Page 1 of 3 Cover Sheet 03/12/2019 06:49:20

Calculations Cover Sheet *


*Light yellow cells are to be edited by the user.

Client Project No.

Calculation Title:

Calculation Identifier:
Originator Checker
Rev. No. Signature/Date Signature/Date
0
1
2
3
4

Seal and Signature (if Req’d)


Comments:

Information Requiring Confirmation:

file:///conversion/tmp/scratch/411680450.xls
Page 2 of 3 Example Calc 03/12/2019 06:49:20
* Fill out light yellow portions of worksheet. Light green shaded cells are protected formulas. To add rows, highlight one row from Column B to AA and click in the lower right hand corner of the highlighted cells and drag down the desired number of new rows.

Revisions
Revision No. Revision By: Description: Date: Checked By:
1 JDoe Modified air flow rates in duct sections 10-12. 10-Oct-09 See Cover Sheet

PROJECT NAME: ABC Tower TEMPERATURE: 70 DEGREES F G - GALVANIZED (SPIRAL SEAM) DUCT ABSOLUTE ROUGHNESS FACTOR: 0.0003 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
PROJECT NUMBER 123456 ELEVATION: 600 FT. A - ALUMINUM, CARBON STEEL, PVC DUCT ABSOLUTE ROUGHNESS FACTOR: 0.0001 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
TAG NUMBER: 50AHU80200 PRESSURE DROP CRITERIA: 0.08 IN. W.C. PER 100 FT. C - CONCRETE OR FLEXIBLE DUCT ABSOLUTE ROUGHNESS FACTOR: 0.01 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
CALCULATED BY: John Doe, PE VELOCITY CRITERIA: 2,000 FPM
DATE: 1-Sep-09 SAFETY FACTOR: 10 PERCENT F - FRP DUCT OR DUCT LINER ABSOLUTE ROUGHNESS FACTOR: 0.003 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
QC REVIEW BY: See Cover Sheet ABSOLUTE AIR PRESSURE: 29.277 In Hg S - STAINLESS STEEL DUCT ABSOLUTE ROUGHNESS FACTOR: 0.0002 ft (Extrapolated from ASHRAE 2009 Fundamentals: Chap 21, Table 1)
DATE: See Cover Sheet CORRECTED AIR DENSITY: 0.073 lbm/ft3 O - OTHER DUCT ABSOLUTE ROUGHNESS FACTOR: 0.030 ft (Manual Input Value)

Duct Fitting Duct Duct Duct Airflow Rectangular Duct Flat Oval Duct Round Equivalent Hydraulic Actual Duct Velocity Calculated Friction Factors Duct Fitting Loss Other Duct Pressure Duct Pressure Section Pressure
Section Number Material Roughness Element Width Height Major Minor Diameter Diameter Diameter Velocity Pressure Reynold's f' f Length Coefficient Losses Drop Drop Press. Drop Loss Velocity
E, ft (CFM) (in) (in) (in) (in) (in) (in) (in) (FPM) (In W.C.) Number (ft) (In W.C.) (In W.C./ft) (In W.C./100 ft) (In W.C.) Test Test
1 SR7-7 A 0.0001 Fan Discharge with elbow down 3,250 36 24 32 29 542 0.018 132,600 0.017 0.017 1.24 0.0001 0.013 0.022
2 SR4-2 A 0.0001 Transition - AHU to Duct in horizontal 3,250 36 24 32 29 542 0.018 132,600 0.017 0.017 0.08 0.0001 0.013 0.001
3 A 0.0001 Duct - Straight - horizontal 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 9 0.0008 0.080 0.007
4 A 0.0001 Elbow - up - 90 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 0.33 0.0008 0.080 0.027
5 A 0.0001 Duct - Straight - vertical up 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 11 0.0008 0.080 0.009
6 A 0.0001 Elbow horizontal - 90 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 0.33 0.0008 0.080 0.027
7 A 0.0001 Duct - Straight - horizontal 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 2 0.0008 0.080 0.002
8 A 0.0001 Elbow horizontal - 90 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 0.33 0.0008 0.080 0.027
9 A 0.0001 Tee - Run - horizontal 3,250 20 20 22 20 1170 0.083 200,304 0.016 0.016 0.87 0.0008 0.080 0.072
10 A 0.0001 Duct - Straight - horizontal 1,550 20 20 22 20 558 0.019 95,530 0.018 0.018 8 0.0002 0.021 0.002
11 A 0.0001 Elbow - down - 90 8,000 20 20 22 20 2880 0.503 493,056 0.013 0.014 0.33 0.0042 0.420 0.166 TOO FAST
12 A 0.0001 Duct - Straight - vertical down 8,000 20 20 22 20 2880 0.503 493,056 0.013 0.014 12 0.0042 0.420 0.050 TOO HIGH TOO FAST
13 A 0.0001 Damper 1,550 20 20 22 20 558 0.019 95,530 0.018 0.018 3.30 0.0002 0.021 0.062
14 A 0.0001 Supply Grille 1,550 20 20 22 20 558 0.019 95,530 0.018 0.018 0.15 0.0002 0.021 0.150
14 A 0.0001 Counterbalance Back draft Damper 750 18 18 20 18 333 0.007 51,360 0.021 0.021 0.025 0.0001 0.010 0.025
14 A 0.0001 Exhaust Louver 750 18 18 20 18 333 0.007 51,360 0.021 0.021 0.08 0.0001 0.010 0.080

Note: This table created for the use of calculating static pressure loss in air systems. The worksheet Total
will calculate the columns that are shaded light green and protected: Equivalent Round Duct Size, Duct Velocity, Press. Drop
Velocity Pressure, Reynolds Number, Duct Friction, Duct Section Pressure Drop, and Total System Pressure drop. (In W.C.)
Simply add the duct absolute roughness factor from ASHRAE and add any additional losses. 0.73
Safety Factor 0.07
Total S.P.: 0.80

file:///conversion/tmp/scratch/411680450.xls
Page 3 of 3 Pressure Drop, IP 03/12/2019 06:49:20
* Fill out light yellow portions of worksheet. Light green shaded cells are protected formulas. To add rows, highlight one row from Column B to AA and click in the lower right hand corner of the highlighted cells and drag down the desired number of new rows.

Revisions
Revision No. Revision By: Description: Date: Checked By:

PROJECT NAME: TEMPERATURE: 70 DEGREES F G - GALVANIZED (SPIRAL SEAM) DUCT ABSOLUTE ROUGHNESS FACTOR: 0.0003 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
PROJECT NUMBER ELEVATION: 600 FT. A - ALUMINUM, CARBON STEEL, PVC DUCT ABSOLUTE ROUGHNESS FACTOR: 0.0001 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
TAG NUMBER: PRESSURE DROP CRITERIA: 0.08 IN. W.C. PER 100 FT. C - CONCRETE OR FLEXIBLE DUCT ABSOLUTE ROUGHNESS FACTOR: 0.01 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
CALCULATED BY: VELOCITY CRITERIA: 2,000 FPM
DATE: SAFETY FACTOR: 10 PERCENT F - FRP DUCT OR DUCT LINER ABSOLUTE ROUGHNESS FACTOR: 0.003 ft (Taken From ASHRAE 2009 Fundamentals: Chap. 21, Table 1)
QC REVIEW BY: ABSOLUTE AIR PRESSURE: 29.277 In Hg S - STAINLESS STEEL DUCT ABSOLUTE ROUGHNESS FACTOR: 0.0002 ft (Extrapolated from ASHRAE 2009 Fundamentals: Chap 21, Table 1)
DATE: CORRECTED AIR DENSITY: 0.073 lbm/ft3 O - OTHER DUCT ABSOLUTE ROUGHNESS FACTOR: 0.030 ft (Manual Input Value)

Duct Fitting Duct Duct Duct Airflow Rectangular Duct Flat Oval Duct Round Equivalent Hydraulic Actual Duct Velocity Calculated Friction Factors Duct Fitting Loss Other Duct Pressure Duct Pressure Section Pressure
Section Number Material Roughness Element Width Height Major Minor Diameter Diameter Diameter Velocity Pressure Reynold's f' f Length Coefficient Losses Drop Drop Press. Drop Loss Velocity
E, ft (CFM) (in) (in) (in) (in) (in) (in) (in) (FPM) (In W.C.) Number (ft) (In W.C.) (In W.C./ft) (In W.C./100 ft) (In W.C.) Test Test
1 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
2 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
3 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
4 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
5 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
6 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
7 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
8 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
9 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
10 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
11 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
12 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
13 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
14 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
15 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000
16 0.0000 0 0 0 0.000 0 0.000 0.003 0.0000 0.000 0.000

Note: This table created for the use of calculating static pressure loss in air systems. The worksheet Total
will calculate the columns that are grayed out and protected: Equivalent Round Duct Size, Duct Velocity, Press. Drop
Velocity Pressure, Reynolds Number, Duct Friction, Duct Section Pressure Drop, and Total System Pressure drop. (In W.C.)
Simply add the duct absolute roughness factor from ASHRAE and add any additional losses. 0.00
Safety Factor 0.00
Total S.P.: 0.00