 lines of 40 characters each)
• 70 W power supply • Operating add-on, 96 display groups each with one red and one yellow – Power supply and communication
• Max. battery capacity: 2x7 Ah each with one red and one yellow LED FCM7212-Y3 (individually addressed) via C-NET,
Power supply kit (150 W) FP2004-A1
• Housing (Eco) FH7201-Z3 and LED FCM7212-Y3 Housing additional DC 24 V supply possible
Power supply for installation in empty housings.
operating add-on (2xLED-ind.) Housing – Comfort: 430x796x160 mm – 282x207x79 mm (WxHxD)
Optional: additional power supply with FP2005-A1
FCM2711-Y3 – Comfort: 430x796x160 mm (WxHxD) (WxHxD) – Max. 8 FT2010/FT2011 per FC721/FC722
is possible.
– 150 W power supply – 150 W power supply – Max. 16 FT2010/FT2011 per FC724
Art. no.: S54400-C31-A2 Art. no.: A5Q00020825
– Max. battery capacity: 2x26 Ah – Max. battery capacity: 2x26 Ah – Max. 50 FT2010/FT2011 per FC726

Art. no.: S54400-C29-A2 Art. no.: S54400-C29-A1 Art. no.: A5Q00014104

Additional power supply (150 W) FP2005-A1


Legend for the interfaces and networks: C-NET Additional power supply can be connected in
the housing directly after FP2004-A1.
Serial interfaces One optional RS232 and/or one RS485 interface
(also freely combinable) per panel or fire terminal (For further details see also Art. no.: A5Q00018779
Backbone (C-WEB/LAN) Network to connect clusters the Cerberus PRO Planning Tool –
Cluster (C-WEB/SAFEDLINK) Network to connect panels C-NET devices) Manual call point, red ASA neural fire detector Alarm sounder
C-NET Network to connect Cerberus PRO devices FDM221 OOH740 FDS221-R © Siemens 2011