IEEE Transactions on Power Delivery, Vol. 21, No.1, Jan. 2006, pp. 362-367.

Instantaneous Reactive Power p-q Theory and Power Properties


of Three-Phase Systems

Leszek S. Czarnecki, Fellow IEEE

Abstract - The paper investigates how power phenomena and As long as the IRP p-q Theory is considered only as a
properties of three-phase systems are described and interpreted control algorithm then, the interpretation of power phenomena
by the Instantaneous Reactive Power (IRP) p-q Theory. as suggested by this theory is irrelevant. It is sufficient for an
The paper demonstrates that this theory misinterprets power algorithm to be acceptable that it enables us to reach the
properties of electrical systems or provides some results that at
least defy a common sense or meaning of some notions in
control objectives. However, to be considered as a power the-
electrical engineering. For example, it suggests the presence of an ory, the IRP p-q Theory should also satisfy other expectations.
instantaneous reactive current in supply lines of purely resistive First, it should provide a credible interpretation of power
loads and the presence of an instantaneous active current in properties and phenomena in power systems.
supply lines of purely reactive loads. Moreover, it suggests that Power properties of three-phase systems are expressed by
line currents of linear loads with sinusoidal supply voltage the IRP p-q Theory in terms of only two, active and reactive,
contain a nonsinusoidal component. p and q, powers, while power properties of such systems, even
The paper shows moreover that the IRP p-q Theory is not without any harmonic distortion, depend on three independent
capable to identify power properties of three-phase loads instan- phenomena. These are: (i) permanent energy transmission, (ii)
taneously. A pair of instantaneous values of p and q powers does
not allow us to conclude whether the load is resistive, reactive,
the voltage and current phase shift and (iii) line current
balanced or unbalanced. It is known that a load imbalance asymmetry due to the load imbalance. These phenomena are
reduces power factor. However, the IRP p-q Theory does not characterized by the active, reactive, and unbalanced powers,
identify the load imbalance as the cause of power factor P, Q and D. These powers specify [14] the apparent power:
degradation.
S = P2+ Q2 + D2 , (1)
Key words – Powers, p-q theory; currents’ physical components,
CPC, switching compensators, active power filters, unbalanced and consequently, power factor, λ = P/S. The number of
systems, power theory. power quantities in the IRP p-q Theory can make one suspi-
I. INTRODUCTION cious that this theory does not characterize power phenomena
in three-phase unbalanced systems correctly. One might sug-
The Instantaneous Reactive Power (IRP) p-q Theory is gest that this major deficiency of the IRP p-q Theory could be
based on the Clarke Transform of voltages and currents in overcome by combining the Q and D powers into a single
three-phase systems into α and β orthogonal coordinates. Its power quantity. Unfortunately, this would be only an apparent
development was a response [3] to “...the demand to instanta- solution. The reactive power Q is a measure of the effect of
neously compensate the reactive power...” Originally, this the current phase shift on the apparent power S, while the
theory was formulated by Akagi, Kanazawa and Nabae [1, 2] unbalanced power D is a measure of the effect of the load
for the active power filter control. imbalance on this power. Thus, these two powers are associ-
Power properties of three-phase systems are described by ated with quite different phenomena in electrical loads.
the IRP p-q Theory in two orthogonal α and β coordinates in The IRP p-q Theory has been developed for three-phase
terms of two, p and q instantaneous powers. They are referred systems with nonsinusoidal voltages and currents. However, if
to [3] as the instantaneous real and the imaginary powers or a theory is true at distorted waveforms, it has to provide
more commonly [4-6], as the instantaneous active and reac- credible results also when applied to systems with sinusoidal
tive powers. According to Authors’ of Ref. [3] claim: “…the voltages and currents, because such systems form a sub-set of
instantaneous imaginary (reactive) power q was introduced systems with distorted waveforms. Therefore, this paper
on the same basis as the conventional real power p in three- investigates only how does the IRP p-q Theory describe
phase circuits and then the instantaneous reactive power in power properties of linear, three-phase, three-wire systems
each phase was defined with the focus on the physical with sinusoidal voltages and currents. Results obtained using
meaning and the reason for naming…” Because of it, the IRP the IRP p-q Theory are compared with results obtained using
p-q Theory has become a very attractive theoretical tool not the Currents’ Physical Components (CPC) Power Theory,
only for the active power filter control [3-6], but also for developed [13-15] for three-phase systems under nonsinusoi-
analysis and identification [7-12, 18] of power properties of dal conditions.
three-phase systems with nonsinusoidal voltages and currents.
------------------------------------------- II. OUTLINE OF THE IRP p-q THEORY
To avoid any confusion between symbols used for the
active current as defined in Ref. [16] and denoted by ia, and
1
the line current of phase “a”, as well to be in accordance with Illustration 1a. Let us apply the IRP p-q Theory to a circuit
symbols used in Refs. [13-15], the phase indices R, S and T with a resistive load as shown in Fig. 2, assuming that the load
are used in this paper, instead of a, b, and c, it means, voltages is supplied from a symmetrical source of a sinusoidal, positive
and currents are denoted as shown in Fig. 1. sequence voltage, with
uR = 2 U cos ω1t, U = 277 V, (11)
assuming that the Δ/Y transformer is a loss-less, ideal trans-
former with the turn ratio 1:1.

Fig. 1. Three-phase, three-wire system


The Clarke’s Transform of phase voltages to the α and β
coordinates has the form:
⎡u ⎤
⎡ uα ⎤ 2 ⎡1 −1 / 2 −1 / 2 ⎤ ⎢ R ⎥
⎢u ⎥ = 3 ⎢ ⎥ uS . (2) Fig. 2. Example of circuit with resistive load
⎣ β⎦ ⎢⎣0 3 / 2 − 3 / 2 ⎥⎦ ⎢ ⎥
⎢⎣ uT ⎥⎦ With such assumptions, the Clarke’s Transform of phase vol-
tages results in
It is assumed that line voltages (uR, uS, uT) are referenced
to an artificial zero, i.e., uR + uS + uT = 0. At such a condition, ⎡ uα ⎤ ⎡ 2 U cosω1t ⎤ ⎡ 3 U cosω1t ⎤
⎢u ⎥ = C ⎢ ⎥=⎢ ⎥ . (12)
the Clarke’s Transform of phase voltages can be simplified to ⎣ β⎦ ⎢⎣ 2 U cos(ω1t − 120o ) ⎥⎦ ⎢⎣ 3 U sinω1t ⎥⎦
the form
The line currents,
⎡ uα ⎤ ⎡ 3 / 2 , 0 ⎤ ⎡ uR ⎤ ⎡ uR ⎤
⎢u ⎥ = ⎢ ⎥⎢ ⎥ = C⎢ ⎥ . (3) iR = 2 I cos (ω1t + 300) = - iS, I = 119.9 A, iT= 0,
⎣ β⎦ ⎢⎣1 / 2 , 2 ⎥⎦ ⎣ uS ⎦ ⎣ uS ⎦ could be transformed to
Similarly, in three-wire systems iR + iS + iT = 0, thus, the ⎡ iα ⎤ ⎡ iR ⎤ ⎡ 3 I cos(ω1t + 30o ) ⎤
Clarke’s Transform of the line currents has the form ⎢ ⎥ = C⎢ ⎥ = ⎢ ⎥ . (13)
⎡ 3 / 2 , 0 ⎤ ⎡iR ⎤ ⎣iβ ⎦ ⎣ − iR ⎦ ⎢⎣ − I cos(ω1t + 30o ) ⎥⎦
⎡ iα ⎤ ⎡iR ⎤
⎢i ⎥ = ⎢ ⎥⎢ ⎥ = C⎢ ⎥ . (4) Thus, the instantaneous real power of such a load is equal to
⎣β⎦ ⎢⎣1 / 2 , 2 ⎥⎦ ⎣ S ⎦
i ⎣ iS ⎦
p = uα iα + u β iβ = 3 U I [1 + cos 2(ω1t + 300)] , (14)
With voltages and currents transformed to the α and β coor-
dinates, the instantaneous active (real) power is defined, and the instantaneous reactive power,
according to Ref. [3], as
q = uα iβ − u β iα = − 3 U I sin 2(ω1t + 300 ) . (15)
p = uα iα + u β iβ , (5)
Since instantaneous reactive power, q, of the load is not
and the instantaneous reactive (imaginary) power as equal to zero hence, according to the IRP p-q Theory, a reac-
q = uα iβ − u β iα . (6) tive current occurs in supply lines. Its value in the α and β
With these two, p and q, instantaneous powers, instantaneous coordinates is equal to
active, and reactive currents are defined. The instantaneous − uβ
iα q = 2 q = I sin 2(ω1t + 300) sinω1t , (16)
active current, ip, is defined in the α and β coordinates as uα + u β2
uα uβ
iα p = p, iβ p = p, (7) uα
uα + u β
2 2
uα + u β2
2 iβ q = q = − I sin 2(ω1t + 300) cosω1t . (17)
uα2 + u β2
and the instantaneous reactive current, iq, in the α and β coor-
Having these values, the inverse Clarke’s Transform results in
dinates is defined as
the reactive current in supply lines, namely
− uβ uα
iαq = q, iβ q = q. (8) ⎡iRq ⎤ −1 ⎡ sin ω1t ⎤
⎢ ⎥ = I sin 2(ω1t + 30 ) C ⎢ ⎥ =
0
uα + u β
2 2
uα + u β2
2
⎣⎢ iSq ⎦⎥ ⎣ − cosω1t ⎦
Line currents can be obtained from currents in the α and β . (18)
coordinates with the inverse Clarke’s Transform: ⎡ sin ω 1t ⎤
= I 2 sin 2(ω1t + 300 ) ⎢ 0 ⎥
⎡iR ⎤ ⎡ 2/ 3 , 0 ⎤ ⎡ iα ⎤ ⎡ iα ⎤
3 ⎢⎣sin(ω1t − 120 ) ⎥⎦
−1
⎢i ⎥ = ⎢ ⎥⎢ ⎥ = C ⎢i ⎥ , (9) One could expect that only an active current could occur
⎣ S⎦ ⎢⎣ −1/ 6 , 1 / 2 ⎥⎦ ⎣ β ⎦
i ⎣β⎦ in a purely resistive, linear circuit. However, according to the
thus, active and reactive currents in supply lines are equal to IRP p-q Theory, in spite of the lack of any reactive elements
in the load and consequently, zero reactive power, Q, there is
⎡iRp ⎤ −1
⎡ iα p ⎤ ⎡iRq ⎤ −1
⎡ iα q ⎤
⎢ ⎥ =C ⎢ ⎥ =C
a reactive current in supply lines. It means that the reactive
⎢ ⎥, ⎢ ⎥. (10)
⎢⎣ iSp ⎥⎦ ⎢⎣iβ p ⎥⎦ ⎢⎣ iSq ⎥⎦ ⎢⎣iβ q ⎥⎦ current in the IRP p-q Theory cannot be associated with the
reactive power, Q, of the load. It occurs in supply lines even
2
of purely resistive loads. It means that results of the IRP p-q should remain in supply lines after total compensation of the
Theory deny a common meaning of a reactive current. Also, load, that means to unity power factor. Indeed, the active
observe that all currents in linear circuits with sinusoidal sup- current in the IRP p-q Theory has nothing in common with the
ply voltage are sinusoidal. However, when the IRP p-q The- meaning of the active current as it has been known in electri-
ory is applied for calculating the instantaneous active current cal engineering since 1932 when this concept was introduced
of the load in the α and β coordinates, then by Fryze. It is a quite different quantity, but its name, i.e., “the
u instantaneous active current” may cause a confusion,
iα p = 2 α 2 p = I [1 + cos 2(ω1t + 300)] cosω1t , (19) especially since formula (24) also specifies the instantaneous
uα + u β
values of the active current.
uβ Illustration 2a. Let us apply the IRP p-q Theory to the circuit
iβ p = p = I [1 + cos 2(ω1t + 300)] sinω1t . (20)
2
uα + u β2 shown in Fig. 3 with a purely reactive load, assuming that it is
supplied like the load in Illustration 1a, thus, with the voltage
Having the active current in the α and β coordinates, its value
in the load supply lines can be calculated, namely
⎡iRp ⎤ ⎡i ⎤
−1 α p
⎢ ⎥ =C ⎢ ⎥ =
⎢⎣ iSp ⎥⎦ ⎢⎣iβ p ⎥⎦
(21)
⎡ cos ω 1t ⎤
= I 2 [1 + cos 2(ω1t + 300 )] ⎢ 0 ⎥
.
3 ⎢⎣ cos(ω1t − 120 ) ⎦⎥
Fig. 3. Example of three-phase circuit with purely reactive load
This active current is not sinusoidal, however. Its waveform in
line R can be expressed in the form in the α and β coordinates specified by formula (12). The line
I currents in such a circuit are equal to
iRp = [2 cos ω1t + cos (ω1t + 600 ) + cos (3ω1t + 600 )] , (22)
6 iR = 2 I cos(ω1t - 600), iS = - iR, iT = 0, I = 119.2 A,
thus, it contains the third order harmonic. Thus, the IRP p-q and could be transformed to
Theory suggests a phenomenon that does not exist in the ⎡ 2 I cos(ω1t − 60o ) ⎤ ⎡ 3 I cos(ω1t − 60o ) ⎤
⎡ iα ⎤
circuit. This conclusion obtained from the IRP p-q Theory, ⎢i ⎥ = C ⎢ ⎥=⎢ ⎥ . (26)
also observed by Willems [17], is in an evident contradiction ⎣β⎦ ⎢⎣ − 2 I cos(ω1t − 60o ) ⎥⎦ ⎢⎣ − I cos(ω1t − 60o ) ⎥⎦
to a common meaning of the active current [16, 19] that was
Thus, the instantaneous real and imaginary powers are
introduced to electrical engineering by Fryze in 1932. The
active current is the current component proportional to the p = uα iα + u β iβ = 3 U I cos (2ω1t − 300 ) . (27)
supply voltage and of the value indispensable for providing
q = uα iβ − u β iα = − 3 U I [1 + sin (2ω1t − 300 )] . (28)
the load active power P. The active current is defined as
P In spite of zero active power, there is a non-zero active current
ia = u, (23) in the circuit. Its value in the α and β coordinates is equal to
|| u ||2
uα I
where ||u|| denotes the supply voltage rms value. Fryze’s defi- iα p = p = [cos(ω1t − 300 ) + cos(3ω1t − 300 )] , (29)
nition of the active current was generalized in Ref. [14] for uα + u β
2 2 2
three-phase systems as follows, uβ −I
⎡iRa ⎤ ⎡uR ⎤ iβ p = p= [sin(ω1t − 300 ) − sin(3ω1t − 300 )] , (30)
⎢i ⎥ = i = P u = P ⎢ u ⎥ , uα + u β
2 2 2
⎢ Sa ⎥ (24)
||u||2 ⎢⎢ ⎥⎥
a S
⎢⎣ iTa ⎥⎦ ||u||2 and in the phase coordinates this current is equal to
⎣ uT ⎦
⎡iRp ⎤ −1 α p
⎡ i ⎤ ⎡ 2/ 3 , 0 ⎤
where ||u|| denotes the rms value of the supply three-phase ⎢ ⎥ = C ⎢ ⎥= ⎢ ⎥×
voltage, that means, ⎣⎢ iSp ⎦⎥ ⎣⎢iβ p ⎦⎥ ⎢⎣ −1/ 6 , 1 / 2 ⎦⎥
||u|| = || uR ||2 + || uS ||2 + || uT ||2 . (25) ⎡ I [cos(ω t − 300 ) + cos(3ω t − 300 )] ⎤ . (31)
⎢ 1 1 ⎥
Thus, the active current in three-phase systems with a sinusoi- ×⎢ 2 ⎥
I
⎢ − [sin(ω1t − 30 ) − sin(3ω1t − 30 )]⎥
0 0
dal supply voltage is sinusoidal. ⎣ 2 ⎦
The main properties of the active current, for which the In particular, this current in line R is
concept of this current is so important for power theory and I
compensation, are summarized [17] by Willems: “The active iRp = [cos(ω1t − 300 ) + cos(3ω1t − 300 )] . (32)
current is hence a current which yields the same average (i.e. 6
active) power as the load current. It is the current with the One could expect that only a reactive current could occur
smallest rms value having this property, and hence it realizes in a purely reactive, linear circuit. However, according to the
the lowest line losses and the largest power factor.” The IRP p-q Theory, in spite of the lack of any resistive elements
instantaneous active current that results from the IRP p-q in the load and consequently, zero active power, P, there is an
Theory does not have any of these properties. Unlike the active current in supply lines. It means that results of the IRP
active current defined by Fryze, it is not the current that p-q Theory deny the common meaning of both the active and
3
reactive currents. Moreover, these currents are nonsinusoidal ||i ||2 = ||ia||2 + ||ir||2 + ||iu||2 . (41)
even if there is no source of harmonics in the supply source
and the load. Multiplying this equation by the square of the supply voltage
Let us compare these results obtained from the IRP p-q rms value, ||u||, the power equation
Theory with results of analysis of power properties of circuits
S 2 = P 2+ Q 2+ D 2 , (42)
considered in Illustrations 1a and 2a using the Currents’
Physical Components (CPC) Power Theory. can be obtained, where
Q = ||u|| ⋅||ir|| , D = ||u|| ⋅ ||iu|| , (43)
III. OUTLINE OF THE CPC POWER THEORY
are the reactive and unbalanced powers, respectively.
The Currents’ Physical Components (CPC) Power Theory,
Let us apply the CPC Theory to circuits analyzed previo-
developed in Ref. [13] for three-phase, three-wire systems
usly in Illustrations 1a and 2a using the IRP p-q Theory.
under nonsinusoidal conditions, is used in this paper as a refe-
rence for analysis of properties of the IRP p-q Theory, when it Illustration 1b. Since line-to-line admittances of the load are:
is applied to systems under sinusoidal conditions. Therefore, YRS = 0.25 S; YST = YTR = 0, formula (33) results in the equi-
only these elements of the CPC Theory that are needed for valent admittance,
describing three-phase, three-wire systems under sinusoidal Ye= Ge+ jBe = YRS+YST + YTR = 0.25 S , (44)
conditions are outlined in this Section.
A linear load as shown in Fig. 4, supplied with a symmet- and formula (34) results in the unbalanced admittance
0
rical sinusoidal voltage, with line-to-line admittances YRS, YST A = − (YST + αYTR + α*YRS) = − α*YRS = 0.25 e j 60 S , (45)
thus, the active current of the load is equal to
⎡iRa ⎤
⎢ ⎥
ia = ⎢ iSa ⎥ = 2 Re{ Ge U e jω1t } =
⎢⎣ iTa ⎥⎦
(46)
Fig. 4. Three-phase load ⎡ cosω1t ⎤
⎢ ⎥
and YTR can be characterized by equivalent admittance = 69.2 2 ⎢ cos(ω1t − 1200 ) ⎥ A.
Ye = Ge + jBe = YRS + YST + YTR , (33) ⎢ 0 ⎥
⎢⎣ cos(ω1t + 120 ) ⎥⎦
and unbalanced admittance
0 Since equivalent susceptance Be of the load considered is
A = − (YST + αYTR + α*YTR ), α = 1 e j 120 .
B

(34) equal to zero, the reactive current does not occur in the load
If the complex rms (crms) values of symmetrical phase volta- supply lines. The unbalanced current is equal to
ges of the supply are arranged into vectors ⎡iRu ⎤
⎡U R ⎤ ⎡U R ⎤ iu = ⎢⎢ iSu ⎥⎥ = 2 Re{A U # e jω1t } =
⎢U ⎥ = U , ⎢U ⎥ = U # , (35)
⎢ S⎥ ⎢ T⎥ ⎢⎣ iTu ⎥⎦
⎢⎣U T ⎥⎦ ⎢⎣ U S ⎥⎦
⎡ cos(ω t + 600 ) ⎤
then, the line currents of the load, arranged into a vector ⎢ 1

⎡iR ⎤ ⎡ IR ⎤ = 69.2 2 ⎢ cos(ω1t + 1800 ) ⎥ A. (47)
⎢ ⎥
i = ⎢ iS ⎥ = 2 Re ⎢⎢ IS ⎥⎥ e jω1t = 2 Re I e jω1t ,
⎢ ⎥ (36) ⎢ cos(ω1t − 600 ) ⎥
⎣ ⎦
⎢⎣ iT ⎥⎦ ⎢⎣ I T ⎥⎦
Indeed, the sum of the active and unbalanced currents is equal
can be decomposed into three components, namely to the line current of the load, namely
i = ia + ir + iu , (37) ⎡ cos(ω t − 600 ) ⎤
where ⎢ 1

ir + iu = 119.9 2 ⎢cos(ω1t + 1200 ) ⎥ A = i . (48)
ia = 2 Re{ Ge U e jω1t } , (38) ⎢ ⎥
⎢ 0 ⎥
is the active current, ⎣ ⎦
ir = 2 Re{ jBe U e jω1t } , (39) Thus, the supply current cannot contain any component other
is the reactive current and than the active and unbalanced currents. The rms value of
three-phase active and unbalanced currents is equal to, res-
iu = 2 Re{A U # e jω1t } , (40) pectively
is the unbalanced current. These three components of the load
line currents are associated with distinctive power related phy- ||ia|| = 69.2 3 = 119.9 A , ||iu|| = 69.2 3 = 119.9A , (49)
sical phenomena. Therefore, these currents are referred to as while the rms value of the three-phase supply current is
currents’ physical components.
The active, reactive and unbalanced current, ia, ir and iu, ||i|| = I R2 + IS2 = ||ia||2+ ||iu||2 = 169.6 A . (50)
are mutually orthogonal [13] thus, rms values of these three
currents fulfill the relationship Since ||u|| = 277 3 V, the load powers are equal to

4
⋅ ia|| = 57.5 kW,
P = ||u|||| ||ir|| = 69.2 3 =119.9A , ||iu|| = 69.2 3 =119.9A , (58)
⋅ ir|| = 0,
Q = ||u|||| while the rms value of the three-phase supply current is
(51)
⋅ iu|| = 57.5 kVA,
D = ||u|||| ||i|| = I R2 + IS2 = ||ir||2+ ||iu||2 = 169.6 A . (59)
⋅ i|| = 81.3 kVA .
S = ||u||||
Since ||u|| = 277 3 V, the load powers are equal to
These results are in an evident accordance with the fact that
the load in Illustration 1 does not contain any reactive com- ⋅ ia|| = 0,
P = ||u||||
ponent and it is unbalanced. Unfortunately, the IRP p-q ⋅ ir|| = 57.5 kVAr,
Q = ||u||||
Theory does not have any power quantity associated with the (60)
load imbalance, although it contributes to the apparent power ⋅ iu|| = 57.5 kVA,
D = ||u||||
increase. Instead, the load imbalance causes, according to the ⋅ i || = 81.3 kVA.
S = ||u||||
IRP p-q Theory, that a reactive current occurs apparently in These results are in a full accordance with the fact that the
the supply current, even if the load has zero reactive power. load in Illustration 2 is purely reactive and unbalanced.
Illustration 2b. Since line-to-line admittances of the load are: However, according to the IRP p-q Theory, the load imba-
YRS = - j¼ S, YST = YTR = 0, formula (33) results in the lance causes that an active current apparently occurs in the
equivalent admittance, supply current.
Ye= Ge+ jBe = YRS+YST + YTR = − j 0.25 S , (52)
IV. INSTANTANEOUS IDENTIFICATION OF POWER
and formula (34) results in the unbalanced admittance PROPERTIES
A = − (YST + αYTR + α*YRS) = − α*YRS = 0.25 e− j 30 S .
0
(53) The attractiveness of the IRP p-q Theory in electrical
Because equivalent conductance Ge is equal to zero, hence engineering community is due to the opinion, expressed by
authors of this Theory [3], that it enables an instantaneous
⎡iRa ⎤ identification of power properties of the load and consequent-
⎢ ⎥
ia = ⎢ iSa ⎥ = 2 Re{ Ge U e jω1t } = 0 , (54) ly, instantaneous compensation of the reactive power. Let us
⎢⎣ iTa ⎥⎦ check whether such an instantaneous identification is possible
or not.
thus, the active current does not occur in the supply current.
Indeed, the p and q powers could be known only with a
The reactive current is
delay needed for calculation, after samples of voltages and
⎡iRr ⎤ currents are provided by a measuring system. Does it mean,
ir = ⎢⎢ iSr ⎥⎥ = 2 Re{ jBe U e jω1t } = however, that power properties of the load are identified the
⎢⎣ iTr ⎥⎦ same moment when these two powers are calculated?
To answer this question, let us return to results of Illus-
⎡ cos(ω t − 900 ) ⎤ tration 1a. According to formulae (14) and (15), instantaneous
⎢ 1
⎥ values of powers p and q taken at the instant of time such that
= 69.2 2 ⎢ cos(ω1t + 1500 ) ⎥ A. (55)
⎢ ⎥ 2(ω1tk + 300) = 900, are mutually equal, with only the opposite
⎢ cos(ω1t + 300 ) ⎥ sign, i.e., pk = - qk. According to formulae (27) and (28), such
⎣ ⎦ a situation that pk = - qk can also occur in the circuit con-
The unbalanced current is equal to sidered in Illustration 2a, namely, at such an instant of time
⎡iRu ⎤ that 2ω1tk - 300 = 0. It means that the same pair of samples of
iu = ⎢⎢ iSu ⎥⎥ = 2 Re{A U # e jω1t } = the p and q powers can occur in a purely resistive and purely
⎢⎣ iTu ⎥⎦ reactive loads. Thus, power properties of the load cannot be
specified instantaneously in terms of the instantaneous active
⎡ cos(ω t − 300 ) ⎤ and reactive, p and q, powers. A sequence of measurements of
⎢ 1
⎥ the load voltages and currents, usually over period T, is
= 69.2 2 ⎢cos(ω1t + 1200 ) ⎥ A. (56) needed to specify power properties of a load.
⎢ ⎥
⎢ cos(ω1t − 150 ) ⎥
0
⎣ ⎦ V. CONCLUSIONS
Indeed, the sum of the reactive and unbalanced currents is The paper demonstrates that the IRP p-q Theory, when
equal to the line current of the load, namely applied to three-phase systems with sinusoidal voltages and
⎡ cos(ω1t − 600) ⎤ currents, provides results that defy common comprehension of
⎢ ⎥ power properties of such systems. It is because the IRP p-q
ir + iu = 119.9 2 ⎢ cos(ω1t + 1200) ⎥ A = i . (57) Theory suggests that
⎢ ⎥ (i) An instantaneous reactive current can occur in supply
⎢ 0 ⎥
⎣ ⎦ lines of purely resistive loads.
Thus, the supply current cannot contain any component other (ii) An instantaneous active current can occur in supply
than the active and unbalanced currents. The rms value of lines of purely reactive loads.
three-phase reactive and unbalanced currents is equal to, res- (iii) A distorted current component can exist in supply
pectively, currents of a linear load supplied with sinusoidal voltages.

5
Moreover, a pair of p and q powers calculated at some [7]. P. Salmeron, J.C. Montano, “Instantaneous power components in
instant of time does not provide information on power pro- polyphase systems under nonsinusoidal conditions,” IEE Proc.
perties of three-phase loads. No conclusions can be drawn on Science, Meas. and Technology, Vol. 143, No. 2, Feb.1996,
with respect to the load power properties. The knowledge of pp. 239-297.
these two powers does not allow us to answer the question: is [8]. J.M. Morendaz-Eguilaz, J. Peracaula, “Understanding AC po-
wer using the generalized instantaneous reactive power theory:
this load active, reactive, balanced or unbalanced?
considerations for instrumentation of three-phase electronic
The main deficiency of the IRP p-q Theory results from converters,” Proc. of the IEEE Int. Symp., Ind. Electr., ISIE ’99,
the fact that three independent power phenomena, i.e., perma- Vol. 3, pp. 1273-1277.
nent energy transmission associated with the active power, P, [9]. J.M. Aller, at al, “Space vector application in power systems,”
phase-shift associated with reactive power, Q, and supply Proc. of the 2000 3rd IEEE Int. Conf. on Devices, Circuits and
current asymmetry associated with unbalanced power, D, are Systems, pp. P78/1-P78/6.
described by the IRP p-q Theory in terms of only two powers, [10]. J.M. Aller, at al, “Advantages of the instantaneous reactive
p and q. Two powers cannot characterize three independent power definitions in three-phase system measurement,” IEEE
power phenomena. Power Eng. Review, Vol. 19, No. 6, June 1999, pp. 54-56.
Misinterpretations of power phenomena in three-phase [11]. Fang Zheng Peng, Jih-Sheng Lai, “Generalized instantaneous
systems, caused by the IRP p-q Theory, could be to some reactive power theory for three-phase power systems,” IEEE
degree attributed to names of currents, referred to as the ins- Trans. on Instr. Meas., Vol. 45, No. 1, Feb. 1996, pp. 293-297.
tantaneous active and reactive currents, that were earlier used [12]. K. Kim, F. Blaabjerg, B. Bak Jensen, “Spectral analysis of
[16] in electrical engineering for currents defined in a dif- instantaneous powers in single-phase and three-phase systems
ferent meaning. However, even if these names are modified, with use of p-q-r theory”, IEEE Trans. on Power Electronics,
the main deficiency of this Theory will remain. The IRP p-q Vol. 17, No. 5 Sept. 2002, pp. 711-720.
Theory does not provide any information as to reasons of the [13]. L.S. Czarnecki, “Orthogonal decomposition of the current in a
apparent power S increase and the power factor decline. Does three-phase non-linear asymmetrical circuit with nonsinusoidal
voltage,” IEEE Trans. Instr. Meas., Vol. IM-37, No. 1, March
this power increase due to the presence of reactive compo-
1988, pp. 30-34.
nents in the load or due to its imbalance? It is an intrinsic
[14]. L.S. Czarnecki, “Power related phenomena in three-phase
deficiency of this Theory. unbalanced systems,” IEEE Trans. on Power Delivery, Vol. 10,
The IRP p-q Theory was developed for three-phase sys- No. 3, 1995, pp. 1168-1176.
tems under nonsinusoidal conditions. Unfortunately, it has a [15]. L.S. Czarnecki, “Harmonics and power phenomena,” Wiley
number of deficiencies, as compiled above, even when it is Encyclopedia of Electrical and Electronics Engineering, John
applied to a relatively simple, sinusoidal situation, where the Wiley & Sons, Inc., Supplement 1, 2000, pp. 195-218.
power phenomena are known. These deficiencies could be [16]. S. Fryze, “Wirk-, Blind-, und Scheinleistung in Elektrischen
considered as irrelevant when the IRP p-q Theory is used as Stromkreisen mit nicht-sinusoidalen Verlauf von Strom und
the fundamental for a switching compensator control algo- Spannung,” ETZ, No. 25, 26 and 27, 1932.
rithm, but not when it is considered as a power theory, it [17]. J.L. Willems, “Mathematical foundations of the instantaneous
means, as a theoretical tool that explains power phenomena power concept: a geometrical approach,” Europ. Trans. on Elec-
and properties of electrical systems. tric Power, ETEP, Vol. 6, No. 5, Sept./Oct. 1996, pp. 299-304.
[18]. W. le Roux and J.D. van Wyk, “Evaluation of residual network
REFERENCES distortion during compensation according to the ‘Instantaneous
[1]. H. Akagi, Y. Kanazawa, A. Nabae, “Generalized theory of the Power Theory,” European Trans. on Electrical Power, ETEP,
instantaneous reactive power in three-phase circuits,” Proc. of Vol. 8, No. 5, pp. 337-344, Sept./Oct. 1998.
the Int. Power Electron. Conf., (JIEE IPEC) Tokyo/Japan, 1983, [19]. L.S. Czarnecki, “Budeanu and Fryze: Two frameworks for
pp. 1375-1386. interpreting power properties of circuits with nonsinusoidal
[2]. H. Akagi, Y. Kanazawa, A. Nabae, “Instantaneous reactive voltages and currents,” Archiv fur Elektrotechnik, (81), N. 2,
power compensators comprising switching devices without ener- 1997, pp. 5-15.
gy storage components,” IEEE Trans. Ind. Appl., IA-20, 1984,
No. 3, pp. 625-630. BIOGRAPHY
[3]. H. Akagi, Y. Nabae, “The p-q theory in three-phase systems
Leszek S. Czarnecki received the M.Sc. and
under non-sinusoidal conditions,” Europ. Trans. on Electric
Ph.D. degrees in electrical engineering and
Power, ETEP, Vol. 3, No. 1, Jan./Feb. 1993, pp. 27-31. Habil. Ph.D. degree from Silesian University of
[4]. A. Nava-Seruga, M. Carmona-Hernandez, “A detailed instanta- Technology, Poland, in 1963, 1969 and 1984,
neous harmonic and reactive compensation analysis of three- respectively, where he was employed as an
phase AC/DC converters, in abc and /spl alpha//spl beta coordi- Assistant Professor. Beginning in 1984 he
nates,” IEEE Trans. on Power Delivery, Vol. 14, No. 3, July worked for two years at the Power Engineering
1999, pp. 1039-1045. Section, Division of Electrical Engineering,
National Research Council (NRC) of Canada as
[5]. M.K. Mishra, A. Joshi, A. Ghosh, “Unified shunt compensator a Research Officer. In 1987 he joined the
algorithm based on generalized instantaneous reactive power Electrical Engineering Dept. at Zielona Gora
theory,” IEEE Trans. on Generation Transmission and Distri- University of Technology, Poland. In 1989 Dr.
bution, Vol. 148, No. 6, Nov. 2001, pp. 583-589. Czarnecki joined the Electrical and Computer Engineering Dept. at Louisiana
State University, Baton Rouge, where he is a Professor of Electrical
[6]. E. Watanabe, M. Aredes, “Compensation of nonperiodic cur-
Engineering now. For developing a power theory of three-phase
rents using the instantaneous reactive power theory,” Proc. of nonsinusoidal unbalanced systems and methods of compensation of such
2000 PES Summer Meeting, Vol. 2, 2000, pp. 994-999. systems, he was elected to the grade of Fellow IEEE in 1996. His research

6
interests include network analysis and synthesis, power phenomena in
nonsinusoidal systems, compensation and supply quality improvement in
such systems. (Electrical and Computer Engineering Dept., LSU, Baton
Rouge, LA 70803, Phone: 225 767 6528), czarneck@ece.lsu.edu). Internet
home page: www.geocities.com/lsczar