SHEDULE OF LOADS

PB1 and PB2 (Typical)

Circuit Qty. Load Description VA Current V Phase Protection Conductor


No.
1 3 Lighting outlets 300 1.30 230 1P 15A ACB 2- 3.5 sq. mm THHN wire + 1- 2.0 sq mm THHN (G)
2 4 Convenience outlets 1440 6.26 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
3 1 Spare 2070 9.00 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
4 1 Spare 2070 9.00 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)

Total 25.56 230 1P 60A ACB 2- 14 sq. mm THW wire + 1- 8.0 sq mm THW (G)

It = 25.56(1.25) = 31.95 amps.


Use: 2 No. 14 sq mm THW wire + 1 – 8.0 sq mm THW wire (G) with 60 A 2P ACB as main disconnect

PB3

Circuit Qty. Load Description VA Current V Phase Protection Conductor


No.
1 6 Lighting outlets 600 2.60 230 1P 15A ACB 2- 3.5 sq. mm THHN wire + 1- 2.0 sq mm THHN (G)
2 6 Lighting outlets 600 2.60 230 1P 15A ACB 2- 3.5 sq. mm THHN wire + 1- 2.0 sq mm THHN (G)
3 6 Lighting outlets 600 2.60 230 1P 15A ACB 2- 3.5 sq. mm THHN wire + 1- 2.0 sq mm THHN (G)
4 7 Convenience outlets 2520 10.95 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
5 7 Convenience outlets 2520 10.95 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
6 1 Spare 2070 9.00 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
7 1 Spare 2070 9.00 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)

Total 47.70 230 1P 70A ACB 2- 22 sq. mm THW wire + 1- 8.0 sq mm THW (G)

It = 47.70(1.25) = 59.62 amps.


Use: 2 No. 22 sq mm THW wire + 1 – 8.0 sq mm THW wire (G) with 70 A 2P ACB as main disconnect
PB4

Circuit Qty. Load Description VA Current V Phase Protection Conductor


No.
1 8 Lighting outlets 800 3.47 230 1P 15A ACB 2- 3.5 sq. mm THHN wire + 1- 2.0 sq mm THHN (G)
2 6 Lighting outlets 600 2.60 230 1P 15A ACB 2- 3.5 sq. mm THHN wire + 1- 2.0 sq mm THHN (G)
3 4 Convenience outlets 1440 6.26 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
4 1 Water pump outlet 2760 12.00 230 1P 30A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)
5 1 Spare 1500 6.52 230 1P 20A ACB 2- 5.5 sq. mm THHN wire + 1- 3.5 sq mm THHN (G)

Total 30.85 230 1P 60A ACB 2- 14 sq. mm THW wire + 1- 8.0 sq mm THW (G)

It = 30.85(1.25) = 38.56 amps.


Use: 2 No. 14 sq mm THW wire + 1 – 8.0 sq mm THW wire (G) with 60 A 2P ACB as main disconnect

MDP (Main Distribution Panel Board – Entire Building)

Feeder Qty. Load Description VA Current V Phase Protection Conductor


No.
1 1 PB1 5880 25.56 230 1P 60A ACB 2- 14 sq. mm THW wire + 1- 8.0 sq mm THW (G)
2 1 PB2 5880 25.56 230 1P 60A ACB 2- 14 sq. mm THW wire + 1- 8.0 sq mm THW (G)
3 1 PB3 10980 47.70 230 1P 70A ACB 2- 22 sq. mm THW wire + 1- 8.0 sq mm THW (G)
4 1 PB4 7100 30.85 230 1P 60A ACB 2- 14 sq. mm THW wire + 1- 8.0 sq mm THW (G)

Total 129.67 230 1P 175A ACB 2- 80 sq. mm THW wire + 1- 22 sq mm THW (GEC)

It = 129.67(1.25) = 162.08 amps.


Use: 2 No. 80 sq mm THW wire + 1 – 22 sq mm THW wire (GEC) with 175 A 2P ACB as main disconnect