Consideration : Farakka-Gokarna 400 KV D/C, Sagardighi-Gokarna 400 KV D/C

THREE PHASE FAULT LEVEL

Bus Name Rated Voltage 3-Phase MVA Fault Cur.


(kV) (MVA) (kA)
---------- ---------- ------------- ----------- ------------------------------------------------------------------
BOLP132 132.000 2054 8.983
SAIN132 132.000 2155 9.426
SDIPR132 132.000 3130 13.690
GOK220 220.000 10233 26.854
SDIPR220 220.000 9405 24.681
BKR220 220.000 11524 30.243
GKN400 400.000 17912 25.855

SINGLE PHASE FAULT LEVEL

Bus Name Rated Voltage 1-Phase MVA Fault Cur.


(kV) (MVA) (kA)
---------- ---------- ------------- ----------- ---------------------------------------------------------------------------------
BOLP132 132.000 1860 8.134
SAIN132 132.000 1953 8.544
SDIPR132 132.000 3554 15.547
GOK220 220.000 10995 28.855
SDIPR220 220.000 8858 23.246
BKR220 220.000 12764 33.498
GKN400 400.000 15683 22.637

Line length of
i) 220kV Gokarna – Sadaipur D/C Line: 3.036 km
ii) 220kV BKTPP – Sadaipur D/C Line: 3.116 km
iii) 132kV Saithia – Sadaipur D/C Line: 17.208 km
iv) 132kV Bolpur – Sadaipur D/C Line: 16.951 km

M/S ABB called for following parameters for relay setting purpose:
i) Fault Current of Local and Remote end for all the 220kV & 132kV Lines
ii) Source Impedance angle in degree for all the 220kV & 132kV Lines
iii) Load angle for all the 220kV & 132kV Lines