You are on page 1of 56

EDFMT391770A

201802

Engineering Data

FXFQ-AVM
50 / 60 Hz
FXFQ-AVM EDFMT391770A

FXFQ-AVM
Ceiling Mounted Cassette Type
(Round Flow)
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................8
3.1 Standard Panel..................................................................................8
3.2 Designer Panel................................................................................11
3.3 Auto Grille Panel..............................................................................14
4. Piping Diagrams........................................................................................17
5. Wiring Diagrams........................................................................................18
6. Electric Characteristics..............................................................................19
7. Safety Devices Setting..............................................................................20
8. Capacity Tables.........................................................................................21
8.1 Cooling Capacity for Te: Auto..........................................................21
8.2 Cooling Capacity for Te: 6°C...........................................................21
8.3 Cooling Capacity for Te: 9°C...........................................................22
8.4 Heating Capacity..............................................................................22
9. Sound Levels.............................................................................................23
10. Centre of Gravity.......................................................................................27
11. Accessories...............................................................................................28
11.1 Optional Accessories (for Unit)........................................................28
11.2 Optional Accessories (for Controls).................................................30
12. Installation Manual....................................................................................31
12.1 FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM /
FXFQ63AVM / FXFQ80AVM / FXFQ100AVM / FXFQ125AVM /
FXFQ140AVM..................................................................................31

1
FXFQ-AVM EDFMT391770A

1. Lineup

2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW 9.0 kW 11.2 kW 14.0 kW 16.0 kW


Capacity range
1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP
Capacity index 25 31.25 40 50 62.5 80 100 125 140

FXFQ 25AVM 32AVM 40AVM 50AVM 63AVM 80AVM 100AVM 125AVM 140AVM

FXFQ 25AVS 32AVS 40AVS 50AVS 63AVS 80AVS 100AVS 125AVS 140AVS
(for Thailand)
FXFQ 25AV4 32AV4 40AV4 50AV4 63AV4 80AV4 100AV4 125AV4 140AV4
(for Indonesia)

VM : 1 phase, 220-240/220-230 V, 50/60 Hz


VS : 1 phase, 220 V, 50 Hz (for Thailand)
V4 : 1 phase, 220-240 V, 50 Hz (for Indonesia)

2
FXFQ-AVM EDFMT391770A

2. Specifications

Model FXFQ25AVM FXFQ32AVM


Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 2,400 3,100
1 3 Cooling capacity Btu/h 9,600 12,300
kW 2.8 3.6
kcal/h 2,800 3,400
2 3 Heating capacity Btu/h 10,900 13,600
kW 3.2 4.0
50 Hz kW 0.029 0.029
Cooling
60 Hz kW 0.029 0.029
Power input
50 Hz kW 0.027 0.027
Heating
60 Hz kW 0.027 0.027
Casing / Colour Galvanised steel plate Galvanised steel plate
Dimensions: (H×W×D) mm 256×840×840 256×840×840
Model QTS48G15M QTS48G15M
Type Turbo fan Turbo fan
Motor output × W 53×1 53×1
Number of units
Fan m /min
3
13/12.5/11.5/11/10 13/12.5/11.5/11/10
Airflow rate
(H/HM/M/ML/L) l/s 217/208/192/183/167 217/208/192/183/167
cfm 459/441/406/388/353 459/441/406/388/353
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form
Liquid pipes mm φ6.4 φ6.4
Piping Gas pipes mm φ12.7 φ12.7
connections
Drain pipe mm φ26 (hole) φ26 (hole)
Mass kg 19 19
4 Sound pressure level (H/HM/M/ML/L) dB(A) 30.0/29.5/28.5/28.0/27.0 30.0/29.5/28.5/28.0/27.0
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Model BYCQ125EAF BYCQ125EAF
Decoration Colour Fresh white Fresh white
panel Dimensions: (H×W×D) mm 50×950×950 50×950×950
(option) Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Operation manual, Installation manual, Pattern Operation manual, Installation manual, Pattern
for installation, Drain hose, Clamp metal, for installation, Drain hose, Clamp metal,
Standard accessories Washer fixing plate, Sealing pads, Clamps, Washer fixing plate, Sealing pads, Clamps,
Screws, Washer for hanging bracket, Insulation Screws, Washer for hanging bracket, Insulation
for fitting, Installation guide for fitting, Installation guide
Specification C: 3D112951B C: 3D112951B
Drawing No.
Sound level C: 4D112880A C: 4D112880A

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.

3
FXFQ-AVM EDFMT391770A

Model FXFQ40AVM FXFQ50AVM


Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 3,900 4,800
1 3 Cooling capacity Btu/h 15,400 19,100
kW 4.5 5.6
kcal/h 4,300 5,400
2 3 Heating capacity Btu/h 17,100 21,500
kW 5.0 6.3
50 Hz kW 0.036 0.040
Cooling
60 Hz kW 0.036 0.040
Power input
50 Hz kW 0.036 0.040
Heating
60 Hz kW 0.036 0.040
Casing / Colour Galvanised steel plate Galvanised steel plate
Dimensions: (H×W×D) mm 256×840×840 256×840×840
Model QTS48G15M QTS48G15M
Type Turbo fan Turbo fan
Motor output × W 53×1 53×1
Number of units
Fan m /min
3
17/13.5/13/12/11 18/17/13.5/12.5/11
Airflow rate
(H/HM/M/ML/L) l/s 283/225/217/200/183 300/283/225/208/183
cfm 600/477/459/424/388 635/600/477/441/388
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form
Liquid pipes mm φ6.4 φ6.4
Piping Gas pipes mm φ12.7 φ12.7
connections
Drain pipe mm φ26 (hole) φ26 (hole)
Mass kg 19 19
4 Sound pressure level (H/HM/M/ML/L) dB(A) 35.0/29.5/29.0/28.0/27.0 35.0/33.5/29.5/28.5/27.0
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Model BYCQ125EAF BYCQ125EAF
Decoration Colour Fresh white Fresh white
panel Dimensions: (H×W×D) mm 50×950×950 50×950×950
(option) Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Operation manual, Installation manual, Pattern Operation manual, Installation manual, Pattern
for installation, Drain hose, Clamp metal, for installation, Drain hose, Clamp metal,
Standard accessories Washer fixing plate, Sealing pads, Clamps, Washer fixing plate, Sealing pads, Clamps,
Screws, Washer for hanging bracket, Insulation Screws, Washer for hanging bracket, Insulation
for fitting, Installation guide for fitting, Installation guide
Specification C: 3D112951B C: 3D112951B
Drawing No.
Sound level C: 4D112874A C: 4D112902A

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.

4
FXFQ-AVM EDFMT391770A

Model FXFQ63AVM FXFQ80AVM


Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 6,100 7,700
1 3 Cooling capacity Btu/h 24,200 30,700
kW 7.1 9.0
kcal/h 6,900 8,600
2 3 Heating capacity Btu/h 27,300 34,100
kW 8.0 10.0
50 Hz kW 0.063 0.096
Cooling
60 Hz kW 0.063 0.096
Power input
50 Hz kW 0.063 0.096
Heating
60 Hz kW 0.063 0.096
Casing / Colour Galvanised steel plate Galvanised steel plate
Dimensions: (H×W×D) mm 256×840×840 256×840×840
Model QTS48G15M QTS48G15M
Type Turbo fan Turbo fan
Motor output × W 53×1 53×1
Number of units
Fan m /min
3
21/20/16/15/13.5 22.5/21.5/21/20/15
Airflow rate
(H/HM/M/ML/L) l/s 350/333/267/250/225 375/358/350/333/250
cfm 741/706/565/530/477 794/759/741/706/530
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form
Liquid pipes mm φ9.5 φ9.5
Piping Gas pipes mm φ15.9 φ15.9
connections
Drain pipe mm φ26 (hole) φ26 (hole)
Mass kg 22 22
4 Sound pressure level (H/HM/M/ML/L) dB(A) 36.0/35.5/31.5/31.0/28.0 37.0/36.5/36.0/35.5/29.5
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Model BYCQ125EAF BYCQ125EAF
Decoration Colour Fresh white Fresh white
panel Dimensions: (H×W×D) mm 50×950×950 50×950×950
(option) Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Operation manual, Installation manual, Pattern Operation manual, Installation manual, Pattern
for installation, Drain hose, Clamp metal, for installation, Drain hose, Clamp metal,
Standard accessories Washer fixing plate, Sealing pads, Clamps, Washer fixing plate, Sealing pads, Clamps,
Screws, Washer for hanging bracket, Insulation Screws, Washer for hanging bracket, Insulation
for fitting, Installation guide for fitting, Installation guide
Specification C: 3D112951B C: 3D112951B
Drawing No.
Sound level C: 4D112877B C: 4D112876B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.

5
FXFQ-AVM EDFMT391770A

Model FXFQ100AVM FXFQ125AVM


Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 9,600 12,000
1 3 Cooling capacity Btu/h 38,200 47,800
kW 11.2 14.0
kcal/h 10,800 12,000
2 3 Heating capacity Btu/h 42,700 47,800
kW 12.5 14.0
50 Hz kW 0.158 0.178
Cooling
60 Hz kW 0.158 0.178
Power input
50 Hz kW 0.150 0.166
Heating
60 Hz kW 0.150 0.166
Casing / Colour Galvanised steel plate Galvanised steel plate
Dimensions: (H×W×D) mm 298×840×840 298×840×840
Model QTS48G15M QTS48G15M
Type Turbo fan Turbo fan
Motor output × W 106×1 106×1
Number of units
Fan m /min
3
32/29/26/23/21 33/30.5/28/25.5/21
Airflow rate
(H/HM/M/ML/L) l/s 533/483/433/383/350 550/508/467/425/350
cfm 1,130/1,024/918/812/741 1,165/1,077/988/900/741
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form
Liquid pipes mm φ9.5 φ9.5
Piping Gas pipes mm φ15.9 φ15.9
connections
Drain pipe mm φ26 (hole) φ26 (hole)
Mass kg 25 25
4 Sound pressure level (H/HM/M/ML/L) dB(A) 43.0/40.5/37.5/35.0/33.0 44.0/41.5/39.0/36.5/33.0
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Model BYCQ125EAF BYCQ125EAF
Decoration Colour Fresh white Fresh white
panel Dimensions: (H×W×D) mm 50×950×950 50×950×950
(option) Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Operation manual, Installation manual, Pattern Operation manual, Installation manual, Pattern
for installation, Drain hose, Clamp metal, for installation, Drain hose, Clamp metal,
Standard accessories Washer fixing plate, Sealing pads, Clamps, Washer fixing plate, Sealing pads, Clamps,
Screws, Washer for hanging bracket, Insulation Screws, Washer for hanging bracket, Insulation
for fitting, Installation guide for fitting, Installation guide
Specification C: 3D112951B C: 3D112951B
Drawing No.
Sound level C: 4D112881A C: 4D112872B

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.

6
FXFQ-AVM EDFMT391770A

Model FXFQ140AVM
Power supply 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 13,800
1 3 Cooling capacity Btu/h 54,600
kW 16.0
kcal/h 13,800
2 3 Heating capacity Btu/h 54,600
kW 16.0
50 Hz kW 0.203
Cooling
60 Hz kW 0.203
Power input
50 Hz kW 0.191
Heating
60 Hz kW 0.191
Casing / Colour Galvanised steel plate
Dimensions: (H×W×D) mm 298×840×840
Model QTS48G15M
Type Turbo fan
Motor output × W 106×1
Number of units
Fan m /min
3
35.5/32.5/29.5/26.5/23
Airflow rate
(H/HM/M/ML/L) l/s 592/542/492/442/383
cfm 1,253/1,147/1,041/935/812
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Polyurethane form
Liquid pipes mm φ9.5
Piping Gas pipes mm φ15.9
connections
Drain pipe mm φ26 (hole)
Mass kg 26
4 Sound pressure level (H/HM/M/ML/L) dB(A) 46.0/43.5/40.5/38.0/35.0
Safety devices Fuse
Refrigerant control Electronic expansion valve
Model BYCQ125EAF
Decoration Colour Fresh white
panel Dimensions: (H×W×D) mm 50×950×950
(option) Air filter Resin net (with mould resistance)
Mass kg 5.5
Operation manual, Installation manual, Pattern for installation, Drain hose, Clamp metal, Washer
Standard accessories fixing plate, Sealing pads, Clamps, Screws, Washer for hanging bracket, Insulation for fitting,
Installation guide
Specification C: 3D112951B
Drawing No.
Sound level C: 4D509731A

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.

7
FXFQ-AVM EDFMT391770A

3. Dimensions
3.1 Standard Panel
FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM
Unit: mm

3D112987A

8
FXFQ-AVM EDFMT391770A

FXFQ63AVM / FXFQ80AVM
Unit: mm

3D112983A

9
FXFQ-AVM EDFMT391770A

FXFQ100AVM / FXFQ125AVM / FXFQ140AVM


Unit: mm

3D112979A

10
FXFQ-AVM EDFMT391770A

3.2 Designer Panel


FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM
Unit: mm

3D112988A

11
FXFQ-AVM EDFMT391770A

FXFQ63AVM / FXFQ80AVM
Unit: mm

3D112985A

12
FXFQ-AVM EDFMT391770A

FXFQ100AVM / FXFQ125AVM / FXFQ140AVM


Unit: mm

3D112980A

13
FXFQ-AVM EDFMT391770A

3.3 Auto Grille Panel


FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM
Unit: mm

3D112991A

14
FXFQ-AVM EDFMT391770A

FXFQ63AVM / FXFQ80AVM
Unit: mm

3D112986A

15
FXFQ-AVM EDFMT391770A

FXFQ100AVM / FXFQ125AVM / FXFQ140AVM


Unit: mm

3D112981A

16
FXFQ-AVM EDFMT391770A

4. Piping Diagrams

FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM / FXFQ63AVM / FXFQ80AVM /


FXFQ100AVM / FXFQ125AVM / FXFQ140AVM

4D024460P

„„ Refrigerant pipe connection port diameters


Unit: mm
Model Gas Liquid
FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM φ12.7 φ6.4
FXFQ63AVM / FXFQ80AVM / FXFQ100AVM / FXFQ125AVM / FXFQ140AVM φ15.9 φ9.5

17
FXFQ-AVM EDFMT391770A

5. Wiring Diagrams

FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM / FXFQ63AVM / FXFQ80AVM /


FXFQ100AVM / FXFQ125AVM / FXFQ140AVM

3D112978A

18
FXFQ-AVM EDFMT391770A

6. Electric Characteristics

FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM / FXFQ63AVM / FXFQ80AVM /


FXFQ100AVM / FXFQ125AVM / FXFQ140AVM

C: 3D112911

19
FXFQ-AVM EDFMT391770A

7. Safety Devices Setting

Model FXFQ25AVM FXFQ32AVM FXFQ40AVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector — — —
Drain pump thermal protector °C — — —

Model FXFQ50AVM FXFQ63AVM FXFQ80AVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector — — —
Drain pump thermal protector °C — — —

Model FXFQ100AVM FXFQ125AVM FXFQ140AVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A
Fan motor thermal protector — — —
Drain pump thermal protector °C — — —
C: 3D112954

20
FXFQ-AVM EDFMT391770A

8. Capacity Tables
8.1 Cooling Capacity for Te: Auto

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFQ25AVM 25 2.5 2.5 2.6 2.7 2.8 2.9 2.8 2.7 2.8 2.6 2.9 2.5 3.0 2.4
FXFQ32AVM 32 3.2 3.2 3.4 3.4 3.5 3.4 3.6 3.2 3.6 3.1 3.7 2.9 3.8 2.8
FXFQ40AVM 40 4.0 4.0 4.2 4.4 4.4 4.4 4.5 4.0 4.6 4.0 4.7 3.8 4.8 3.7
FXFQ50AVM 50 4.9 4.8 5.3 4.9 5.5 5.1 5.6 4.7 5.7 4.6 5.8 4.5 5.9 4.3
FXFQ63AVM 63 6.3 5.8 6.7 6.2 7.0 6.2 7.1 5.7 7.2 5.6 7.3 5.3 7.5 5.0
FXFQ80AVM 80 7.9 6.9 8.5 7.1 8.8 7.3 9.0 6.8 9.1 6.6 9.3 6.4 9.5 6.1
FXFQ100AVM 100 9.9 9.0 10.5 9.4 11.0 9.6 11.2 8.8 11.3 8.6 11.6 8.4 11.8 8.1
FXFQ125AVM 125 12.3 10.4 13.2 10.8 13.8 11.1 14.0 10.3 14.2 10.2 14.5 9.8 14.8 9.4
FXFQ140AVM 140 14.1 11.8 15.0 12.3 15.7 12.5 16.0 11.6 16.2 11.5 16.5 11.1 16.9 10.5

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.2 Cooling Capacity for Te: 6°C

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFQ25AVM 25 1.9 1.9 2.3 2.3 2.6 2.6 2.8 2.7 2.8 2.6 2.9 2.5 3.0 2.4
FXFQ32AVM 32 2.4 2.4 2.9 2.8 3.4 3.1 3.6 3.2 3.6 3.1 3.7 2.9 3.8 2.8
FXFQ40AVM 40 3.0 3.0 3.6 3.6 4.2 4.0 4.5 4.0 4.6 4.0 4.7 3.8 4.8 3.7
FXFQ50AVM 50 3.8 3.6 4.5 4.1 5.2 4.6 5.6 4.7 5.7 4.6 5.8 4.5 5.9 4.3
FXFQ63AVM 63 4.8 4.4 5.7 5.1 6.6 5.6 7.1 5.7 7.2 5.6 7.4 5.3 7.5 5.0
FXFQ80AVM 80 6.1 5.2 7.2 5.9 8.4 6.6 9.0 6.8 9.1 6.6 9.3 6.4 9.5 6.1
FXFQ100AVM 100 7.6 6.8 9.0 7.8 10.5 8.7 11.2 8.8 11.3 8.6 11.6 8.4 11.9 8.1
FXFQ125AVM 125 9.4 7.8 11.3 9.0 13.1 10.1 14.0 10.3 14.2 10.2 14.5 9.8 14.9 9.5
FXFQ140AVM 140 10.8 8.9 12.9 10.2 15.0 11.4 16.0 11.6 16.2 11.5 16.6 11.1 17.0 10.6

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

21
FXFQ-AVM EDFMT391770A

8.3 Cooling Capacity for Te: 9°C

For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFQ25AVM 25 1.4 1.4 1.8 1.8 2.1 2.1 2.3 2.3 2.4 2.4 2.5 2.3 2.7 2.2
FXFQ32AVM 32 1.8 1.8 2.2 2.2 2.8 2.8 3.0 2.9 3.1 2.8 3.2 2.7 3.4 2.6
FXFQ40AVM 40 2.3 2.3 2.8 2.8 3.5 3.5 3.8 3.7 3.9 3.7 4.1 3.6 4.3 3.4
FXFQ50AVM 50 2.9 2.9 3.5 3.5 4.3 4.1 4.7 4.3 4.9 4.2 5.1 4.2 5.3 4.0
FXFQ63AVM 63 3.3 3.3 4.2 4.2 5.2 4.9 5.7 5.0 5.9 5.0 6.3 4.8 6.6 4.5
FXFQ80AVM 80 4.2 4.2 5.3 5.0 6.6 5.8 7.3 6.0 7.5 5.9 8.0 5.7 8.3 5.5
FXFQ100AVM 100 5.2 5.2 6.4 6.4 8.1 7.5 8.9 7.6 9.2 7.5 9.7 7.4 10.3 7.3
FXFQ125AVM 125 6.4 6.1 8.0 7.4 10.2 8.7 11.2 9.0 11.6 8.9 12.2 8.7 12.8 8.6
FXFQ140AVM 140 7.4 7.1 9.6 8.6 11.9 10.0 13.0 10.2 13.5 10.2 14.3 10.0 15.0 9.7

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.4 Heating Capacity

Indoor air temp.


Capacity
Model 16°CDB 18°CDB 20°CDB 21°CDB 22°CDB 24°CDB
indication
kW kW kW kW kW kW
FXFQ25AVM 25 3.4 3.2 3.2 3.1 3.0 2.8
FXFQ32AVM 32 4.2 4.2 4.0 3.9 3.7 3.5
FXFQ40AVM 40 5.2 5.2 5.0 4.8 4.7 4.4
FXFQ50AVM 50 6.6 6.6 6.3 6.1 5.9 5.5
FXFQ63AVM 63 8.4 8.4 8.0 7.7 7.5 7.0
FXFQ80AVM 80 10.5 10.5 10.0 9.7 9.4 8.7
FXFQ100AVM 100 13.1 13.1 12.5 12.1 11.7 10.9
FXFQ125AVM 125 16.8 16.8 16.0 15.5 15.0 13.9
FXFQ140AVM 140 18.9 18.9 18.0 17.4 16.8 15.7

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

22
FXFQ-AVM EDFMT391770A

9. Sound Levels

FXFQ25AVM / FXFQ32AVM

4D112880A
FXFQ40AVM

4D112874A

23
FXFQ-AVM EDFMT391770A

FXFQ50AVM

4D112902A
FXFQ63AVM

4D112877B

24
FXFQ-AVM EDFMT391770A

FXFQ80AVM

4D112876B
FXFQ100AVM

4D112881A

25
FXFQ-AVM EDFMT391770A

FXFQ125AVM

4D112872B
FXFQ140AVM

4D509731A

26
FXFQ-AVM EDFMT391770A

10. Centre of Gravity

FXFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM / FXFQ63AVM / FXFQ80AVM /


FXFQ100AVM / FXFQ125AVM / FXFQ140AVM

Unit: mm

4D052237S

27
FXFQ-AVM EDFMT391770A

11. Accessories
11.1 Optional Accessories (for Unit)

Model
Item
FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXFQ80AVM
Fresh white BYCQ125EAF
Standard panel 
Black BYCQ125EAK
Designer panel (Note 1)  Fresh white BYCQ125EAPF
Auto grille panel Fresh white BYCQ125EASF
(Note 2,3) 
For usage of 3-, 4-way KDBH551C160
Sealing material of air flow
discharge outlet (Note 4) For usage of 2-way KDBH552C160
flow
Panel spacer KDBP55H160FA
Chamber Without KDDP55B160 [Components : KDDP55C160-1, KDDP55B160-2]
type T-duct joint
(Note With T-duct
Fresh air intake kit 5,6,8) KDDP55B160K [Components : KDDP55C160-1, KDDP55B160K2]
joint
Direct installation type KDDP55X160A
(Note 7)
(Colormetric method
High efficiency filter unit KAFP556C80
65%)
(Including filter chamber)
(Note 9) (Colormetric method KAFP557C80
90%)
(Colormetric method KAFP552B80
Replacement high 65%)
efficiency filter (Note 9,10) (Colormetric method
KAFP553B80
90%)
Filter chamber KDDFP55C160
Replacement long-life filter KAFP551K160
Replacement long-life filter (Auto grille panel) KAFP551H160
Ultra long-life filter unit (Including filter chamber) KAFP55C160
(Note 9)
Replacement ultra long-life filter (Note 9,10) KAFP55H160H
Branch duct chamber (Note 4) KDJP55C80
Insulation kit for high humidity (Note 9,11) KDTP55K80
C: 3D112950A
Notes:
1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate
2 and 3 way flow.
2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
4. Circulation airflow is not available with this option.
5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.
6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit.
Introducing higher quantities will increase the operating sound and may also influence temperature sensing.
7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when
more fresh air is necessary.
8. Please order using the name of both components instead of set name.
9. This option cannot be installed to designer panel and auto grille panel.
10. Filter chamber is required.
11. Please use in case temperature / humidity inside ceiling may get over 30°C, 80%RH.
 These panels do not contain the sensing function.

28
FXFQ-AVM EDFMT391770A

Model
Item
FXFQ100AVM FXFQ125AVM FXFQ140AVM
Fresh white BYCQ125EAF
Standard panel 
Black BYCQ125EAK
Designer panel (Note 1)  Fresh white BYCQ125EAPF
Auto grille panel Fresh white BYCQ125EASF
(Note 2,3) 
For usage of 3-, 4-way KDBH551C160
Sealing material of air flow
discharge outlet (Note 4) For usage of 2-way KDBH552C160
flow
Panel spacer KDBP55H160FA
Chamber Without KDDP55B160 [Components : KDDP55C160-1, KDDP55B160-2]
type T-duct joint
(Note With T-duct
Fresh air intake kit 5,6,8) KDDP55B160K [Components : KDDP55C160-1, KDDP55B160K2]
joint
Direct installation type KDDP55X160A
(Note 7)
(Colormetric method
High efficiency filter unit KAFP556C160
65%)
(Including filter chamber)
(Note 9) (Colormetric method KAFP557C160
90%)
(Colormetric method KAFP552B160
Replacement high 65%)
efficiency filter (Note 9,10) (Colormetric method
KAFP553B160
90%)
Filter chamber KDDFP55C160
Replacement long-life filter KAFP551K160
Replacement long-life filter (Auto grille panel) KAFP551H160
Ultra long-life filter unit (Including filter chamber) KAFP55C160
(Note 9)
Replacement ultra long-life filter (Note 9,10) KAFP55H160H
Branch duct chamber (Note 4) KDJP55C160
Insulation kit for high humidity (Note 9,11) KDTP55K160
C: 3D112950A
Notes:
1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate
2 and 3 way flow.
2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
4. Circulation airflow is not available with this option.
5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.
6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit.
Introducing higher quantities will increase the operating sound and may also influence temperature sensing.
7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when
more fresh air is necessary.
8. Please order using the name of both components instead of set name.
9. This option cannot be installed to designer panel and auto grille panel.
10. Filter chamber is required.
11. Please use in case temperature / humidity inside ceiling may get over 30°C, 80%RH.
 These panels do not contain the sensing function.

29
FXFQ-AVM EDFMT391770A

11.2 Optional Accessories (for Controls)

Model
Item
FXFQ25AVM FXFQ32AVM FXFQ40AVM FXFQ50AVM FXFQ63AVM FXFQ80AVM
Remote Cooling Only BRC7M635F(Fresh white) / BRC7M635K (Black) (Note 4)
Wireless
controller Heat Pump BRC7M634F(Fresh white) / BRC7M634K (Black) (Note 4)
Navigation remote controller BRC1E63 (Note 4)
(Wired remote controller)
Adaptor for wiring (Note 1) KRP1C11A
Wiring adaptor for electrical KRP4AA53
appendices (Note 1)
Installation box for adaptor printed KRP1H98A (Note 2, 3)
circuit board
Remote sensor (for indoor KRCS01-5B
temperature)
External control adaptor for outdoor DTA104A62
unit (Note 1)
Adaptor for multi tenant (Note 1) DTA114A61

Model
Item
FXFQ100AVM FXFQ125AVM FXFQ140AVM
Remote Cooling Only BRC7M635F(Fresh white) / BRC7M635K (Black) (Note 4)
Wireless
controller Heat Pump BRC7M634F(Fresh white) / BRC7M634K (Black) (Note 4)
Navigation remote controller BRC1E63 (Note 4)
(Wired remote controller)
Adaptor for wiring (Note 1) KRP1C11A
Wiring adaptor for electrical KRP4AA53
appendices (Note 1)
Installation box for adaptor printed KRP1H98A (Note 2, 3)
circuit board
Remote sensor (for indoor KRCS01-5B
temperature)
External control adaptor for outdoor DTA104A62
unit (Note 1)
Adaptor for multi tenant (Note 1) DTA114A61
C: 3D112950A
Notes:
1. Installation box for adaptor printed circuit board (KRP1H98A) is necessary.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Some function can be set only via wired remote controller BRC1E63. Cannot be set via other remote controllers. Please see Function List
below.

Function List
FXFQ-A with FXFQ-A with
Item Wired type remote controller Wireless type remote controller
Wired BRC1E63 —
Remote Cooling Only — BRC7M635F(Fresh white) / BRC7M635K (Black)
controller Wireless
Heat Pump — BRC7M634F(Fresh white) / BRC7M634K (Black)
Circulation airflow 
Individual airflow direction control 
Switchable 5 step fan speed  
Auto airflow rate  
Auto swing  
Swing pattern selection  
High ceiling application 

30
FXFQ-AVM EDFMT391770A

12. Installation Manual


12.1 F XFQ25AVM / FXFQ32AVM / FXFQ40AVM / FXFQ50AVM / FXFQ63AVM / FXFQ80AVM / FXFQ100AVM / FXFQ125AVM / FXFQ140AVM

VRV SYSTEM Air Conditioners Installation manual

• Consult your local dealer regarding what to do in case of


CONTENTS refrigerant leakage.
1. SAFETY PRECAUTIONS .......................................... 1 When the air conditioner is installed in a small room, it is
necessary to take proper measures so that the amount of
2. BEFORE INSTALLATION .......................................... 2 any leaked refrigerant does not exceed the concentration
3. SELECTION OF INSTALLATION LOCATION ............ 4 limit in the event of a leakage.
4. PREPARATION BEFORE INSTALLATION ................ 5 Otherwise, this may lead to an accident due to oxygen
deficiency.
5. INSTALLATION OF INDOOR UNIT ........................... 6 • Be sure to use only the specified parts and accessories for
6. REFRIGERANT PIPING WORK ................................ 8 installation work.
Failure to use the specified parts may result in the air
7. DRAIN PIPING WORK ............................................ 10 conditioner falling down, water leakage, electric shocks,
8. ELECTRIC WIRING WORK ..................................... 12 a fire, etc.
9. MOUNTING DECORATION PANEL ........................ 17 • Install the air conditioner on a foundation that can withstand
its mass.
10. FIELD SETTING AND TEST OPERATION.............. 17 Insufficient strength may result in the air conditioner falling
down and causing injury.
In addition, it may lead to vibration of indoor units and cause
1. SAFETY PRECAUTIONS unpleasant chattering noise.
• Carry out the specified installation work in consideration of
Please read the these “SAFETY PRECAUTIONS” strong winds, typhoons, or earthquakes.
carefully before installing air conditioning unit and be sure to Improper installation may result in an accident such as air
install it correctly. After completing the installation, make sure conditioner falling.
that the unit operates properly during the start-up operation. • Make certain that all electrical work is carried out by qualified
Please instruct the customer on how to operate the unit and personnel according to the applicable legislation (note 1)
keep it maintained. and this installation manual, using a separate circuit.
Also, inform customers that they should store this installation In addition, even if the wiring is short, make sure to use a
manual along with the operation manual for future reference. wiring that has sufficient length and never connect additional
This product comes under the term “appliances not accessible wiring to make the length sufficient.
to the general public”. Insufficient capacity of the power supply circuit or improper
This is a class A product. In a domestic environment this electrical construction may lead to electric shocks or a fire.
product may cause radio interference in which case the user (note 1) applicable legislation means “All international,
may be required to take adequate measures. national and local directives, laws, regulations
and/or codes which are relevant and applicable for
• This manual classifies the precautions into WARNINGS and
a certain product or domain”.
CAUTIONS.
• Earth the air conditioner.
Be sure to follow all the precautions below: They are all Do not connect the earth wiring to gas or water piping,
important for ensuring safety. lightning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a fire.
WARNING ..............Indicates a potentially • Be sure to install an earth leakage breaker.
hazardous situation which, Failure to do so may cause electric shocks and a fire.
if not avoided, could result in • Disconnect the power supply before touching the electric
death or serious injury. components.
CAUTION ...............Indicates a potentially If you touch the live part, you may get an electric shocks.
hazardous situation which, • Make sure that all wiring is secure, using the specified wirings
if not avoided, may result in and ensuring that external forces do not act on the terminal
minor or moderate injury. connections or wirings.
It may also be used to alert Incomplete connection or fixing may cause an overheat or a fire.
against unsafe practices. • When wiring between the indoor and outdoor units, and
wiring the power supply, form the wirings orderly so that the
• After the installation is completed, test the air conditioner
control box lid can be securely fastened.
and check if the air conditioner operates properly. Give the
If the control box lid is not in place, overheat of the terminals,
user adequate instructions concerning the use and cleaning
electric shocks or a fire may be caused.
of the indoor unit according to the Operation Manual. Ask the
• If refrigerant gas leaks during installation work, ventilate the
user to keep this manual and the Operation Manual together
area immediately.
in a handy place for future reference.
Toxic gas may be produced if refrigerant gas comes into
contact with a fire.
WARNING
• After completing the installation work, check to make sure
• Ask your local dealer or qualified personnel to carry out that there is no leakage of refrigerant gas.
installation work. Toxic gas may be produced if refrigerant gas leaks into the
Improper installation may result in water leakage, electric room and comes into contact with a source of a fire, such as
shocks or a fire. a fan heater, stove or cooker.
• Perform installation work in accordance with this installation
• Never directly touch any accidental leaking refrigerant.
manual.
Improper installation may result in water leakage, electric This could result in severe wounds caused by frostbite.
shocks or a fire.

3P468397-1D

31
FXFQ-AVM EDFMT391770A

CAUTION SPECIAL NOTICE PRODUCT


• Do not allow children to climb on the outdoor unit and avoid • The refrigerant R410A requires that strict precautions be
placing objects on the unit. observed for keeping the system clean, dry and tightly
Injury may result if the unit becomes loose and falls. sealed.
• Make sure to provide for adequate measures in order to Clean and dry
prevent that the outdoor unit be used as a shelter by small Strict measures must be taken to keep impurities
animals.
(including SUNISO oil and other mineral oils as well as
Small animals making contact with electrical parts can cause
moisture) out of the system.
malfunctions, smoke or fire. Please instruct the customer to
keep the area around the unit clean. Tightly sealed
• Install in a machine room that is free of moisture. The unit is R410A contains no chlorine, does not destroy the ozone
designed for indoor use. layer and so does not reduce the earth's protection against
• Disposal requirements harmful ultraviolet radiation. R410A will contribute only
Dismantling of the unit, treatment of the refrigerant, of oil slightly to the greenhouse effect if released into the
and of other parts must be done in accordance with relevant atmosphere.
local and national legislation. • Since design pressure is 4.0 MPa or 40 bar (for R407C units:
• Install drain piping according to this installation manual to 3.3 MPa or 33 bar), the thickness of pipes must be greater
ensure good drainage, and insulate the piping to prevent than previously. Since R410A is a mixed refrigerant, the
condensation. required additional refrigerant must be charged in its liquid
Improper drain piping may cause water leakage, make the state.
furniture get wet. (If the system is charged with refrigerant in its gaseous state,
• Install the air conditioner, power supply wiring, remote due to composition change, the system will not function
controller wiring and transmission wiring at least 1 meter normally). The indoor unit is designed for R410A use.
away from televisions or radios to prevent image interference See the catalogue for indoor unit models that can be
or noise. connected. (Normal operation is not possible when
(Depending on the radio waves, a distance of 1 meter may connecting units that are originally designed for other
not be sufficient to eliminate the noise.) refrigerants.)
• Install the indoor unit as far as possible from fluorescent
lamps.
If a wireless remote controller kit is installed, the transmission
distance may be shorter in a room where an electronic lighting
type (inverter or rapid start type) fluorescent lamp is installed. 2. BEFORE INSTALLATION
• Do not install the air conditioner in places such as the
When unpacking the indoor unit or moving the unit after
following:
1. Where there is mist of oil, oil spray or vapour for example unpacked, hold the hangers (4 places) and do not apply
a kitchen. force to other parts (particularly refrigerant piping, drain
Resin parts may deteriorate, and cause them to fall out piping and resin parts).
or water to leak. • Make sure to check in advance that the refrigerant to be
2. Where corrosive gas, such as sulfurous acid gas, is used for installation work is R410A.
produced. (The air conditioner will not properly operate if a wrong
Corrosion of copper pipings or brazed parts may cause refrigerant is used.)
the refrigerant to leak. • For installation of the outdoor unit, refer to the installation
3. Where there is machinery which emits electromagnetic manual attached to the outdoor unit.
waves. • Do not throw away the accessories until the installation work
Electromagnetic waves may disturb the control system, is completed.
and cause malfunction of the equipment. • After the indoor unit is carried into the room, to avoid the
4. Where flammable gases may leak, where carbon fibre indoor unit from getting damaged, take measures to protect
or ignitable dust is suspended in the air or where volatile the indoor unit with packing materials.
flammables, such as thinner or gasoline, are handled.
(1) Determine the route to carry the unit into the room.
If the gas should leak and remained around the air
(2) Do not unpack the unit until it is carried to the installation
conditioner, it may cause ignition.
location.
• Pay attention to product transportation.
Carry by hold the handle position that display on packing Where unpacking is unavoidable, use a sling of soft
material. material or protective plates together with a rope when
In case of hold PP hand, PP band will get loose, it will be lifting, to avoid damage or scratches to the indoor unit.
dangerous. • Have the customer actually operate the air conditioner while
looking at the operation manual.
Instruct the customer how to operate the air conditioner
(particularly cleaning of the air filters, operation procedures,
and temperature adjustment).
• For selection of installation location, use the installation
pattern paper as reference.
• Do not use the air conditioner where in the salty atmosphere
such as coastal areas, vehicles, vessels or the voltage
fluctuation is frequent such as factories.
• Take off static electricity from the body when carrying out
wiring and the control box lid is removed.
The electric parts may be damaged.

3P468397-1D

32
FXFQ-AVM EDFMT391770A

2-1 ACCESSORIES Table 2


Check if the following accessories are attached to the Remote controller
indoor unit. Wired type BRC1E63
(2) Metal (3) Washer for Heat pump BRC7M634F/K
Name (1) Drain hose (4) Clamp Wireless type
clamp hanger Cooling only BRC7M635F/K

Quantity 1 pc. 1 pc. 8 pcs. 6 pcs. NOTE


• If you wish to use a remote controller that is not listed in
Shape “Table 2” on page 3, select a suitable remote controller after
consulting catalogs and technical materials.

Name
(5) Installation (6) Screw (7) Washer Joint insulating CARRY OUT THE WORK GIVING CAUTION
pattern paper (M4) clamp material
TO THE FOLLOWING ITEMS AND AFTER THE
Quantity 1 sheet 4 pcs. 4 pcs. 1 each
WORK IS COMPLETED CHECK THESE AGAIN.
Upper part
of packing
(8) For gas 1. Items to be checked after the installation work is
piping completed
Shape

Items to be checked In case of defective Check column


(9) For liquid
piping Are the indoor and outdoor Drop · vibration ·
units rigidly fixed? noise
Name Sealing material The unit may
Are the installation works of
Quantity 1 each 1 sheet 1 pc. the outdoor and indoor units malfunction
or the components
(10) Large completed?
burn out
Have you carried out a
(12) Medium-2 leakage test with the test It may result in
pressure specified in the insufficient cooling /
Shape
(13) Small outdoor unit installation insufficient heating
(14) manual?
Is the insulation of
(11) Medium-1 refrigerant piping and drain
Water leakage
piping completely carried
out?
Name (15) Installation guide
Does the drain flow out
Quantity 1 sheet (Miscellaneous) Water leakage
smoothly?
• Operation manual
Is the power supply voltage The unit may
• Installation manual
Shape identical to that stated in the malfunction
manufacturer’s label on the or the components
air conditioner? burn out
The unit may
Are you sure that there is no
2-2 OPTIONAL ACCESSORIES malfunction
wrong wiring or piping or no
• This indoor unit separately requires a decoration panel and a or the components
loose wiring? burn out
remote controller.
• Confirm if a decoration panel shown in the Table 1 is It may result in
Is unit safety grounded?
prepared and meets your model. electric shock
(Refer to the installation manual attached to the decoration Are the sizes of electric The unit may
malfunction
panel for how to install.) wiring according to the
or the components
specification?
burn out
Table 1
Is any of air outlets or
Unit model Optional decoration panel inlets of the indoor and
outdoor units blocked with It may result in
FXFSQ25 · 32 · 40 · 50 · 63 · 80 · 100 · 125 · 140AVM BYCQ125EEF/EEK obstacles? insufficient cooling /
FXFQ25 · 32 · 40 · 50 · 63 · 80 · 100 · 125 · 140AVM BYCQ125EAF/EAK insufficient heating
(It may lead to capacity drop
FXFSQ25 · 32 · 40 · 50 · 63 · 80 · 100 · 125 · 140AV4 BYCQ125EAPF
due to fan speed drop or
FXFQ25 · 32 · 40 · 50 · 63 · 80 · 100 · 125 · 140AV4 BYCQ125EASF
malfunction of equipment.)
Have you recorded the
Color : Fresh white/Black
refrigerant piping length Refrigerant charge
• There are 2 kinds of remote controller; wired type and and the refrigerant charge amount is not clear
wireless type. added?
Select a remote controller from Table 2 according to Make sure to recheck the items of “SAFETY PRECAUTIONS”.
customer request and install in an appropriate place.
(Refer to the installation manual attached to the remote
controller for how to install.)

3P468397-1D

33
FXFQ-AVM EDFMT391770A

2. Items to be checked at delivery • Where there is strength to withstand the mass


of the indoor unit. (If the strength is the
Items to be checked Check column indoor unit may vibrate and get in contact with the ceiling
and generate unpleasant chattering noise.)
Have you carried out field setting? (if necessary)
• Where a space for installation and service can
Are the control box lid, the air filter and the suction be ensured. (Refer to Fig. 1)
grille attached? • Where the piping length between the indoor and the
Does the cool air discharge during the cooling outdoor units is ensured within the allowable length.
operation and the warm air discharge during the (Refer to the installation manual attached to the outdoor
heating operation? Does the indoor unit makes unit.)
unpleasant sound of air discharge?
• Where there is no risk of gas leak.
Have you explained how to operate the air
conditioner showing the operation manual to the Required installation space (mm)
customer?
Have you explained the description of cooling,
heating, program dry and automatic (cooling/
heating) given in the operation manual to the
customer?
If you set the fan speed at thermostat OFF, did you
Discharge Suction Discharge
explain the set fan speed to the customer. At least
1800 from
Have you handed the operation manual and the a floor
installation manual to the customer?
Floor level
Points of the operation explanation

In addition to the general usage, since the items in the


*≥1500
operation manual with the WARNING and *≥1500
CAUTION marks are likely to result in human bodily
injuries and property damages, it is necessary not only
to explain these items to the customer but also to have
the customer read them.

2-3 NOTE TO THE INSTALLER


Be sure to instruct customers how to properly operate the unit *≥1500

*≥1500
(especially cleaning filters, operating different functions, and
adjusting the temperature) by having them carry out operations
themselves while looking at the manual. Fig. 1
[mm]
MODEL NAME BYCQ125EEF/EEK
BYCQ125EAPF BYCQ125EASF
BYCQ125EAF/EAK
3. SELECTION OF INSTALLATION FXFSQ25 · 32 · 40 · 50 · 63 · 80AVM
LOCATION FXFQ25 · 32 · 40 · 50 · 63 · 80AVM
261 303 316
FXFSQ25 · 32 · 40 · 50 · 63 · 80AV4
Hold the hangers at 4 locations to move the indoor unit FXFQ25 · 32 · 40 · 50 · 63 · 80AV4
when unpacking or after unpacked, and do not apply force
to the piping (refrigerant and drain) and resin parts. FXFSQ100 · 125 · 140AVM
FXFQ100 · 125 · 140AVM
If the temperature and humidity in the ceiling is likely to FXFSQ100 · 125 · 140AV4
303 345 358
exceed 30°C, RH80%, use the optional kit for coping with FXFQ100 · 125 · 140AV4
high temperature and humidity, or additionally stick the
insulation to the indoor unit.
Use the insulation such as glass wool or polyethylene (Note 1) Exhaust
Indoor unit Lighting Indoor unit
that has thickness of 10 mm or more. However, keep the fan
insulated outside dimension smaller than the ceiling
*1500 or
opening so that the unit may go through the opening at more from 1500 or
installation. a wall more
from any fixture
At least 1500

(NOTE) 2000 or more


The direction of air discharge for this product can be 4000 or more
selected. Sealing material of air discharge outlet is
available option for 4-way with sealed corners, 3-way
and 2-way.
Obstacles (unit [mm])
(1) Select the installation location that meets the following Fig. 2
conditions and get approval of the customer.
• Where the cool and warm air spreads evenly in the NOTE
room. • The clearance from the wall (indicated with *) must be
• Where there is no obstacles in the air passage. 500 mm or more if the air outlet is closed or the horizontal
• Where drainage can be ensured. blade is set to Airflow block and, if the corners (left and right
• Where the ceiling lower surface is not remarkably corners of the target air outlet) are also closed, 200 mm
inclined. or more.

3P468397-1D

34
FXFQ-AVM EDFMT391770A

CAUTION (4) Use hanging bolts for installation.


Investigate if the installation place can withstand the mass
• Any vents, light or other appliances which may
of the indoor unit and, if necessary, hang the indoor unit
disturb the might cause ceiling to become dirty if
with bolts after it is reinforced by beams etc.
located too nearby, so follow Fig. 2 when installing.
(Refer to the installation pattern paper (5) for the mounting
Note)
pitch.)
1. This restriction applies to the exposed type lighting, but
does not apply to the recessed type (which does not (5) Infrared sensor’s sensing area
protrude below the ceiling line). The sensing area is as shown in the below.
2. For how to set the direction (including
Infrared floor [Target of detected area]
block) with the horizontal blade, refer to “Individual
sensor
Direction” in the operation manual attached to Infrared
the remote controller. presence
• Install the indoor and outdoor units, power supply wiring, sensor h
remote controller wiring and transmission wiring at least
1 meter away from televisions or radios to prevent image Floor
800 mm level
interference or noise.
(Depending on the radio waves, a distance of 1 meter may φa
not be to eliminate the noise.) φb
• Install the indoor unit as far as possible from
lamps. Indoor unit installation height h [m] 2.7 3.5 4.0
If a wireless remote controller kit is installed, the transmission Approx. Approx. Approx.
Infrared presence sensor φa [m]
distance may be shorter in a room where an electronic 8.5 11.5 13.5
lighting type (inverter or rapid start type) lamp is Infrared sensor φb [m]
Approx. Approx. Approx.
installed. 11 14 16
• Localized temperature difference from the room temperature,
if too large, can affect how the infrared floor sensor judges.
(This may occur, for example, in an area where floor heating/
high-temperature heat generating equipment is installed.) 4. PREPARATION BEFORE INSTALLATION
• Each sensor has been set so that the center of the sensing
(1) Check the relation of location between the ceiling
area is located in the center of the product 800 mm above
opening and the indoor unit hanging bolts.
the (in case of the infrared presence sensor) or 0 mm
above the (in case of the infrared sensor) when Refrigerant
the ceiling height is approximately 2.7 m. piping
860 – 910 (Ceiling opening)
950 (Decoration panel)

780 (Hanging bolt pitch)

(2) Ceiling height


840 (Indoor unit)

• This indoor unit can be installed in a space of which


ceiling height is up to 3.5 m (Type 100 · 125 · 140 : 4.2 m)
• However, if the ceiling height exceeds 2.7 m (Type 100 · Hanging
125 · 140 : 3.2 m), it is necessary to set from the remote bolt (×4)
controller on site. Refer to the section “10. FIELD
SETTING AND TEST OPERATION”.

(3) Direction of the air discharge


• Select the number of directions of the optimum air 710 (Hanging bolt pitch)
discharge for the shape or the position of the room. 840 (Indoor unit)
• The number of directions of the air discharge can be
860 – 910 (Ceiling opening)
changed by installing a sealing material.
• When installing a sealing material, the setting from 950 (Decoration panel)
the remote controller is required. For details, refer the
operation manual attached to the sealing materials. A (unit [mm])
(It is set to the setting position number “01” (Standard ·
All round outlet) when shipped from the factory.) Fig. 4
• To use the optional sealing material kit to change the Hanger
setting of air discharge direction (4-way blow type (with
corners sealed)/3-way blow type/2-way blow type), refer
to the installation manual attached to it. Ceiling

[Direction of air discharge]

* * * * View as seen from A

Fig. 5

All round 4-way 3-way 2-way Decoration Panel BYCQ125EEF/EEK BYCQ125EAPF BYCQ125EASF
BYCQ125EAF/EAK
*: Refrigerant piping
[mm] 125~130 167~172 180~185
Fig. 3

3P468397-1D

35
FXFQ-AVM EDFMT391770A

CAUTION
5. INSTALLATION OF INDOOR UNIT
• Reduce the distance between the unit and ceiling to 35 mm
or below in order to maintain an overlapping panel margin of <<It is easy to attach the optional parts (except for
20 mm for the opening on the ceiling. decoration panel) before installing the indoor unit. Refer
• If the distance exceeds 35 mm, attach a ceiling material to to also the installation manual attached to the optional
the part marked or replace the ceiling. (Refer to Fig. 6) parts.>>
For installation, use the attached installation parts and
specified parts.
[Install the indoor unit in the order of steps (1), (2), (3), (4),

(Dimension inside frame)


and (5) in case of a newly built ceiling, or in the order of steps
(1), (3), (4) and (5) in case of an existing ceiling.]

840
910
(1) Install the indoor unit temporarily.
• Fix the hanger to the hanging bolt.
Make sure to securely the hanger with the nut and
the washer for hanger (3) from the upper and lower side.
(Refer to Fig. 7)
840 If the washer clamp (7) is used, the upper side washer
910 for hanger (3) may be protected from falling off.
(Dimension inside frame) (Refer to Fig. 8)
(unit [mm])
[To fix hanger] Hanging bolt
Frame Nut
(Field supply) Washer for hanger (3)
(accessory)

Ceiling
material ≤35 ≤35

≥20 860 – 910 ≥20 Hanger


(Ceiling opening dimension) (Ceiling-panel
overlapping
dimension)
Tighten the nut
(double nut)
(unit [mm])
Fig. 6
Fig. 7
(2) Make the ceiling opening required for installation.
(in case of existing ceiling) [Washer clamp (7) fixing method]
• Use the installation pattern paper (5) matched to the Washer clamp (7)
ceiling opening dimension. (accessory)
• Make the ceiling opening required for installation at the
installation location and carry out refrigerant/drain piping,
Insert
power supply wiring, remote controller wiring (not
needed in case of wireless remote controller) and wiring Upper side nut
between the indoor and outdoor units. (Refer to each
section “6. REFRIGERANT PIPING WORK, 7. DRAIN
PIPING WORK and 8. ELECTRIC WIRING WORK ”)
• After making the opening, sometimes it is necessary to Fig. 8
reinforce the ceiling framework to keep the level of the
ceiling and prevent vibration of the ceiling. (2)
For details, consult with the builder and interior designer. • The installation pattern paper (5) is matched to the
(3) Install the hanging bolts. ceiling opening dimension.
• Use M8 or M10 bolts for hanging the indoor unit. For the height of ceiling lower surface from the
Use hole-in-anchors for the existing bolts and embedded level, with the builder of ceiling.
inserts or foundation bolts for new bolts, and the • The center of the ceiling opening is shown in the
indoor unit to the building so that it may withstand installation pattern paper (5).
the mass of the unit. The center of the indoor unit is indicated as triangle
In addition, adjust clearance (50 - 100 mm) from the marks on the sides and bottom of the unit and those on
ceiling in advance. the installation pattern paper (5).
• Put the installation pattern paper (5) to the indoor unit
<Installation examples> with four screws (6).
Ceiling slab At this time, put the installation pattern paper (5) to the
indoor unit with the triangle marks on the indoor unit and
50-100 mm

Foundation bolt those on the installation pattern paper (5) aligned.


Long nut or turn-buckle
Hanging bolt

Ceiling surface

Note) The above shown parts are all field supply.

3P468397-1D

36
FXFQ-AVM EDFMT391770A

Center of the Center of (4) Check the level of the unit. (Refer to Fig. 9)
indoor unit ceiling opening (5) Remove the washer clamp (7) used for preventing the
Center mark washer for hanger (3) from dropping and tighten the upper
Installation
of the unit side nut.
pattern
paper (5)
(accessory)

Screw (6)
Screw (6) (accessory)
(accessory)

[Installation of the installation pattern paper]


Level Vinyl tube
< Installation work after the ceiling work is finished >
(3) Adjust so that the unit will be properly positioned. [Maintaining horizontality]
( Refer to “4. PREPARATION BEFORE INSTALLATION Fig. 9
– (1)” )
• Using the Installation guide (15) allows you to check the
positions from the underside of the unit to the lower CAUTION
ceiling surface. • Install the indoor unit leveled.
If the indoor unit is inclined and the drain piping side gets
• Apply the short side of the cut-out section
high, it may cause malfunction of a switch and results
in case of standard grille.
in water leakage.
<BYCQ125EEF/EEK> • Attach nuts on the upper and lower side of hanger.
<BYCQ125EAF/EAK> If there is no upper nut and the lower nut is over-tightened,
the hanger and the top plate will deform and cause abnormal
sound.
• Do not insert materials other than that into
the clearance between the hanger and the washer for
Lower ceiling Underside hanger (3).
surface of the unit
Unless the washers are properly attached, the hanging
bolts may come off from the hanger.
Installation guide (15)
(accessory) WARNING
The indoor unit must be securely installed on a place
that can withstand the mass.
• Apply the long side of the cut-out section If the strength is the indoor unit may fall down
in case of designer grille. and cause injuries.
<BYCQ125EAPF>

Lower ceiling
surface Underside
of the unit

Installation guide (15)


(accessory)

• Apply the long side by cut one of the


cut-out section in case of auto grille.
<BYCQ125EASF>

Lower ceiling
surface Underside
of the unit

Installation guide (15)


(accessory)

3P468397-1D

37
FXFQ-AVM EDFMT391770A

Table 3
6. REFRIGERANT PIPING WORK
Piping Tightening Dimension for
• For the outdoor unit refrigerant piping, refer to the installation size torque processing flare Flare shape
manual attached to the outdoor unit. (mm) (N·m) A (mm)
• Carry out insulation of both gas and liquid refrigerant piping φ 6.4 15.7 ± 1.5 8.9 ± 0.2

°
securely. If not insulated, it may cause water leakage. For

2
°±
gas piping, use insulation material of which heat resistant

45
φ 9.5 36.3 ± 3.6 13.0 ± 0.2 R0.6±0.2
temperature is not less than 120°C.

90°±2°
For use under high humidity, strengthen the insulation φ 12.7 54.9 ± 5.4 16.4 ± 0.2

A
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat.
φ 15.9 68.6 ± 6.8 19.5 ± 0.2
• Before installation work, make sure that the refrigerant
is R410A. (Unless the refrigerant is R410A, the normal
operation cannot be expected.)
CAUTION
CAUTION Do not have oil adhere to the screw part of resin
This air conditioner is a dedicated model for new parts.
refrigerant R410A. Make sure to meet the requirements If oil adheres, it may weaken the strength of screwed part.
shown below and carry out installation work. Do not tighten nuts too tight.
• Use dedicated piping cutters and tools for If a flare nut cracks, the refrigerant may leak.
R410A.
• When making a connection, coat the inner • If there is no torque wrench, use Table 4 as a rule of
surface only with ether oil or ester oil. thumb.
• Use only the nuts attached to the air conditioner. When tightening a nut with a spanner harder and
If other nuts are used, it may cause refrigerant harder, there is a point where the tightening torque
leakage. suddenly increases.
• To prevent contamination or moisture from getting From that position, tighten the nut additionally the angle
into the piping, take measures such as pinching or shown in Table 4.
taping the pipings. After the work is check securely that there is no
Do not mix substance other than the specified gas leak.
refrigerant such as air into the refrigeration circuit. If the nut is not tightened as instructed, it may cause slow
If the refrigerant leaks during the work, ventilate the refrigerant leak and result in malfunction (such as does
room. not cool or heat).

• The refrigerant is pre-charged in the outdoor unit. Table 4


• When connecting the pipings to the air conditioner, make Piping size Tightening Recommended arm length of
sure to use a spanner and a torque wrench as shown in (mm) angle tool used
Fig. 10. φ 6.4 60° - 90° approx. 150 mm
• For the dimension of part and the tightening torque, φ 9.5 60° - 90° approx. 200 mm
refer to the Table 3. φ 12.7 30° - 60° approx. 250 mm
• For flare nut, use the mounting one to the body. φ 15.9 30° - 60° approx. 300 mm
• When making a connection, coat the inner
surface only with ether oil or ester oil.
(Refer to Fig. 11) CAUTION
Then, turn the nut 3 to 4 times with your hand and
Insulation of piping must be carried out up to the
screw in the nut.
connection inside the casing.
Torque wrench If the piping is exposed to the atmosphere, it may cause
sweating, burn due to touching the piping, electric shocks or
a fire due to the wiring touching the piping.
Spanner
• After leak test, referring to Fig. 12, insulate both the gas
and liquid piping connection with the attached joint
Flare nut insulating material (8) and (9) to prevent the pipings from
getting exposed.
Then, tighten the both ends of insulating material with the
clamp (4).
Union joint
• Wrap the sealing material (Medium-1, 2) (11) (12) around
Fig. 10 the joint insulating material (8) and (9) nut section),
both the gas and liquid piping.
• Make sure to bring the seam of joint insulating material (8)
Coat the flared inner surface and (9) to the top.
only with ether oil or ester oil

Fig. 11

3P468397-1D

38
FXFQ-AVM EDFMT391770A

Gas side piping insulating method • Before brazing refrigerant piping, have nitrogen flow
through the refrigerant piping and substitute air with
Joint insulating nitrogen (NOTE 2) (Refer to Fig. 13). Then, carry out
material (8) brazing (NOTE 3).
(accessory)
After all the brazing works are carry out
Flare nut Piping insulating connection with the indoor unit. (Refer to Fig. 12)
connection material (main unit) Wind around the
piping until top of the
Bring the flare nut connection, Pressure reducing valve
seam Do not leave beginning at the base.
to the top. clearance. Taping
Brazing place
Indoor unit
Nitrogen
Clamp (4)
Piping (accessory) Sealing material
insulating
Tighten the portion (11) Medium-1 Refrigerant piping Stop valve
material
where overlapped by (accessory) Nitrogen
(field supply)
the piping insulating Fig. 13
Do not expose the material.
piping in order to
prevent the vapor NOTE
condensation.
1. After indoor unit installation completed, in case will
perform the air tight test of field pipe and indoor unit,
for air tight test pressure, refer the installation manual
attached in outdoor unit.
2. The proper pressure for having nitrogen through the
piping is approximately 0.02 MPa, a pressure that makes
one feel like breeze and can be obtained through a
pressure reducing valve.
Gas piping 3. Do not use when brazing refrigerant piping.
Piping holding plate screw Use phosphor copper brazing metal (BCuP-2: JIS Z
Liquid piping
(2 points) 3264/B-Cu93P-710/795: ISO 3677) that does not require
Liquid side piping insulating method
(If chlorinated is used, the piping will be corroded and,
Joint insulating in addition if is contained, the refrigerant oil will
material (9) be deteriorated and the refrigerant circuit will be affected
(accessory)
badly.)
Flare nut Piping insulating
connection material (main unit) 4. When carrying out leakage test of refrigerant piping and
Wind around the the indoor unit after the installation of indoor unit is
Bring the piping, beginning finished, confirm the connecting outdoor unit installation
seam Do not leave at the base.
to the top. clearance. manual for test pressure.
Refer to also the outdoor unit installation manual or
technical document for refrigerant piping.
Indoor unit 5. In case of refrigerant shortage due to forgetting additional
refrigerant charge etc., it will result in malfunc tion such as
Piping Clamp (4) Sealing material does not cool or does not heat.
insulating (accessory) (12) Medium-2
material Refer to the outdoor unit installation manual or technical
Tighten the portion (accessory) document for refrigerant piping.
(field supply)
where overlapped by
Do not expose the the piping insulating
material. CAUTION
piping in order to
prevent the vapor Do not use antioxidant when brazing piping.
condensation. It may result in malfunction of components and clogging of
piping due to residue.
Fig. 12

3P468397-1D

39
FXFQ-AVM EDFMT391770A

7. DRAIN PIPING WORK CAUTION


• Do not tighten the metal clamp (2) with the torque more
(1) Carry out drain piping.
than the value.
Carry out drain piping so that drainage can ensured.
The drain hose (1), the socket or the metal clamp (2) may
• Select the piping diameter equal to or larger than
be damaged.
(except for riser) that of the connection piping (polyvinyl
chloride piping, nominal diameter 25 mm, outside
< Caution to be taken when carrying out upward drain
diameter 32 mm).
piping (Refer to Fig. 16) >
• Install the drain piping as short as possible with down-
• The maximum height of the drain riser is 675 mm.
ward inclination of 1/100 or more and without where air
Since the drain pump mounted on this indoor unit is a high
may stagnate. (Refer to Fig. 14) (It may cause abnormal
head type, from the characteristic point of view, the higher
sound such as bubbling noise.)
the drain riser the lower the draining noise.
Therefore, the drain riser of 300 mm or higher is
1~1.5 m recommended.
• For upward drain piping, keep the horizontal piping
Support Downward distance of 300 mm or less between the drain socket root
inclination of to the drain riser.
1/100 or more
(unit [mm])
Ceiling slab
Good
300 or less 1~1.5 m Support

(850 or less)
Wrong
Adjustable
Metal clamp (2) (accessory) (675 or less)
Fig. 14
Drain hose (1) (accessory)
Upward drain piping
CAUTION Drain riser
If drain stagnates in the drain piping, the piping may be
clogged.
Drain hose (1)
(accessory)
• If downward inclination cannot be ensured,
carry out upward drain piping.
• Install supports at a distance of 1 to 1.5 m so that the
piping may not deflect. (Refer to Fig. 14)
• Make sure to use the attached drain hose (1) and the
metal clamp (2). Level or upward
inclination
CAUTION Keep the drain hose level or make a slight up-grade so
Using old drain hose, clamp fixture may cause water that air may not stagnate in the drain hose.
If air stagnates, the drain may flow oppositely when
leakage.
the drain pump stops and generate abnormal sound.
• Insert the drain hose (1) into the drain socket up to the
point where the socket diameter becomes larger. Fig. 16
Put the metal clamp (2) to the taped hose end and
tighten the metal clamp (2) with torque 1.35±0.15 N·m
(135±15 N·cm).
Hose end
Drain socket Drain hose (1)
(accessory)

Metal clamp (2)


(accessory) VP20 side VP25 side

Tape

Fig. 15

10

3P468397-1D

40
FXFQ-AVM EDFMT391770A

CAUTION
• To avoid the attached drain hose (1) getting excessive
force, do not bend nor twist it.
It may cause water leakage.
• In case of centralized drain piping, carry out piping work
according to the procedure shown in the following Fig. 17.
Sealing material (14)
0 ~ 675 mm

(accessory)

Fig. 19

CAUTION
Do not add the external force to float switch.
Centralized drain piping It may cause failure.
Make a downward inclination of 1/100
or more to avoid stagnancy of air. [When the electric wiring work is not finished]
If water stagnates in the drain • For electric wiring operation shall refer the details in
piping, it may cause clogging of “8. ELECTRIC WIRING WORK”
drain piping. • The electric wiring works (including earthing) must be
carried out by a electrician.
Fig. 17
• If a person is not present, after the electric wiring
• As for the size of centralized drain piping, select the size work is check the drainage according to the
that meet the capacity of indoor units to be connected. method in [When the electric wiring work is
(Refer to the technical document) .
• At replacement with new indoor unit, use the attached 1. Open the control box lid and connect the single phase
new drain hose (1) and the metal clamp (2). 220 - 240 V power supply to the terminal (L, N) on the
If an old drain hose or a metal clamp is used, it may terminal block (X2M).
cause water leakage. Connect the earth wiring to the earth terminal. (Refer
to Fig. 20)

(2) After piping is check if the drain


smoothly.
[When the electric wiring work is
• Gradually pour 1 liter of water from the air outlet on the
left side of the drain socket into the drain pan giving
caution to avoid splashing water on the electric Terminal block (X2M)
components such as drain pump and confirm drainage
by operating the indoor unit under cooling mode
according to “10. FIELD SETTING AND TEST
OPERATION”. (Refer to Fig. 18)

Drain piping

Control box lid

Drain outlet for service Single phase


power supply
≥100 mm

(with rubber plug) (50 Hz 220-240V, R(L)


L

Use it when draining water 60 Hz 220-230V) S(N)


N

in the drain pan Earth wiring

Plastic container for pouring water Earth terminal


(Tube length of 100 mm or more
is necessary.)

[Method of adding water] Fig. 20


Fig. 18

• After checking the drainage of water, refer to Fig. 19 and


attach the sealing material (14) to perform the thermal
insulation of the drain socket.

11

3P468397-1D

41
FXFQ-AVM EDFMT391770A

2. Make sure the control box lid is closed before turning


on the power supply. 8. ELECTRIC WIRING WORK
• Throughout the whole process, carry out the work
8-1 GENERAL INSTRUCTIONS
giving caution to the wiring around the control box
so that the connectors may not come off. • Make certain that all electric wiring work is carried out by
qualified personnel according to the applicable legislation
3. Gradually pour 1 liter of water from the air outlet on
and this installation manual, using a separate dedicated
the left side of the drain socket into the drain pan
circuit.
giving caution to avoid splashing water on the electric
Insufficient capacity of the power supply circuit or improper
components such as drain pump. (Refer to Fig. 18)
electrical construction may lead to electric shocks or a fire.
4. When the power supply is turned on, the drain pump • Make sure to install an earth leakage breaker.
will operate. Drainage can be checked at the Failure to do so may cause electrical shocks and a fire.
transparent part of the drain socket. • Do not turn on the power supply (branch switch, branch
(The drain pump will automatically stop after 10 overcurrent circuit breaker) until all the works are finished.
minutes.) • Multiple number of indoor units are connected to one
After checking the drainage of water, refer to Fig. 19 outdoor unit. Name each indoor unit as A-unit, B-unit ….. and
and attach the sealing material (14) to perform the the like. When these indoor units are wired to the outdoor unit
thermal insulation of the drain socket. and the BS unit, always wiring the indoor unit to the terminal
• Do not connect the drain piping directly to the indicated with the same symbol on the terminal block. If the
sewage that gives off ammonia odor. wiring and the piping are connected to the different indoor
The ammonia in the sewage may go through the units and operated, it will result in malfunction.
drain piping and corrode the heat exchanger of the • Make sure to earth the air conditioner.
indoor unit. Earthing resistance should be according to applicable
• Do not apply external force to the switch. (It legislation.
may result in malfunction) • Do not connect the earth wiring to gas or water pipings,
5. Turn off the power supply after checking drainage, lightning conductor or telephone earth wiring.
and remove the power supply wiring. • Gas piping .................Ignition or explosion may occur if
6. Attach the control box lid as before. the gas leaks.
• Do not touch the electronic parts other than the • Water piping ..............Hard vinyl tubes are not effective
terminal block (X2M). earths.
• Lightning conductor or telephone earth wiring ..................
(3) Sweating may occur and result in water leakage. Electric potential may rise abnormally if struck by a light-
Therefore, make sure to insulate the following 2 ning bolt.
locations (drain piping and drain sockets that laid • For electric wiring work, refer to also the “WIRING
indoors). DIAGRAM” attached to the control box lid.
After drainage is checked, put the attached sealing • Carry out wiring between the outdoor units, indoor units and
material (14) referring to Fig. 19, and insulate the drain the remote controllers according to the wiring diagram.
hose (1) and the metal clamp (2) with the attached sealing • Carry out installation and wiring of the remote controller
material (Large) (10) referring to Fig. 21. according to the “installation manual” attached to the remote
controller.
Sealing material - Large • Do not touch the Printed Circuit Board assembly. It may
(10) (accessory) cause malfunction.
Be sure to lay the
sealing material 8-2 ELECTRICAL CHARACTERISTICS
(10) on (14).
Do not have
Units Power supply Fan motor
the clearance.
Sealing material (14)
Voltage
(accessory) Model Hz Volts MCA MFA kW FLA
range
FXFSQ25AVM 0.3 16 0.053 0.2
FXFSQ32AVM 0.3 16 0.053 0.2
Metal
clamp (2) Sealing material (Large) (10) FXFSQ40AVM 0.4 16 0.053 0.3
FXFSQ50AVM 220- Max. 264 0.4 16 0.053 0.3
(accessory) (accessory) 50
FXFSQ63AVM 240 Min. 198 0.6 16 0.053 0.5
FXFSQ80AVM 1.0 16 0.053 0.8
Drain hose (1) FXFSQ100AVM 1.4 16 0.106 1.1
(accessory) FXFSQ125AVM 1.6 16 0.106 1.3
FXFSQ140AVM 1.8 16 0.106 1.4
FXFQ25AVM 0.3 16 0.053 0.2
≥ 4 mm FXFQ32AVM 0.3 16 0.053 0.2
FXFQ40AVM 0.4 16 0.053 0.3
220- Max. 264
50
Fig. 21 FXFQ50AVM 240 Min. 198 0.4 16 0.053 0.3
FXFQ63AVM 0.6 16 0.053 0.5
FXFQ80AVM 1.0 16 0.053 0.8
FXFQ100AVM 1.4 16 0.106 1.1
FXFQ125AVM 1.6 16 0.106 1.3
FXFQ140AVM 1.8 16 0.106 1.4

12

3P468397-1D

42
FXFQ-AVM EDFMT391770A

UnitAs Power supply Fan motor


8-3 SPECIFICATION FOR FIELD SUPPLY FUSES
AND WIRING
Voltage
Model Hz Volts MCA MFA kW FLA Remote controller wiring
range Power supply wiring
FXFSQ25AV4 0.3 16 0.053 0.2 Transmission wiring
FXFSQ32AV4 0.3 16 0.053 0.2 Model
Field
FXFSQ40AV4 0.4 16 0.053 0.3 fuses Wiring Size Wiring Size
FXFSQ50AV4 220- Max. 264 0.4 16 0.053 0.3
50
FXFSQ63AV4 240 Min. 198 0.6 16 0.053 0.5 FXFSQ25AVM
FXFSQ80AV4 1.0 16 0.053 0.8 FXFSQ32AVM
FXFSQ100AV4 1.4 16 0.106 1.1 FXFSQ40AVM
FXFSQ125AV4 1.6 16 0.106 1.3 FXFSQ50AVM
FXFSQ140AV4 1.8 16 0.106 1.4 FXFSQ63AVM
FXFQ25AV4 0.3 16 0.053 0.2 FXFSQ80AVM
FXFQ32AV4 0.3 16 0.053 0.2 FXFSQ100AVM
FXFQ40AV4 0.4 16 0.053 0.3 FXFSQ125AVM
FXFQ50AV4 0.4 16 0.053 0.3 FXFSQ140AVM
220- Max. 264
FXFQ63AV4 50 0.6 16 0.053 0.5 FXFQ25AVM
240 Min. 198
FXFQ80AV4 1.0 16 0.053 0.8 FXFQ32AVM
FXFQ100AV4 1.4 16 0.106 1.1 FXFQ40AVM
FXFQ125AV4 1.6 16 0.106 1.3 FXFQ50AVM
FXFQ140AV4 1.8 16 0.106 1.4 FXFQ63AVM
FXFSQ25AVM 0.3 16 0.053 0.2 FXFQ80AVM
FXFSQ32AVM 0.3 16 0.053 0.2 FXFQ100AVM Vinyl cord
FXFSQ40AVM 0.4 16 0.053 0.3 FXFQ125AVM with sheath
0.4 16 0.053 0.3 FXFQ140AVM H05VV-U3G 2.5 mm2
FXFSQ50AVM 220- Max. 253 or cable 0.75-
60 16A
FXFSQ63AVM 230 Min. 198 0.6 16 0.053 0.5 FXFSQ25AV4 (2 core) 1.25 mm2
NOTE 1, 2) NOTE 4)
FXFSQ80AVM 1.0 16 0.053 0.8 FXFSQ32AV4
FXFSQ100AVM 1.4 16 0.106 1.1 FXFSQ40AV4 NOTE 3)
FXFSQ125AVM 1.6 16 0.106 1.3 FXFSQ50AV4
FXFSQ140AVM 1.8 16 0.106 1.4 FXFSQ63AV4
FXFQ25AVM 0.3 16 0.053 0.2 FXFSQ80AV4
FXFQ32AVM 0.3 16 0.053 0.2 FXFSQ100AV4
FXFQ40AVM 0.4 16 0.053 0.3 FXFSQ125AV4
FXFQ50AVM 0.4 16 0.053 0.3 FXFSQ140AV4
220- Max. 253
60 16 0.053 0.5
FXFQ63AVM 230 Min. 198 0.6 FXFQ25AV4
FXFQ80AVM 1.0 16 0.053 0.8 FXFQ32AV4
FXFQ100AVM 1.4 16 0.106 1.1 FXFQ40AV4
FXFQ125AVM 1.6 16 0.106 1.3 FXFQ50AV4
FXFQ140AVM 1.8 16 0.106 1.4 FXFQ63AV4
FXFQ80AV4
MCA: Min. Circuit Amps (A) MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A) FXFQ100AV4
FXFQ125AV4
FXFQ140AV4

13

3P468397-1D

43
FXFQ-AVM EDFMT391770A

The lengths of remote controller wiring and transmission (Abnormal heating may occur if the wirings are not tightened
wirings are as follows: securely.)
(1) Remote controller wiring • Use the required wirings, connect them securely and fix
(indoor unit - remote controller).....................Max. 500 m these wirings securely so that external force may not apply to
(2) Transmission wirings .............Total wiring length 2000 m the terminals.
• Outdoor unit - Indoor unit.............................Max. 1000 m • Use a proper screw driver for tightening the terminal screws.
• Outdoor unit - BS unit ..................................Max. 1000 m If an improper screw driver is used, it may damage the screw
• BS unit - Indoor unit .....................................Max. 1000 m head and a proper tightening cannot be carried out.
• Indoor unit - Indoor unit ...............................Max. 1000 m • If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
NOTE terminals.
1. Shows only in case of protected piping. Use H07RN-F in
Tightening torque (N·m)
case of no protection.
Terminal block for remote controller
2. Supply cords shall not be lighter than polychloroprene 0.88 ± 0.08
and transmission wirings
sheathed flexible cord (code designation 60245 IEC 57)
Terminal for power supply 1.20 ± 0.12
3. Vinyl cord with sheath or cable (Insulated thickness : 1 mm
Earth terminal 1.20 ± 0.12
or more)
4. Wiring size and length must comply with local codes or • Do not carry out soldering when stranded wirings
IEC 60335-1 (Table 11)
are used.

8-4 WIRING CONNECTION METHOD WARNING


• When wiring, form the wirings orderly so that the control box
CAUTION FOR WIRING
lid can be securely fastened. If the control box lid is not in
• For connection to the terminal block, use a ring type crimp place, the wirings may float up or be sandwiched by the box
style terminals with insulation sleeve or insulate the wirings and the lid and cause electric shocks or a fire.
properly.
< Power supply wiring · earth wiring · remote controller
Wiring wiring · transmission wiring connecting method >
Insulation sleeve • Power supply wiring, earth wiring
Pull the wiring through the wiring penetrating hole (high
Ring type crimp voltage). After connecting the power supply wiring to [L ·
style terminals N] on the power supply terminal block (X2M) and the earth
wiring to the earth terminal, clamp them near the terminal
• Connect the terminal as shown in Fig. 23. block using the attached clamp (4). (Refer to page 15)
• Do not carry out soldering finish when stranded wires are • Remote controller wiring, transmission wiring
used. (Otherwise, the loosening of wires may result in Pull the wiring through the wiring penetrating hole (low
abnormal heat radiation.) voltage). After connecting the remote controller wiring to [P1
· P2] and the transmission wiring to [F1 · F2] on the terminal
block (X1M), clamp them near the terminal block using the
attached clamp (4). (Refer to page 15)
• After connecting the wiring, make sure to stick the sealing
material (Small) (13) to the wiring penetrating hole. (Refer to
Fig. 24)
(It is to prevent water from entering into the indoor unit.)
CAUTION
• Never connect the power supply wiring to the terminal block
for remote controller/transmission wiring (X1M).
Use wires the same in size
If may damage the total system.
(if the air conditioner is
in simultaneous multi operation) • Do not connect the remote controller/transmission wiring
to the wrong terminal bock.
Fig. 22

14

3P468397-1D

44
FXFQ-AVM EDFMT391770A

[Remote controller wiring, Transmission wiring]


Remote Transmission
controller wiring wiring
Sheathed part of P1 P2 F1 F2 T1 T2
remote controller wiring,
transmission wiring
Approx.
Wiring 7 mm Forced off
penetrating hole R10
Strand the 10 - 15 mm
Power supply wiring (high voltage) wirings after or more
Earth wiring sheath is 70 - 90 mm Clamp (4)
peeled off. (Sheath peeling After the wirings are clamped,
off allowance.) cut off the extra part.

Transmission
Terminal block for wiring
power supply wiring/
earth wiring (X2M)

Remote
controller wiring

Wiring penetrating
hole (low voltage)

Printed
[Power supply wiring, Earth wiring] Circuit Board
Terminal block for
remote controller wiring/
Sheathed transmission wiring (X1M)
part

Control box lid


Earth Clamp (4) Wiring diagram label
10 - 15 mm
(Sheath peeling

wiring
off allowance.)
70 - 90 mm

R(L) After the (on backside of control box lid)


L

S(N) wirings are


N

clamped, cut
off the extra
part.
R10
or more Earth terminal

Fig. 23

15

3P468397-1D

45
FXFQ-AVM EDFMT391770A

Wiring penetrating hole < No. 2 system: When carrying out group control or 2
remote controller control. >
Power supply wiring/earth
Power supply
wiring or remote controller
220-240 V
wiring/transmission wiring
1~
Sealing material 50 Hz
(Small) (13) or
(accessory) 220-230 V
1~ Outdoor
Putty or insulation 60 Hz unit Note) It is not needed to set the
(field supply) L N indoor unit address when
using group control.
IN/D OUT/D
F1 F2 F1 F2

Fig. 24 (It is automatically set when


the power is turned on.)
<<Mending method of wiring penetrating hole>>
• After wiring connection is finished, to prevent the penetration Most down-
of water, small animals and insects into the indoor unit L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
stream
from the outside, mend the respective covers for wiring indoor unit
Indoor Indoor
penetrating hole for the power supply wiring/earth wiring and unit A unit B
the remote controller wiring/transmission wiring.
• Cut the sealing material (Small) (13) into two pieces and Remote P1 P2 P1 P2 P1 P2
wrap each wiring with each piece. controller
• Seal the clearance around the wirings with putty and (option) Case of group Remote Remote
control controller controller
insulating material (field supply). (option)
(If insects and small animals get into the indoor unit, short For use with 2
circuiting may occur inside the control box.) remote controllers
• Keep the distance of 50 mm or more between the low voltage
wiring (remote controller wiring, transmission wiring) and < No. 3 system: When BS unit is used >
the high voltage wiring (power supply wiring, earth wiring) Outdoor unit BS unit
at anywhere outside the indoor unit. If both the wirings are Power supply L N
IN/D OUT/D OUT/D IN/D
laid down together, they may be affected by electric noise 220-240 V F1 F2 F1 F2 F1 F2 F1 F2

(outside noise) and cause malfunction or failure. 1~


50 Hz
or
8-5 EXAMPLE OF WIRING
220-230 V
< No. 1 system: When 1 remote controller is used for 1 1~
indoor unit. > 60 Hz
Power supply L N P1 P2 F1 F2 T1 T2

220-240 V
1~ Indoor unit A
50 Hz
or Remote controller
P1 P2
220-230 V (option)
1~ Outdoor
60 Hz unit
L N
NOTE
IN/D OUT/D
F1 F2 F1 F2 1. Remote controller wiring and transmission wiring have no
polarity.

WARNING
Indoor
unit B Be sure to install an earth leakage breaker.
Failure to do so may cause electric shocks and a
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2

Indoor Most 8-6 FOR CONTROL WITH 2 REMOTE CONTROL-


unit A downstream
Indoor unit LERS (TO CONTROL 1 INDOOR UNIT WITH 2
P1 P2 P1 P2 P1 P2 REMOTE CONTROLLERS)
Remote Remote • For control with 2 remote controllers, set one remote
Remote
controller controller controller controller as Main and the other remote controller as Sub.
(option) (option) (option) < Changeover method from Main to Sub and vice versa >
Refer to the installation manual attached to the remote
controller.
< Wiring method >
(1) Remove the control box lid.
(2) Carry out additional wiring from the remote controller
2 (Sub) to the terminals (P1, P2) for remote controller
wiring on the terminal block (X1M) in the control box.

16

3P468397-1D

46
FXFQ-AVM EDFMT391770A

Terminal block 9. MOUNTING DECORATION PANEL


(X1M)
<<If test operation is required before mounting the
decoration panel, “10. FIELD SETTING AND TEST
Terminal for remote OPERATION” can be carried out before “9. MOUNTING
controller wiring (P1, P2) DECORATION PANEL”.>>
No polarity
CAUTION
In case of a wireless remote controller, unless the decoration
panel is mounted, field setting and test operation cannot be
carried out.
Remote Remote
controller 1 controller 2 Refer to the installation manual attached to the decoration
(Main) (Sub) panel.
< Caution > • After the decoration panel is mounted, check if no clearance
• When using the group control and the 2 remote control- exists between the panel and the unit.
lers control at the same time, connect the remote control- • If test operation is carried out before mounting the decoration
ler 2 (Sub) to the indoor unit at the end of the crossover panel, check the swing blade action after the panel is
wiring (the largest No.). (Refer to Fig. 25) mounted.
Indoor unit
Indoor unit 1 Indoor unit 2 largest No.
10. FIELD SETTING AND TEST OPERATION
<<Refer to also the installation manual attached to the
Remote Crossover Remote outdoor unit.>>
controller 1 wiring (Remote controller 2
(Main) controller) (Sub) CAUTION
Fig. 25 Before carrying out field setting, check the items mentioned in
the clause 2 “1. Items to be checked after the installation
8-7 FOR CENTRALIZED CONTROL work is completed” on page 3.
• When centralized equipment (such as centralized controller) • Check if all the installation and piping works for the air
is used for control, it is required to set the group No. on the conditioner are completed.
remote controller. • Check if the control box lids of the air conditioner are closed.
For details, refer to the manuals attached to the centralized
equipment. < FIELD SETTING >
• Connect the centralized equipment to the indoor unit <<After turn on the power supply, carry out field setting
connected to the remote controller. from the remote controller according to the installation
state.>>
8-8 FOR REMOTE CONTROL (FORCE OFF OR ON / • Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
OFF OPERATION) and “SECOND CODE No.”.
(1) Wiring method and specification The settings shown by “ ” in the table indicate those
• Remote control is available by connecting the external when shipped from the factory.
input to the terminal T1 and T2 on the terminal block for • The method of setting procedure and operation is shown in
remote controller and transmission wiring (X1M). the installation manual attached to the remote controller.
Sheathed vinyl (Note) Though setting of “Mode No.” is carried out as a group,
Wiring
cord or 2 core if you intend to carry out individual setting by each
F2 T1 T2 cable indoor unit or confirmation after setting, carry out
FORCED Wiring size 0.75-1.25 mm2 setting with the Mode No. shown in the parenthesis ( ).
OFF Wiring length Max. 100 m • In case of remote control, for changeover of input to
Contact that can FORCED OFF or to ON/OFF OPERATION.
Input A External make and break [1] Enter into the field setting mode with the remote controller.
contact spec the min. load of [2] Select Mode No. “12”.
DC 15 V · 1 mA [3] Set the FIRST CODE No. to “1”.
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”.
(2) Actuation [4-2] For ON/OFF OPERATION, set the SECOND CODE
• Input A of FORCED OFF and ON/OFF OPERATION will No. to “02”.
be as the table shown below. (It is set to FORCE OFF when shipped from the factory.)
Input A = ON Input A = OFF • Ask your customer to keep the manual attached to the remote
In case of FORCED Remote controller Remote controller controller together with the operation manual.
OFF prohibited permitted • Do not carry out settings other than those shown in the table.
In case of ON/OFF
Operation Stop
OPERATION

(3) How to choose FORCED OFF or ON/OFF OPERATION


• For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to “10. FIELD SETTING AND TEST OPERATION”)

17

3P468397-1D

47
FXFQ-AVM EDFMT391770A

10-1 SETTING CEILING HEIGHT Table 7


• Set the SECOND CODE No. according to the ceiling height Contamination
Hours until
Mode No.
FIRST SECOND
as shown in the Table 5. indication CODE No. CODE No.
Approx.
Table 5 Normal 01
2500 hrs
Ceiling height (m) FIRST SECOND 0
Mode More Approx.
Setting 25-80 100-140 CODE CODE 10 (20) 02
No. contaminated 1250 hrs
type type No. No. With indication 01
3
Standard 2.7 or less 3.2 or less 01 No indication* 02
* Use “No indication” setting when cleaning indication is not
High ceiling 1 2.7 - 3.0 3.2 – 3.6 13 (23) 0 02 necessary such as the case of periodical cleaning being
carried out.
High ceiling 2 3.0 - 3.5 3.6 – 4.2 03
< TEST OPERATION >
• After cleaning the indoor unit inside, carry out test operation
10-2 SETTING AIR DISCHARGE DIRECTION according to installation manual attached to the outdoor unit.
• Refer to the installation manual attached to the sealing • When the remote controller operation lamp flashes, it shows
material of air discharge outlet sold separately and that something is abnormal.
engineering data book, for ceiling height settings for four- Check the malfunction codes on the remote controller.
direction (part of corner closed off), three-direction and two- The relation between the malfunction codes and malfunction
direction. (The SECOND CODE No. is factory set to “01” details is described in the operation manual attached to the
(all round outlet) before shipping.) outdoor unit.
Particularly, if the indication is one of those shown in the
10-3 SETTING WHEN AN OPTIONAL ACCESSORY IS Table 8, it may be an error in the electrical wiring or the
ATTACHED power supply is disconnected. Therefore, recheck wiring.
• For setting when attaching an optional accessory, refer to the
installation manual attached to the optional accessory. Table 8
Remote controller
10-4 WHEN USING WIRELESS REMOTE CONTROLLER indication
Details
• When using a wireless remote controller, it is necessary to Though the central-
set the wireless remote controller address. • The terminals (T1 · T2) for FORCED OFF on
ized control is not
Refer to the installation manual attached to the wireless the indoor unit transmission terminal block is
carried out, the lamp
short circuited.
remote controller. “ ” turns on.
• The power supply to the outdoor unit is not
10-5 SETTING FAN SPEED DURING THERMOSTAT made.
OFF • The power supply work to the outdoor unit is
• Set the fan speed according to the using environment after “U4” turns on not carried out.
consultation with your customer. “UH” turns on • The transmission wiring and the remote
• When the fan speed is changed, explain the set fan speed to controller wiring and FORCED OFF wiring
are connected wrongly.
your customer.
• The transmission wiring is disconnected.
Table 6 • The power supply to the indoor unit is not
made.
FIRST SECOND • The power supply work to the indoor unit is
Setting Mode No.
CODE No. CODE No. not carried out.
No indication
Fan speed during LL
01
• The remote controller wiring and the
cooling (Extra low) 12 (22) 6 transmission wiring and FORCED OFF
thermostat OFF Setting 02 wiring are connected wrongly.
Fan speed during LL • The remote controller wiring is disconnected.
01
heating (Extra low) 12 (22) 3
thermostat OFF Setting 02 Note) In case of use wireless remote control, shall refer
operation manual attached to wireless remote
10-6 SETTING FILTER SIGN control.
• A message to inform the air filter cleaning time will be
indicated on the remote controller. • At test operation, if the decoration panel is mounted, check
• Set the SECOND CODE No. shown in the Table 7 according the actuation of the swing blade.
to the amount of dust or pollution in the room.
• Though the indoor unit is equipped with the long life filter, it is
necessary to periodically clean the filter to avoid clogging of
the filter. Please also explain the set time to the customer.

18

3P468397-1D

48
FXFQ-AVM EDFMT391770A

CAUTION
After test operation is completed, check the items mentioned
in the clause 2 “2. Items to be checked at delivery” on
page 4.
If the interior work is not completed when the test
operation is for protection of the air conditioner,
ask the customer not operate the air conditioner until the
interior work is completed.
If the air conditioner is operated, the inside of the indoor
units may be polluted by substances generated from the
coating and adhesives used for the interior work
and cause water splash and leakage.

To the operator carrying out test operation


After test operation is completed, before delivering the air
conditioner to the customer, that the control box
lid, the air and suction grille are attached.
In addition, explain the power supply status (power supply
ON/OFF) to the customer.

19

3P468397-1D

49
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trade mark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

●Specifications, designs and other content appearing in this brochure are current as of February 2018 but subject to change without notice.

©All rights reserved 02/18 FS

You might also like