TELENOR PAKISTAN LTD.

TECHNICAL REPORT
ON

THE GEOTECHNICAL INVESTIGATIONS & SOIL


ANALYSIS FOR THE ERECTION OF 60 M. HIGH
SELF-SUPPORTED TELENOR TOWER AT VILLAGE
MONHAR AHMADI DARGAH (SHAMILAT), TEHSIL &
DISTRICT SHERANI
(SITE CODE: ZHB037-A)

CONTRACTOR:

IKAN ENGINEERING SERVICES


PLOT # 09
SANITARY MARKET
SECTOR I-11/3
ISLAMABAD

April, 2016

geo-tech consultancy services


CONSULTING GEO-TECH ENGINEERS
HYDROLOGISTS AND GROUND WATER INVESTIGATORS
3360, Lane-3, Officer Colony, I-8, Misriyal Rd. Rawalpindi.
Ph:+92 51 5166707 & 4320334, Fax: +92 51 4862507, Email: gcs_zarar@yahoo.com
TECHNICAL REPORT ON THE GEOTECHNICAL
INVESTIGATIONS FOR THE ERECTION OF 60 M. HIGH
SELF-SUPPORTED TELENOR TOWER AT VILLAGE
MONHAR AHMADI DARGAH (SHAMILAT), TEHSIL &
DISTRICT SHERANI. (SITE CODE: ZHB037-A)

1. INTRODUCTION

In this rapidly developing era, the necessity of Telecommunication


needs no emphasis. Various organizations are engaged in this field
for advancement of Telecommunication Network in Pakistan.
IKAN Engineering Services Karachi, is one of the largest
Telecommunication companies presently busy in providing latest
technology.

For economical and safe foundation design, the knowledge of


subsoil stratification and engineering characteristics of the
foundation material is very essential. Accordingly M/s Geo-tech
Consultancy Services of Islamabad have been engaged to carryout
geotechnical investigations & recommending safe Bearing
Capacity.

2. LOCATION OF SITE

The site is located on a hill top at Village Monhar Ahmadi Dargah


(Shamilat), Tehsil & District Sherani.
3. FIELD INVESTIGATIONS

3.1 Sub-Soil Stratification

The site was explored through Pits dug maximum up to 0.3 m.


depth from the present ground level. The subsoil strata are given
as follows:-

P-1
0.0 - 0.2 m. = Gravels & Boulders.
0.2 - 0.3 m. = Hard Rock.

P-2
0.0 - 0.1 m. = Gravels & Boulders.
0.1 - 0.2 m. = Hard Rock.

P-3
0.0 - 0.2 m. = Gravels & Boulders.
0.2 - 0.3 m. = Hard Rock.

P-4
0.0 - 0.1 m. = Gravels & Boulders.
0.1 - 0.2 m. = Hard Rock.

The soil profile is graphically explained in Geological Profile as


Appendix-I.

1
3.2 Subsoil Strength Characteristics

The strength characteristics of subsoil foundation material were


investigated by employing Standard Penetration Tests. The “qu” is
172.35 (kN/m2). The S.P.T. “N” values for the whole strata falls in
the range of “Refusal”. The results of in-situ moisture contents and
Bulk Density are given in Table-II and the SPT “N” values are
recorded in the geological profile as Appendix-I.

It may be noted that standard penetration test is by far the most


popular and economical method of obtaining subsurface
information. Significant numbers of foundation design procedures
make use of SPT results. Testing method essentially consists of
driving a split spoon sampler of specified dimensions at a distance
of 46 cm. into the soil at the bottom of the borehole/Pit. A 63.5 kg.
Hammer falling free from a height of 2.5 ft. is used to drive the
sampler. Number of blows required to drive the last 12 inches is
recorded as ‘N’ value. The standard penetration tests were carried
in accordance with the specification of ASTM D-1586.

3.3 Ground Water Table


The ground water table was not encountered up to the depth of
investigations.

4. LABORATORY TESTING

Most of the samples collected in the field were extracted from the
Split-spoon Sampler during S.P.T but some testing like Bulk

2
Density, Unconfined Compression Strength and in-situ moisture
contents were also conducted in the laboratory for which U.D.S
were collected. Samples thus collected are subjected to following
laboratory tests in accordance with latest AASHTO standards. It
includes:-

a. Sieve Analysis (T-27-99).


b. Hydrometer Test (T-88-00).
c. Liquid Limit (T-89-96)
d. Plastic Limit (T-90-00).
e. Specific Gravity (T-100-95).
f. Unconfined Compressive Strength discussed under field
testing (T-208-96).
g. Direct Shear Tests (T-236-92).
h. Chemical Analysis of Soil.

The results of above tests are given in different tables attached, and
are also briefly discussed as under:-

4.1 Gradation/Grain Size Analysis


The grain size analysis was performed on selected samples. The
analysis indicates that the subsoil contains Gravels & Boulders
which is under laid by Hard Rock in the Pits for the entire
excavated depth and falls under A-5 & A-6 groups of AASHTO
(M-145) Soil Classification System.

4.2 Atterberg Limits

Selected samples were subjected to plasticity tests. The results show


that the soil is semi-plastic in nature and as a whole falls under
“GW & GP” groups of Unified Classification System.

3
4.3 Unconfined Compression Strength

The results of unconfined compression strength are discussed in


Para 3.2 above.

4.4 Direct Shear Test

Selected samples were subjected to Direct Shear Tests. The Angle


of internal friction “” was tested to be 35.30 degree & cohesion
“c” is 0.025 (psi). The results are given in Table-II.

4.5 Chemical Analysis of Soil


Selected samples close to the foundation depth were tested for
Sulphate Contents. The results indicate that the soil does not
contain harmful quantity of Sulphates in the tested soil samples.
Therefore “Ordinary Portland Cement” (O.P.C.) can be used in the
foundations. The results are given in Table-IV.

4
5. TYPE & DEPTH OF FOUNDATION
Raft foundation for Tower at 2.0 m. depth.

6. BEARING CAPACITY
Self-Supported Tower (Raft foundation)
2.0 m. Depth

qa = 360 (N-3) Rw


where qa = Allowable Bearing Capacity for 1
maximum settlement.
N = Design S.P.T “N” values within
Stress zone = 13
Rw = Water table correction = 1.0
qa (net) = 360 (N - 3) Rw
= 360 (13 - 3) 1.0
= 360 x 10 x 1.0
= 3600 lbs/sq.ft.
= 1.633 tons/sq.ft.
= 172.35 kN/m2
qa (Gross) = qa (net) + Df
= 1.633 + 0.90
= 2.533 tons/sq.ft.
= 267.33 kN/m2

Note: Other values of “qa” (Gross) and “qu” at different depths are given
in Table-I

5
7. GENERAL RECOMMENDATIONS

1. Prior to providing foundation concrete, the foundation rock


should be exposed properly to have a strong bond between
rock and concrete.

2. Drainage may be kept efficient and no surplus water be


allowed to penetrate into the foundation soil from any source.

3. No significant concentration of Sulphate contents observed


in the foundation soils, therefore “Ordinary Portland
Cement (O.P.C.)” can be used for foundation construction.

4. The required raising may be done preferably with organic


and salt free Clayey soil, which should be thoroughly
compacted up to the specified state of compaction.

5. Soil conditions need the use of Jack Hammer and blasting for
excavation.

(GHULAM JAFAR)
Geophysicist
GEO-TECH CONSULTANCY SERVICES
ISLAMABAD.

6
DISCUSSION OF LAB.
RESULTS

7
TABLE - I

RESULTS OF BEARING CAPACITY W.R.T. DIFFERENT DEPTHS

Depth Bearing Capacity


Sr. Location In For 1” Max. (For 2” Max. Qu
# Meter Settlement ) Settlement ) kN/m2
qa (Gross) qa (Gross)
kN/m2 kN/m2

1 P-1-4 2.0 267.33 288.10 172.35

2 // 2.4 272.40 293.53 172.58

3 // 2.7 275.93 296.72 172.79

4 // 3.0 278.28 299.61 173.00

8
T A B L E - II

RESULTS OF INSITU MOISTURE CONTENTS, BULK DENSITY


AND UNCONFINED COMPRESSIVE STRENGTH

Depth In-situ Bulk


Sr. Location In Moisture Density “qu”
# Meter Content gm/cc kN/m2
%

1. P-1-4 2.0 1.20 1.90 172.35

2. // 2.4 1.21 1.90 172.58

3. // 2.7 1.21 1.90 172.79

4. // 3.0 1.21 1.90 173.00

9
T A B L E - III

RESULTS OF DIRECT SHEAR TESTS

Angle of Apparent
Sr. Location Depth Internal cohesion
# In Friction “c”
Meter “” Psi

1. P-1-4 2.0 35.30 0.025

2. // 2.4 35.30 0.025

10
T A B L E - IV

RESULTS OF CHEMICAL ANALYSIS OF SOIL

Depth Sulphate Content


Sr. Location In SO4
# Meter %

1. P-1-4 2.0 0.060

2. // 2.4 0.060

Maximum limit of Sulphate

Content for Foundations = 0.18% Maximum

11
INDEX
Sr. C o n t e n t s Page
# #
------- -------------------------------------------------------------------------------------
1. INTRODUCTION 0

2. LOCATION OF SITE 0

3. FIELD INVESTIGATIONS 1

3.1 Subsoil Stratification 1


3.2 Subsoil Strength Characteristics 1
3.3 Ground Water Table 1

4. LABORATORY TESTING 2

4.1 Grain Size Analysis 2


4.2 Atterberg Limits 3
4.3 Unconfined Compression Strength 3
4.4 Direct Shear Test 3
4.5 Chemical Analysis of Soil 3

5. TYPE & DEPTH OF FOUNDATION 4

6. BEARING CAPACITY 4

7. GENERAL RECOMMENDATIONS 5

Table-I RESULTS OF BEARING CAPACITY W.R.T.


DIFFERENT DEPTHS 6
Table-II RESULTS OF INSITU MOISTURE CONTENTS,
BULK DENSITY AND UNCONFINED
COMPRESSIVE STRENGTH 7
Table-III RESULTS OF DIRECT SHEAR TESTS 8
Table-IV RESULTS OF CHEMICAL ANALYSIS OF SOIL 9
Appendix:
FIELD PIT LOG
BEARING CAPACITY ANALYSIS

12
SITE ID: ZHB037-A IKAN ENGINEERING
CONTRACTOR SERVICES
VILLAGE MONHAR AHMADI

GCS geo-tech consultancy services


LOCATION: DARGAH,
TEH. & DISTT. SHERANI.
DEPTH: 2.0 M.
DATE: 16-04-2016
CONSULTING GEO-TECH ENGINEERS
HYDROLOGISTS AND GROUND WATER INVESTIGATORS

CHECKED BY: GHULAM JAFAR


CEMENT: O. P. C.

BEARING CAPACITY
for

TOWER FOUNDATION

BEARING CAPACITY (kPa)


00 20 40 60 80 100 120 140 160
00

10

20

30
SETTLEMENT (mm)

40

50

60

70

80
LEGEND
90
Width = 1m
100 Width = 3m

110 Width = 5m
Width = 7m
120
Width = 9m
130

GRAPH-1: BEARING CAPACITY ANALYSIS FOR DEPTH 2.0 M.

Suit # 29,3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:051-4320334
SITE ID: ZHB037-A IKAN ENGINEERING
CONTRACTOR SERVICES
VILLAGE MONHAR AHMADI

GCS geo-tech consultancy services


LOCATION: DARGAH,
TEH. & DISTT. SHERANI.
DEPTH: 2.5 M.
DATE:
CONSULTING GEO-TECH ENGINEERS
16-04-2016
HYDROLOGISTS AND GROUND WATER INVESTIGATORS

CHECKED BY: GHULAM JAFAR


CEMENT O. P. C.

BEARING CAPACITY
for

TOWER FOUNDATION

BEARING CAPACITY (kPa)


00 20 40 60 80 100 120 140 160
00

10

20

30
SETTLEMENT (mm)

40

50

60

70

80
LEGEND
90
Width = 1m
100 Width = 3m

110 Width = 5m
Width = 7m
120
Width = 9m
130

GRAPH-2: BEARING CAPACITY ANALYSIS FOR DEPTH 2.5 M.

Suit # 29,3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:051-4320334
SITE ID: ZHB037-A IKAN ENGINEERING
CONTRACTOR SERVICES
VILLAGE MONHAR AHMADI

GCS geo-tech consultancy services


LOCATION: DARGAH,
TEH. & DISTT. SHERANI.
DEPTH: 2.7 M.
DATE:
CONSULTING GEO-TECH ENGINEERS
16-04-2016
HYDROLOGISTS AND GROUND WATER INVESTIGATORS

CHECKED BY: GHULAM JAFAR


CEMENT: O. P. C.

BEARING CAPACITY
for

TOWER FOUNDATION

BEARING CAPACITY (kPa)


00 20 40 60 80 100 120 140 160
00

10

20

30
SETTLEMENT (mm)

40

50

60

70

80
LEGEND
90
Width = 1m
100 Width = 3m

110 Width = 5m
Width = 7m
120
Width = 9m
130

GRAPH-3: BEARING CAPACITY ANALYSIS FOR DEPTH 2.7 M.

Suit # 29,3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:051-4320334
SITE ID: ZHB037-A IKAN ENGINEERING
CONTRACTOR SERVICES
VILLAGE MONHAR AHMADI

GCS geo-tech consultancy services


LOCATION: DARGAH,
TEH. & DISTT. SHERANI.
DEPTH: 3.0 M.
DATE:
CONSULTING GEO-TECH ENGINEERS
16-04-2016
HYDROLOGISTS AND GROUND WATER INVESTIGATORS

CHECKED BY: GHULAM JAFAR


CEMENT: O. P. C.

BEARING CAPACITY
for

TOWER FOUNDATION

BEARING CAPACITY (kPa)


00 20 40 60 80 100 120 140 160
00

10

20

30
SETTLEMENT (mm)

40

50

60

70

80
LEGEND
90
Width = 1m
100 Width = 3m

110 Width = 5m
Width = 7m
120
Width = 9m
130

GRAPH-4: BEARING CAPACITY ANALYSIS FOR DEPTH 3.0 M.

Suit # 29,3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:051-4320334
SITE ID: ZHB037-A IKAN ENGINEERING
CONTRACTOR SERVICES
VILLAGE MONHAR AHMADI

GCS geo-tech consultancy services


LOCATION: DARGAH,
TEH. & DISTT. SHERANI.
DEPTH: 1.0 M.
DATE:
CONSULTING GEO-TECH ENGINEERS
16-04-2016
HYDROLOGISTS AND GROUND WATER INVESTIGATORS

CHECKED BY: GHULAM JAFAR


CEMENT: O. P. C.

BEARING CAPACITY
for
GENERATOR FOUNDATION

BEARING CAPACITY (kPa)


00 20 40 60 80 100 120 140 160
00

10

20

30
SETTLEMENT (mm)

40

50

60

70

80
LEGEND
90
Width = 1m
100 Width = 2m

110 Width = 3m

120

130

GRAPH-5: BEARING CAPACITY ANALYSIS FOR DEPTH 1.0 M.

Suit # 29,3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:051-4320334
SITE ID: ZHB037-A IKAN ENGINEERING
CONTRACTOR SERVICES
VILLAGE MONHAR AHMADI

GCS geo-tech consultancy services


LOCATION: DARGAH,
TEH. & DISTT. SHERANI.
DEPTH: 1.5 M.
DATE:
CONSULTING GEO-TECH ENGINEERS
16-04-2016
HYDROLOGISTS AND GROUND WATER INVESTIGATORS

CHECKED BY: GHULAM JAFAR


CEMENT: O. P. C.

BEARING CAPACITY
for
SOLAR PANEL FOUNDATION

BEARING CAPACITY (kPa)


00 20 40 60 80 100 120 140 160
00

10

20

30
SETTLEMENT (mm)

40

50

60

70

80
LEGEND
90
Width = 1m
100 Width = 2m

110 Width = 3m

120

130

GRAPH-6: BEARING CAPACITY ANALYSIS FOR DEPTH 1.5 M.

Suit # 29,3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:051-4320334
geo- tech consultancy services
CONSULTING GEO-TECH ENGINEERS
HYDROLOGISTS AND GROUNDWATER INVESTIGATORS

UNCONFINED COMPRESSION TEST (result)


Project: Telenor Tower. Date: 15-04-2016
Location: Village Monhar Ahmadi Dargah Sample.UDS-1
(Shamilat), Tehsil & District Sherani.
Pit No. 1 Sample Depth: 1-2 ft.
Testing Method: ASTM D-2166

Specimen Cross-section: 3.40 cm Specimen Height (H): 5.6 Cm.


Water Contents (w): 1.20% Dry Density (rd): 1.90 g/Cm.3
Unconfined Compression Strength Undisturbed : 1.63 Kg/cm2 Rebounded – kg/cm3
Remarks : Failure strain 2.65 %

2.6

2.4

2.2

2.0

1.8

1.6

1.4
Axial Stress Kg/cm2.

1.2

1.0

0.8

0.6

0.4

0.2

Failure Sketch
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Axial Strain %

TESTED BY: CHECKED BY:

Suit # 29, 3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:+92 51 4442055, 4862507
geo- tech consultancy services
CONSULTING GEO-TECH ENGINEERS
HYDROLOGISTS AND GROUNDWATER INVESTIGATORS

UNCONFINED COMPRESSION TEST (result)


Project: Telenor Tower. Date: 15-04-2016
Location: Village Monhar Ahmadi Dargah Sample.UDS-1
(Shamilat), Tehsil & District Sherani.
Pit No. 2 Sample Depth: 1-2 ft.
Testing Method: ASTM D-2166

Specimen Cross-section: 3.40 cm Specimen Height (H): 5.7 Cm.


Water Contents (w): 1.20% Dry Density (rd): 1.90 g/Cm.3
Unconfined Compression Strength Undisturbed : 1.58 Kg/cm2 Rebounded – kg/cm3
Remarks : Failure strain 2.90 %

2.6

2.4

2.2

2.0

1.8

1.6

1.4
Axial Stress Kg/cm2.

1.2

1.0

0.8

0.6

0.4

0.2

Failure Sketch
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Axial Strain %

TESTED BY: CHECKED BY:

Suit # 29, 3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:+92 51 4442055, 4862507
geo- tech consultancy services
CONSULTING GEO-TECH ENGINEERS
HYDROLOGISTS AND GROUNDWATER INVESTIGATORS

UNCONFINED COMPRESSION TEST (result)


Project: Telenor Tower. Date: 15-04-2016
Location: Village Monhar Ahmadi Dargah Sample.UDS-1
(Shamilat), Tehsil & District Sherani.
Pit No. 3 Sample Depth: 1-2 ft.
Testing Method: ASTM D-2166

Specimen Cross-section: 3.40 cm Specimen Height (H): 5.8 Cm.


Water Contents (w): 1.20% Dry Density (rd): 1.90 g/Cm.3
Unconfined Compression Strength Undisturbed : 1.58 Kg/cm2 Rebounded – kg/cm3
Remarks : Failure strain 3.10 %

2.6

2.4

2.2

2.0

1.8

1.6

1.4
Axial Stress Kg/cm2.

1.2

1.0

0.8

0.6

0.4

0.2

Failure Sketch
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Axial Strain %

TESTED BY: CHECKED BY:

Suit # 29, 3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:+92 51 4442055, 4862507
geo- tech consultancy services
CONSULTING GEO-TECH ENGINEERS
HYDROLOGISTS AND GROUNDWATER INVESTIGATORS

UNCONFINED COMPRESSION TEST (result)


Project: Telenor Tower. Date: 15-04-2016
Location: Village Monhar Ahmadi Dargah Sample.UDS-1
(Shamilat), Tehsil & District Sherani.
Pit No. 4 Sample Depth: 1-2 ft.
Testing Method: ASTM D-2166

Specimen Cross-section: 3.40 cm Specimen Height (H): 5.8 Cm.


Water Contents (w): 1.20% Dry Density (rd): 1.90 g/Cm.3
Unconfined Compression Strength Undisturbed : 1.62 Kg/cm2 Rebounded – kg/cm3
Remarks : Failure strain 3.25 %

2.6

2.4

2.2

2.0

1.8

1.6

1.4
Axial Stress Kg/cm2.

1.2

1.0

0.8

0.6

0.4

0.2

Failure Sketch
0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Axial Strain %

TESTED BY: CHECKED BY:

Suit # 29, 3rd Floor, Twin City Plaza, I-8 Markaz, Islamabad. Ph:+92 51 4442055, 4862507
GEOLOGICAL
PROFILE
PHOTOGRAPHS
Figure 1: Road Leading to Site.

Figure 2: Way to Site.


Figure 3: Site View.

Figure 4: Digging started at site.


Figure 5: Location of P-2.

Figure 6: Evidence of Rock.


Figure 7: Surface Material.