The range of Autel’s electronic control devices is wide enough to satisfy the demands both of
small and big dimensions plants. Autel makes three models of cyclical Timers: The economic
and compact timer Mod. STR-REC, the cyclical economic generators GC and the single-exit
TC. The reliable STR-REC are compact and available from a minimun of 2 to a maximum of 6
exits, but they can be extended through REC expansion (remote expansion control), thus they
are suitable for being used in small and medium dimensions plants. The cyclical generators GC
have been planned for the continuous and sequencial control and they allow the layout of the
pause and working times through graduated grips. This device can be supplied in different
models which can control from a minimun of 2 to a maximun of 96 electrovalves, so that they
can be used both in small and in big dimensions plants. For very big plants, Autel can build, on
demand, expansions which allow the timers to control more than 96 electrovalves. The cyclical
generator TC is a very simple and reliable single-exit timer, which has been planned for the
direct application on the valve to be driven. Autel advices to use Ecomatic, planned for the
intelligent piloting of the filtration plants, which allows a saving in terms of energetic
consumption of the compressed-air in filters These devices are able to pilot the electrovalves
and they include a differencial pressure gauge . This latter allows the direct control of the
obstruction degree of the filter and it allows the cleaning process only when and where it is
necessary. This intelligent device is able to recognise the outputs in which a load is applied ,
thus it can command automatically and directly only the exits effectively used. This device can
be supplied in different models and it can control from a min. of 2 to a max. of 96 electrovalves,
thus it can be used both in small and in big dimensions plants. On demand, it is possible to
applied to the Ecomatic expansion modules in order to guarantee the control of more than 96
electrovalves, thus being used in bigger dimensions plants .

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

General Description
The ECOMATIC Economizers, planned for the management of filtration systems, built-in
differential pressure gauge able to control the filter level of obstruction. The device will command
only outputs connected to a load and the sequence will be automatically regulated. The
differential pressure measuring device will start the cycle-generator only when necessary. The
start and end washing pressure, post-cleaning pressure, alarm pressure and pause-times,
operation time and post-cleaning time are adjustable through 3 keys and 3-digits display.
Moreover other programmable functions are available.

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

AVAILABLE MODELS

Models MAX CONTROLLABLE Weight (Kg)


OUTPUTS NUMBER
ECO 4 4 Electrovalves 1,3
ECO 6 6 Electrovalves 1,3

ECO 12 12 Electrovalves 2,0

ECO 20 20 Electrovalves 4,3

ECO 32 32 Electrovalves 4,3

ECO 64 64 Electrovalves 4,6

ECO 96 96 Electrovalves 6,0

Technical specifications
Protection rating IP 56
Power supply 24 Vac +/- 10%, 45-60Hz or 115 Vac +/- 10%, 45-60Hz or
230 Vac +/- 10%, 45-60Hz
24 Vdc power supply available on request
Absorbed power 30VA
Fuse F1 e F2¹ = 2A 5x20 quick acting
Operating temperature -10/+50 °C
Connection Screw type terminal boards
PAUSE time Duration: 1 - 999 sec Precision: 0,01 sec
OPERATION time Duration: 0.03 - 9.99 sec Precision: 0,01 sec
POST-CLEANING Time Duration: 0 - 999 sec Precision: 0,01 sec
Outputs Triac with zero-crossing activation/deactivation 24, 115 or 230 Vac
with max. current 2A.
Transistor type for versions designed to control 24 Vdc solenoid
valves (optional).
Alarm relay outputs 1A resistance load 115 Vac
Hour counter range 0 – 99999 hours
Cycle counter range 0 – 99999 cycles
Nominal measurement range From -99 to 999 mmH2O
Accuracy ± 1% F.S. , ± 1 digit
Max applicable pressure 0,5 bar

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out

80
9 10 11
5 55 25

12

1 2 3 4 P A
16 21
RETE CARICHI
POWER LOADS

F1 F2 Dimensions in mm
OUTPUT
4-20mA
_ 1
+
C 1 2 3 4

6,8

195
8 7 6 5 4 15 3 2

125
13

70
62
148
172
14

Weight 1,3Kg
ECO 4: the instrument is supplied with 2 fixing brackets which can be mounted as required
in one of the four positions indicated in the drawing

Key
1 - F1 Mains fuse 8 - Output active LED
F2 Load protection fuse 9 - Decrease key ( ↓ )
2 - Power supply terminal board 10 - 3-digit display
3 - Post-cleaning input from remote contactor 11 - Increase key ( ↑ )
(on = post-cleaning; off = stop) 12 - Enter Key ( E )
4 - Alarm output (relay changeover contact) 13 - Fixing bracket
5 - Power On LED 14 - Pneumatic union
6 - Pause LED 15 - 4-20mA output (optional)
7 - Pilot connection terminal board

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out ECO6
80
9 10 11
5 55 25

12

1 2 3 4 5 6 P A
16 21
RETE CARICHI
POWER LOADS

F1 F2 Dimensions in mm
Dimensions in mm
OUTPUT
4-20mA
_ 1
+
C 1 2 3 4 5 6

6,8

8 7 6 5 4 15 3 2 195

13
125

70
62
148
172
14
Weight 1,3 Kg

ECO 6: the instrument is supplied with 2 fixing brackets which can be mounted as required
in one of the four positions indicated in the drawing

Key
1 - F1 Mains fuse 8 - Output active LED
F2 Load protection fuse 9 - Decrease key ( ↓ )
2 - Power supply terminal board 10 - 3-digit display
3 - Post-cleaning input from remote contactor 11 - Increase key ( ↑ )
(on = post-cleaning; off = stop) 12 - Enter Key ( E )
4 - Alarm output (relay changeover contact) 13 - Fixing bracket
5 - Power On LED 14 - Pneumatic union
6 - Pause LED 15 - 4-20mA output (optional)
7 - Pilot connection terminal board

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out

9 10 11

15
12
4

1 2 3 4 5 6 7 8 9 P A

3
RETE
POWER

C1 2 3 4 5 6 C 7 8 9 F1
1
CARICHI F2
Dimensions in mm
LOADS

8 7 6 5 2

6,8

13

195
217

14
Weight 2Kg
ECO 12 : The instrument is supplied with 4 fixing brackets.

Key
1 - F1 Mains fuse 8 - Output active LED
F2 Load protection fuse 9 - Decrease key ( ↓ )
2 - Power supply terminal board 10 - 3-digit display
3 - Post-cleaning input from remote contactor 11 - Increase key ( ↑ )
(on = post-cleaning; off = stop) 12 - Enter Key ( E )
4 - Alarm output (relay changeover contact) 13 - Fixing bracket
5 - Power On LED 14 - Pneumatic union
6 - Pause LED 15 - 4-20mA output (optional)
7 - Pilot connection terminal board

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out ECO 20

Dimensions in mm

Weight 4,3 Kg

ECO 20 : The instrument is supplied with 4 fixing brackets.

Key
1 - F1 Mains fuse 8 - Output active LED
F2 Load protection fuse 9 - Decrease key ( ↓ )
2 - Power supply terminal board 10 - 3-digit display
3 - Post-cleaning input from remote contactor 11 - Increase key ( ↑ )
(on = post-cleaning; off = stop) 12 - Enter Key ( E )
4 - Alarm output (relay changeover contact) 13 - Fixing bracket
5 - Power On LED 14 - Pneumatic union
6 - Pause LED 15 - 4-20mA output (optional)
7 - Pilot connection terminal board

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out ECO 32

Dimensions in mm

Weight 4,3 Kg

ECO 32 : The instrument is supplied with 4 fixing brackets.

Key
1 - F1 Mains fuse 8 - Output active LED
F2 Load protection fuse 9 - Decrease key ( ↓ )
2 - Power supply terminal board 10 - 3-digit display
3 - Post-cleaning input from remote contactor 11 - Increase key ( ↑ )
(on = post-cleaning; off = stop) 12 - Enter Key ( E )
4 - Alarm output (relay changeover contact) 13 - Fixing bracket
5 - Power On LED 14 - Pneumatic union
6 - Pause LED 15 - 4-20mA output (optional)
7 - Pilot connection terminal board

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out ECO64

20

_ +
C 1 2 3 4 5 6 7 8 C 9 C C

Dimensione
Dimensions in in
mm mm

6,8

17

310
332
18

Weight 4,6 Kg
Peso 4,6Kg

ECO 64: The instrument is supplied with 4 fixing brackets.

Key

1 - F1 Mains fuse 12 - Enter Key (E)


F2 Load protection fuse 13 - Connectors for economiser
2 - Power supply terminal board connection to expansion card
3 - Post-cleaning input from remote contactor 14 - Terminal board for connection of
(on = post-cleaning; off = stop) solenoid valves on expansion card
4 - Alarm output (relay changeover contact) 15 - Connectors for expansion card
5 - Power On LED connection to economiser
6 - Pause LED 16 - Expansion card output active LED
7 - Pilot connection terminal board 17 - Fixing bracket
8 - Output active LED 18 - Pneumatic coupling
9 - Decrease key (↓) 19 - 4-20mA output (optional)
10 - 3-digit display 20 - Tribo-electric input (optional)
11 - Increase key (↑)

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
ECONOMIZER ECOMATIC
DEVICES

Lay-out ECO96

9 10 11 6 15 16 14 15 16

13

C
C
13

C
13
12
RETE CARICHI
1 2 3 4 5 6 7 8 9 POWER LOADS
8

C
F1 F2 1
5 _+
C 1 2 3 4 5 6 7 8 C 9 C C

C
C

C
3 19 4 7 2

C
15 14 15

17

18

6,8

Dimensions in mm

310 310

647
Weight 6 Kg

ECO 96: The instrument is supplied with 4 fixing brackets.

Key

1 - F1 Mains fuse 12 - Enter Key (E)


F2 Load protection fuse 13 - Connectors for economiser
2 - Power supply terminal board connection to expansion card
3 - Post-cleaning input from remote contactor 14 - Terminal board for connection of
(on = post-cleaning; off = stop) solenoid valves on expansion card
4 - Alarm output (relay changeover contact) 15 - Connectors for expansion card
5 - Power On LED connection to economiser
6 - Output active LED 16 - Expansion card output active LED
7 - Pilot connection terminal board 17 - Fixing bracket
8 - Output active LED 18 - Pneumatic coupling
9 - Decrease key (•) 19 - 4-20mA output (optional)
10 - 3-digit display
11 - Increase key (•)

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
DEVICES

Notes:

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

General Descrption

The GC sequential timers are electronic instruments comprising a microprocessor card designed to
control solenoid valves for filtration systems. These devices command only the outputs connected to a
load and the sequence will be automatically regulated. Two knobs with a graduated scale enable the
user to set the pause time and the operation time. On request they can also be equipped with a post-
cleaning input.
The duration of the post-cleaning cycle is variable (up to 30 min) and it can be set by means of a third
potentiometer mounted on the frontal panel of the board. The device is equipped with LEDs to display
activation of outputs, pause phases and power on.
All sequential timers are designed with AC solenoid valve outputs; the output stage comprises triacs
with zero-crossing activation/deactivation to reduce disturbance. Versions are available on request with
transistor type output stages for solenoid valves with 24 V dc operating voltage. Each model is
supplied with a polycarbonate enclosure with transparent lids and IP56 protection rating.

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

AVAILABLE MODELS

Models MAX CONTROLLABLE Weight (Kg)


OUTPUTS NUMBER
GC 4 P 4 Electrovalves 1,2
GC 6 P 6 Electrovalves 1,2

GC 12 P 12 Electrovalves 2,0

GC 20 P 20 Electrovalves 4,3

GC 32 P 32 Electrovalves 4,3

GC 64 P 64 Electrovalves 4,6

GC 96 P 96 Electrovalves 6,0

Technical specifications

Protection rating IP 56
Power supply 24 Vac +/- 10%, 45-60Hz or 115 Vac +/- 10%, 45-60Hz or
230 Vac +/- 10%, 45-60Hz
24 Vdc power supply available on request
Absorbed power 30VA
Fuse F1 and F2¹ = 2A 5x20 quick acting
Operating temperature -10/+50 °C
Connection Screw type terminal boards
PAUSE time Duration: 0.05 - 180 sec
OPERATION time Duration: 0.05 - 1 sec
POST-CLEANING Time Duration: 1 - 30 min (post-cleaning is optional )
Accuracy 0,01 sec
Outputs Triac with zero-crossing activation/deactivation 24, 115 or
230 Vac
with max. current 2A.
Transistor type for versions designed to control 24 Vdc
solenoid valves (optional).

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 4 P

Dimensions in mm

Weight 1,2Kg

GC 4P : the instrument is supplied with 2 fixing brackets which can be mounted as required
in one of the four positions indicated in the drawing

Key
1 - F1 Mains protection fuse 6 - Pause indicator LED
F2 Load protection fuse 7 - Solenoid valve output terminal board
2 - Power supply terminal board 8 - Active output indicator LED
3 - Post-cleaning input 9 - OPERATION time adjusting knob
(on = post-cleaning; off = stop) 10 - PAUSE time adjusting knob
4 - Input for DPF-series differential pressure 11 - AUTOMATIC/MANUAL selector
gauge 12 - Fixing bracket
5 - Power mains indicator LED

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 6 P

Dimensions in mm

Weight 1,2Kg

GC 6P : the instrument is supplied with 2 fixing brackets which can be mounted as required
in one of the four positions indicated in the drawing

Key

1 - F1 Mains protection fuse 6 - Pause indicator LED


F2 Load protection fuse 7 - Solenoid valve output terminal board
2 - Power supply terminal board 8 - Active output indicator LED
3 - Post-cleaning input 9 - OPERATION time adjusting knob
(on = post-cleaning; off = stop) 10 - PAUSE time adjusting knob
4 - Input for DPF-series differential pressure 11 - AUTOMATIC/MANUAL selector
gauge 12 - Fixing bracket
5 - Power mains indicator LED

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 12 P
13 9 10 11

12

Dimensions in mm
4 S2

S1

3
1 2 3 4 5 6 7 8 9 P A

RETE
POWER

C 1 2 3 4 5 6 C 7 8 9 F1
1
CARICHI F2
LOADS

8 7 6 5 2

217
195
Weight 1,25Kg

70
148

6,8
74

70

GC 12P : the instrument is supplied with 2 fixing brackets which can be mounted as required
in one of the six positions indicated in the drawing

Key
1 - F1 Mains protection fuse 6 - Pause indicator LED
F2 Load protection fuse 7 - Solenoid valve output terminal board
2 - Power supply terminal board 8 - Active output indicator LED
3 - Post-cleaning input 9 - OPERATION time adjusting knob
(on = post-cleaning; off = stop) 10 - PAUSE time adjusting knob
4 - Input for DPF-series differential pressure 11 - AUTOMATIC/MANUAL selector
gauge (Optional) 12 - Fixing bracket
5 - Power mains indicator LED 13 - Post cleaning time adjusting knob

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 20 P

Dimensions in mm
Weight 2,15Kg
84
230
62
84

6,8

GC 20P : the instrument is supplied with 4 fixing brackets

Key
1 - F1 Mains protection fuse 6 - Pause indicator LED
F2 Load protection fuse 7 - Solenoid valve output terminal board
2 - Power supply terminal board 8 - Active output indicator LED
3 - Post-cleaning input 9 - OPERATION time adjusting knob
(on = post-cleaning; off = stop) 10 - PAUSE time adjusting knob
4 - Input for DPF-series differential pressure 11 - AUTOMATIC/MANUAL selector
gauge (Optional) 12 - Fixing bracket
5 - Power mains indicator LED 13 - Post cleaning time adjusting knob

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 32 P
13 9 10 11

12

8
6
RETE CARICHI
1 2 3 4 5 6 7 8 9 POWER LOADS

1 F1 F2 1
S1 S2

C 1 2 3 4 5 6 7 8 C 9 C C
1
3
5

4 7 2

Dimensions in mm
Weight 2,15Kg
84
230
62
84

6,8

GC 32P : the instrument is supplied with 4 fixing brackets

Key
1 - F1 Mains protection fuse 6 - Pause indicator LED
F2 Load protection fuse 7 - Solenoid valve output terminal board
2 - Power supply terminal board 8 - Active output indicator LED
3 - Post-cleaning input 9 - OPERATION time adjusting knob
(on = post-cleaning; off = stop) 10 - PAUSE time adjusting knob
4 - Input for DPF-series differential pressure 11 - AUTOMATIC/MANUAL selector
gauge (Optional) 12 - Fixing bracket
5 - Power mains indicator LED 13 - Post cleaning time adjusting knob

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 64 P

138 9 10 11 6

S1 S2

Dimensions in mm

6,8

12

310
Weight 4,4Kg
332

GC 64P : the instrument is supplied with 4 fixing brackets.

Key
1 - F1 Mains fuse 10 - PAUSE time adjusting knob
F2 Load protection fuse 11 - AUTOMATIC/MANUAL selector
2 - Power supply terminal board 12 - Fixing bracket
3 - Post-cleaning input from remote contactor 13 - Post cleaning time adjusting knob
(on = post-cleaning; off = stop) 14 - Connectors for connection of
4 - Input for DPF-series differential pressure gauge sequential timer to expansion cards
5 - Power On LED 15 - Terminal board for connection of
6 - Pause LED solenoid valves on expansion card
7 - Solenoid valve output terminal board 16 - Connectors for connection of
8 - Output active LED expansion card to sequential timer
9 - OPERATION time adjusting knob 17 - Expansion card output active LED

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CYCLIC GENERATORS GC
DEVICES

Lay-out GC 96 P

13 9 10 11 6 16 17 15 16 17

14

C
C
14

C
14
RETE CARICHI
1 2 3 4 5 6 7 8 9 POWER LOADS
8

C
F1 F2 1
S1 S2
5
C 1 2 3 4 5 6 7 8 C 9 C C

C
3

C
4

C
7 2

16 15 16

12

6,8

310 310

647

GC 96P: The instrument is supplied with 4 fixing brackets

Key
1 - F1 Mains protection fuse 10 - PAUSE time adjusting knob
F2 Load protection fuse 11 - AUTOMATIC/MANUAL selector
2 - Power supply terminal board 12 - Fixing bracket
3 - Post-cleaning input(ON = post-cleaning; OFF = stop) 13 - Post cleaning time adjusting knob
4 - Input for DPF-series differential pressure gauge 14 - Connectors for connection of se
5 - Power mains indicator LED quential timer to expansion cards
6 - Pause indicator LED 15 - Terminal board for connection of sol
7 - Solenoid valve output terminal board enoid valves on expansion card
8 - Active output indicator LED 16 - Connectors for connection of expan
9 - OPERATION time adjusting knob sion card to sequential timer
17 - Active output indicator LED on expan
sion card

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL
CICLIC GENERATOR TC01
DEVICES

General Description
The TC 1 cyclic timer is a very simple and versatile programmable switch with
contained dimensions. Within the ambit of the air filtering systems it can be used
in different applications, such as:
- to control electric drive valves in small dimension plants;
- to start up the control solenoid valve in the tanks assigned to the store broken;
- to download the condensate in the tanks provided with electric drive drain valve.

The adjustment of the working and the pause time occurs through two grips.
During the operating phase a green LED lights up, during the pause phase a
yellow LED lights up. The timer is provided with a TEST pushbutton, which
allows to check its right operation.

NOTE: the load must have the same supply voltage as the TC 1 input
supply

Lay-out

28
50.7
22.9

10
5
2 15
SEC ON
20

10 20
5 30
MIN OFF www.aeautel.it
40 Electric TIMER
TC 1
84.7

voltage: 24 … 230Vac
switch current: 0.8A

INGRESSO
SUPPLY INPUT CONNECTOR
CONNETTORE
26

ALIMENTAZIONE OUTPUT
USCITA

30.1 36.4

Technical Specifications
Power supply 24Vac ... 230Vac – 50/60Hz (on demand also 24 … 230 Vac/dc)
Max. power 0.8A
Absorbed power 2mA (at rest)
OPERATION time 0-1 sec / 0-20 sec (+/-3%)
PAUSE time 0-5 min / 0-40 min (+/-3%)
Case plastic self-estinguishable material (UL94V0)
Protection level IP65
Connections DIN43650 B connesctor
Preservation 1 fuse = 1A quick acting

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
ECONOMIC AND COMPACT TIMER CONTROL
STR 2-3-4-5-6 OUTPUTS DEVICES

General description
STR control device is a compact, reliable and economic Cyclical Timer with 2-3-4-5-6 outputs,
adapted for small and medium filtration systems. The easiness of installation and use are its
power. In order to connect the outputs of the instrument to the pneumatic valves on the filter is
enough to use an ordinary tube RILSAN. The costs of the electrical wiring are limit to the single
power. The regulation of the operating cycle (pause time and operation time) is provided by means
accessible trimmer on the circuit.

Technical specifications
Power supply 90 ÷ 240 Vac 50/60Hz (On request 24 Vac)
OPERATION time 0.08 ÷ 0.65 sec
PAUSE time 4 ÷ 210 sec
Operating temperature - 10 ÷ +60 °C
Protection rating IP 65
Absorbed power 25 VA
Security fuse 0,5A delayed
Protection fuse PTC 0.1 A
NOTE Acting on a simple Dip-Switch it is possible:
1. to increase the pause time of a factor 10 (x 10)
2. to ability the modality test:
operation time 0.2 sec – pause time 2 sec

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it
CONTROL ECONOMIC AND COMPACT TIMER
DEVICES STR 2-3-4-5-6 OUTPUTS

Lay-out and dimensions

GROUND POWER
CONNECTOR CONNECTOR
WALL FIXING Dimensions in mm
HOLES CLOSING
HOOK

6 OUTPUT FOR
PNEUMATIC VALVES

External Connections
Fase (L)

Input DP
Neutro (N)

Input
from differential
pressure gauge

Only power from 90 to 240


Vac 50760 Hz
On request other power

ATTENZION
The cyclical-timer must be connected to ground

Regulation (inside the board)


Max Min
| | Working time Position Pause Position Pause
trimmer: (sec) (sec)
| |
| |

| | | 0,08s - 0,65s
CD
AB Rotary dip-switch
EF012
89

pause time
67

34 5

Option
dip-switc
DIP POSITION 1 Not used
DIP POSITION 2 SET ON
DIP POSITION 3 SET ON
DIP POSITION 4 ON=TEST (Pause time 1s)

Autel S.r.l. – Electrical and Electronic Systems for air filtration – www.aeautel.it
Via D. Bagnoli n°9, Sassuolo (MO) ITALY. Phone: +39/0536 802104 Fax: +39/0536 803372 Email: info@aeautel.it