ATS Operation
The 2 transformers provide the power supply to the facility. Our function here is to control the closing and opening of the
2 CB’s (circuit breaker) for the 2 transformers. The most important condition is not to have the 2 CB’s closed at the same
time. To ensure the safety of operation there is different interlocks used either software or hardwire. We will control the
action of the breakers due to different input signals to the Zelio which indicate the state of the supply and the presence
of any faults. These input signals are:
The operation of the 2 transformers depends on the condition of the supply, which is detected using the undervoltage
sensors on the 2 transformers (UV1, UV2). The UV sensor gives a signal when there is a voltage present on the
transformer. If at the start the 2 UV sensors are ON, Transformer 1 will have the priority over Transformer 2 and CB 1 is
closed after a time (T1 = 5 sec) and a feedback signal from CB1-FB is ON. Then in case of supply failure on incoming
(1), the UV (1) signal is OFF and switching occurs with CB (1) is opened and CB (2) is closed after a time (T2 = 5 sec).
The system is then monitored all the time for UV and SDE signals to either switch the supply or open the 2 CB’s in case
of short circuit.
The overall operation can be controlled either automatically (Zelio smart relay) or manually by selecting the mode of
operation from the front keys of the Zelio. The mode of operation is displayed on the front display of the Zelio.
Faults
The system takes a signal from the CB to indicate a SDE fault (short circuit).
In this case the 2 CB’s are opened so that neither one of the Transformers is connected to the network. And a fault
message appears on the Zelio front display to indicate short circuit fault. Also there is software interlock to prevent the 2
CB’s to be connected both at the same time for safety. Following is the wiring for control circuit of the Zelio smart relay.