Dear Sir,
With reference to the above subject and Tender reference, we would like to submit the
clarification / question related this tender process. Detail clarification / question as per
the attached table
M. Oskar Indarto
Director
Tender no. & Ref. : 10003726R1 & Piping Installation from Grissik Metering Station to PGN/COPI
Ref. 1 : Exhibit C Contractor verification work shall include but not limited to:
– Scope of Work, 2. Verification of DED data:
Point 02-01, a. Final structural frame fender model and calculation
Engineering Clarification:
Endorsement Frame fender AFC drawing (B-85001-MA-CC0-DDD-JY-00-0001) has been received in
Company Supplied Data (Ref.2). However, the latest STAAD PRO analysis file and
Ref. 2 : Exhibit G calculation is needed for future verification.
- Company
Supplied Data.
b. Connection of cone/rubber fender to frame fender detail design
Tender no. & Ref. : 10003726R1 & Piping Installation from Grissik Metering Station to PGN/COPI
Clarification:
No detail drawing and calculation found for this specific item. Company to advise.
e. Tie Beam Rebar development length calculation for Fixed Head Type Connection
Clarification:
Tie beam rebar calculation that is available on document "Bore Pile Verification using
Plaxis 3D" (B-84555-MA-SS0-DRT-JY-00-0001) page 164 stated that some of tie beam
bars are inadequate. Hence, strengthening of tie beams may be needed. Therefore,
refer to Ref.1 page 49, this may cover as an additional work.
Ref. 1 : MOM
Pre-Bid
Clarification:
Company may subject to additional work regarding tie-rods, mooring bollards, or sheet
piles that may need to be replaced.
Tender no. & Ref. : 10003726R1 & Piping Installation from Grissik Metering Station to PGN/COPI
Ref.3
Ref. 1 :
Constructability
Report Matak
Jetty Repair
Project
(B-84555-MA-
YY4-DRT-JY-00-
0001 ), page 26
Ref. 2 : Exhibit C
– Scope of Work,
page 46
Clarification:
On Ref.1, looks like no backfill on the sacrificial stagger location. However, Ref.2 stated
that the excavated area may be backfilled and compacted. Company to confirm.
Tender no. & Ref. : 10003726R1 & Piping Installation from Grissik Metering Station to PGN/COPI
No details found on the arrangement or standard specification for the sacrificial stagger.
Company to confirm.