You are on page 1of 2

ECM700 Multifunction

Power Meter

Description
ECM 700 series can measure accurately almost all parameters in electrical systems.

They offer voltage, current, active power, reactive power, input energy and output
energy, power factor and frequency etc. measurements.

Except for measurements, ECM700 series can provide optional functions internal
clock, set point, SOE and TOU with proper software and hardware. With set
point, ECM700 can monitor and control reliably LV or HV power systems. With
SOE, ECM700 make it convenient for users to analyze events happened.
An optional module can be selected and mounted easily to ECM700 to complete
some optional functions. ECM700 series offer maximum visibility with a custom
backlit LCD display. The display is fully visible under most conditions and from
most angels. ECM700 series have communication ports and support MODBUS
protocol. Software of ECM700 can be upgraded through communication.

Feature
• One Meter to Measure all your Values and Replaces • Individual Harmonic Distortion up to the 31st (Option)
Multiple Analog Meters • Support Set point and TOU
• Commercial/Industrial Metering • Wide LCD Display for Easy Viewing.
• True RMS Measurement of Voltage, Current, 4 Quadrant • The Front Panel supports Local Data Display and Basic Setup
Power, 4 Quadrant Energy, Power Factor, Frequency • Communication with MODBUS/PROFIBUS Protocol
• 4 Control Relays; 4 Digital Inputs with SOE/2 Control
Relays; 8 Digital Inputs with SOE (Option)

Parameters
Instantaneous, RMS value Meters
Current (3I, In) Active and reactive energy 4 quadrants ( Imp kWh,
Phase to neutral and phase to phase voltage (U, UF) Exp kWh, Imp kvarh, Exp kvarh)
Frequency (F)
Total and per phase active, reactive and apparent power Input/Output
(ΣP, ΣQ, ΣS, 3P, 3Q, 3S) 4 Status Inputs (Dry Contact) + 4 Relay Output Ports
Per phase power factor (3PF) 8 Status Inputs (Dry Contact) + 2 Relay Output Ports
2 Pulse Outputs + 2 (4-20mA) Analog Outputs
Average and maximum value Clock and SOE (Event Log) Function
Average demand 15 min : 3I, ΣP, ΣQ, ΣS (Option)
Maximum demand 15 min : 3I, ΣP, ΣQ, ΣS (Option) Communication
RS-485 MODBUS Protocol/PROFIBUS (Option)
Power quality values
Voltage and current individual harmonic odd level up to row 31st (Option)

14
Electrical Characteristic
Current measurement Auxiliary power supply
CT primary up to 49,999 A Voltage 85-265 VAC/45-65 Hz, 100-300 VDC
CT secondary 1 or 5A Power consumption < 3VA
Overload capacity 1.3 times of rated Communication
Voltage measurement Link RS-485
Direct measurement 300V L-N, 520V L-L Protocol MODBUS
PT primary up to 999,999V MODBUS Speed 2,400 - 38,400 bauds
PT secondary 57.7/100V Status input
Overload capacity 1.3 times of rated Number of status 4 or 8
Power measurement Internal power supply 30 VDC
Per phase 0 - 100 MW/var/VA Relay output
Total 0 - 300 MW/var/VA Number of relay 2 or 4
Power factor measurement Capacity of relay 250VAC/5A, 30VDC/5A
Measurement range -1.000 - + 1.000 Analog outputs
Frequency measurement Number of output 2
Measurement range 45-65Hz Range 4-20 mA
Energy metering Maximum load 500 Ω
Metering range 0 -±99,999,999.9 kWh, kvarh Pulse outputs
Analog measurement Number of output 2
Number of input 1 Type 5VDC, 12VDC, 24VDC
Range 4-20 mA Pulse constant 1~6000pulse/ kWh or kvarh
Accuracy Environment
Current 0.20% Operating temperature -25°C to +55°C
Voltage 0.20% Storage temperature -30°C to +80°C
Power 0.50% Relative humidity 5% to 95%, non-condensing
Active energy class 1 Insulating property
Reactive energy class 2 Power frequency withstand voltage AC2kV
Power factor 0.50% Impulse withstand voltage 5kV (peak), 1.2/50S
Frequency 0.01Hz Insulation Resistance ≥ 50M

Dimension and Installation (Unit : mm)


Type panel mounting
Dimension WxHxD without option module 96 x 96 x 55
Dimension WxHxD with option module 96 x 96 x 88
Cut-out dimension 89.5 x 89.5 (+0.5)
Panel protection rating IP54
Side and back protection rating IP20
Display type LCD
Weight 400 g

Order Information Standards


ECM700 IEC61000-4-2, Level 3 Electrostatic discharge
1 2 3 4 immunity test
1 : Module Structure IEC61000-4-3, Level 3 Radiated immunity test
N Basic Module IEC61000-4-4, Level 3 Electrical fast transient/burst
A Basic Module + 4 Status Inputs (Dry Contact) + 4 Relay Output Ports
B Basic Module + 8 Status Inputs (Dry Contact) + 2 Relay Output Ports immunity test
C Basic Module + 4 Status Inputs (External Voltage Required) + 4 Relay Output Ports IEC61000-4-5, Level-3 Surge immunity test
D Basic Module + 8 Status Inputs (External Voltage Required) + 2 Relay Output Ports EN55022, Class B Conducted emissions
E Basic Module + 2 Pulse Outputs + 2 (4-20mA) Analog Outputs
2 : Auxiliary Function EN55022, Class B Radiated emissions
H Up to 31st Harmonic
T Clock and SOE (Event Log) Function
F TOU (Time of use)
M Two RS485 Communication Ports
3 : Analog Port
AI One 4-20mA Analog Input
AO One 4-20mA Analog Output
4 : Measurement Parameter
V1 Rated Voltage/Current Input : 57.7/100V, 5A
V2 Rated Voltage/Current Input : 57.7/100V, 1A
V3 Rated Voltage/Current Input : 220/380V, 5A
V4 Rated Voltage/Current Input : 220/380V, 1A
Note : One RS-485 Communication is included in each module structure