ASCOTM Series

ADVANCED REDUNDANT CONTROL SYSTEM 141

The ASCO ARCS are specially designed redundant solution for emergency shut
down valves (ON/OFF vales)(1) and various redundant configurations (1oo2, 2oo2 &
2oo3) to meet both safety & availability.

The ASCO ARCS 2oo3 redundant solenoid valve piloting system combines the
advantages of both 1oo2 & 2oo2 systems to achieve a high level of process safety
and reliability.
(1)
For fail safe application of control valves, please contact ASCO representative

REDUNDANT CONFIGURATIONS
1oo2 - Redundancy built to achieve a high level of process safety
Hardware fault tolerant = 1 SIL3

2oo2 - Redundancy built to achieve high availability and prevent nuisance trips
Hardware fault tolerant = 0 SIL2

2oo3 - Redundancy built to achieve a high level of process safety and availability
Hardware fault tolerant = 1 SIL3
** 2oo3 configuration with 3 channels and 3oo4 configuration with 4 channels wiring

SOLENOID VALVES ARE BASED ON ASCO 327-SERIES, 3 WAY


- Direct-acting solenoid valve technology
- Low friction = Low power = High reliability
- Reduced total cost of ownership (TCO)

OPTIONS AVAILABLE
- Aluminum or stainless steel solenoid operator option including
Flameproof or Intrinsically safe
- Manual operator or manual reset function
- Pressure gauge, visual indicator (Stainless steel)
- Solenoid valve diagnostic - pressure switches
- Options with Ex proof and intrinsically safe wiring for pressure switches

FULL RANGE OF CERTIFICATIONS AND APPROVALS


327 certified for SIL applications (Exida and TUV)
Up to SIL 3 accreditation from Exida for redundant configuration

ONLINE MAINTENANCE
Common by pass - allows online replacement of solenoid valve
Individual isolation - 2oo2 & 2oo3 - Hot swapping that allow on-line replacement
of solenoid valve while maintaining the system capability to bring the process to safe
mode in the event of an emergency.

FEATURES & BENEFITS


• Compact and fully integrated module

• Direct valve-to-valve design

• Status indication (visual) & Digital input feedback

• Online maintenance - individual isolation valves (Option)


API-ARCS-2018/R1.8

Visit our website at www.emerson.com 1


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
GENERAL
Differential pressure 1 - 10 bar [1 bar = 100kPa]
Maximum viscosity 65 cSt (mm2/s)
Response times 75 - 100 ms
Fluid Temperature Range (TS) Seal Materials
Dry & Non Lubricated Air -20°C to +60°C FPM
Note: Filtered (5 micron) instrument air recommended

SPECIFICIATION

Pipe Operating Power


Prefix Solenoid Options Operation Basic
Size Pressure Level Fluid
Material Basic Ordering
Temperature
of Solenoid Code for
Exd Exi IP67 IP65 Ts(3)
Construction Valve Solenoid
NPT MIN MAX ~/= (oC)
NF / EM / NFIS / WP / Valve
WSCR WSTIS SC
WSNF WSCREM WSCRIS WS
• • • • • Auto Reset -20 to +90 SS316L 327B202 536398
MP • • • • Auto Reset -20 to +90 Aluminium 327B203 536403

• • • Manual Reset -20 to +90 SS316L 327B232 536401

• • • • • Auto Reset -20 to +90 SS316L 327B102 536397


1/4" RP • • • • Auto Reset -20 to +90 Aluminium 327B103 536402
or 0/1(2) 10
1/2" • • • Manual Reset -20 to +90 SS316L 327B132 536400

• • • • Auto Reset -20 to +90 SS316L 327B302 536399

• • • Auto Reset -20 to +90 Aluminium 327B303 536405


LP
• • • Manual Reset -20 to +90 SS316L 327B332 536406
• Auto Reset -20 to +60 SS316 307B005(1) 503838
(1)
For detail specification and dimensions, please refer to ASCO representative
(2)
Zero bar applicable for redundant configuration without online maintenance and diagnostic feature options only
(3)
Can be limited by the operator ambient temperature range for explosion proof solenoids

FLOW RATE
Inlet to Outlet Outlet to Exhaust
Flow at ANR
ANR (lpm) Kv Flow (lpm) Kv
2oo3 353 0.29 944 0.25
2oo2 497 0.39 851 0.23
1oo2 234 0.19 542 0.23
Note: Exhaust flow pressure at 6 bar, atmospheric pressure is 1 bar
API-ARCS-2018/R1.8

2 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
EXPLANATION OF TEMPERATURE RANGES OF SOLENOID VALVES
Valve temperature range The valve temperature range (TS) is determined by the selected seal material,
the temperature range for proper operation of the valve and sometimes by the
fluid (e.g. steam)
Operator ambient temperature range The operator ambient temperature range is determined by the selected power
level and the safety code
Total temperature range The temperature range of the complete solenoid valve is determined by the
limitations of both temperature range above

AMBIENT TEMPERATURE
Standard Temperature Version -20°C to +60°C

ELECTRICAL CHARACTERISTICS
Operator
Power Rating Electrical
Inrush Holding Ambient Coil
(~) (~) temperature Enclosure
Prefix Safety Code Insulation
(~) Hot/Cold = Range Protection
Class
(EN60529)
VA VA W W (°C)
Medium Power (MP)
(NF/WSNF/ II2G Ex d IIC Gb T6/T5/T4,
5.8 5.8 5.8 5.2/5.7 -60 to +40/75/90 H IP66/67, Alu/SS
WSCR) II2D Ex t IIIC Db
II2G Ex eb mb IIC Gb T6/T4,
EM 5.8 5.8 5.8 5.2/5.7 -60 to +40/75/90 H IP66/67, steel
II2D Ex tb IIIC Db
II2G Ex eb mb IIC Gb T6/T4,
WSCREM 5.8 5.8 5.8 5.2/5.7 -60 to +40/75/90 H IP66/67, SS
II2D Ex tb IIIC Db
WP/WS 5.8 5.8 5.8 5.2/5.7 -60 to +90 EN 60730 H IP66/67, steel/SS
SC 5.8 5.8 5.8 5.2/5.7 -60 to +90 EN 60730 F IP65, moulded
Reduced Power (RP)
(NF/WSNF/ II2G Ex d IIC Gb T6/T5/T4,
3.7 3.7 3.7 3.2/3.6 -60 to +/60 H IP66/67, Alu/SS
WSCR) II2D Ex t IIIC Db
II2G Ex eb mb IIC Gb /T5/T4,
EM 3.7 3.7 3.7 3.2/3.6 -40 to +40/55 H IP66/67, steel
II2D Ex tb IIIC Db
II2G Ex eb mb IIC Gb T6/T5/T4,
WSCREM 3.7 3.7 3.7 3.2/3.6 -60 to +40/60/90 H IP66/67, SS
II2D Ex tb IIIC Db
WP/WS 3.7 3.7 3.7 3.2/3.6 -60 to +55 EN 60730 H IP66/67, steel/SS
SC 3.7 3.7 3.7 3.2/3.6 -60 to +55 EN 60730 F IP65, moulded
Low Power (LP)
(NF/WSNF/ II2G Ex d IIC Gb T6/T5,
1.85 1.85 1.85 1.5/1.8 -60 to +55 H IP66/67, Alu/SS
WSCR) II2D Ex t IIIC Db
II2G Ex eb mb IIC Gb T6/T5,
WSCREM 1.85 1.85 1.85 1.5/1.8 -60 to +55 H IP66/67, SS
II2D Ex t IIIC Db
Intrinsically Safe (IS)
(NFIS/
II2G Ex ia IIC Gb T6,
WSNFIS/ - - - 0.5 -40 to +60 H IP66/67, Alu/SS
II2D Ex t IIIC Db
WSCRIS)
II2G Ex ia IIC Gb T6,
WSTIS - - - 0.4 -20 to +60 H IP66/67, SS
II2D Ex t IIIC Db
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 3


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
HOW TO ORDER
8 141 A 1 1 0 FN A00 H1

Voltage
00 = None
Port Type H1 = 24V DC
8 = NPT connections H9 = 48V DC
HJ = 110V DC
HD = 120V DC
Product Series J1 = 125V DC
141 = ARCS DA Series HQ = 24V/50-60HZ AC
JY = 110V/50-60HZ AC
Revision Letter HC = 115V/50-60HZ AC
A = Initial release HA = 120V/50-60HZ AC
JV = 220V/50-60HZ AC (1)
Function HH = 230V/50-60HZ AC (1)
(1)
1 = 1oo2 Manifold Assembly, without Not applicable for Low and Reduced Power options
Online Maintenance & without Diagnostic
2 = 1oo2 Manifold Assembly, with Common Options (3)
By-pass & without Diagnostic A00 = No Options
3 = 2oo2 Manifold Assembly, without Online A01 = SS Visual Indicator
Maintenance & Diagnostic A02 = SS Pressure Gauge
4 = 2oo2 Manifold Assembly, without Online B01 = Pressure Switch, IP66 Protected
Maintenance, with Diagnostic (For Intrinsically Safe Wiring)
5 = 2oo2 Manifold Assembly, with Common B02 = Pressure Switch (For Exproof Wiring)
By-pass with Diagnostic M01 = With Manual Override (1)
6 = 2oo2 Manifold Assembly, with Individual D01 = INMETRO
Isolation with Diagnostic D02 = KOSHA
7 = 2oo3 Manifold Assembly, without Diagnostic D03 = CUTR
& Online Maintenance D04 = NEFSI
8 = 2oo3 Manifold Assembly, without Online D05 = PESO
Maintenance, with Diagnostic (1)
Manual override M01 option applicable for Auto Reset SOV only
A = 2oo3 Manifold Assembly, with Individual (3)
Select Options using '+'
Isolation & with Diagnostic Example: A01+B01+D01
For multiple options, please use online configurator on the wesbite
to generate the part number or consult ASCO representative

Port Size / Body Material Electrical Connection Type


1 = Standard Flow-Port Size 1/4" NPT, SS 316 FN = NF
2 = Standard Flow-Port Size 1/4" NPT, Aluminium FT = NFET
3 = Standard Flow-Port Size 1/2" NPT, SS 316 F1 = NFTIS (1)
4 = Standard Flow-Port Size 1/2" NPT, Aluminium X1 = NFETIS (1)
FS = WSNF
FU = WSNFET
WR = WSCR
X2 = WSCRET
Solenoid Valve - 3 Way, Direct Acting
X3 = WSCRTIS (1)
0 = 327B102, Auto Reset, FPM sealing, SS, Power 3.6/3.7W (RP)
X4 = WSCRETIS (1)
1 = 327B202, Auto Reset, FPM sealing, SS, Power 5.7/5.8W (MP)
X5 = WSTIS (1)
2 = 327B302, Auto Reset, FPM sealing, SS, Power 1.7/1.8W & IS 0.5W (LP)
X6 = WSETIS (1)
7 = 327B132, Tamper Proof Reset,FPM sealing, SS, Power 3.6/3.7W (RP)
MV = EM
8 = 327B232, Tamper Proof Reset, FPM sealing, SS, Power 5.7/5.8W (MP)
MT = EMT
9 = 327B332, Tamper Proof Reset, FPM sealing, SS, Power 1.7/1.8W (LP)
X7 = WSCREM
M = 327B103, Auto Reset, FPM sealing, Alu, Power 3.6/3.7W (RP) (2)
X8 = WSCREMET
N = 327B203, Auto Reset, FPM sealing, Alu, Power 5.7/5.8W (MP) (2)
X9 = WP
P = 327B303, Auto Reset, FPM sealing, Alu, Power 1.7/1.8W & IS 0.5W (LP) (2)
XA = WPET
Q = 307B005, Pilot Operated, Auto Reset, FPM sealing, Power IS 0.5W (LP) (3)
(2)
XC = WS
Applicable only for Aluminium version in Body Material Selection XD = WSET
(3)
Applicable for Electrical Connection Type X5 & X6
XE = WPT
For other specification & dimensions, please contact ASCO representative
XF = WST
S1 = SC
API-ARCS-2018/R1.8

(1)
Intrinsically safe voltage selection restricted to
24VDC H1 option

Disclaimier: Selection chart shown for reference. For right configuration/available options,
Please use ARCS configurator in www.asco.com or contact local ASCO sales office

4 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
ELECTRICAL CONNECTIONS

Code Connection Prefix


Solenoid Housing, Die Cast Aluminium, Explosion Proof with 1/2 NPT cable entry,
FN Safety Code II2G Ex d IIC Gb T6/T5/T4, II2D Ex t IIIC Db, ATEX/IEC Ex Certified NF
Solenoid Housing, Die Cast Aluminium, Explosion Proof with M20 * 1.5 cable entry,
FT NFET
Safety Code II2G Ex d IIC Gb T6/T5/T4, II2D Ex t IIIC Db , ATEX/IEC Ex Certified
Solenoid Housing, Die Cast Aluminium, Intrinsically Safe with 1/2 NPT cable entry,
F1 NFTIS
Safety Code II2G Ex ia IIC Gb T6, II2D Ex t IIIC Db (Standard Flow Only), ATEX/IEC Ex Certified (1)
Solenoid Housing, Die Cast Aluminium, Intrinsically Safe with M20 * 1.5 Cable entry,
X1 Safety Code II2G Ex ia IIC Gb T6, II2D Ex t IIIC Db (Standard Flow Only), ATEX/IEC Ex Certified(1) NFETIS
316 Stainless Steel Water Tight Junction Box w/ Flameproof Direct Cable Entry 1/2 NPT,
FS WSNF
Safety Code II2G Ex d IIC Gb T6/T5/T4, II2D Ex t IIIC Db (WSNF-IECEx), ATEX/IEC Ex Certified
Solenoid Housing, Stainless Steel, Explosion Proof with M20 * 1.5 cable entry,
FU WSNFET
Safety Code II2G Ex d IIC Gb T6/T5/T4, II2D Ex t IIIC Db, ATEX/IEC Ex Certified
Solenoid Housing, Stainless Steel, Explosion Proof with 1/2 NPT cable entry,
WR WSCR
Safety Code II2G Ex d IIC Gb T6/T5/T4, II2D Ex t IIIC Db, (WSCR-IECEx), ATEX/IEC Ex Certified
Solenoid Housing, Stainless Steel, Explosion Proof with M20 * 1.5 cable entry,
X2 WSCRET
Safety Code II2G Ex d IIC Gb T6/T5/T4, II2D Ex t IIIC Db, (WSCR-IECEx), ATEX/IEC Ex Certified
Solenoid Housing, Stainless Steel, Intrinsically Safe with 1/2 NPT cable entry,
X3 WSCRTIS
Safety Code II2G Ex ia IIC Gb T6, II2D Ex t IIIC Db (Standard Flow Only), ATEX/IEC Ex Certified (1)
Solenoid Housing, Stainless Steel, Intrinsically Safe with M20 * 1.5 Cable entry,
X4 WSCRETIS
Safety Code II2G Ex ia IIC Gb T6, II2D Ex t IIIC Db (Standard Flow Only), ATEX/IEC Ex Certified (1)
Solenoid Housing, Stainless Steel, Intrinsically Safe with 1/2 NPT cable entry,
X5 WSTIS
Safety Code II2G Ex ia IIC Gb T6, II2D Ex t IIIC Db (Standard Flow Only), CCOE (1)
Solenoid Housing, Stainless Steel, Intrinsically Safe with M20 * 1.5 Cable entry,
X6 WSETIS
Safety Code II2G Ex ia IIC Gb T6, II2D Ex t IIIC Db (Standard Flow Only), CCOE (1)
Solenoid Housing, Steel with, Increased Safety with 1/2"NPT cable entry,
MV EM
Safety Code: II2G Ex e mb IIC Gb T6/T5, II2D Ex tb IIIC Db, ATEX/IEC Ex Certified
Solenoid Housing, Steel with, Increased Safety with M20 *1.5 cable entry,
MT EMT
Safety Code: II2G Ex e mb IIC Gb T6/T5, II2D Ex tb IIIC Db, ATEX/IEC Ex Certified
Solenoid Housing, Stainless Steel with, Increased Safety with 1/2"NPT cable entry,
X7 WSCREM
Safety Code: II2G Ex e mb IIC Gb T6/T5, II2D Ex tb IIIC Db, ATEX/IEC Ex Certified
Solenoid Housing, Stainless Steel with, Increased Safety with M20 *1.5 cable entry,
X8 WSCREMET
Safety Code: II2G Ex e mb IIC Gb T6/T5, II2D Ex tb IIIC Db, ATEX/IEC Ex Certified
X9 Waterproof IP67 -with M20*1.5 Cable Gland, Metal enclosure WP
XA Waterproof IP67 -M20*1.5 cable entry, Metal enclosure WPET
XC Waterproof IP67 -with M20*1.5 Cable Gland, Stainless Steel enclosure WS
XD Waterproof IP67 -with M20*1.5 Cable entry, Stainless Steel enclosure WSET
XE Waterproof IP67 -1/2"NPT cable entry, Metal enclosure WPT
XF Waterproof IP67 -with 1/2"NPT Cable entry, Stainless Steel enclosure WST
S1 Spade plug connector (EN/IEC 60730), IP65 SC

ACCESSORIES
Visual Indicators Pressure Gauge
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 5


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141

1oo2 Logic Table


CH 1 CH 2
Outlet
V1 V2
1 1 1
1 0 0
0 1 0
0 0 0
CH 1 - CHANNEL 1
CH 2 - CHANNEL 2
0 - VALVE DE-ENERGIZED
1 - VALVE ENERGIZED

Schematic 1 Schematic 2

2oo2 Logic Table


CH 1 CH 2
Outlet
V1 V2
1 1 1
1 0 1
Schematic 3 Schematic 4 0 1 1
0 0 0

CH 1 - CHANNEL 1
CH 2 - CHANNEL 2
0 - VALVE DE-ENERGIZED
1 - VALVE ENERGIZED
API-ARCS-2018/R1.8

Schematic 5 Schematic 6
6 Visit our website at www.emerson.com
ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
2oo3 Logic Table *
CH 1 CH 2 CH 3
Outlet
V1 V2 V3 V4
1 0 0 0 0
1 1 0 0 0
1 1 1 0 1
1 1 1 1 1
0 1 0 0 0
0 1 1 0 0
0 1 1 1 1
0 1 0 1 1
0 0 1 0 0
0 0 1 1 0
1 0 1 1 1
1 0 1 0 1
0 0 0 1 0
1 0 0 1 1
1 1 0 1 1
0 0 0 0 0
CH 1 - CHANNEL 1
CH 2 - CHANNEL 2
CH 3 - CHANNLE 3
0 - VALVE DE-ENERGIZED
1 - VALVE ENERGIZED
* FOR SCHEMATIC - 7

Schematic 7

2oo3 Logic Table *


CH 1 CH2 CH 3
Outlet
V1 V4 V2 V3
1 0 0 0 0
1 0 1 0 0
1 0 1 1 1
1 1 1 1 1
0 0 1 0 0
0 0 1 1 1
0 1 1 1 1
0 1 1 0 1
0 0 0 1 0
0 1 0 1 0
1 1 0 1 1
1 0 0 1 1
0 1 0 0 0
1 1 0 0 0
1 1 1 0 1
0 0 0 0 0
CH 1 - CHANNEL 1
CH 2 - CHANNEL 2
CH 3 - CHANNLE 3
0 - VALVE DE-ENERGIZED
1 - VALVE ENERGIZED
API-ARCS-2018/R1.8

* FOR SCHEMATIC - 8,A

Schematic 8 Schematic A

Visit our website at www.emerson.com 7


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
1oo2 without Online Maintenance and Diagnostic
E
B 85 115
125 38 116 36 30

C
155
130
56

70
25
37

CONSTRUCTION REF - 1
MOUNTING HOLES
Ø11-(4x)

A
CONSTRUCTION BASIC APPROX. WT
TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 230 16


02 WP/WS/EM 112 205 - 171 239 17
327B102/202
03 NF/WSNF 136 180 146 195 249 19/21

40
04 WSCR/WSCREM 140 200 160 199 246 20
03 NF/WSNF/NFIS 146 180 156 205 249 19/21/21
1 327B302 WSCR/WSCREM/
04 140 200 160 199 246 20
WSCRIS
01 SC 109 190 - 168 230 8
327B103/203 02 WP/EM 112 205 - 171 239 8 CONSTRUCTION REF - 2
03 NF 136 180 146 195 249 11
327B303 03 NF/WSNF/NFIS 146 180 156 205 249 11/13/11
01 SC 109 190 - 168 230 17
327B132/232 02 WP/WS/EM 112 205 - 171 239 17
2
03 NF/WSNF 136 180 146 195 249 20/22
327B332 04 WSCR/WSCREM 140 200 160 199 246 21

TYPE 01: TYPE 02:


Epoxy moulded Metal, epoxy coated / AISI 316 SS
SC :IEC 335 / ISO 4400 WP / WS : IEC 335
EM / WSEM : EN/IEC 60079-7, 60079-18
EN/IEC 60079-31,

327B102 / 202 / 103 / 203 / 132 / 232 327B102 / 202 / 103 / 203 / 132 / 232

TYPE 04:
TYPE 03: AISI 316L SS
Aluminium, epoxy coated / AISI 316L SS WSCR : EN/IEC 60079-0, 60079-1, 60079-31
API-ARCS-2018/R1.8

NF / WSNF : EN/IEC 60079-1, 60079-31 WSCREM : EN/IEC 60079-0, 60079-7, 60079-18


NFIS / WSNFIS : EN/IEC 60079-11, 60079-31 : EN/IEC 60079-31
WSCRIS : EN/IEC 60079-0, 60079-11, 60079-31

327B102 / 202 / 302 / 332


327B102 / 202 / 302 / 103 / 203 / 303 / 132 / 232

8 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
1oo2 with Common Bypass, with Diagnostic

E
B 85 115
125 38 116 15 30

C
130
155

44

15
VISUAL INDICATOR

25
35

117
MOUNTING HOLES
Ø11-(4x)

PADLOCK

F
CONSTRUCTION REF - 1

G
CONSTRUCTION BASIC APPROX. WT
TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 230 18


02 WP/WS/EM 112 205 - 171 239 19
327B102/202 A
03 NF/WSNF 136 180 146 195 249 21/23
04 WSCR/WSCREM 140 200 160 199 246 22
03 NF/WSNF/NFIS 146 180 156 205 249 21/23/21
1 327B302 WSCR/WSCREM/
04 140 200 160 199 246 22
WSCRIS
01 SC 109 190 - 168 230 10
40

327B103/203 02 WP/EM 112 205 - 171 239 10


03 NF 136 180 146 195 249 13
327B303 03 NF/WSNF/NFIS 146 180 156 205 249 13/15/13
01 SC 109 190 - 168 230 19
327B132/232 02 WP/WS/EM 112 205 - 171 239 19
2
03 NF/WSNF 136 180 146 195 249 22/23
327B332 04 WSCR/WSCREM 140 200 160 199 246 23

CONSTRUCTION REF - 2

ACCESSORIES F G
VISUAL INDICATOR 164 217
PRESSURE GAUGE 172 224
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 9


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo2 without Online Maintenance and Diagnostic
E
B 85 115
125 38 116 25 30

C
155
130

70
56

25
30
CONSTRUCTION REF - 1

A
CONSTRUCTION BASIC APPROX. WT
TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 230 16


02 WP/WS/EM 112 205 - 171 239 17
327B102/202
03 NF/WSNF 136 180 146 195 249 19/21

40
04 WSCR/WSCREM 140 200 160 199 246 20
03 NF/WSNF/NFIS 146 180 156 205 249 19/21/19
1 327B302 WSCR/WSCREM/
04 140 200 160 199 246 20
WSCRIS
CONSTRUCTION REF - 2
01 SC 109 190 - 168 230 8
327B103/203 02 WP/EM 112 205 - 171 239 8
03 NF 136 180 146 195 249 11
327B303 03 NF/WSNF/NFIS 146 180 156 205 249 11/13/11
01 SC 109 190 - 168 230 17
327B132/232 02 WP/WS/EM 112 205 - 171 239 17
2
03 NF/WSNF 136 180 146 195 249 20/22
327B332 04 WSCR/WSCREM 140 200 160 199 246 21

API-ARCS-2018/R1.8

10 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo2 without Online Maintenance, with Diagnostic
E
B 85 115
125 38 116 14 30

C
155
130

70
45

VISUAL INDICATOR

25
92
MOUNTING HOLES
Ø11-(4x)
PRESSURE SWITCH

14 F

CONSTRUCTION REF - 1

CONSTRUCTION BASIC APPROX. WT


TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 230 17


02 WP/WS/EM 112 205 - 171 239 18
327B102/202 A
03 NF/WSNF 136 180 146 195 249 20/22
04 WSCR/WSCREM 140 200 160 199 246 21
03 NF/WSNF/NFIS 146 180 156 205 249 20/22/20
1 327B302 WSCR/WSCREM/
04 140 200 160 199 246 21
WSCRIS
40

01 SC 109 190 - 168 230 9


327B103/203 02 WP/EM 112 205 - 171 239 9
03 NF 136 180 146 195 249 12
327B303 03 NF/WSNF/NFIS 146 180 156 205 249 12/14/12
01 SC 109 190 - 168 230 18
327B132/232 02 WP/WS/EM 112 205 - 171 239 18
2
03 NF/WSNF 136 180 146 195 249 21/23
327B332 04 WSCR/WSCREM 140 200 160 199 246 22
CONSTRUCTION REF - 2

ACCESSORIES F G
VISUAL INDICATOR 137 217
PRESSURE GAUGE 144 224
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 11


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo2 with Common Bypass, with Diagnostic
E
B 85 115
125 38 116 15 30

C
155
130
44

VISUAL INDICATOR

25
92
MOUNTING HOLES

114
Ø11-(4x)

PRESSURE SWITCH
PADLOCK

F
CONSTRUCTION REF - 1

G
CONSTRUCTION BASIC APPROX. WT
TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 230 18


02 WP/WS/EM 112 205 - 171 239 19
327B102/202
03 NF/WSNF 136 180 146 195 249 21/23 A
04 WSCR/WSCREM 140 200 160 199 246 22
03 NF/WSNF/NFIS 146 180 156 205 249 21/23/21
1 327B302 WSCR/WSCREM/
04 140 200 160 199 246 22
WSCRIS
01 SC 109 190 - 168 230 10
40

327B103/203 02 WP/EM 112 205 - 171 239 10


03 NF 136 180 146 195 249 13
327B303 03 NF/WSNF/NFIS 146 180 156 205 249 13/15/13
01 SC 109 190 - 168 230 19
327B132/232 02 WP/WS/EM 112 205 - 171 239 19
2
03 NF/WSNF 136 180 146 195 249 22/24
327B332 04 WSCR/WSCREM 140 200 160 199 246 23

CONSTRUCTION REF - 2

ACCESSORIES F G
VISUAL INDICATOR 164 217
PRESSURE GAUGE 172 224
API-ARCS-2018/R1.8

12 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo2 with Individual Isolation, with Diagnostic
E
B 85 115
125 38 116 14 30

C
130
155

70
45

VISUAL INDICATOR

25
92
114
MOUNTING HOLES
Ø11-(4x)

14

PADLOCK
F
CONSTRUCTION REF - 1

CONSTRUCTION BASIC APPROX. WT


TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 230 19


02 WP/WS/EM 112 205 - 171 239 20
327B102/202
03 NF/WSNF 136 180 146 195 249 22/25
A
04 WSCR/WSCREM 140 200 160 199 246 23
03 NF/WSNF/NFIS 146 180 156 205 249 22/24/22
1 327B302 WSCR/WSCREM/
04 140 200 160 199 246 23
WSCRIS
01 SC 109 190 - 168 230 11
327B103/203 02 WP/EM 112 205 - 171 239 11
40

03 NF 136 180 146 195 249 14


327B303 03 NF/WSNF/NFIS 146 180 156 205 249 14/16/14
01 SC 109 190 - 168 230 20
327B132/232 02 WP/WS/EM 112 205 - 171 239 20
2
03 NF/WSNF 136 180 146 195 249 23/25
327B332 04 WSCR/WSCREM 140 200 160 199 246 24

CONSTRUCTION REF - 2

ACCESSORIES F G
VISUAL INDICATOR 137 217
PRESSURE GAUGE 144 224
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 13


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo3 without Online Maintenance and Diagnostic

E
B 85 115 115 115
125 38 116 116 116 30 30

C
130
155

70
56

25
14
MOUNTING HOLES
Ø11-(8x)
CONSTRUCTION REF - 1

40
CONSTRUCTION BASIC APPROX. WT
TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 460 30


02 WP/WS/EM 112 205 - 171 469 31
327B102/202
03 NF/WSNF 136 180 146 195 479 36/41 CONSTRUCTION REF - 2
04 WSCR/WSCREM 140 200 160 199 476 38
03 NF/WSNF/NFIS 146 180 156 205 479 36/41/36
1 327B302 WSCR/WSCREM/
04 140 200 160 199 476 38
WSCRIS
01 SC 109 190 - 168 460 14
327B103/203 02 WP/EM 112 205 - 171 469 15
03 NF 136 180 146 195 479 21
327B303 03 NF/WSNF/NFIS 146 180 156 205 479 21/25/21
01 SC 109 190 - 168 460 31
327B132/232 02 WP/WS/EM 112 205 - 171 469 32
2
03 NF/WSNF 136 180 146 195 479 37/42
327B332 04 WSCR/WSCREM 140 200 160 199 476 39 API-ARCS-2018/R1.8

14 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo3 without Online Maintenance, with Diagnostic
E
B 85 115 115 115
125 60 38 116 116 116 21 30

C
130
155

45

40
VISUAL INDICATOR

25
92
MOUNTING HOLES
Ø11-(8x)
PRESSURE SWITCH
F
14

CONSTRUCTION REF - 1
G

CONSTRUCTION BASIC APPROX. WT


TYPE PREFIX A B C D E
REF CAT. NO. (KG)

40
01 SC 109 190 - 168 460 33
02 WP/WS/EM 112 205 - 171 469 34
327B102/202
03 NF/WSNF 136 180 146 195 479 39/44
04 WSCR/WSCREM 140 200 160 199 476 41
03 NF/WSNF/NFIS 146 180 156 205 479 39/44/39
1 327B302 WSCR/WSCREM/
04 140 200 160 199 476 41
WSCRIS
01 SC 109 190 - 168 460 17 CONSTRUCTION REF - 2
327B103/203 02 WP/EM 112 205 - 171 469 18
03 NF 136 180 146 195 479 24
327B303 03 NF/WSNF/NFIS 146 180 156 205 479 24/28/24
01 SC 109 190 - 168 460 34
327B132/232 02 WP/WS/EM 112 205 - 171 469 35
2
03 NF/WSNF 136 180 146 195 479 40/45
327B332 04 WSCR/WSCREM 140 200 160 199 476 42

ACCESSORIES F G
VISUAL INDICATOR 137 217
PRESSURE GAUGE 144 224
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 15


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
DIMENSIONS(mm), WEIGHT(kg)
2oo3 with Individual Isolation, with Diagnostic
E
B 85 115 115 115
125 60 38 116 116 116 21 30

D
C
155
130
45

40
VISUAL INDICATOR

25
92
120
MOUNTING HOLES
Ø11-(8x) PRESSURE SWITCH

14 PADLOCK F

CONSTRUCTION REF - 1

CONSTRUCTION BASIC APPROX. WT


TYPE PREFIX A B C D E
REF CAT. NO. (KG)

01 SC 109 190 - 168 460 36


02 WP/WS/EM 112 205 - 171 469 37 40
327B102/202
03 NF/WSNF 136 180 146 195 479 42/47
04 WSCR/WSCREM 140 200 160 199 476 44
03 NF/WSNF/NFIS 146 180 156 205 479 42/47/42
1 327B302 WSCR/WSCREM/
04 140 200 160 199 476 44
WSCRIS
01 SC 109 190 - 168 460 20
327B103/203 02 WP/EM 112 205 - 171 469 21
03 NF 136 180 146 195 479 27 CONSTRUCTION REF - 2
327B303 03 NF/WSNF/NFIS 146 180 156 205 479 27/31/27
01 SC 109 190 - 168 460 37
327B132/232 02 WP/WS/EM 112 205 - 171 469 38
2
03 NF/WSNF 136 180 146 195 479 43/448
327B332 04 WSCR/WSCREM 140 200 160 199 476 45

ACCESSORIES F G
VISUAL INDICATOR 137 217
PRESSURE GAUGE 144 224
API-ARCS-2018/R1.8

16 Visit our website at www.emerson.com


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
SPARES CODE
Solenoid Valve
Description: ASCO 327 series, 3/2 Way, direct acting, normally closed, with 5.7mm orifice, stainless steel 316

X 327 536397 001 H1

Special Mounting for 141 series Voltage Code


X H1 = 24V DC
H9 = 48V DC
Valve series HJ = 110V DC
327 HD = 120V DC
307 J1 = 125V DC
HQ = 24V/50-60HZ AC
JY = 110V/50-60HZ AC
Odering Code HC = 115V/50-60HZ AC
HA = 120V/50-60HZ AC
536397 = 327B102 Basic Catalog
JV = 220V/50-60HZ AC (4)
536398 = 327B202 Basic Catalog
HH = 230V/50-60HZ AC (4)
536399 = 327B302 Basic Catalog (4)
Not applicable for Low and Reduced Power options
536400 = 327B132 Basic Catalog
536401 = 327B232 Basic Catalog
536402 = 327B103 Basic Catalog
Electrical Connection/Enclosure Protection(2) (3)
536403 = 327B203 Basic Catalog
536405 = 327B303 Basic Catalog *** = Three digit code for applicable Electrical
536406 = 327B332 Basic Catalog connection and other options
(2)
503838 = 307B005(1) Basic Catalog Refer ASCO Representative for applicable Electrical
(1)
Connection/Enclosure Protection and code (3 digit)
Selection of base catalog no. 307B005 will restrict to the (3)
Refer Solenoid Operator Chart
voltage code H1 and Solenoid operator codes WSTIS/WSETIS

Voltage Code-XX
Class H Voltage
H0 120/60,110/50
H1 24/DC
H3 12/DC
H5 220/50
H8 230/50
H9 48/DC
HA 120/50-60
HD 120/DC
HE 110/50
HH 230/50-60
HJ 110VDC
API-ARCS-2018/R1.8

Visit our website at www.emerson.com 17


ASCOTM
ADVANCED REDUNDANT CONTROL SYSTEM SERIES 141
SPARES CODE
3 Way Push-Pull Manual Valve with LOTO
Description: ASCO 551 series, 3/2 way, manual push button operated, normally closed, with 6mm orifice, stainless
steel 316 and lock out tag out for tamper proof lock arrangement. Used for common by pass in 1oo2, 2oo2 & 2oo3 and
individual isolation in 2oo2 & 2oo3

Ordering Code Item Description


X55150616600100 Individual Isolation Valve
X55152879900100 Common By Pass Valve

ACCESSORIES - SPARES CODE


Ordering Code Item Description
508133-005 Visual Indicator-SS
Pressure Switch
509123-003
(Weather proof & Intrinscially safe wiring)
Pressure Switch
509123-004
(Ex proof wiring)

ARCS - CUSTOMISED SOLUTIONS

Availability, design and specifications are subject to change without notice. All rights reserved.
ASCO offer a complete customised solutions to meet customer's requirements. We provide panel (open frame and closed enclosure) for
ARCS system for mounting valve automation accessories like filter regulators, pilot operated valves, junction boxes for switches (feedback
wiring) with Exia, Exe and Exd protection etc.
Our control panel enclosure are available in Exe stainless steel 304, 316 materials with IP65 ratings.
API-ARCS-2018/R1.8