GROUNDING CALCULATION
POLYETHYLENE PLANT JE-R0-E5-CS-138962
AL-JUBAIL, SAUDI ARABIA
GROUNDING CALCULATION
CONTENTS
1.0 SCOPE 3
2.0 STANDARDS 3
CONDUCTOR
6.0 CONCLUSION 7
7.0 ATTACHMENTS
CONSTRUCTION OF ISO-PENTANE TANK AT
POLYETHYLENE
1.0 SCOPE
1.1 The intent of this document is to define the basis for design of safety grounding
system required for the Isopentane Storage Tank Area at Al-Jubail, Saudi Arabia,
for Tank (RV-4902) & Pump Motor (RPM-4902A/S) area .
2.0 REFERENCE
The entire grounding system will be designed in accordance with the following
standards/specifications as given below :
3.1 As per the 'Electrical Primary One Line diagram 480V MCC 27-76MC-1B', drawing No.
P0N0-E2-DW-105018, Rev. A, the switchgear rating for three phase symmetrical fault current at 480V bus is
65 kA for 2 Sec. Considering the actual three phase fault current as 50 kA and ground fault current as 60% of
the phase fault current with maximum clearing time of 1 sec., following are the design paramaters.
4.1 As per the above considering ground fault current as 30 kA ,the Main Conductor is sized. The size of
the ground grid conductor is decided on mechanical, thermal and electrical considerations.
The following formula from IEEE Standard 80 -2000 is used for determining the size of ground grid conductor.
1/2
TCAP X 10-4 Ko + Tm
I = A tc x α r x ρ r ln Ko + Ta
(As per IEEE Std-80, clause no.11.3.1 & Table-1 ),Refer attachment.
Where,
I = Maximum ground fault current in kA = 30
A = Conductor cross section area in mm2
CONSTRUCTION OF ISO-PENTANE TANK AT
POLYETHYLENE
I
∴ A =
TCAP X 10-4 Ko + Tm 1/2
tc x α r x ρ r ln Ko + Ta
30
A = 1/2
-4
3.42 X 10 ln 242.0 + 1084
1 x 0.00381 x 1.78 242.0 + 35
30
A =
1326 1/2
0.05043 ln 277.0
∴ A = 106.75 Sq.mm
Above ground, connection to equipment, structure etc. shall be grounded through PVC insulated copper cable.
For ground cable size details refer 'Grounding Layout', Drg. No. JE-R0-E5-SD-138957, Rev. 1
CONSTRUCTION OF ISO-PENTANE TANK AT
POLYETHYLENE
5.1 Considering 2Nos., 19mm dia., 3000mm long (without joints)Copper Claded
Steel Rod type Ground Electrodes to be provided in the Tank-RV-4902
and Pump motor (RPM-4902A/S) shed area grid. Distribution of ground
electrodes shall be as given below :
Tank & Pump Shed Area (GE-1) & (GE-2) :2Nos.
Total : 2Nos.
R1 x R2 - Rm2
Rg = ---- (i)
R1+ R2 - (2Rm )
The above equation is as per IEEE Std-80, clause no. 14.3
Where,
Rg = Total ground Resistance in ohm.
R1 = Ground Resistance of the grid in ohm.
R2 = Ground Resistance of the rods in ohm.
Rm = Mutual Ground Resistance between the group of
grid conductors, R1 and group of ground rods
R2, in ohm.
ρ = Resistivity of soil in ohm-meter = 200 (as per GES-018-09)
CL. No. 4.1, Sr. No. 7
ρ ln 2 Lc + k1 Lc - k2
R1 = ------------ (ii)
Π Lc a' √A
(The length indicated above is including the length of RV-4902 area only).
a' = √a x 2h = 0.089
for conductors buried at depth h in mtrs. h = 0.6 (Assumed)
a' = 'a' for conductor on earth surface in mtrs.
CONSTRUCTION OF ISO-PENTANE TANK AT
POLYETHYLENE
k1, k2 = the coefficients as per figure (25) a & b [ IEEE - 80 ],Refer attachment.
k1 = 1.08 & k2 = 4.5
Where,
LR = total length of ground rod in mtrs. = 6.0
Lr = the length of each rod in mtrs. = 3.0
2b = the diameter of rod in mtrs. = 0.019 ∴ b = 0.0095
nR = no. of rods placed in area 'A' = 2
Rm = ρ ln 2 Lc + k1 Lc - k2 +1 ------- (iv)
Π Lc Lr √A
∴ Rm = 1.524 ohm
37.078
= 17.294
∴ Rg = 2.144 ohm
6.0 CONCLUSION 1
The above value of 2.144 ohm for the ground resistance is well within the minimum
permissible value of 5 ohm (as per GES-018-09), considering the burried conductor and 2 Nos.
ground rods.
However, the new earth grid will be connected to the existing grid with 2Nos.
Connections by 1C x 120 Sq.mm Bare Copper cable, hence the effective
resistance of the ground grid will be less than 2.144 ohm.
CONSTRUCTION OF ISO-PENTANE TANK AT
POLYETHYLENE
ATTACHMENTS