FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET

As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) Project Services Company PSC (S.A.E) Qarit Oraby, Desert Ro
(Name and Ad

Purchaser Elsewedy Power System Projects, Zone A3 - 10th of Ramadan City, Sharkia,
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21050-31 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: B 31 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Drawing No. Service Hydrotest D.P D.T Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5,7,10,11 21050-470-13-301 LP MAIN STM INSTR CONN 17 11 270 3/4"


4,5,7,10,11 21050-470-13-302 LP MAIN STM INSTR CONN 17 11 270 3/4"
4,5,7,10,11 21050-470-13-322 LP MAIN STM INSTR CONN 17 11 270 1"
4,5,7,10,11 21050-470-13-323 LP MAIN STM INSTR CONN 17 11 270 1"
4,5,7,10,11 21050-470-13-320 LP MAIN STM INSTR CONN 17 11 270 1"
4,5,7,10,11 21050-470-13-333 LP MAIN STM INSTR CONN 17 13 270 1"
4,5,7,10,11 21050-470-13-334 LP MAIN STM INSTR CONN 17 13 270 1"
4,5,7,10,11 21050-470-13-404 LP MAIN STM DRN 17 13 270 2"
4,5,7,10,11 21050-470-13-405 LP MAIN STM DRN 17 11 270 1"
4,5,7,10,11 21050-470-61-502 AUX STM CONN VNT 17 11 270 1"
TURERS' DATA REPORT SUPPLEMENTARY SHEET
ons of the ASME Boiler and Pressure Vessel Code Rules

Project Services Company PSC (S.A.E) Qarit Oraby, Desert Road, Amria, Alexandria, Egypt.
(Name and Address)

wer System Projects, Zone A3 - 10th of Ramadan City, Sharkia, Egypt


(Name and Address)

Recovery Steam Generator: Triple Pressure VNC + Benson HP

N/A 2017
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. STD SA106-B,SA105


Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,bloc
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu


Hydrotest
Data Items by Line Drawing No. Service *D.P *D.T
Pressure Size (NPS)
No. 21051 Boiler External Piping bar(g) °C
bar(g)

4,5 & 7 410-13-193 LP MAIN STM SV INL 17 11 270 6"


4,5 & 7 470-13-301 LP MAIN STM INSTR CONN 17 11 270 3/4"
4,5 & 7 470-13-302 LP MAIN STM INSTR CONN 17 11 270 3/4"
4,5 & 7 470-13-330 LP MAIN STM INSTR CONN 17 11 270 2"
4,5 & 7 470-13-331 LP MAIN STM INSTR CONN 17 11 270 1"
4,5 & 7 470-13-332 LP MAIN STM INSTR CONN 17 11 270 1"
4,5 & 7 470-13-333 LP MAIN STM INSTR CONN 17 13 270 1"
4,5 & 7 470-13-334 LP MAIN STM INSTR CONN 17 13 270 1"
4,5 & 7 470-13-404 LP MAIN STM DRN 17 13 270 2"
4,5 & 7 470-13-405 LP MAIN STM DRN 17 11 270 1"
4,5 & 7 470-61-402 AUX STM DRN 17 13 270 1"
4,5 & 7 470-61-403 AUX STM DRN 17 13 270 1"
4,5 & 7 470-61-502 AUX STM CONN VNT 17 11 270 2"
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,bloc
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu


Hydrotest
Data Items by Line Drawing No. Service *D.P *D.T
Pressure Size (NPS)
No. 21051 Boiler External Piping bar(g) °C
bar(g)

Date Signed By MEGA For Constructio


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Commiss
ERS' DATA REPORT SUPPLEMENTARY SHEET
the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

ustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

ery Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, Material Spec. No. Remark


Sch.

Sch. STD SA105


Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
ERS' DATA REPORT SUPPLEMENTARY SHEET
the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

ustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

ery Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Ru

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,blo
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 470-13-324 LP MAIN STM INSTR CONN 26 19 270 1"


4,5 & 7 470-13-323 LP MAIN STM INSTR CONN 26 19 270 1"
4,5 & 7 470-13-322 LP MAIN STM INSTR CONN 26 17 270 1"
4,5 & 7 470-13-305 LP MAIN STM INSTR CONN 26 17 270 3/4"
4,5 & 7 470-13-320 LP MAIN STM INSTR CONN 26 17 270 2"
4,5 & 7 470-13-321 LP MAIN STM INSTR CONN 26 17 270 1"
4,5 & 7 470-13-402 LP MAIN STM DRN 26 17 270 2"
4,5 & 7 470-13-601 LP MAIN STM SAMPLE 26 17 270 3/4"
4,5 & 7 470-24-601 LP FW SAMPLE 26 21.3 210 3/4"
4,5 & 7 470-24-606 LP FW DOSING CONN 26 21.3 210 1"
4,5 & 7 470-35-211 LP EVAP N2 CONN 26 20 210 1"
4,5 & 7 470-35-212 LP EVAP N2 CONN 26 20 210 1"
4,5 & 7 470-35-300 LP DRM MEAS HDR 26 17 210 2"
4,5 & 7 470-35-301 LP DRM INSTR CONN 26 17 210 1"
4,5 & 7 470-35-303 LP DRM INSTR CONN 26 17 210 1"
4,5 & 7 470-35-305 LP DRM INSTR CONN 26 17 210 3/4"
4,5 & 7 470-35-307 LP DRM INSTR CONN 26 17 210 3/4"
4,5 & 7 470-35-411 LP DRM LI DRN 26 20 210 1"
4,5 & 7 470-35-501 LP DRM VNT 26 17 210 1"
4,5 & 7 470-35-601 LP DRM WTR SAMP 26 19 210 3/4"
4,5 & 7 470-36-001 LP IBD 26 21.5 210 2"
4,5 & 7 470-36-401 LP EVAP DRN 26 20 210 2"
4,5 & 7 470-36-402 LP EVAP DRN 26 20 210 2"
4,5 & 7 470-36-411 LP EVAP PRESS TST CONN 26 21.5 210 1"
4,5 & 7 470-38-001 LP CBD 26 20 210 1"
4,5 & 7 470-42-412 NITROGEN 26 17 210 1"
4,5 & 7 470-42-414 NITROGEN DRN 26 17 210 1/2"
4,5 & 7 470-42-501 LP SAT STM VNT 26 17 210 1"
4,5 & 7 470-42-604 LP SAT STM SAMP 26 17 210 3/4"
4,5 & 7 410-13-003 LP MAIN STM 26 17 270 18"
4,5 & 7 470-13-191 LP MAIN STM SV INL 26 17 270 1 1/2 "
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Ru

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,blo
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Constructio


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Com
URERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

ndustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. STD SA106-B,SA105


Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA234-WPB,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. 40S SA312-TP304H,SA182-F304H
Sch. STD SA106-B
Sch. STD SA105
URERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

ndustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 21050-470-24-401 LP FW DRN 60 40 200 1"


4,5 & 7 21050-470-24-501 LP FW VNT 60 40 200 1"
4,5 & 7 21050-470-26-303 COND PHTR INL INSTR CONN 60 40 252 1/2"
4,5 & 7 21050-470-26-401 COND PHTR INL DRN 60 40 252 1"
4,5 & 7 21050-470-26-404 COND PHTR OUTL DRN 60 40 252 2"
4,5 & 7 21050-470-26-501 COND PHTR INL VNT 60 40 252 1"
4,5 & 7 21050-470-44-412 NITROGEN 60 40 252 1"
4,5 & 7 21050-470-44-414 NITROGEN DRN 60 40 252 1/2"
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Constructio


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Commiss
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. STD SA106-B,SA105


Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 21050-470-24-191 LP FW SA-V INL 68 43 210 1"


4,5 & 7 21050-470-24-403 LP FW DRN 68 43 210 1"
4,5 & 7 21050-470-41-422 NITROGEN 68 45 450 1"
4,5 & 7 21050-470-41-424 NITROGEN DRN 68 45 450 1/2"
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Constructio


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Commiss
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. STD SA106-B,SA105


Sch. STD SA106-B,SA105
Sch. STD SA335-P11,SA234- WP11
Sch. STD SA335-P11,SA234- WP11
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY
As Required by the Provisions of the ASME Boiler and Pressure Vess

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz A


(Name and A

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile


(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VN

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.)

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Tem

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 470-12-301 IP MAIN STM INSTR CONN 75 50 342 3/4"


4,5 & 7 470-12-302 IP MAIN STM INSTR CONN 75 50 342 3/4"
4,5 & 7 470-12-310 IP MAIN STM INSTR CONN 75 50 342 2"
4,5 & 7 470-12-311 IP MAIN STM INSTR CONN 75 50 342 1"
4,5 & 7 470-12-312 IP MAIN STM INSTR CONN 75 50 342 1"
4,5 & 7 470-12-305 IP MAIN STM INSTR CONN 75 50 450 3/4"
4,5 & 7 470-12-313 IP MAIN STM INSTR CONN 75 52 342 1"
4,5 & 7 470-12-314 IP MAIN STM INSTR CONN 75 52 342 1"
4,5 & 7 470-12-402 IP MAIN STM DRN 75 52 342 2"
4,5 & 7 470-12-407 IP MAIN STM DRN 75 50 450 1"
4,5 & 7 470-12-601 IP MAIN STM SAMPLE 75 50 342 3/4"
4,5 & 7 470-28-601 IP DRM INL SAMP 75 62.5 266 3/4"
4,5 & 7 470-28-653 IP DRM PHOS DOS CONN 75 62.5 266 1"
4,5 & 7 470-33-211 IP EVAP N2 CONN 75 53 266 1"
4,5 & 7 470-33-212 IP EVAP N2 CONN 75 53 266 1"
4,5 & 7 470-33-300 IP DRM MEAS HDR 75 50 266 2"
4,5 & 7 470-33-301 IP DRM INSTR CONN 75 50 266 1"
4,5 & 7 470-33-303 IP DRM INSTR CONN 75 50 266 1"
4,5 & 7 470-33-305 IP DRM INSTR CONN 75 50 266 3/4"
4,5 & 7 470-33-307 IP DRM INSTR CONN 75 50 266 3/4"
4,5 & 7 470-33-406 IP DRM LI DRN 75 53 266 1"
4,5 & 7 470-33-501 IP DRM VNT 75 50 266 1"
4,5 & 7 470-34-001 IP IBD 75 62.5 266 2"
4,5 & 7 470-34-401 IP EVAP DRN 75 53 266 2"
4,5 & 7 470-34-402 IP EVAP DRN 75 53 266 2"
4,5 & 7 470-34-411 IP EVAP PRESS TEST CONN 75 62.5 266 1"
4,5 & 7 470-37-001 IP CBD 75 53 266 1"
4,5 & 7 470-37-601 IP DRM WTR SAMP 75 53 266 3/4"
4,5 & 7 470-41-412 NITROGEN 75 50 266 1"
4,5 & 7 470-41-414 NITROGEN DRN 75 50 266 1/2"
4,5 & 7 470-41-501 IP SAT STM VNT 75 50 266 1"
4,5 & 7 470-41-601 IP SAT STM SAMP 75 50 266 3/4"
4,5 & 7 470-76-002 RH ATP SPRW RECI 75 62.5 266 1/2"
4,5 & 7 470-12-191 IP MAIN STM SV INL 75 50 342 1 1/2 "
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY
As Required by the Provisions of the ASME Boiler and Pressure Vess

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz A


(Name and A

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile


(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VN

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.)

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Tem

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Construction & I


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (N
DATA REPORT SUPPLEMENTARY SHEET
ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

s (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt


(Name and Address)

eam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. STD SA106-B,SA105


Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA234-WPB
Sch. STD SA106-B,SA234-WPB
Sch. STD SA106-B,SA234-WPB
Sch. STD SA335-P11,SA335-F11
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105
Sch. STD SA106-B,SA105,SA234-WPB
Sch. STD SA335-P11,SA234-WP11,SA182-F22
Sch. STD SA106-B,SA105
Sch. XS SA335-P11,SA182-F11
Sch. XS SA335-P11,SA182-F11
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105,SA105-N
Sch. XS SA106-B,SA105,SA105-N
Sch. XS SA106-B,SA105-N
Sch. XS SA106-B,SA105-N
Sch. XS SA106-B,SA105,SA105-N
Sch. XS SA106-B,SA105-N
Sch. XS SA106-B,SA105,SA217GR-WC6
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA234-WPB,SA105
Sch. XS SA106-B,SA105,SA105-N
Sch. STD SA106-B,SA234-WPB,SA105
Sch. STD SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. 40S SA312-TP304H,SA312-F304H
Sch. STD SA106-C,SA105,SA234-WPC-SA182-F316
Sch. STD SA105
DATA REPORT SUPPLEMENTARY SHEET
ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

s (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt


(Name and Address)

eam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 21050-470-23-012 IP FW 165 110 200 2"


4,5 & 7 21050-470-23-303 IP FW INSTR CONN 165 110 200 3/4"
4,5 & 7 21050-470-23-304 IP FW INSTR CONN 165 110 319 3/4"
4,5 & 7 21050-470-23-401 IP FW DRN 165 110 200 1"
4,5 & 7 21050-470-23-405 IP FW DRN 165 110 319 1"
4,5 & 7 21050-470-23-501 IP FW VT 165 110 319 1"
4,5 & 7 21050-470-41-421 NITROGEN 165 110 319 1"
4,5 & 7 21050-470-41-434 NITROGEN DRN 165 110 319 1/2"
4,5 & 7 21050-470-66-401 HP BYPASS STN SPRW DRN 165 85 470 1"
4,5 & 7 21050-470-73-010 RH ATP SPRW RECI 165 110 200 1/2"
4,5 & 7 21050-470-76-001 RH ATP SPRW RECI 165 110 200 1/2"
4,5 & 7 21050-470-73-311 RH INTSTG ATP SPRW INSTR 165 110 200 3/4"
4,5 & 7 21050-470-73-401 RH ATP SPRW DRN 165 110 200 1"
4,5 & 7 21050-470-74-401 RH ATP SPRW DRN 165 110 200 1"
4,5 & 7 21050-470-74-403 RH ATP SPRW DRN 165 110 200 1"
4,5 & 7 21050-470-23-191 IP FW SV INL 165 110 319 2"
4,5 & 7 21050-470-76-401 RH ATP SPRW RECI DRN 165 110 200 1/2"

Date Signed By MEGA For Constructio


Date
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Commiss
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. STD SA106-C,SA234-WPC


Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA234-WPC
Sch. STD SA106-C
Sch. XS SA335-P22,A182F22
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch.XS SA335-P11,SA182-F11
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
Sch. STD SA105
Sch. STD SA106-C,SA105

By MEGA For Construction & Industies


RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,bloc
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (N

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Tempe

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 21050-470-10-301 HP SH3 OUTL INSTR CONN 294 196 595 3/4"
4,5 & 7 21050-470-11-012 HP MAIN STM 294 196 595 2"
4,5 & 7 21050-470-11-301 HP MAIN STM INSTR CONN 294 196 595 3/4"
4,5 & 7 21050-470-11-304 HP MAIN STM INSTR CONN 294 196 595 3/4"
4,5 & 7 21050-470-11-305 HP MAIN STM INSTR CONN 294 196 595 3/4"
4,5 & 7 21050-470-11-306 HP MAIN STM INSTR CONN 294 196 595 3/4"
4,5 & 7 21050-470-11-405 HP MAIN STM DRN 294 196 595 1"
4,5 & 7 21050-470-11-580 HP MAIN STM HYDROTEST CONN 294 196 595 1"
4,5 & 7 21050-470-11-601 HP MAIN STM SAMPLE 294 196 595 3/4"
4,5 & 7 21050-470-21-304 HP FW INSTR CONN 294 220 375 3/4"
4,5 & 7 21050-470-21-405 HP FW DRN 294 220 375 1"
4,5 & 7 21050-470-21-501 HP FW VNT 294 220 375 2"
4,5 & 7 21050-470-21-502 HP FW VNT 294 220 375 1"
4,5 & 7 21050-470-21-503 HP FW VNT 294 196 458 2"
4,5 & 7 470-27-301 HP ECO OUTL INSTR CONN 294 211 371 3/4"
4,5 & 7 21050-470-27-303 HP ECO OUTL INSTR CONN 294 211 371 3/4"
4,5 & 7 21050-470-27-305 HP ECO OUTL INSTR CONN 294 211 371 3/4"
4,5 & 7 21050-470-27-401 HP ECO DRN 294 220 375 2"
4,5 & 7 21050-470-27-403 HP ECO DRN 294 213 375 2"
4,5 & 7 21050-470-27-501 HP ECO 3-4 CONN VNT 294 220 375 2"
4,5 & 7 21050-470-27-502 HP ECO 3-4 CONN VNT 294 205 458 2"
4,5 & 7 21050-470-27-503 HP ECO OUTL VNT 294 211 371 2"
4,5 & 7 21050-470-27-504 HP ECO OUTL VNT 294 205 458 2"
4,5 & 7 21050-470-28-301 IP FW CV INL INSTR CONN 294 110 319 3/4"
4,5 & 7 21050-470-28-401 IP ECO OUTL DRN 294 110 319 1"
4,5 & 7 21050-470-28-501 IP FW CV INL VNT 294 110 319 1"
4,5 & 7 21050-470-28-651 IP FW CHEM DOS CONN 294 110 319 1"
4,5 & 7 21050-470-30-301 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-302 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-303 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-304 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-305 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-306 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-307 HP SEP INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-30-308 HP SEP INSTR CONN 294 205 458 3/4"
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,bloc
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (N

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Tempe

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Construction


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Comm
RS' DATA REPORT SUPPLEMENTARY SHEET
the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

stries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

ry Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. XS SA335-P91,SA182-F91
Sch.160 SA335-P91,SA182-F91
Sch. XS SA335-P91,SA182-F91
Sch. XS SA335-P91,SA182-F91
Sch. XS SA335-P91,SA182-F91
Sch. XS SA335-P91,SA182-F91
Sch. 160 SA335-P91,SA182-F91
Sch. 160 SA335-P91,SA182-F91
Sch. XS SA335-P91,SA182-F91
Sch. STD SA106-C,SA105
Sch. XS SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. XS SA106-C,SA105
Sch. 160 SA335-P22
Sch.xs SA106-B , SA105
Sch.xs SA106-B , SA105
Sch.xs SA106-B , SA105
Sch.160 SA106-B , SA105-B
Sch.160 SA106-B , SA105
Sch160 SA106-B , SA105-B
Sch.XS SA106-B , SA105-B
Sch.160 SA106-B , SA105
Sch.160 SA335-P11,SA182-F11
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch. XS SA106-B,SA105
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
RS' DATA REPORT SUPPLEMENTARY SHEET
the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

stries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

ry Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 21050-470-30-411 HP SEP PRESS TEST CONN 294 211.5 458 1"
4,5 & 7 21050-470-30-601 HP SEP WTR SAMP 294 211.5 458 1"
4,5 & 7 21050-470-32-301 HP SEP INL INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-32-303 HP SEP INL INSTR CONN 294 205 458 3/4"
4,5 & 7 21050-470-32-407 HP EVAP DRN 294 207 458 2"
4,5 & 7 21050-470-32-501 HP SEP INL VNT 294 205 458 1"
4,5 & 7 21050-470-32-502 HP SEP INL VNT 294 205 458 1"
4,5 & 7 21050-470-32-503 HP SEP INL VNT 294 205 458 1"
4,5 & 7 21050-470-32-504 HP SEP INL VNT 294 205 458 1"
4,5 & 7 21050-470-32-505 HP SEP INL VNT 294 205 458 1"
4,5 & 7 21050-470-32-506 HP SEP INL VNT 294 205 458 1"
4,5 & 7 21050-470-39-411 NITROGEN 294 205 458 1"
4,5 & 7 21050-470-39-412 NITROGEN 294 220 458 1"
4,5 & 7 21050-470-39-413 NITROGEN 294 220 458 1/2"
4,5 & 7 21050-470-39-414 NITROGEN DRN 294 220 458 1/2"
4,5 & 7 21050-470-39-417 NITROGEN DRN 294 196 458 1/2"
4,5 & 7 21050-470-39-421 NITROGEN 294 220 458 1"
4,5 & 7 21050-470-39-501 HP SEP STM OUTL VNT 294 205 458 1"
4,5 & 7 21050-470-40-403 HP SH3 INL DRN 294 220.5 571 2"
4,5 & 7 21050-470-40-501 HP INTSTG ATP OUTL VNT 294 205 571 3/4"
4,5 & 7 21050-470-67-002 HP BYPASS STN SPRW RECI 294 220 375 1/2"
4,5 & 7 21050-470-70-002 HP ATP SPRW RECI 294 220 375 1/2"
4,5 & 7 21050-470-40-402 HP SH3 INL DRN 294 205 571 2"
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,block1
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Constructio


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Commiss
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch.160 SA335-P22,SA182-F22
Sch. XS SA335-P11,SA182-F11
Sch.XS SA335-P11,SA182-F11
Sch.XS SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch.160 SA335-P11,SA182-F11
Sch. 160 SA335-P11,SA182-F12
Sch. 160 SA335-P11,SA182-F12
Sch. 160 SA335-P11,SA182-F11
Sch. 160 SA335-P11,SA182-F11
Sch. 160 SA335-P11,SA182-F11
Sch. 160 SA335-P11
Sch. XS SA335-P11,SA182-F11
Sch. 160 SA335-P91,SA182-F91
Sch.XS SA335-P91,SA182-F91
Sch. STD SA106-C,SA105
Sch. STD SA106-C,SA105
CL 6000 SA182-F91
RERS' DATA REPORT SUPPLEMENTARY SHEET
of the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

dustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

overy Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,bloc
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

4,5 & 7 21050-470-21-012 HP FW 450 300 200 2"


4,5 & 7 21050-470-21-303 HP FW INSTR CONN 450 300 200 3/4"
4,5 & 7 21050-470-21-401 HP FW DRN 450 300 200 1"
4,5 & 7 21050-470-27-515 HP ECO BYPASS VNT 450 300 200 1"
4,5 & 7 21050-470-66-020 HP BYPASS STN SPRW RECI 450 300 200 1/2"
4,5 & 7 21050-470-66-402 HP BYPASS STN SPRW DRN 450 300 200 1"
4,5 & 7 21050-470-67-001 HP BYPASS STN SPRW RECI 450 300 200 1/2"
4,5 & 7 21050-470-67-401 HP BYPASS STN SPRW DRN 450 300 200 1/2"
4,5 & 7 21050-470-70-001 HP ATP SPRW RECI 450 300 200 1/2"
4,5 & 7 21050-470-71-010 HP ATP SPRW RECI 450 300 200 1/2"
4,5 & 7 21050-470-71-311 HP INTSTG ATP SPRW INSTR 450 300 200 3/4"
4,5 & 7 21050-470-71-401 HP ATP SPRW DRN 450 300 200 1"
4,5 & 7 21050-470-72-401 HP ATP SPRW DRN 450 300 200 1"
4,5 & 7 21050-470-72-403 HP ATP SPRW DRN 450 300 200 1"
4,5 & 7 21050-470-72-303 HP FNL STG ATP SPRW INSTR 450 300 200 3/4"
4,5 & 7 21050-470-90-401 HP FILING DRN 450 300 200 1"
4,5 & 7 21050-470-90-501 HP FILING VT 450 300 200 1"
4,5 & 7 21050-470-91-401 HP FILING DRN 450 300 200 1"
4,5 & 7 21050-470-70-401 HP ATP SPRW RECI DRN 450 300 200 1/2"
4,5 & 7 21050-470-66-501 HP BYPASS STN SPRW VT 450 300 200 1"
FORM P-6 MANUFACTURERS' DATA REPORT SUPPLEMENTARY SHEET
As Required by the Provisions of the ASME Boiler and Pressure Vessel Code Rules

Manufacturer (or Engineering-Contractor) MEGA for Construction & Industies ,8 Markaz Al Maloumat St. ,bloc
(Name and Address)

Purchaser ORASCOM Construction Industries (OCI),2005A Corniche El Nile ,Nile City South Tow
(Name and Address)

Type of Boiler Heat Recovery Steam Generator: Triple Pressure VNC + Benson HP

Boiler No. 21051-41 N/A See Below Table


(Mfrs. Serial No.) (CRN) (Drawing No.) (Nat

P-4A ID: MEGA-001/H41 *D.P : Design Pressure *D.T : Design Temperatu

Data Items by Line Service Hydrotest D.P D.T


Drawing No. Size (NPS)
No. Boiler External Piping Pressure bar(g) °C

Date Signed By MEGA For Constructio


Date
Ibrahim Eldesoky
Commissions
(Authorized Inspector) (National Board Commiss
ERS' DATA REPORT SUPPLEMENTARY SHEET
the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

ustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

ery Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

Sch. 160 SA106-C,SA105


Sch. 160 SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. XS SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. XS SA106-C,SA105
Sch. XS SA106-C,SA105
Sch. XS SA106-C,SA105
Sch. XS SA106-C,SA105
Sch.XS SA335-P11,SA182-F11
Sch. 160 SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch.XS SA335-P11,SA182-F11
Sch. 160 SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. 160 SA106-C,SA105
Sch. XS SA106-C,SA105
Sch.160 SA106-C,SA105
ERS' DATA REPORT SUPPLEMENTARY SHEET
the ASME Boiler and Pressure Vessel Code Rules

nstruction & Industies ,8 Markaz Al Maloumat St. ,block1157,Sheraton Helopolis area-Cairo,Egypt


(Name and Address)

ustries (OCI),2005A Corniche El Nile ,Nile City South Tower, Cairo, Egypt
(Name and Address)

ery Steam Generator: Triple Pressure VNC + Benson HP

N/A 2018
(Nat'l Bd. No.) (Year Built)

*D.P : Design Pressure *D.T : Design Temperature

Thickness, mm Or Material Spec. No. Remark


Sch.

By MEGA For Construction & Industies

(National Board Commission Number and Endorsement)


Hydrotest
Data Items Service *D.P *D.T
Drawing No. Pressure
by Line No. Boiler External Piping bar(g) °C
bar(g)

4,5 & 7 410-13-193 LP MAIN STM INSTR 17 11 270


CONN 11 270
4,5 & 7 470-13-301 LP MAIN STM INSTR 17
470-13-302 CONN
LP MAIN STM INSTR 17 11 270
4,5 & 7
CONN 11 270
4,5 & 7 470-13-320 LP MAIN STM INSTR 17
CONN 11 270
4,5 & 7 470-13-322 LP MAIN STM INSTR 17
CONN 13 270
4,5 & 7 470-13-323 LP MAIN STM INSTR 17
CONN 13 270
4,5 & 7 470-13-333 LP MAIN STM INSTR 17
CONN 13 270
4,5 & 7 470-13-334 LP MAIN STM DRN 17
4,5 & 7 470-13-404 LP MAIN STM DRN 17 11 270
4,5 & 7 470-13-405 AUX STM CONN VNT 17 11 270
4,5 & 7 470-61-402 LP MAIN SV INL 17 11 270
4,5 & 7 470-61-403 AUX STM DRN 17 13 270
4,5 & 7 470-61-502 AUX STM DRN 17 13 270
Thickness,
Size (NPS) Material Spec. No. Remark
Sch.

6" Sch. STD SA106-B,SA105


3/4" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
2" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B,SA105
1" Sch. STD SA106-B
1" Sch. STD SA106-B
1" Sch. STD SA106-B
Elsewedy Power System Projects, Zone A3 - 10

Heat Recovery Steam Generator: Triple Pressure