You are on page 1of 1

LVAC OPERATION PHILOSOPHY

MODE OF  INCOMER‐1 BUS SECTION‐1  INCOMER‐2       BUS SECTION‐2  INCOMER‐3       Emergency DG 


S.NO. CONDITION
OPERATION (2QM)            (3QM) (4QM) (7QM) (8QM) (6QM)

1. NORMAL AUTO/MANUAL ON OFF ON OFF ON OFF

2. LOSS OF INC‐1 AUTO/MANUAL OFF ON ON OFF ON OFF

AUTO ON OFF OFF ON ON OFF

3. LOSS OF INC‐2 ON ON OFF OFF ON OFF


MANUAL
ON OFF OFF ON ON OFF

4. LOSS OF INC‐3 AUTO/MANUAL ON OFF ON ON OFF OFF

AUTO OFF OFF OFF ON ON OFF


5. LOSS OF INC‐1 & 2
ON IF REQUIRED  
MANUAL OFF OFF ON ON OFF
**

AUTO ON ON OFF OFF OFF OFF


6. LOSS OF INC‐2 & 3
ON IF REQUIRED  
MANUAL ON ON OFF OFF OFF
**

AUTO OFF OFF ON ON OFF OFF


7. LOSS OF INC‐1 & 3
ON IF REQUIRED  
MANUAL OFF ON ON OFF OFF
**

AUTO OFF OFF OFF OFF OFF ON


8. LOSS OF INC‐1, 2 & 3
ON IF REQUIRED   ON IF REQUIRED  
MANUAL OFF OFF OFF ON*
* *
* OUTGOING LOAD MANAGEMENT TO BE DONE MANUALLY WHILE DG INCOMER IS IN CLOSE
POSITION IN MANUAL MODE.
** OUTGOING LOAD MANAGEMENT TO BE DONE MANUALLY WHILE ONE INCOMER IS IN
CLOSE POSITION IN MANUAL MODE.

You might also like