PRELIMINARY DESIGN FIRE WATER TANK FOUNDATION

Equipment data

Equipment Size:
ID Inside diameter 44,000 mm
OD Outside diameter 44,016 mm
H Total Height 17,070 mm

Estimated Weight based on Mechanical\:


W(E) Empty 4,905.0 kN
W(O) Operating 249,174.0 kN
W(T) Testing 257,022.0 kN

Estimated Weight (with contigency 10%):


W(E) Empty 5,395.5 kN
W(O) Operating 274,091.4 kN
W(T) Full of Water 282,724.2 kN

Loading Data

Axial Load:
D Footing weight 39,121.19 kN
W(E) Empty 5,395.50 kN
W(O) Operating 274,091.40 kN
W(T) Full of Water 282,724.20 kN
Lateral Load:
Wx Wind force at X direction 342.03 kN
Wy Wind force at Y direction 342.03 kN
Eqex Base shear in empty cont'd at X dir. 48.44 kN
Eqey Base shear in empty cont'd at Y dir. 48.44 kN
Eqox Base shear in operating cont'd at X dir. 24,359.42 kN
Eqoy Base shear in operating cont'd at Y dir. 24,359.42 kN
Overturning Moment:
Mwx Moment due to wind load in X dir. 3,261.23 kN.m
Mwy Moment due to wind load in Y dir. 3,261.23 kN.m
MEqex Mom' due to EQ in emp' cond' in X dir. 461.91 kN.m
MEqey Mom' due to EQ in emp' cond' in Y dir. 461.91 kN.m
MEqox Mom' due to EQ in opr' cond' in X dir. 232,267.12 kN.m
MEqoy Mom' due to EQ in opr' cond' in Y dir. 232,267.12 kN.m

Load Combination

Factored Load Combination


The following factored load combination is used to design concrete reinforcement by Ultimate Strength
Design method:
Empty Condition:
LC1-1 1.4D + 1.4E(E)
LC1-2 0.9D + 0.9E(E) + 1.6W
LC1-3 0.9D + 0.9E(E) + EQ
Operating Condition:
LC1-4 1.4D + 1.4 E(O)
LC1-5 1.2D + 1.2E(O) + 0.8W
LC1-6 0.9D + 0.9E(O) + 1.3W
LC1-7 1.2D + 1.2E(O) + EQ
LC1-8 0.9D + 0.9E(O) + EQ
Test Condition:
LC1-9 0.9D + 0.9E(T) + 1.6W

Unfactored Load Combination


The following unfactored load combination is used to check piling stability capacity by Allowable Stress Design

Empty Condition: Increase in Allowable Stress


LC2-1 D + E(E) 1.00
LC2-2 D + E(E) + W 1.33
LC2-3 D + E(E) + EQ 1.33
Operating Condition:
LC2-4 D + E(O) 1.00
Operating Condition + Wind:
LC2-5 D + E(O) + W 1.33
Operating Condition + Earthquake:
LC2-6 D + E(O) + EQ 1.33
Test Condition:
LC2-7 D + E(T) + 0.25W 1.33
LC2-8 D + E(T) 1.00

Spun Pile 500 mm , depth 24 m


Compression Capacity of spun pile with 500 mm Ø at depth 24m is based on material pile capacity.

Condition Qcomp Qtens Qlat


( kN ) ( kN ) ( kN )
Allowable Capacity :
Permanent 1629.98 -119.80 108.00
Temporary, increase 33% from permanent 2167.87 -155.74 140.40

Footing Data

B pilecap diameter 46.00 m


tf pilecap thickness 1.00 m
n Number of pile 248 ea
Dpp Pile to pile maximum distance 4.00 m
ODp Pile diameter 0.50 m
Lpi Pile Length 24 m

Use D22 - 175 for top and bottom flexural reinforcement