You are on page 1of 1

STORAGE TANK SPECIFICATION Sheet 1 of 1

(English Units)

Rev. No.
Project No.

1 Service : Equipment No. :


2 Location : Unit : Design Engineer : Seth A. Duazo
3 Manufacturer : Model : Mfr Ref. No. : No. Req'd :
4 P&ID No. Plot Plan No. : Other Ref. Dwg No. :
5
6
7
8 M
9 A P G
10
11
12
13 125.30 Ft
14 H
15 46.00 Ft 24" X 36"
16 FLUSH
E CLEANOUT E
17
18
19 L F D
20
21
22 N1 N2 J I
23
24 Shell Diameter : 125.30 Feet Shell Height : 46.00 Feet Nominal Volume : 101,026 Barrels
25 Roof Type : Cone Bottom Floor Type: Sloped
26 OPERATING/DESIGN DATA NOZZLES/CONNECTIONS
27 Fluid Stored : LUBE OIL Sp. Gr. : 0.9000 Mark Service Qty Size Rating Face
28 This Tank Service is considered: Cyclic TH1 Roof Manway 1 24" 150# F. F.
29 Vapor Pressure @ Max. Operating Temperature 5.5 psia TH Shell Manway 2 24" 125# R. F.
30 Flash Point (Closed Cup) : ºF Operating Design TH2 Flush Cleanout MW 1 24"x36" 125# R. F.
31 Negative Pressure oz/in.2 0.00 0.50 G Stilling Vent 1 8" 150# F. F.
32 Positive Pressure psig 1.00 2.00 H Temperature Indicator 0 0 150# L. J.
33 (Hydro)test Pressure expressed in Psig ---- B Outlet Nozzle 1 12" 150# API
34 Minimum Fluid Temperature ºF -25 A Fill Nozzle 1 8" 150# L. J.
35 Maximum Fluid Temperature ºF 200 K Mixer Manway 0 0 150# F. F.
36 Emergency Vacuum Design ? No Set @ 0.0.3 oz/in.2 D Water Draw Nozzle 1 4" 150# R. F.
37 METALLURGY M Top Center Vent 1 4" 150# API
38 Component Material CA, in. Remarks F Sample Tap 2 3/4" 150# R. F.
39 Shell & Bottom A36 0.0625 Normalized F Sample Tap 1 3/4" 150# F. F.
40 Roof A36 0.0313 Normalized P Roof Nozzle 1 4" 150# L. J.
41 Lining/Coating D Spare 1 3/4" 150# API
42 150# API
43 Stress Relieve ? No for: 150# API
44 CONSTRUCTION/FABRICATION
45 Code (as appl.): API 650 LATEST EDITION Internals (attach separate sheet, as req'd): Others:
46 Design Specifications: Sump
47 Tank Insulation ? No Thickness : in. Seismic Zone 3 Design Wind Velocity 120 mph
48 Insulation Type: Hot Radiograph 85 % Inspection Req'd ? Yes
49 Fireproofing ? No Paint Spec. EmptyTank Weight lb Full of Water lb
50 Remarks
51 1. Items marked with an asterisk (*) to be completed by Vendor/Fabricator.
52 2. Rafter supported type cone roof
Approvals
Rev Date Description By Chk. Appr. Rev Date Description By Chk. Appr.
0 J543