REFERRAL GUIDE

w.e.f.: 01.01.2013

Electromechanical &
Numerical Relays

Channel Partner-India:
SYSTEM CONTROLS & SWITCHGEARS
www.systemcontrols.co.in
Content
A. Electromechanical Relays
MiCOM ALSTOM Protection>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>4
i AGILE Feeder Management>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>5
ii Overcurrent & Feeder Management Relays>>>>>>>>>>>>>>>>>> 6
iii Motor & Generator Management Relays>>>>>>>>>>>>>>>>>>>>>> 7
iv Distance protection relays>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>8
B. Numerical Relays
i P14x for Feeder Protection>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>> 9
ii P24x for Motor Protection>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>10
iii P34 x for Interconnection & Generator Protection>>>>>>>>11
iv P44x for Distance Protection>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>12
v P64x>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>13
vi MX Range>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>>14 -15
A. Electromechanical Relays
Sr. Model of relay REFERAL ANSI Code
No. PRICE
1 CCUM21, 1 ½ D Vert ,2NO S/R Reverse Power Relay, PTR 110V AC 29370 32
2 CDG11,1D Vert , 2NO S/R 1 Element O/C or E/F, 1DV CASE 6460 51 or 51 N
3 CDG31,3DHorz,2NO S/R 3 Element O/C or E/F 18200 51 or 51 & 51 N
4 CDG61,3D Horz,2NO S/R 3 Element O/C & E/F with high Set 31470 51 & 50 or 51,50,
51N, 50 N
5 CDV62,3D Horz,2NO S/R O/C Relay Voltage Restrained 28850 51 V
6 VDG11,1D Vert,110 V AC Inverse O/V Relay 10960 59
7 VDG13,ID Vert,110 V AC Inverse U/V Relay 12130 27
8 VDG14,1D Vert Field Failure Neutral Displacement 13440 59N
9 CAG12, AC instantaneous O/C or E/F relay, 1/2N VERT 4490 50
10 CAG14,1D Vert Restricted Earth Fault With stab Resistance 9790 87 N, 64 R
11 CAG34,1D , Vert Generator Differential With stab Resisitance 22210 87
12 VAA11, 1/4 N Vert, 2NO+2C/O S/R , Auxilliary with S/R Contacts 3030 30 ****
13 VAA12, 1/4 N Vert, 2NO+2C/O S/R / H/R Auxilliary with S/R+H/R 2980 30 ****
14 VAA13, 1/4 N Vert, 2NO+2C/O H/R Auxilliary with H/R Contacts 2980 30 ****
15 VAA21,1/2N Horz, 2NO+1N/C S/R Auxilliary with S/R Contacts 4930 30 ****
16 VAA22,1/2 N Horz, 2NO+1C/O ,S/R / H/R Auxilliary with S/R+H/R 4930 30 ****
17 VAA23, ½ N Horz, 2NO+1C/O, H/R Auxilliary with H/R Contacts 4970 30 ****
18 VAA31,1/2N Horz , 2NO S/R Auxilliary with S/R Contacts 5140 30 ****
19 VAA32,1/2N Horz , 2NO S/R / H/R Auxilliary with S/R+H/R Contacts 5520 30 ****
20 VAA33, ½ N Horz,2NO H/R Auxilliary with H/R Contacts 5420 30 ****
21 VAG11, 1/4N Vert - Single Pole Instantaneous FIX SETTING - U/V 3290 27 or 59 ####
or O/V relay
22 VAGM22,1D Vert , 110 V AC U/V or O/V variable Seting 9340 27 or 59
23 VAJC11, Single element voltage operated control relay with electrical 9430 83
reset contacts,1/2N V
24 VAJH13,1/4N Vert Master Trip Relay HR Contacts 2940 86
25 VAJH23,1/2 N Vert Master Trip Relay HR Contacts 5590 86
26 VAJHM13, Single element high speed tripping relay with hand reset 3320 86
contacts. 1/4 N V,HR Contacts
27 VAJHM23, Two element high speed tripping relay with hand reset 5590 86
contacts. ½ N H , HR Contacts
28 VAM12 Semaphore Indicator- 51MM Panel Cut Out 2680 -
29 VAM22 Semaphore Indicator- 71 MM Panel Cut Out 3090 -
30 VAX31, ½ N Horz Trip Ckt Supervision- DC Volt 5940 95 TC
31 CTNM12, ½ N Horz Negative Phase Sequence 8510 46
32 SKE11,1D Vert Check Synchronising- 1D Vert 63700 25
33 VTT11, 1/2N Horz TIMER, Time Delay For DC Relay 6650 2
34 VTT11, 1/2N Horz TIMER, Time Delay For aC Relay 8870
35 MFVUM12 Under/Over Frequency 1 Stage 53280 81
36 MFVUM22 Under/Over Frequency 2 Stage 67160 81
37 VAPM 31, Fuse Failure Relay , 1D Vert 12260 60
38 DTH31 Transformer Differential, 3D Vert 75080 87
39 CAEM 21, Battery Earth Fault Relay, 1D Vert 18510 95 Battery
40 CTU12, Static definite time single pole O/C or E/F Relay ,1D Vert 15000 50 or 50 N
41 CTU32, Three pole static O/C or 2 O/C & 1 E/F relay, 1D Vert 19660 50 or 50 & 50 N
42 CTU15, Single pole sensitive definite time static E/F relay , 1D VERT 32330 50
43 CTUM15, Single pole definite time static sensitive E/F relay, 12180 50N
1/2N HorzCASE
The above prices are Referral prices and not MRP. All Taxes and duties are extra.
####: This Price is only for Std O/V or UV Settings. Additional Prices applicable for Non Std Settings
**** PRICES APPLICABLE FOR DC Relay only
MICOM RELAYS PRICES ARE AVAILABLE ON REQUEST.
4
MiCOM ALSTOM Protection AGILE Feeder Management

ANSI Code Function P14NB P14NZ P14DB P14DG P14DL P14DZ P94VB P94VP
Nion Directional Directional Voltage &
Frequencx

50 Definite time overcurrent 6 6 6 6 6 6


50N Neutral/Earth definite time overcurrent 4 4 4 4 4 4
51 IDMT overcurrent 3 3 3 3 3 3
51N Neutral/Earth IDMT overcurrent 2 2 2 2 2 2
50/51SEF Sensitive earth fault 4 4 4 4 4 4
51V Voltage controlled overcurrent . . . .
50 SOTF Voltage restrained overcurrent . . .
68 Switch on to fault . . . . . .
In rush blocking . . . . . .
Cold load pick up . . . . . .
Load encroachment supervision (Load blinders) . .
HIF High impedance earth fault . .
46 Negative sequence overcurrent 4 4 4 4 4 4
46BC Broken conductor . . . . . .
Programmable curves 4 4 4 4 4 4
67 Directional phase overcurrent 6 6 6 6
67N Directional neutral overcurrent 4 4 4 4
Sensitive directional earth faul 4 4 4 4
Watt metric earth fault . . . .
Blocking scheme . . . . . .
37 Undercurrent detection (low load) . . . . . .
32 Phase directional power (Forward/Reverse/Under/Over 2 2 2
49 Thermal overload . . . . . .
50BF CB failure 2 2 2 2 2 2
21FL Fault locator . .
27 Under voltage 3 3 3 3 3 3
59 Over voltage 3 3 3 3 3 3
59N Residual over voltage 3 3 3 3 3 3
47 Negative sequence over voltage . . . . . .
Dv/Dt Rate of change of voltage 4 4 4
79 Auto reclose (number of shots) 4 4 4
25 Check synchronising . . . . .
81O Over frequency 9 9 9 9 9 9
81U Under frequency 9 9 9 9 9 9
81V Under voltage blocking of frequency protection . . . . . .
81 df/dt Rate of change of frequency with opitonal frequency 9 9 9 9 9 9
81Rf Supervision and averaging
81RAV
81R Frequency restoration 9 9 9
64N Restricted earth fault . . . .
87B High impedance busbar . .
PSL Programmable scheme logic . . . . . . . .
86 Latching output contacts (Lockout) . . . . . . . .
VTS VTSupervision . . . .
CTS CTSupervision . . . .
DCSupply supervision . . . . . . . .
CBCondition monitoring . . . . . .
Setting groups 4 4 4 4 4 4 4 4

* Prices Available on Request

5
MiCOM ALSTOM Protection Overcurrent & Feeder Management Relays

Device P141 P142 P143 P145

CT inputs 5 5 5 5
VT inputs 3 3 3/4 3/4
Opto inputs (max)1 8 16 32 32
Output contacts (max)1 7 15 30 32
Function keys/Hotkeys 2 2 2 12
Interlocking logic X X X X

Protection
Autoreclose 79 X X X X
Check synchronising 25 - - X X
3 Phase overcurrent 50/51P X X X X
Ground fault 50/51N X X X X
Phase directional 67P X X X X
Ground fault directionalr 67N X X X X
Sensitive directional earth fault 67N X X X X
Wattmetric Earth fault 67W X X X X
Neutral Admittance YN X X X X
Restricted Earth fault 64 X X X X
Voltage dependent overcurrent 51V X X X X
Negative sequence overcurrent 46 X X X X
Thermal overload 45 X X X X
Undercurrent 37 X X X X
Over/Under Voltage 27/59 X X X X
Residual overvoltage 59N X X X X
Negative sequence over voltage 47 X X X X
Over/Under frequency 810U X X X X
Rate of change of frequency 87R X X X X
Lock out 86 X X X X
Directional Power 32 X X X X
Circuit breaker failure 50BF X X X X
Broken conductor 46BC X X X X
Voltage Transformer Supervision VTS X X X X
Current Transformer Supervision CTS X X X X
Cold load pick-up X X X X
Inrush blocking X X X X
Switch on to fault SOTF X X X X
Circuit breaker monitoring X X X X
Trip Circuit Supervision TCS X X X X
Inter Micom X X X X

* Prices Available on Request

6
MiCOM ALSTOM Protection Motor & Generator Management Relays

Device P241 P242 P243 P341 P342 P343 P344 P345 P346
CT inputs 4 4 7 4 5 8 8 9 8
VT inputs 3 3 3 4 4 4 5 6 4
Opto inputs (max) 8 16 16 16 24 32 32 32 32
Output contacts (max) 7 16 16 15 24 32 32 32 32
RTDs (optional) 10 10 10 - 10 10 10 10 10
Analogue (optional) 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Function keys/Hotkeys X X X X X X X X X
Interlocking logic X X X X X X X X X
Protection
Motor Protection
Short circuit 50/51 X X X
Motor differential 87M X
Locked rotor 50S/51SLR/51S X X X
Reverse power 32R X X X - - - - - -
Reacceleration/LVride-through/Autorestart 27LV X X X - - - - - -
Startup monitoring/Excessive long start 66/48/51 X X X - - - - - -
Negative sequence overvoltage 47 X X X - - - - - -
Out of step 55 X X X - - - - - -
Loss of load 37 X X X - - - - - -
Under current 37P/37N X X X - - - - - -
Unbalance/Lock-out 30/46/86 X X X - - - - - -
Speed switch inputs 14 X X X - - - - - -
Anti back spin 27ABS X X X
Generator protection
Generator/Transformer differential 87GT - - - - - X X X X
Check synchronising 25 - - - - X X X X X
Interurn/split phase 50DT - - - - - X X X X
Under impedence 21 - - - - X X X X X
Polr slipping 78 - - - - - X X X -
Directional power 32 - - - X X X X X X
Loss of field 40 X X X - X X X X X
Restricted earth fault 64 - - - - X X X X X
100 stator earth fault 3rd harmonic 27TN/59TN - - - - - X X X -
100 stator earth fault low freq injector 64S - - - - - - - X -
Over fluxing 24 - - - - X X X X X
Unintentional energisation at standstil 50/27 - - - - X X X X X
Voltage opendent O/c 51V - - - - X X X X X
Rotor earth fault 64R - - - - X X X X X
Auxillary Functions
Phase overcurrent 50/51P X X X X X X X X X
Phase directional 67P - - - X X X X X X
Ground fault 50N/51N X X X X X X X X X
Sensitive directional earth fault 67N X X X X X X X X X
Wattmetric earth fault 64N/32N X X X X X X X X X
Negative sequence over current 460C X X X - X X X X X
Negative sequence thermal 46T - - - - X X X X X
Thermal overload 38/49 X X X X X X X X X
Under/Over voltage 27/59 X X X X X x X X X
Residual over voltage 59N X X X X X X X X X
Negative sequence over voltage 47 X X X X X X X X X
Under frequency 81U X X X X X X X X X
Over frequency 81D - - - X X X X X X
Turbine abnormal frequency 81AB - - - - X X X X X
Voltage vector shift Dv - - - X - - - - -
Rate of change of frequency 81R - - - X X X X X X
Circuit breaker fall and monitoring 50BF X X X X X X X X X
Loss of life/ Thru fault monitor LOL/Thru - - - X X X X X X
Dynamic line rating 49DLF - - - X - - - - -
Trip circuit supervision TCS X X X X X X X X X

* Prices Available on Request

7
MiCOM ALSTOM Protection Distance protection relays

Device P441 P442 P443 P444

CT inputs 4 4 4 4
VT inputs 4 4 4 4
Opto inputs (max)1 8 16 32 24
Output contacts (max)1 14 21 32 46
Function keys/Hotkeys X X X X
Protection
Distance Protection 21/21N X X X X
Phase Mho/Quad 21P -/X -/X X/X -/X
Ground Mho/Quad 21G -/X -/X X/X -/X
3 pole X - - -
Auto reclose 79
1/3 pole - X X X
Out-of step tripping 78 X X X X
Out-of step tripping 68 - - X X
Check synchronizing 25 X X X X
Switch on to fault 50/27 X X X X
Mutual compensation X X X X
Phaser Measurement PMU - - - -
Ancillary function X X X X
Phase overcurrent 50/51 X X X X
Phase directional 67P X X X X
Delta directional comparsion 1V - - X -
Ground fault 50/51N X X X X
Ground fault directional 67N X X X X
Negatrive sequence overcurrent 46 X X X X
Directional negative sequence 46/67 X X X X
Thermal overlload 49 X X X X
Under/Over voltage 27/59 X X X X
Residual over voltage 59N X X X X
Under/over frequency 81U/O - X X X
Rate of change of frequency 81R - - X -
Circuit breaker failure 50BF X X X X
Broken conductor 46BC X X X X
Stub Bus protection 50ST X X X X
Voltage/Current Transformer Supervision VTS/CTS X X X X
Capactive voltage Transformer Supervision CVTS X X - X
Channel Aided Scheme Logic 85 X X X X
Trip Circuit Supervision TCS X X X X
Inter Micom - X X X
* Prices Available on Request

8
B. Numerical Relays
MiCOM ALSTOM P14x

Feeder Protection

Application Model ANSI Code Price Input Output Case Size/Cut Out
Dimensions

FEEDER P141 50/51/67,50N/51N/67N, 67N, 67W, 170000 8 7 40 TE


YN, 64, 51V, 46, 49, 37P/37N, 27,
59, 59N, 47, 81U, 81O, 81R, BC,
50BF, VTS, CTS, 49SR, 50/51P
67P ,87R ,86 ,32
P142 50/51/67, 50N/51N/67N, 67N, 67W, 180000 8 7 40 TE
YN ,64, 51V, 46, 49, 37P/37N, 27,
59, 59N, 47, 81U, 81O, 81R, BC
50BF, VTS, CTS, 49SR, 79, 50/51P,
67P, 87R, 86, 32
P143 50/51/67, 50N/51N/67N, 67N, 67W, 196000 16 14 60 TE
YN, 64, 51V, 46, 49, 37P/37N, 27,
59, 59N, 47, 81U, 81O, 81R, BC,
50BF, VTS, CTS, 49SR, 79, 25,
50/51P, 67P, 87R, 86, 32
P144 50/51/67, 50N/51N/67N, 67N, 67W, 210000 8 7 60 TE
YN, 64, 51V, 46, 49, 37P/37N, 27,
59, 59N, 47, 81U, 81O, 81R, BC,
50BF, VTS, CTS, 49SR, 79, 50/51P,
67P, 87R, 86, 32
P145 50/51/67, 50N/51N/67N, 67N, 67W, 239500 16 16 60 TE
YN, 64, 51V, 46, 49, 37P/37N, 27,
59, 59N, 47, 81U, 81O, 81R, BC,
50BF, VTS, CTS, 49SR, 79, 25,
50/51P, 67P, 87R, 86, 32

ALL PRICES ARE INCLUSIVE OF ALL TAXES AND DUTIES

9
MiCOM ALSTOM P24x

Motor Protection

P241 in 40 TE P241 in 80 TE

Application Model ANSI Code Price Input Output Case Size/Cut Out
Dimensions

MOTOR P241 50/51, 50N/51N, 50N/51N/67N, 136500 8 7 40 TE


32N/64N, 50BF, 66, 37, 46, 32R, without
47, 49, 27/59, 59N, 81U, 48/51LR, RTD,
51S, 14, 26 185500
with RTD
P242 50/51, 50N/51N, 50N/51N/67N, 220000 16 16 60 TE
32N/64N, 50BF, 66, 37, 46, 32R,
47, 49, 27/59, 59N, 81U, 48/51LR,
51S, 14, 26
P243 50/51, 50N/51N, 50N/51N/67N, 279500 16 16 80 TE
32N/64N, 50BF, 66, 37, 46, 32R, 47
49, 87, 27/59, 59N, 81U, 48/51LR,
51S, 14, 26

ALL PRICES ARE INCLUSIVE OF ALL TAXES AND DUTIES

10
MiCOM ALSTOM P34x

Interconnection & Generator Protection

MiCOM ALSTOM P34x

Application Model ANSI Code Price Input Output Case Size/Cut Out
Dimensions

INTERCON- P341 81R, ∆Vθ, 50/51/67, 50N/51N/67N, 310000 8 7 40 TE


NECTION 67N/67W, 64, 59N, 27/59, 81U/81O
& GENERATOR 32R/32L/32O, 49, 46, 47, 50BF
P342 50/51/67, 50N/51N, 67N/67W, 64, 359500 8 7 40 TE
51V, 21, 59N, 27/59, 81U/81O,
81AB, 32R/32L/32O, 40, 46T, 46OC,
47, 49, 24, 50BF, 49G, 49T, 64R,
81R, 37P/37N, 25
P343 87, 50/51/67, 50N/51N, 67N/67W 439000 16 14 60 TE,
64, 51V, 21, 59N, 27/59, 81U/81O,
81AB, 32R/32L/32O, 40, 46T, 46OC,
47, 49, 24, 78, 27TN/59TN, 50/27,
50BF, 49G, 49T, 64R, 81R,
37P/37N, 25
P344 87, 50/51/67, 50N/51N, 67N/67W, 469000 24 24 80 TE
64, 51V, 21, 59N, 27/59, 81U/81O,
81AB, 32R/32L/32O, 40, 46T, 46OC,
47, 49, 24, 78, 27TN/59TN, 50/27,
50BF, 49G, 49T, 64R, 81R, 37P/37N,
25
P345 87, 50/51/67, 50N/51N, 67N/67W, 519000 24 24 80 TE
64, 51V, 21, 59N, 27/59, 81U/81O,
81AB, 32R/32L/32O, 40, 46T, 46OC,
47, 49, 24, 78, 27TN/59TN, 50/27,
50BF, 64S, 49G, 49T, 64R, 81R,
37P/37N, 25
P346 87, 50/51/67, 50N/51N, 67N/67W, 399000 16 14 60 TE
64, 51V, 21, 59N, 27/59, 81U/81O,
81AB, 32R/32L/32O, 40, 46T, 46OC,
47, 49, 24, 50BF, 49G, 49T, 64R,
81R, 37P/37N, 25

ALL PRICES ARE INCLUSIVE OF ALL TAXES AND DUTIES

11
MiCOM ALSTOM P44x

40 TE case Distance Protection 80 TE case

Application Model ANSI Code Price Input Output Case Size/Cut Out
Dimensions

DISTANCE P441 21P, 21G, 50/51/67, 50N/51N/67N, 299500 8 14 40 TE


67N, 32N, 67/46, 68, 50/27, 85, 49,
79, 25, 27, 59, 46BC, 50ST, 50BF,
VTS, CVTS, CTS, 51FF, 21/21N, 78,
50/51P, 67P, 46, 59N
P442 21P, 21G, 50/51/67, 50N/51N/67N, 359500 16 21 60 TE
67N, 32N, 67/46, 68, 50/27, 85, 49,
79, 25, 27, 59, 37, 81U/O, 46BC,
50ST, 50BF, VTS, CVTS, CTS, 51FF,
21/21N, 78, 50/51P, 67P, 46, 59N
P443 21P/21G, 85, 50/27, 68, 78, ∆I/∆V, 558600 16 24 80 TE
67N, 50/51/67, 50N/51N/67N, 67/46,
46BC, 49, 27, 59, 59N, 50BF,
CTS/VTS, 79, 25, FL, 21/21N, 78,
50/51P, 67P, 46, 59N, 81R
P444 21P, 21G, 50/51/67, 50N/51N/67N, 499000 24 32 80 TE
67N, 32N, 67/46, 68, 50/27, 85, 49,
79, 25, 27, 59, 37, 81U/O, 46BC,
50ST, 50BF, VTS, CVTS, CTS, 51FF,
21/21N, 78, 50/51P, 67P, 46, 59N
P445 21P/21G, 85, 50/27, 68, 67N, 598500 8 8 40 TE
50/51/67, 50N/51N/67N, 67/46, 46BC,
49, 27, 59, 59N, 50BF, CTS/VTS, 79,
25, FL, 21/21N, 78, 50/51P, 67P, 46,
59N, 81R

ALL PRICES ARE INCLUSIVE OF ALL TAXES AND DUTIES

12
MiCOM ALSTOM P64x

Application Model ANSI Code Price Input Output Case Size/Cut Out
Dimensions

TRANSFORMER P642 87T, 64, 49, 24, 50/51, 50N/51N, 279500 8 8 40 TE


46, 50BF, CTS, TCS, 87G/64,
50/51P
P643 87T, 64, 49, 24, 50/51, 50N/51N, 379000 16 16 60 TE
46, 67/67N, 50BF, 27/59/59N,
81U/81O, VTS, CTS, TCS, 87G/64,
50/51P, 67P
P645 87T, 64, 49, 24, 50/51, 50N/51N, 459000 16 16 60 TE
46, 67/67N, 50BF, 27/59/59N,
81U/81O, VTS, CTS, TCS, 87G/64,
50/51P, 67P
MX3DPT3A 87T ,50BF 154000

ALL PRICES ARE INCLUSIVE OF ALL TAXES AND DUTIES

13
MX RANGE

Application Description Model ANSI Code Price


Number
Multifunction numerical 3 Phase current and earth MX3AJ30A 49-49-50-51-51-
fault relay for HV,MV,LV cables and machinery. MX3AJ30F 37-50N-51N-51N

Numerical protection and control for MV and MX3AJM30A 49-49-49-50-46-


LV motors 51R-37-51N-66

Multifunction numerical 3 Phase and earth fault MX3AM30A 50-51-51-50N-


over current relay for HV,MV,LV applications 51N-51N

Multifunction numerical sensitive directional earth MX3AMD0A 67N-67N-67N-59N


fault relay for HV,MV,LV applications

Multifunction numerical 3 Phase directional MX3AMD3A 67-67-67


overcurrent relay for HV,MV,LV applications

Multifunction numerical 2 Phase directional MX3AMD20A 67-67-67-67N- On request


overcurrent ans sensitive directional earth fault 67N-67N-59N
relay for HV,MV,LV applications

Multifunction numerical 3 Phase overcurrent and MX3AMD30A 51-51-50-67N-67N


sensitive directional earth fault relay for HV,MV,LV -67N-59N
applications

Numerical 3 phase biased differential protection MX3DPT3A 87T


for two windings transformer application

Numerical high impedance differential for MX3DVZ3A 87S(51N-51N-27


-59 50BF)

Numerical module for automatic synchronizing MX3EG1A 90F-90U-25


of generators

Numerical 3 Phase biased differential protection MX3DPG3A 87G


for generator and motor application

ALL PRICES ARE INCLUSIVE OF ALL TAXES AND DUTIES

14
A Single window solution for every electrical installation

SYSTEM CONTROLS & SWITCHGEARS


30 / 30, GF East Patel Nagar, New Delhi - 110 008
Phone: 45631920 (100 lines), Fax: 45631903
E-mail : system.controls@gmail.com
Customer Care: 9717003397, custcare.scs@gmail.com
Website : www.systemcontrols.co.in

Channel Partner

TRINITY
Making Energy Matters

A Brand of
Schneider
Electric
PIERLITE

UNIVERSAL
TRANSFORMER
CABLES

You might also like