EEI CORPORATION

Construction Division
Engineering Department

DESIGN REVIEW FORM

Client: ULC Date: 11/28/17


Project: MRT-7
Location: Station 5 Ref. No.: _____ Sht. No. _ of _

Submittal:
Preliminary Others
For Approval __________________
Final __________________
Reviewed by: ACSarmiento

Document No. Comments Action Taken EEI Remarks


1. Kindly optimize intermediate For practical and aesthetic reason,
beams (CD-1) between Gridlines some e.g. diaphrgam beams
B-B1, C-D & D1-E. Largest value connecting deep beams/girders
D-S05-SS-03004 of utility ratio in staad model is are made larger than is required.
0.0997

Complied
2. Kindly verify if columns on
roof beam elevation along grids
D-S05-SS-03051 1a, 1b - 15a should be reflected
on the section drawing.

3. Please verify thickness of Thickness corrected to 16mm


D-S05-SS-03053 stiffener plates.
4. Based on provided Splice location is correct. The
connection detail at D-S05-SS- detail is not drawn to scale due to
03058,l ength of bottom flange space constraint.
splice required on CG-4 is
D-S05-SS-03053 1,500mm. Kindly verify
constructability of BPL-2.

Detail is shown in Section R1-C


5. Please provide detailed
connection of intermediate
D-S05-SS-03057 rafter. See attached file for
mark-up comment.
Splice plates for connection details
are sized from bolt number and
spacing (typically 2.67xBolt Dia).
Note added in drawing D-S05-SS-
6. Kindly show bolt spacing and 03058 regarding bolt spacing and
D-S05-SS-03058 edge distances on connection edge distance criteria.
details.

7. Please update connection Complied


D-S05-SS-03058 schedule based on revised
sections.

PAGE 1 OF 6 EEI CORPORATION


Document No. Comments Action Taken EEI Remarks
8. Kindly identify shear or Document is updated. All
moment connection on connections and splices are
connection schedule. moment/shear connected except
D-S05-SS-03058 where noted as "Not Applicable".

PAGE 2 OF 6 EEI CORPORATION


Document No. Comments Action Taken EEI Remarks
9. Please incorporate weight of The weight of fascia truss, cladding
gutter and fascia trusses on the and gutter are included in Staad
design model, design of fascia truss and
subsequently the forces are
D-S05-SS-03059 transferred to Sta 5 structure
model as loads.

10. Kindly verify supporting The stair was idealized in Staad as


column at end of stairs (1.50m a beam 2500 wide bt 200 deep.
high) as reflected on staad There is no column support at Elev
model. 75.83. Below the ground is a wall
D-S05-SS-03061 footing to support the stair.

11. Please apply property Complied


reduction factor on concrete
D-S05-SS-03061 structures (beams and columns)
to all stair towers.
12. Kindly provide stair For further study.
foundations on shallow footing.

PAGE 3 OF 6 EEI CORPORATION


EEI CORPORATION
onstruction Division
ineering Department

SIGN REVIEW FORM

Ref. No.: _____ Sht. No. _ of _

EEI Remarks

PAGE 4 OF 6 EEI CORPORATION


EEI Remarks

PAGE 5 OF 6 EEI CORPORATION


EEI Remarks

PAGE 6 OF 6 EEI CORPORATION