You are on page 1of 2

HISAC Ultima - Test Report

HEADER : Test Date Time: 28-07-2018 04:40:22

Substation DHALKEBAR Breaker ID 201 Gas Pressure 6.1


Bay 201-Bph Breaker Type 3AP1FI Air Pressure NIL
Operator HITECH Serial Number 17132 Oil Pressure NIL
Manufacturer Siemens Voltage (kV) 220

SETTINGS :
Trigger Option DCRM Sampling Speed (kC) 10 Reistance Range mW 4000
Plot Length(ms) 500 Delay tco (ms) 300 Delay toc (ms) 120
Current Range C1(A) 25 Current Range C2(A) 25 Current Range C3(A) 0
Current Range C4(A) 0 Current Range C5(A) 0 Current Range C6(A) 0
Velocity Enabled PIR Disabled Auxiliary Disabled
Analog Channels Enabled

T1 (mm) 141.7 T2 (mm) 0 T3 (mm) 0


Velocity Points :
Close1 0% Open1 10 % DefClose 10 ms
Close2 10 % Open2 0% DefOpen 10 ms

GRAPH :

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 14/08/2018 Page 1 of 2
HISAC Ultima - Test Report

Travel Results :

TR1 TR2 TR3 TR4 TR5 TR6

Mechanism Travel (mm) 141.75 0 0 0 0 0


Contact Travel (mm) 141.75 0 0 0 0 0
Close - Datum Velocity (m/s) 0.43 0 0 0 0 0
Open - Datum Velocity (m/s) 0.44 0 0 0 0 0
Close - Over Travel (mm) 0.59 0 0 0 0 0
Open - Rebound (mm) 2.93 0 0 0 0 0

Coil Current Results:


Coil Current (A) C1 C2 C3 C4 C5 C6
4.609 7.584 0 0 0 0

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India. 14/08/2018 Page 2 of 2