Technical guide P122/EN ST/B11

MiCOM P122C

Setting Tables and


Setting Sheets
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 1/16

CONTENTS

1. SETTING TABLES AND SETTING SHEETS 3


1.1 Substation reference 3
1.2 Protection device data 3
1.3 Menu OP PARAMETERS 3
1.4 Menu CONFIGURATION 3
1.4.1 Submenu GLOBAL SETTINGS 3
1.4.2 Submenu LOCAL INDICATION 4
1.4.3 Submenu INPUTS 4
1.4.4 Submenu INPUT MODE 4
1.4.5 Submenu OUTPUT RELAYS 5
1.4.6 Submenu OUTPUT RELAY MODE 6
1.4.7 Submenu LATCH OUTPUT RELAYS 6
1.4.8 Submenus LED 5, LED 6, LED 7 and LED 8 7
1.4.9 Submenu COMMUNICATION 8
1.4.10 Submenu RECORD SETTING 9
1.5 Menu AUTOMAT.CTRL 10
1.5.1 Submenus TRIP COMMAND and LATCH TRIP ORDER 10
1.5.2 Submenu CB FAILURE 10
1.5.3 Submenu SWITCH ON FAULT 10
1.5.4 Submenu SETTING GROUP SELECT 11
1.5.5 Submenu COLD LOAD PICKUP 11
1.5.6 Submenu BLOCKING LOGIC 1 12
1.5.7 Submenu BLOCKING LOGIC 2 12
1.5.8 Submenu LOGIC SELECT 1 12
1.5.9 Submenu LOGIC SELECT 2 13
1.5.10 Submenu CB SUPERVISION 13
1.5.11 Submenu CT SUPERVISION 13
1.6 Menus PROTECTION G1 and PROTECTION G2 14
1.6.1 Submenu [50/51] SHORT CIRCUIT 14
1.6.2 Submenu [50N/51N] EARTH FAULT 15
1.6.3 Submenu [46] UNBALANCE 16
1.6.4 Submenu [49] THERMAL OVERLOAD 16
1.6.5 Submenu [37] LOSS OF LOAD 16
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 2/16 MiCOM P122C

BLANK PAGE
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 3/16

1. SETTING TABLES AND SETTING SHEETS


1.1 Substation reference

Substation:
Bay designation:

1.2 Protection device data


MiCOM device type P122C
P/O number P122C-
F-number F-
Inom A~
IN,nom A~
Vaux,nom V
Communication protocol
Language

1.3 Menu OP PARAMETERS


Parameter Default Values range Setting
Reference ALST AAAA...9999
NB of inputs 2 2 Inputs or 7 Inputs
Date 01/01/94 00/00/00...31/12/99
Time 00:00:00 00:00:00...23:59:59

1.4 Menu CONFIGURATION

1.4.1 Submenu GLOBAL SETTINGS


Parameter Default Values range Setting
Line CT primary 1000 1...9999 A
Line CT sec 1 1 A or 5 A
IN/Gnd CT primary 1000 1...3000 A
IN/Gnd CT sec 1 1 A or 5 A
Phase Sequence A-B-C A-B-C or A-C-B
General starting w. IN/I2 w. IN/I2 or w/o. IN/I2
tGS 0.00 0.00...100.00 s
Nom. Frequency 50 Hz 50 Hz or 60 Hz
Password AAAA AAAA...ZZZZ
Password F3,F4 AAAA AAAA...ZZZZ
tClose pulse 0.10 0.10...5.00 s
tOpen pulse 0.10 0.10...5.00 s
Relays CMD 00000000 00000000...11111111
Function release I>Funct. Pos CB or I>Funct.
I> fct.release 0.05 0.03..0.15 In
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 4/16 MiCOM P122C

1.4.2 Submenu LOCAL INDICATION


Parameter Default Values range Setting
Default display IB Rms IA Rms
IB Rms
IC Rms
IN Rms
IA, B, C, N
Therm St.
Phase A Text 1 A / 1 / L1 / R
Phase B Text 2 B / 2 / L2 / S
Phase C Text 3 C / 3 / L3 / T
E/Gnd Text E N/E/0
Inst.self reset No Yes or No
Reset on fault Yes Yes or No
Battery alarm Yes Yes or No

1.4.3 Submenu INPUTS


Parameter Default Values range Setting
Input 1 None None Trip Circ
Input 2 None Ext reset Rst Leds
Input 3 None 52a Rst Latch
Input 4 None 52b Mod.Maint
Input 5 None CB Fail BlockTher
Input 6 None Ext 1 Chang.Grp
Input 7 None Ext 2 Group 1
Ext 3 Group 2
Ext 4 Open Ord
BlockLog1 Close Ord
BlockLog2 Reset all
Dist Trig Man.Close
C.L.S. Test Mode
Log.Sel.1 Cmd Block
Log.Sel.2 Sg/Mea.Bl
θ Reset
tExt 1 0.00 0.00...200.00 s
tExt 2 0.00 0.00...200.00 s
tExt 3 0.00 0.00...200.00 s
tExt 4 0.00 0.00...200.00 s

1.4.4 Submenu INPUT MODE


Parameter Default Values range Setting
Inputs 1=H/0=L 1111111 0000000...1111111 for 7
11 inputs
00...11 for 2 inputs
Voltage input DC AC or DC
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 5/16

1.4.5 Submenu OUTPUT RELAYS


Selection Default Values range Output relays setting
RL 7 RL 6 RL 5 RL 4 RL 3 RL 2
I> No (0) No or Yes (0/1)
tl> No (0) No or Yes (0/1)
I>> No (0) No or Yes (0/1)
tl>> No (0) No or Yes (0/1)
I>>> No (0) No or Yes (0/1)
tl>>> No (0) No or Yes (0/1)
IN> No (0) No or Yes (0/1)
tIN> No (0) No or Yes (0/1)
tIN> int. No (0) No or Yes (0/1)
IN>> No (0) No or Yes (0/1)
tIN>> No (0) No or Yes (0/1)
IN>>> No (0) No or Yes (0/1)
tIN>>> No (0) No or Yes (0/1)
tl< No (0) No or Yes (0/1)
I2> No (0) No or Yes (0/1)
tI2> No (0) No or Yes (0/1)
I2>> No (0) No or Yes (0/1)
tI2>>> No (0) No or Yes (0/1)
Therm Trip No (0) No or Yes (0/1)
Therm Alarm No (0) No or Yes (0/1)
Trip Circ. Fail No (0) No or Yes (0/1)
CB Oper NB No (0) No or Yes (0/1)
Sum A n No (0) No or Yes (0/1)
CB Open Time No (0) No or Yes (0/1)
CB Close Time No (0) No or Yes (0/1)
CB Fail No (0) No or Yes (0/1)
Close Order No (0) No or Yes (0/1)
Trip Order No (0) No or Yes (0/1)
tExt 1 No (0) No or Yes (0/1)
tExt 2 No (0) No or Yes (0/1)
tExt 3 No (0) No or Yes (0/1)
tExt 4 No (0) No or Yes (0/1)
Group 2 Active No (0) No or Yes (0/1)
Group 1 Active No (0) No or Yes (0/1)
FB F3 No (0) No or Yes (0/1)
FB F4 No (0) No or Yes (0/1)
Input 1 No (0) No or Yes (0/1)
Input 2 No (0) No or Yes (0/1)
Input 3 No (0) No or Yes (0/1)
Input 4 No (0) No or Yes (0/1)
Input 5 No (0) No or Yes (0/1)
Input 6 No (0) No or Yes (0/1)
Input 7 No (0) No or Yes (0/1)
General Start No (0) No or Yes (0/1)
tGS No (0) No or Yes (0/1)
CT Fail No (0) No or Yes (0/1)
Warning No (0) No or Yes (0/1)
Alarm No (0) No or Yes (0/1)
Starting GF No (0) No or Yes (0/1)
Trip by CB Fail No (0) No or Yes (0/1)
Phase A Start. No (0) No or Yes (0/1)
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 6/16 MiCOM P122C

Selection Default Values range Output relays setting


RL 7 RL 6 RL 5 RL 4 RL 3 RL 2
Phase B Start. No (0) No or Yes (0/1)
Phase C Start. No (0) No or Yes (0/1)
Therm Block No (0) No or Yes (0/1)
Reset Therm No (0) No or Yes (0/1)
Order 1 No (0) No or Yes (0/1)
Order 2 No (0) No or Yes (0/1)
Trip by SOTF No (0) No or Yes (0/1)

1.4.6 Submenu OUTPUT RELAY MODE


Parameter Default Values range Setting
Relay 1 NO NO or NC
Relay 2 NO NO or NC
Relay 3 NO NO or NC
Relay 4 NO NO or NC
Relay 5 NO NO or NC
Relay 6 NO NO or NC
Relay 7 NO NO or NC

1.4.7 Submenu LATCH OUTPUT RELAYS


Parameter Default Values range Setting
Latch Relay 2 No Yes or No
Latch Relay 3 No Yes or No
Latch Relay 4 No Yes or No
Latch Relay 5 No Yes or No
Latch Relay 6 No Yes or No
Latch Relay 7 No Yes or No
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 7/16

1.4.8 Submenus LED 5, LED 6, LED 7 and LED 8


Selection Default Values range LED setting
LED 5 LED 6 LED 7 LED 8
I> No Yes or No
tl> No Yes or No
l>> No Yes or No
tl>> No Yes or No
I>>> No Yes or No
tI>>> No Yes or No
IN> No Yes or No
tIN> No Yes or No
tIN> int. No Yes or No
IN>> No Yes or No
tIN>> No Yes or No
tl>>> No Yes or No
IN>>> No Yes or No
tIN>>> No Yes or No
Therm Overload No Yes or No
Θ Alarm No Yes or No
CB Fail No Yes or No
CT Failure No Yes or No
I2> No Yes or No
tI2> No Yes or No
I2>> No Yes or No
tI2>> No Yes or No
tl< No Yes or No
Phase A Start. No Yes or No
Phase B Start. No Yes or No
Phase C Start. No Yes or No
CB Superv. No Yes or No
tExt 1 No Yes or No
tExt 2 No Yes or No
tExt 3 No Yes or No
tExt 4 No Yes or No
Mode Maint. No Yes or No
Starting GF No Yes or No
General Start. No Yes or No
tGS No Yes or No
Group 1 Active No Yes or No
Group 2 Active No Yes or No
Reset Therm No Yes or No
Therm Block No Yes or No
Trip by CB Fail No Yes or No
Input 1 No Yes or No
Input 2 No Yes or No
Input 3 No Yes or No
Input 4 No Yes or No
Input 5 No Yes or No
Input 6 No Yes or No
Input 7 No Yes or No
Trip by SOTF No Yes or No
CB Close No Yes or No
CB Open No Yes or No
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 8/16 MiCOM P122C

1.4.9 Submenu COMMUNICATION


Communication protocol according to IEC 60870-5-103
Parameter Default Values range Setting
Relay Addr.(CU) 1 1...254
Communication No Yes or No
Baud Rate 19200 300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
Parity Even Without or Even or Odd
Relay Addr.(PU) 1 1...255
Connect. RS485 2 Wires 2 Wires or 4 Wires
Line idle state Light On Light On or Light Off
Spont. Sign None None
All
IEC Only
Command Block. Yes Yes or No
Signals/Measures No Yes or No
Block.
Test Mode No Yes or No
Transm.Enab. CyclDat None None
ASDU3.1
ASDU3.4
ASDU9
Prv
ASDU3.1&3.4
ASDU9&3.4
ASDU9&Prv
Delta I 0.03 0.0…0.15 In

Delta f 0.02 0.0...0.02 fn


Delta Priv.Meas 0.03 0.0...0.15
Delta t 1 0...15 min

Communication protocol according to MODBUS


Parameter Default Values range Setting
Relay Addr. 1 1...255
Communication No Yes or No
Baud Rate 19200 300
600
1200
2400
4800
9600
19200
38400
Parity Even Without or Even or Odd
Stop bits 1 1/2
Connect. RS485 2 Wires 2 Wires or 4 Wires
Line idle state Light On Light On or Light Off
Date format Private Private or IEC
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 9/16

1.4.10 Submenu RECORD SETTING


Parameter Default Values range Setting
Disturb Rec Pre Time 1.0 0.1...3.0 s
Disturb Rec Post Time 2.0 0.1...3.0 s
Dist Trig Gen. Start Yes Yes or No
Dist Trig other Inst No Yes or No
Dist Trig Trip Yes Yes or No
Time Window 5 5, 10, 15, 30 or 60 min
Sub Period 1 1...60 min
Num of Sub Per. 1 1...24
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 10/16 MiCOM P122C

1.5 Menu AUTOMAT.CTRL


1.5.1 Submenus TRIP COMMAND and LATCH TRIP ORDER
Selection Default Values range Setting
Trip Command Latch Trip Order
tI> No Yes or No
tI>> No Yes or No
tl>>> No Yes or No
tIN> No Yes or No
tIN> int. No Yes or No
tIN>> No Yes or No
tIN>>> No Yes or No
tI< No Yes or No
tI2> No Yes or No
tI2>> No Yes or No
Therm Overload No Yes or No
tExt 1 No Yes or No
tExt 2 No Yes or No
FB F3 No Yes or No
FB F4 No Yes or No
Trip by CB Fail No Yes or No
Trip by SOTF No Yes or No
CT fail No Yes or No

1.5.2 Submenu CB FAILURE


Parameter Default Values range Setting
CB Fail Funct No Yes or No
I< BF 10 2...100 %In
tBF 0.13 0.03...10.00 s
Block I>;>>;>>> BF No Yes or No
Block IN>;>>;>>>BF No Yes or No

1.5.3 Submenu SWITCH ON FAULT


Parameter Default Values range Setting
Switch on Fault Funct No Yes or No
tMan.Close 1.00 0.00...10.00 s
Trip by I> No Yes or No
Trip by I>> Yes Yes or No
Trip by I>>> No Yes or No
Trip by General Start. No Yes or No
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 11/16

1.5.4 Submenu SETTING GROUP SELECT


Parameter Default Values range Setting
Change Group mode Edge Edge
Level
Level 2
Setting Group 1 1/2
Keep Time Yes Yes or No
tKeep 0.01 0.01...65.00 s

1.5.5 Submenu COLD LOAD PICKUP


Parameter Default Values range Setting
Cold Load Pickup No Yes or No
Detect PU Input + I Log.Input
Input + I
Trans I
I> PU 10 10...200 %In
Cold Load PU I> No Yes or No
Cold Load PU I>> No Yes or No
Cold Load PU I>>> No Yes or No
Cold Load PU IN> No Yes or No
Cold Load PU IN>> No Yes or No
Cold Load PU IN>>> No Yes or No
Cold Load PU I2> No Yes or No
Cold Load PU I2>> No Yes or No
Cold Load PU Iref No Yes or No
Cold Load PU Level 100 20...500 %
Cold Load PU tCL 0.0 0.0...3600.0 s
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 12/16 MiCOM P122C

1.5.6 Submenu BLOCKING LOGIC 1


Parameter Default Values range Setting
Block.Log1 tI> No Yes or No
Block.Log1 tI>> No Yes or No
Block.Log1 tI>>> No Yes or No
Block.Log1 tIN> No Yes or No
Block.Log1 tIN> i. No Yes or No
Block.Log1 tIN>> No Yes or No
Block.Log1 tIN>>> No Yes or No
Block.Log1 tI2> No Yes or No
Block.Log1 tI2>> No Yes or No
Block.Log1 tI< No Yes or No
Block.Log1 Therm No Yes or No
Block.Log1 tExt1 No Yes or No
Block.Log1 tExt2 No Yes or No
Block.Log1 tCT No Yes or No

1.5.7 Submenu BLOCKING LOGIC 2


Parameter Default Values range Setting
Block.Log2 tI> No Yes or No
Block.Log2 tI>> No Yes or No
Block.Log2 tI>>> No Yes or No
Block.Log2 tIN> No Yes or No
Block.Log2 tIN> i. No Yes or No
Block.Log2 tIN>> No Yes or No
Block.Log2 tIN>>> No Yes or No
Block.Log2 tI2> No Yes or No
Block.Log2 tI2>> No Yes or No
Block.Log2 tI< No Yes or No
Block.Log2 Therm No Yes or No
Block.Log2 tExt1 No Yes or No
Block.Log2 tExt2 No Yes or No
Block.Log2 tCT No Yes or No

1.5.8 Submenu LOGIC SELECT 1


Parameter Default Values range Setting
Log.Sel.1 tI>> No Yes or No
Log.Sel.1 tI>>> No Yes or No
Log.Sel.1 tIN>> No Yes or No
Log.Sel.1 tIN>>> No Yes or No
tLog.Sel.1 1.00 0.00...150.00 s
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 13/16

1.5.9 Submenu LOGIC SELECT 2


Parameter Default Values range Setting
Log.Sel.2 tI>> No Yes or No
Log.Sel.2 tI>>> No Yes or No
Log.Sel.2 tIN>> No Yes or No
Log.Sel.2 tIN>>> No Yes or No
tLog.Sel.2 1.00 0.00...150.00 s

1.5.10 Submenu CB SUPERVISION


Parameter Default Values range Setting
Trip Circuit Superv No Yes or No
tSup 2.00 0.10...10.00 s
CB Opening Time No Yes or No
Superv
CB Opening Time 0.15 0.05...1.00 s
CB Closing Time Superv No Yes or No
CB Closing Time 0.15 0.05...1.00 s
CB Operation NB No Yes or No
Superv
CB Operation NB 7500 0...50000
Sum A n Superv No Yes or No
Sum A n 6 0...4000 MAn
n 1 1/2

1.5.11 Submenu CT SUPERVISION


Parameter Default Values range Setting
CT Superv No Yes or No
Mode CT Superv I2/I1 I2/I1 or Imax/Imin
Idiff> 0.30 0.25...0.50 Imax
tCT 5.00 0.00...500.00 s
I2/I1> 20 20...100 %
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 14/16 MiCOM P122C

1.6 Menus PROTECTION G1 and PROTECTION G2


1.6.1 Submenu [50/51] SHORT CIRCUIT
Parameter Default Values range Setting
Protection G1 Protection G2
I> Function No Yes or No
I> 1.00 0.10…40.00 In
I> Delay Type DMT DMT, IDMT or RI
I> Curve IEC SI IEC STI / IEC SI /
IEC VI / IEC EI /
IEC LTI / CO2 /
IEEE MI / CO8 /
IEEE VI / IEEE EI /
RC
I> Tms 1.00 0.03...4.00
I> K 1.00 0.05...10.00
tI> 1.00 0.00...150.00 s
I> Reset Type DMT DMT or IDMT
I> Rtms 0.025 0.025...3.200
I> tReset 0.00 0.00...600.00 s
I>> Function No Yes or No
I>> 4.00 0.10…40.00 In
I>> Delay Type DMT DMT, IDMT or RI
I>> Curve IEC SI IEC STI / IEC SI /
IEC VI / IEC EI /
IEC LTI / CO2 /
IEEE MI / CO8 /
IEEE VI / IEEE EI /
RC
I>> Tms 1 0.03...4.00
I>> K 1 0.05...10.00
tI>> 0.50 0.00...150.00 s
I>> Reset Type DMT DMT or IDMT
I>> Rtms 0.025 0.025...3.200
I>> tReset 0.00 0.00...600.00 s
I>>> Function No Yes or No
I>>> 4.00 0.10…40.00 In
tI>>> 0.50 0.00...150.00 s
Technical guide P122/EN ST/B11
Setting tables and setting sheets
MiCOM P122C Page 15/16

1.6.2 Submenu [50N/51N] EARTH FAULT


Parameter Default Values range Setting
Protection G1 Protection G2
IN> Function No Yes or No
IN> 1.00 0.10...40.00 INn
0.250 0.010...8.000 INn
0.025 0.002...0.800 INn
IN> Delay Type DMT DMT, IDMT, RI or
LABOR 1)
IN> Curve IEC SI for IDMT:
or 1 IEC STI / IEC SI /
IEC VI / IEC EI /
IEC LTI / CO2 /
IEEE MI / CO8 /
IEEE VI / IEEE EI /
RC
for LABOR.:
1 / 2 / 3 1)
IN> Tms 1.00 0.03...4.00
IN> K 1.00 0.05...10.00
tIN> 1.00 0.00...150.00 s
tIN> int. 1.00 0.00...150.00 s
IN> Reset Type DMT DMT or IDMT
IN> Rtms 0.025 0.025...3.200
IN> Rst Type DMT Normal Normal or Interm
IN> tReset 0.00 0.00...600.00 s
IN> tReset int. 0.00 0.00...600.00 s
IN> tProl int. 0.08 0.01...10.00 s
IN>> Function No Yes or No
IN>> 1.00 0.10...40.00 INn
0.250 0.010...8.000 INn
0.025 0.002...0.800 INn
IN>> Delay Type DMT DMT, IDMT, RI or
LABOR 1)
IN>> Curve IEC SI for IDMT:
or 1 IEC STI / IEC SI /
IEC VI / IEC EI /
IEC LTI / CO2 /
IEEE MI / CO8 /
IEEE VI / IEEE EI /
RC
for LABOR.:
1 / 2 / 3 1)
IN>> Tms 1.00 0.03...4.00
IN>> K 1.00 0.05...10.00
tIN>> 1.00 0.00...150.00 s
IN>> Reset Type DMT DMT or IDMT
IN>> Rtms 0.025 0.025...3.200
IN>> tReset 0.00 0.00...600.00 s
IN>>> Function No Yes or No
IN>>> 1.00 0.10...40.00 INn
0.250 0.010...8.000 INn
0.025 0.002...0.800 INn
tIN>>> 1.00 0.00...150.00 s
1) Available only on relay models with residual current input range: 0.01...8 INn
P122/EN ST/B11 Technical guide
Setting tables and setting sheets
Page 16/16 MiCOM P122C

1.6.3 Submenu [46] UNBALANCE


Parameter Default Values range Setting
Protection G1 Protection G2
I2> Function No Yes or No
I2> 0.30 0.10…40.00 In
I2> Delay Type DMT DMT, IDMT or RI
I2> Curve IEC SI IEC STI / IEC SI /
IEC VI / IEC EI /
IEC LTI / CO2 /
IEEE MI / CO8 /
IEEE VI / IEEE EI
I2> Tms 1.00 0.03...4.00
I2> K 1.00 0.05...10.00
tI2> 4.00 0.00...150.00 s
I2> Reset Type DMT DMT or IDMT
I2> Rtms 0.025 0.025...3.200
I2> tReset 0.00 0.00...600.00 s
I2>> Function No Yes or No
I2>> 0.50 0.10…40.00 In
tI2>> 1.00 0.00...150.00 s

1.6.4 Submenu [49] THERMAL OVERLOAD


Parameter Default Values range Setting
Protection G1 Protection G2
Thermal Overload No Yes or No
Funct.
Iref 1.00 0.10…3.20 In
Te 20 1...200 min
K 1.15 1.00...1.50
θ Trip 100 50...200 %
θ Alarm No Yes or No
θ Alarm 80 50...200 %

1.6.5 Submenu [37] LOSS OF LOAD


Parameter Default Values range Setting

Protection G1 Protection G2
I< Function No Yes or No
I< 0.30 0.05…1.00 In
tI< 20.00 0.00...150.00 s