You are on page 1of 4

Part of GE

Security
INTELLIGENT INPUT/OUTPUT DEVICES
Compatibility Î | QS4/QS1 | EST2 | EST3

Input Modules
Models SIGA-MM1 & SIGA-WTM

Features
„ Monitor and waterflow/tamper applications
Includes Alarm with delayed latching (retard) for waterflow
applications, Supervisory, and Monitor.
„ Non-volatile memory
Permanently stores serial number, type of device, and jobnumber.
Automatically updates historic information including hours of opera-
tion, last maintenance date, number of alarms and troubles, and time
and date of last alarm. Patented

„ Automatic device mapping


Each module transmits wiring information to the loop controller Description
regarding its location with respect to other devices on the circuit.
The SIGA-MM1 Monitor Module and SIGA-WTM Waterflow/Tamper
„ Electronic addressing Module are part of EST’s Signature Series system. They are intelligent
Permanently stores programmable address; there are no switches or analog addressable devices used to connect one or two Class B
dials to set. Addresses are downloaded from a PC, or the SIGA-PRO normally-open Alarm, Supervisory, or Monitor type dry contact Initiating
Signature Program/Service Tool. Device Circuits (IDC). The function of the SIGA-MM1 and SIGA-WTM is
determined by the factory loaded “personality code”.
„ Intelligent module c/w integral microprocessor
All decisions are made at the module allowing lower The input modules gather analog information from the initiating devices
communication speed while substantially improving control connected to them and convert it into digital signals. The module’s on-
panel response time. Less sensitive to line noise and circuit wiring board microprocessor analyzes the signal and decides whether or not
properties; twisted or shielded wire is not required. to input an alarm.

„ Ground fault detection by address The microprocessor in each module provides four additional benefits -
Detects ground faults right down to the device level. Self-diagnostics and History Log, Automatic Device Mapping, Stand-
alone Operation and Fast, Stable Communication.
„ Stand-alone operation
The module makes decisions and inputs an alarm from initiating Self-diagnostics and History Log - Each Signature Series module
devices connected to it even if the loop controller’s polling interroga- constantly runs self-checks to provide important maintenance informa-
tion stops. tion. The results of the self-check are automatically updated and
permanently stored in the module’s non-volatile memory. This informa-
„ Diagnostic LEDs tion is accessible for review any time at the control panel, PC, or by
Status LEDs are visible only when face plate is removed; flashing using the SIGA-PRO Signature Program/Service Tool.
GREEN shows normal polling; flashing RED shows alarm/active state.
The information stored in the module’s memory includes:
„ Designed for high ambient temperature operation - module serial number, address, and module type
Install in ambient temperatures up to 120oF (49oC).
- date of manufacture, hours of operation, and last maintenance date²
„ Designed to ISO 9001 standards - number of recorded troubles and alarms²
Manufactured to strict international quality standards for highest - time and date of last alarm¹
reliability. - most recent trouble code logged by the module — 24 possible
trouble codes may be used to diagnose faults

¹ EST3 V.2 only.


² Retrievable with SIGA-PRO programming tool.

www.gesecurity.com
2 0 1 C I T Y C E N T R E D R I V E S U I T E 500, M I S S I S S AU G A , O NTARIO, CANADA L5B 2T4
P H O N E : (001) 9 0 5 -2 7 0 - 1 7 1 1 • F A X : (001) 9 0 5 -2 7 0 - 9 5 5 3
imagination at work U.S. SALES: BRADENTON, FL; PHONE 888-378-2329; FAX 866-503-3996
CANADA SALES: OWEN SOUND, ON; PHONE 519-376-2430; FAX 519-376-7258
Literature Sheet #85001-0297 Issue 5
Not to be used for installation purposes. Page 1 of 4
NOT TO BE USED FOR INSTALL ATION PURP OSES .

Automatic Device Mapping - The loop controller learns where each Installation
device’s serial number address is installed relative to other devices on
the circuit. The loop controller keeps a map of the Signature Series The SIGA-MM1 and SIGA-WTM modules mount to North American 2-1/2
devices connected to it. inch (64 mm) deep one-gang boxes and 1-1/2 inch (38 mm) deep 4 inch
square boxes with one-gang covers and SIGA-MP mounting plates. The
The Signature Series Data Entry Program also uses the mapping terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire
feature. With interactive menus and graphic support, the wired circuits size.
between each device can be examined. Layout or “as-built” drawing
information showing wire branches (T-taps), device types and their GE Security recommends that this module be installed according to
address are stored on disk for printing hard copy. This takes the latest recognized edition of national and local fire alarm codes.
mystery out of the installation. The preparation of as-built drawings is Electronic Addressing - The loop controller electronically addresses
fast and efficient. each module, saving valuable time during system commissioning.
Device mapping allows the Signature loop controller to discover: Setting complicated switches or dials is not required. Each module has
- unexpected additional device addresses its own unique serial number stored in its on-board memory. The loop
- missing device addresses controller identifies each device on the loop and assigns a “soft”
address to each serial number. If desired, the modules can be ad-
- changes to the wiring in the circuit.
dressed using the SIGA-PRO Signature Program/Service Tool.
Stand-alone Operation - A decentralized alarm decision by the module
Personality codes are assigned by the factory. No user configuration is
is guaranteed. On-board intelligence permits the module to operate in
required for these modules.
stand-alone mode. If loop controller CPU communications fail for more
than four seconds, all devices on that circuit go into stand-alone mode.
The circuit acts like a conventional alarm receiving circuit. Each module
on the loop continues to collect and analyze information from its slave
device and will alarm should their slave device activate.
Compatible electrical box
Fast Stable Communication - Built-in intelligence means less informa-
tion needs to be sent between the module and the loop controller.
Other than regular supervisory polling response, the module only
needs to communicate with the loop controller when it has something
new to report. This provides very fast control panel response time and
allows a lower baud rate (speed) to be used for communication on the
circuit. The lower baud rate offers several advantages including: Wall plate, white
- less sensitivity to circuit wire characteristics (1-gang)
- less sensitivity to noise glitches on the cable
- less emitted noise from the analog wiring
- twisted or shielded wiring is not required.
Diagnostic LEDs - Twin LEDs provide visual indication of normal and
alarm/active conditions. They are visible only when the front plate is
removed. A flashing GREEN LED shows normal system polling from the
loop controller. A flashing RED LED means the module is in alarm/active ALA
RM
FIRE DULE
MO
state. Both LEDs on steady shows alarm state - stand-alone mode.
Construction - All modules in EST’s Signature Series are constructed of
high-impact polymer designed to endure the effects of aging. They are
finished in white and are identified with front plate markings “FIRE ALARM
MODULE”. A self-adhesive French label for the front plate is included to
be applied by the installer if desired.
Quality and Reliability - GE Security modules are manufactured in
North America to strict international ISO 9001 standards. All electronics
utilize surface mount technology (SMT) for smaller size and greater
immunity to RF noise. A conformal coating is used for humidity and
corrosion resistance.

www.gesecurity.com
Page 2 of 4 Literature Sheet #85001-0297 Issue 5
N O T TO B E U S E D F O R I N S TA L L AT I O N P U R P O S E S .

Testing & Maintenance


The module’s automatic self-diagnosis identifies when it is defective and causes a trouble message. The user-friendly maintenance program shows
the current state of each module and other pertinent messages. Single modules may be turned off (de-activated) temporarily, from the control panel.
Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having
Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards. Availability of maintenance features is dependent on the fire alarm
system used.

Typical Wiring
The module will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2), #12 AWG (2.50mm2) wire sizes.
Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for
detailed wiring requirement specifications.

Initiating (Slave) Device Circuit Wire Specifications


Maximum Allowable Wire Resistance 50 ohms (25 ohms per wire) per Circuit
Maximum Allowable Wire Capacitance 0.1µF per Circuit
For Design Reference: Wire Size Maximum Distance to EOLR
#18 AWG (0.75 mm²)
#16 AWG (1.00 mm²)
4,000 ft (1219 m)
#14 AWG (1.50 mm²)
#12 AWG (1.50 mm²)

Model SIGA-WTM Model SIGA-MM1

Notes

1 Maximum 25 ohms resistance per wire.


2 Maximum #12 AWG (2.5mm2) wire. Min. #18 (0.75mm2)
3 Refer to Signature Loop Controller Installation Sheet for
wiring specifications.
4 Maximum 10 Vdc @ 350μA.
5) All wiring power limited and supervised.
6) This module will NOT support 2-wire smoke detectors.

www.gesecurity.com
Issue 5 Literature Sheet #85001-0297 Page 3 of 4
NOT TO BE USED FOR INSTALL ATION PURP OSES .

Application Compatibility
The duty performed by the SIGA-MM1 and SIGA-WTM is determined by The Signature Series modules are compatible only with EST’s Signature
their factory assigned sub-type code or “Personality Code”. Loop Controller.
SIGA-WTM NORMALLY-OPEN ALARM - DELAYED LATCHING (Factory
set Personality Code 2) - Assigned to one circuit. Configures circuit 1
for Class B normally-open Waterflow Alarm Switches. An ALARM signal Warnings & Cautions
is sent to the loop controller when the input contact is closed for
approximately 16 seconds. The alarm condition is latched at the This module will not operate without electrical power. As fires frequently
module. cause power interruption, we suggest you discuss further safeguards
with your local fire protection specialist.
SIGA-WTM NORMALLY-OPEN ACTIVE - LATCHING (Factory set
Personality Code 4) - Assigned to one circuit. Configures circuit 2 for
Class B normally open dry contact Supervisory and Tamper Switches. Ordering Information Table
An ACTIVE signal is sent to the loop controller when the input contact is
Catalog Ship Wt
closed. The active condition is latched at the module.
Number Description lbs (kg)
SIGA-MM1 NORMALLY-OPEN ACTIVE - NON-LATCHING (Factory set SIGA-MM1 Monitor Module - UL/ULC Listed
Personality Code 3) - Assigned to one circuit. Configures circuit 1 for Waterflow/Tamper Module .4 (.15)
Class B normally-open dry contact monitoring input such as from Fans, SIGA-WTM
- UL/ULC Listed
Dampers, Doors, etc. An ACTIVE signal is sent to the loop controller Accessories
when the input contact is closed. The active condition is not latched at
the module. 27193-11 Surface Mount Box - Red, 1-gang
1 (.6)
27193-16 Surface Mount Box - White, 1-gang
Multifunction Fire Cabinet - Red, supports
MFC-A 7.0 (3.1)
Signature Module Mounting Plates
Signature Module Mounting Plate,
SIGA-MP1 1.5 (0.70)
1 footprint
Signature Module Mounting Plate,
SIGA-MP2 0.5 (0.23)
1/2 footprint
Signature Module Mounting Plate,
SIGA-MP2L 1.02 (0.46)
1/2 extended footprint

Specifications Table
Catalog Number SIGA-MM1 SIGA-WTM
Description Monitor Module Waterflow/Tamper Module
Type Code 48 (factory set personality code 3) 49 (factory set personality code 2,4)
Address Requirements Uses One Module Address Uses Two Module Addresses
Operating Current Standby = 250µA; Activated = 400µA Standby = 396µA; Activated = 680µA
Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
Construction & Finish High Impact Engineering Polymer one-gang front plate - White
Operating Temperature: 32ºF to 120ºF (0ºC to 49ºC)
Storage and Operating Environment Storage Temperature: -4ºF to 140ºF (-20ºC to 60ºC)
Humidity: 0 to 93% RH
On-board Green LED - Flashes when polled
LED Operation On-board Red LED - Flashes when in alarm/active
Both LEDs - Glow steady when in alarm (stand-alone)
Use With Signature Loop Controller
Compatibility Agency Listings
UL, ULC, CSFM, MEA
North American 2-1/2 inch (64 mm) deep one-gang boxes
Mounting and 1-1/2 inch (38 mm) deep 4 inch square boxes with one-gang covers and
SIGA-MP mounting plates

www.gesecurity.com
It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements.
All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact GE Security.
© 2003 GE Security Printed in Canada
Page 4 of 4 Literature Sheet #85001-0297 Issue 5

You might also like