You are on page 1of 20

DENKO THILAWA OIL STORAGE

TANK TERMINAL PROJECT


TVC Job No. VF-003
SPECIFICATION FOR HYDROCARBON
VAPOR, HYDROCARBON LIQUID AND
FLAME DETECTOR

25-Jan-19 Rev.3 Doc. No.: VF003-IN-SPE-0019 Sheet 2 of 20

Revision History Sheet

Rev. Date Description


0 9-Oct-18 For Approval
1 21-Nov-18 For Approval
2 26-Dec-18 For Approval
3 25-Jan-19 For Construction
INDEX LIST
HYDROCARBON VAPOR, HYDROCARBON LIQUID & FLAME DETECTOR

Item
Tag No. Area Type Page No. Rev. No Remark
No.

1 300-AL-005 Oily Water System Hydrocarbon Vapor Detector 4 3

2 300-AL-006 Oily Water System Hydrocarbon Vapor Detector 5 3

3 300-AL-008 Oily Water System Hydrocarbon Vapor Detector 6 3

4 300-AL-010 Oily Water System Hydrocarbon Vapor Detector 7 3

5 300-AL-012 Oily Water System Hydrocarbon Vapor Detector 8 3

6 300-AL-016 Oily Water System Hydrocarbon Vapor Detector 9 3

Oily Water System At


7 400-AL-001 Hydrocarbon Vapor Detector 10 3
Jetty
Oily Water System At
8 400-AL-003 Hydrocarbon Vapor Detector 11 3
Jetty

9 300-AS-003 Oily Water System Hydrocarbon Liquid Detector 12 3

10 300-AS-013 Oily Water System Hydrocarbon Liquid Detector 13 3

11 300-AS-014 Oily Water System Hydrocarbon Liquid Detector 14 3

12 300-AT-015 Oily Water System Oil In Water Hydrocarbon Liquid Monitor 15 3

Oily Water System At


13 400-AS-002 Hydrocarbon Liquid Detector 16 3
Jetty
Oily Water System At
14 400-AS-004 Hydrocarbon Liquid Detector 17 3
Jetty

15 300-AS-017 Truck Loading Flame Detector 18 3

16 300-AS-018 Truck Loading Flame Detector 19 3

17 300-AS-019 Truck Loading Flame Detector 20 3

Sheet 3 off 20
1 Tag Number Quantity 300-AL-005 1 set

2 Service Detect Hydrocarbon Vapor At Pump Pit Diesel / Gasoline Pumps


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Pump Station

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 4

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 4 of 20
1 Tag Number Quantity 300-AL-006 1 set

2 Service Detect Hydrocarbon Vapor At Pump Pit Diesel / Gasoline Pumps


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Pump Station

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 4

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 5 of 20
1 Tag Number Quantity 300-AL-008 1 set

2 Service Detect Hydrocarbon Vapor At T-203A~B Sump Pit


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Tank Farm

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 4

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 6 of 20
1 Tag Number Quantity 300-AL-010 1 set

2 Service Detect Hydrocarbon Vapor At T-202A~B Sump Pit


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Tank Farm

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 4

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 7 of 20
1 Tag Number Quantity 300-AL-012 1 set

2 Service Detect Hydrocarbon Vapor At T-201A~B Sump Pit


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Tank Farm

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 3

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 8 of 20
1 Tag Number Quantity 300-AL-016 1 set

2 Service Detect Hydrocarbon Vapor At A-301 Oil Separator


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 1 Oil Separator

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 2

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 9 of 20
1 Tag Number Quantity 400-AL-001 1 set

2 Service Detect Hydrocarbon Vapor At Sump Berth 1


GENERAL
3 P&ID No. VF003-PR-PID-400001

4 Area Classification Location Zone 2 Jetty

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 2

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Calibration Gas B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 10 of 20
1 Tag Number Quantity 400-AL-003 1 set

2 Service Detect Hydrocarbon Vapor At Sump Berth 2


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Jetty

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 2

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocarbon Vapor


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) B.V

10 Ambient Conditions Tropical


0 0
11 Design Temperature ( C) 0-65 C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection IR Point Type

16 Sensor Material B.V

17 Sensor Life 3 to 5 years


SENSOR
18 Accuracy ±3% At <50% LEL, ±5% At > 50% LEL

19 Measuring Range 0-100% LEL Hydrocacbon

20 Response Time T90 < 10 S

21 Repeatability ±2% of LEL

22 Sensor Housing Aluminium Coating

23 Interfering gases -

24 Manufacturer B.V

25 Model B.V

26 Type Electronic

27 Output 4-20mA with HART

28 Calibration Range 0-100%


TRANSMITTER
29 High Alarm Setpoint High High Alarm Setpoint 20% LEL 50% LEL

30 Power Supply 24VDC

31 Load B.V

32 Detector Fault Signal < 1mA

33 Inhibit (cal.) signal <3 mA

34 Over range signal >21mA

35 Enclosure Material Aluminium Coating

36 Cable Entry 1/2" NPT(F)

37 Cable Type 3 wires


HOUSING
38 Ingress Protection (transmitter) IP66
39 Area Classification Zone 2

40 Mounting Style Mounting with Sensor

41 Electrical Protection Ex d IIA T4

42 Calibration Kit Yes (Gas for commissioning)

43 LCD Display Yes


OPTIONS
44 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

45 Sunshade Yes

46 Manufacturer B.V

47 Model B.V
PURCHASE
48 Purchase Order No. B.V

49 Serial Number B.V

50 Drawing No.

ADDITIONAL 51 Certification CO, CQ, Inspection Report


FEATURES
52 Crippled Mode Detection

53 Others Designed as SIL2 at least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 11 of 20
1 Tag Number Quantity 300-AS-003 1 set

2 Service Detect Hydrocarbon Liquid At Pump Pit Gasoline Pumps


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Pump Station

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 4

6 Fluid State Liquid

7 Fluid Type Oil / Hydrocarbon Of Gasoline 92/95

8 Detection Oil / Hydrocarbon On Water


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) 650 x 600 x 700

10 Ambient Conditions Tropical


0
11 Design Temperature ( C) 0 - 65 0C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Type Float type

16 Method Of Detection Resistive Measuring Sensors (Conductivity)

17 Sensor Protection Class IP66 As Minimum


SENSOR
18 Sensor Material 316 SS

19 Minimum Detectable Oil layer Thickness 2 mm

20 Measuring Range 0-25 mm

21 Response Time < 1 Minute

22 Wetted Parts Waterproof PVC / SS

23 Weight B.V

24 Manufacturer B.V

25 Model B.V

26 Type Electronic
TRANSMITTER
27 Output 1 SPDT Contact Output

28 Alarm Setpoint 3 mm

29 Power Supply 230VAC External Power

30 Load B.V

31 Enclosure Material SS

32 Cable Entry 2 x 1/2" NPT(F)


33 Ingress Protection (transmitter) IP65 As Minimum
HOUSING
34 Area Classification Zone 2

35 Mounting Bracket Mounted

36 Electrical Protection Ex d IIA T4

37 Integral Cable 15 m Supplied With Sensor

38 LCD Display Yes


OPTIONS
39 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

40 Sunshade Yes

41 Manufacturer B.V

42 Model B.V
PURCHASE
43 Purchase Order No. B.V

44 Serial Number B.V

45 Drawing No.

ADDITIONAL 46 Certification CO, CQ, Inspection Report


FEATURES
47 Crippled Mode Detection

48 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Float guide shall be provided by vendor if needed for sensor balance
5. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
6. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh HYDROCARBON VAPOR, HYDROCARBON


LIQUID & FLAME DETECTOR
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By 12/24/2018 Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 12 of 20
1 Tag Number Quantity 300-AS-013 1 set

2 Service Detect Hydrocarbon Liquid At T-102A~B Sump Pit


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Tank Farm

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 3

6 Fluid State Liquid

7 Fluid Type Oil / Hydrocarbon Of Gasoline 92/95

8 Detection Oil / Hydrocarbon On Water


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) 650 x 600 x 700

10 Ambient Conditions Tropical


0
11 Design Temperature ( C) 0 - 65 0C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Type Float type

16 Method Of Detection Resistive Measuring Sensors (Conductivity)

17 Sensor Protection Class IP66 As Minimum


SENSOR
18 Sensor Material 316 SS

19 Minimum Detectable Oil layer Thickness 2 mm

20 Measuring Range 0-25 mm

21 Response Time < 1 Minute

22 Wetted Parts Waterproof PVC / SS

23 Weight B.V

24 Manufacturer B.V

25 Model B.V

26 Type Electronic
TRANSMITTER
27 Output 1 SPDT Contact Output

28 Alarm Setpoint 3 mm

29 Power Supply 230VAC External Power

30 Load B.V

31 Enclosure Material SS

32 Cable Entry 2 x 1/2" NPT(F)


33 Ingress Protection (transmitter) IP65 As Minimum
HOUSING
34 Area Classification Zone 2

35 Mounting Bracket Mounted

36 Electrical Protection Ex d IIA T4

37 Integral Cable 15 m Supplied With Sensor

38 LCD Display Yes


OPTIONS
39 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

40 Sunshade Yes

41 Manufacturer B.V

42 Model B.V
PURCHASE
43 Purchase Order No. B.V

44 Serial Number B.V

45 Drawing No.

ADDITIONAL 46 Certification CO, CQ, Inspection Report


FEATURES
47 Crippled Mode Detection

48 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Float guide shall be provided by vendor if needed for sensor balance
5. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
6. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh HYDROCARBON VAPOR, HYDROCARBON


LIQUID & FLAME DETECTOR
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 13 of 20
1 Tag Number Quantity 300-AS-014 1 set

2 Service Detect Hydrocarbon Liquid At T-101A~B Sump Pit


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Tank Farm

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 3

6 Fluid State Liquid

7 Fluid Type Oil / Hydrocarbon Of Gasoline 92/95

8 Detection Oil / Hydrocarbon On Water


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) 650 x 600 x 700

10 Ambient Conditions Tropical


0
11 Design Temperature ( C) 0 - 65 0C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Type Float type

16 Method Of Detection Resistive Measuring Sensors (Conductivity)

17 Sensor Protection Class IP66 As Minimum


SENSOR
18 Sensor Material 316 SS

19 Minimum Detectable Oil layer Thickness 2 mm

20 Measuring Range 0-25 mm

21 Response Time < 1 Minute

22 Wetted Parts Waterproof PVC / SS

23 Weight B.V

24 Manufacturer B.V

25 Model B.V

26 Type Electronic
TRANSMITTER
27 Output 1 SPDT Contact Output

28 Alarm Setpoint 3 mm

29 Power Supply 230VAC External Power

30 Load B.V

31 Enclosure Material SS

32 Cable Entry 2 x 1/2" NPT(F)


33 Ingress Protection (transmitter) IP65 As Minimum
HOUSING
34 Area Classification Zone 2

35 Mounting Bracket Mounted

36 Electrical Protection Ex d IIA T4

37 Integral Cable 15 m Supplied With Sensor

38 LCD Display Yes


OPTIONS
39 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

40 Sunshade Yes

41 Manufacturer B.V

42 Model B.V
PURCHASE
43 Purchase Order No. B.V

44 Serial Number B.V

45 Drawing No.

ADDITIONAL 46 Certification CO, CQ, Inspection Report


FEATURES
47 Crippled Mode Detection

48 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Float guide shall be provided by vendor if needed for sensor balance
5. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
6. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh HYDROCARBON VAPOR, HYDROCARBON


LIQUID & FLAME DETECTOR
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 14 of 20
1 Tag Number Quantity 300-AT-015 1 set

2 Service Detect Hydrocarbon Liquid At A-301 Oil Separator


GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 1 Oil Separator

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 2

6 Fluid State Liquid

7 Fluid Type Oil / Hydrocarbon Of Gasoline 92/95

8 Detection Oil / Hydrocarbon In Water


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) 1000 x 2300 x 3300

10 Ambient Conditions Tropical


0
11 Design Temperature ( C) 0 - 55 0C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Method Of Detection UV Fluorescence

16 Limit Of Detection <1ppm

17 Accuracy ±0.3 ppm


SENSOR
18 Range 0-15 ppm

19 Response Time T90 < 10 S

20 Calibration Factory calibration with UV fluorescence calibration standard

21 Sensor Material SS

22 Weight B.V

23 Manufacturer B.V

24 Model B.V

25 Type Electronic

26 Output 4-20mA with HART

27 Claibration Range 0-15 ppm

28 Alarm Setpoint 12 ppm

29 Power Supply 24VDC

30 Load B.V

31 Detector Fault Signal < 1mA

32 Inhibit (cal.) signal <3 mA

33 Over range signal >21mA

34 Power Supply 230 VAC External Power

35 Load B.V

36 Enclosure Material SS

37 Cable Entry 2 x 1/2" NPT(F)

38 Cable Type 2 Wire


HOUSING
39 Ingress Protection (transmitter) IP65 As Minimum
40 Area Classification Zone 2

41 Mounting Bracket Mounted

42 Electrical Protection Ex d IIA T4

43 Integral Cable 15 m Supplied With Sensor

44 LCD Display Display Unit Yes ppm


OPTIONS
45 Assembly bolting / mounting bracket 2" Mounting Bracket

46 Sunshade Yes

47 Manufacturer B.V

48 Model B.V
PURCHASE
49 Purchase Order No. B.V

50 Serial Number B.V

51 Drawing No.

ADDITIONAL 52 Certification CO, CQ, Inspection Report


FEATURES
53 Crippled Mode Detection

54 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 15 of 20
1 Tag Number Quantity 400-AS-002 1 set

2 Service Detect Hydrocarbon Liquid At Sump Berth 1


GENERAL
3 P&ID No. VF003-PR-PID-400001

4 Area Classification Location Zone 2 Jetty

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 2

6 Fluid State Liquid

7 Fluid Type Oil / Hydrocarbon Of Gasoline 92/95

8 Detection Oil / Hydrocarbon On Water


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) 1000 x 1000 x 1000

10 Ambient Conditions Tropical


0
11 Design Temperature ( C) 0 - 65 0C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Type Float Type

16 Method Of Detection Resistive Measuring Sensors (Conductivity)

17 Sensor Protection Class IP66 As Minimum


SENSOR
18 Sensor Material 316 SS

19 Minimum Detectable Oil layer Thickness 2 mm

20 Measuring Range 0-25 mm

21 Response Time < 1 Minute

22 Wetted Parts Waterproof PVC / SS

23 Weight B.V

24 Manufacturer B.V

25 Model B.V

26 Type Electronic
TRANSMITTER
27 Output 1 SPDT Contact Output

28 Alarm Setpoint 3 mm

29 Power Supply 230VAC External Power

30 Load B.V

31 Enclosure Material SS

32 Cable Entry 2 x 1/2" NPT(F)


33 Ingress Protection (transmitter) IP65 As Minimum
HOUSING
34 Area Classification Zone 2

35 Mounting Bracket Mounted

36 Electrical Protection Ex d IIA T4

37 Integral Cable 15 m Supplied With Sensor

38 LCD Display Yes


OPTIONS
39 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

40 Sunshade Yes

41 Manufacturer B.V

42 Model B.V
PURCHASE
43 Purchase Order No. B.V

44 Serial Number B.V

45 Drawing No.

ADDITIONAL 46 Certification CO, CQ, Inspection Report


FEATURES
47 Crippled Mode Detection

48 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified plug in accordance to the area classification
5. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification

HYDROCARBON VAPOR, HYDROCARBON


3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 16 of 20
1 Tag Number Quantity 400-AS-004 1 set

2 Service Detect Hydrocarbon Liquid At Sump Berth 2


GENERAL
3 P&ID No. VF003-PR-PID-400001

4 Area Classification Location Zone 2 Jetty

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 2

6 Fluid State Liquid

7 Fluid Type Oil / Hydrocarbon Of Gasoline 92/95

8 Detection Oil / Hydrocarbon On Water


SERVICE CONDITION
9 Sump pit size (L:mm x W:mm x H:mm) 1000 x 1000 x 1000

10 Ambient Conditions Tropical


0
11 Design Temperature ( C) 0 - 65 0C

12 Humidity (%RH) 0% - 95% RH

13 Manufacturer B.V

14 Model B.V

15 Type Float Type

16 Method Of Detection Resistive Measuring Sensors (Conductivity)

17 Sensor Protection Class IP66 As Minimum


SENSOR
18 Sensor Material 316 SS

19 Minimum Detectable Oil layer Thickness 2 mm

20 Measuring Range 0-25 mm

21 Response Time < 1 Minute

22 Wetted Parts Waterproof PVC / SS

23 Weight B.V

24 Manufacturer B.V

25 Model B.V

26 Type Electronic
TRANSMITTER
27 Output 1 SPDT Contact Output

28 Alarm Setpoint 3 mm

29 Power Supply 230VAC External Power

30 Load B.V

31 Enclosure Material SS

32 Cable Entry 1/2" NPT(F)


33 Ingress Protection (transmitter) IP65 As Minimum
HOUSING
34 Area Classification Zone 2

35 Mounting Bracket Mounted

36 Electrical Protection Ex d IIA T4

37 Integral Cable 15 m Supplied With Sensor

38 LCD Display Yes


OPTIONS
39 Assembly bolting / mounting bracket 2" Pole Mounting Bracket

40 Sunshade Yes

41 Manufacturer B.V

42 Model B.V
PURCHASE
43 Purchase Order No. B.V

44 Serial Number B.V

45 Drawing No.

ADDITIONAL 46 Certification CO, CQ, Inspection Report


FEATURES
47 Crippled Mode Detection

48 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Float guide shall be provided by vendor if needed for sensor balance
5. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
6. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh HYDROCARBON VAPOR, HYDROCARBON


LIQUID & FLAME DETECTOR
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 17 of 20
1 Tag Number Quantity 300-AS-017 1 set

2 Service Detect & Respond To The Presence Of A Flame Or Fire At Truck Loading
GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Truck Loading

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 5

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocacbon Flame


SERVICE CONDITION
9 Ambient Conditions Tropical
0
10 Design Temperature ( C) 0 - 65 0C

11 Humidity (%RH) 5% - 95% RH

12 Manufacturer B.V

13 Model B.V

14 Method Of Detection Multi-Spectrum IR (IR3)

15 Sensor Life 3 to 5 years


SENSOR
16 Sensor Housing SS 316

17 Detection Range / Sensitivity 45 m As Minimum For Gasoline Or Diesel Fires At 1ft2 (0.1 m2) Pan Fire

18 Response Time ≤ 5s At 15m Gasoline Or Diesel Fires At 1ft2 (0.1 m2)

19 Field of View Horizontal: 90°, Vertical: 90° With 50% Off Axis Sensitivity As Minimum

20 False Alarm Immunity Extremely High

21 Manufacturer B.V

22 Model B.V

23 Type Electronic

24 Self-Diagnostics Yes: Continuous Optical Path Monitoring

25 Output 4-20 mA (Stepped) Sinking


TRANSMITTER
26 Warning Setpoint Alarm Setpoint 16mA 20mA

27 Power Supply 24VDC

28 Detector Fault Signal < 1mA

29 Inhibit (cal.) signal <3 mA

30 Over range signal >21mA

31 Load B.V

32 Enclosure Material SS 316

33 Cable Entry 1/2" NPT(F)

34 Cable Type 3 wires


HOUSING
35 Ingress Protection (transmitter) IP65 As Minimum
36 Area Classification Zone 2

37 Mounting Bracket Mounted

38 Electrical Protection Ex d IIA T4

39 Calibration Kit Long range IR3 Fire Simulator

40 LCD Display Yes


OPTIONS
41 Assembly bolting / mounting bracket Yes (Tilt Mounting Bracket)

42 Hart Protocol Yes (HART® Communications on The 4–20 mA Analog Current)

43 Weather Cover -

44 Manufacturer B.V

45 Model B.V
PURCHASE
46 Purchase Order No. B.V

47 Serial Number B.V

48 Drawing No.

ADDITIONAL 49 Certification CO, CQ, Inspection Report


FEATURES
50 Crippled Mode Detection

51 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 18 of 20
1 Tag Number Quantity 300-AS-018 1 set

2 Service Detect & Respond To The Presence Of A Flame Or Fire At Truck Loading
GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Truck Loading

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 5

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocacbon Flame


SERVICE CONDITION
9 Ambient Conditions Tropical
0
10 Design Temperature ( C) 0 - 65 0C

11 Humidity (%RH) 5% - 95% RH

12 Manufacturer B.V

13 Model B.V

14 Method Of Detection Multi-Spectrum IR (IR3)

15 Sensor Life 3 to 5 years


SENSOR
16 Sensor Housing SS 316

17 Detection Range / Sensitivity 45 m As Minimum For Gasoline Or Diesel Fires At 1ft2 (0.1 m2) Pan Fire

18 Response Time ≤ 5s At 15m Gasoline Or Diesel Fires At 1ft2 (0.1 m2)

19 Field of View Horizontal: 90°, Vertical: 90° With 50% Off Axis Sensitivity As Minimum

20 False Alarm Immunity Extremely High

21 Manufacturer B.V

22 Model B.V

23 Type Electronic

24 Self-Diagnostics Yes: Continuous Optical Path Monitoring

25 Output 4-20 mA (Stepped) Sinking


TRANSMITTER
26 Warning Setpoint Alarm Setpoint 16mA 20mA

27 Power Supply 24VDC

28 Detector Fault Signal < 1mA

29 Inhibit (cal.) signal <3 mA

30 Over range signal >21mA

31 Load B.V

32 Enclosure Material SS 316

33 Cable Entry 1/2" NPT(F)

34 Cable Type 3 wires


HOUSING
35 Ingress Protection (transmitter) IP65 As Minimum
36 Area Classification Zone 2

37 Mounting Bracket Mounted

38 Electrical Protection Ex d IIA T4

39 Calibration Kit Long range IR3 Fire Simulator

40 LCD Display Yes


OPTIONS
41 Assembly bolting / mounting bracket Yes (Tilt Mounting Bracket)

42 Hart Protocol Yes (HART® Communications on The 4–20 mA Analog Current)

43 Weather Cover -

44 Manufacturer B.V

45 Model B.V
PURCHASE
46 Purchase Order No. B.V

47 Serial Number B.V

48 Drawing No.

ADDITIONAL 49 Certification CO, CQ, Inspection Report


FEATURES
50 Crippled Mode Detection

51 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 19 of 20
1 Tag Number Quantity 300-AS-019 1 set

2 Service Detect & Respond To The Presence Of A Flame Or Fire At Truck Loading
GENERAL
3 P&ID No. VF003-PR-PID-300001

4 Area Classification Location Zone 2 Truck Loading

5 Gas Detector Layout No. VF003-IN-WLT-0002 Sheet 5

6 Fluid State Gas

7 Fluid Type Hydrocarbon

8 Detection Hydrocacbon Flame


SERVICE CONDITION
9 Ambient Conditions Tropical
0
10 Design Temperature ( C) 0 - 65 0C

11 Humidity (%RH) 5% - 95% RH

12 Manufacturer B.V

13 Model B.V

14 Method Of Detection Multi-Spectrum IR (IR3)

15 Sensor Life 3 to 5 years


SENSOR
16 Sensor Housing SS 316

17 Detection Range / Sensitivity 45 m As Minimum For Gasoline Or Diesel Fires At 1ft2 (0.1 m2) Pan Fire

18 Response Time ≤ 5s At 15m Gasoline Or Diesel Fires At 1ft2 (0.1 m2)

19 Field of View Horizontal: 90°, Vertical: 90° With 50% Off Axis Sensitivity As Minimum

20 False Alarm Immunity Extremely High

21 Manufacturer B.V

22 Model B.V

23 Type Electronic

24 Self-Diagnostics Yes: Continuous Optical Path Monitoring

25 Output 4-20 mA (Stepped) Sinking


TRANSMITTER
26 Warning Setpoint Alarm Setpoint 16mA 20mA

27 Power Supply 24VDC

28 Detector Fault Signal < 1mA

29 Inhibit (cal.) signal <3 mA

30 Over range signal >21mA

31 Load B.V

32 Enclosure Material SS 316

33 Cable Entry 1/2" NPT(F)

34 Cable Type 3 wires


HOUSING
35 Ingress Protection (transmitter) IP65 As Minimum
36 Area Classification Zone 2

37 Mounting Bracket Mounted

38 Electrical Protection Ex d IIA T4

39 Calibration Kit Long range IR3 Fire Simulator

40 LCD Display Yes


OPTIONS
41 Assembly bolting / mounting bracket Yes (Tilt Mounting Bracket)

42 Hart Protocol Yes (HART® Communications on The 4–20 mA Analog Current)

43 Weather Cover -

44 Manufacturer B.V

45 Model B.V
PURCHASE
46 Purchase Order No. B.V

47 Serial Number B.V

48 Drawing No.

ADDITIONAL 49 Certification CO, CQ, Inspection Report


FEATURES
50 Crippled Mode Detection

51 Others Designed As SIL2 At Least


Notes: 1. SS Tag name plate to be stamped with tag No. manufacture's name, Model No.shall be provided on the instrument.
2. Mfr.Std = Manufacturer Standard
3. SS= Stainless Steel
4. Spare cable entries shall be provided with certified metal dummy plug in accordance to the area classification
5. B.V. = By Vendor

3 P.T.Phuoc 25-Jan-19 For Construction D.S.Nien/D.T.Quan T.H.N.Linh


HYDROCARBON VAPOR, HYDROCARBON
2 P.T.Phuoc 26-Dec-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh LIQUID & FLAME DETECTOR
1 P.T.Phuoc 21-Nov-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
0 P.T.Phuoc 9-Oct-18 For Approval D.S.Nien/D.T.Quan T.H.N.Linh
No. Made By Date Description Check Appr. Code: Doc. No: VF003-IN-SPE-0019 Sheet: 20 of 20