Fan Type DIDW Airfoil
Absorbed Power in kW
Unit ADA400/CM (CLI) 1.0
Operating Conditions Ducted
0.8
Air Volume 3500 cfm
0.6
Static Pressure 40.0 mmwg
Velocity Pressure 2.5 mmwg 0.4
Total Pressure 42.5 mmwg 0.2
Outlet Velocity 6.46 m/s 0
Fan Total Efficiency 79.2 % 60 Static Pressure in mmwg
Fan Static Efficiency 74.6 %
50
Fan Speed 1338 rpm
Air Temperature 20.0 °C 40
Altitude 0m 30
Fan Absorbed Power 0.89 kW
Recommended Motor D90S ( 1.10 kW ) 20
Motor Speed - 10
Service Factor 0%
0
Plenum Size -
Total Efficiency %
Outlet Size - 100
Rec. Airflow Variation - 80
Fan Pulley / Bush / Shaft - 60
Motor Pulley / Bush / Shaft - 40
Belt Length - 20
Number of Belts / f -
0
Static Belt Tension/Belt - 0 1000 2000 3000 4000 5000 6000 7000
Belt Deflection -
Air Volume in cfm
Belt Speed (<40m/s) -
Bearing Life ( L10 / L50 ) - Hz 63 125 250 500 1k 2k 4k 8k Overall
Starting Torque - Lwi(Lin)73 72 74 74 68 63 58 52 80 dB
Operating Limits Lwi(A) 47 57 66 71 68 64 59 51 74 dB(A)
Max. Absorbed Power 6.00 kW Lpi(A) 40 50 59 64 60 57 52 44 67 dB(A)
Max. Fan Speed 2500 rpm * Sound data is for the inlet side
Temperature (Min-Max) -20° to +85°C * Sound Pressure Level 1m, Room Conditions

A B C D E F G H J K L M P R t t1 w z Od UxS

736 650 432 506 506 402 290 612 546 586 726 70 38 5 8 7 40 33 30 13x18