Professional Documents
Culture Documents
Abstract- The design of reactive power compensation II. HV MEASUREMENTS OF HARMONIC POLLUTION
capacitor banks is evaluated on the basis of harmonic
Harmonic measurements at the different Dutch 380 kV
measurements, harmonic analysis in the high voltage network
and transient studies. Two designs of mechanical switched substations were performed to obtain zero-base harmonic data
capacitor banks, based on a simple capacitor design with turn-on (before installations of reactive power compensation
reactor and a C-Type filter with harmonic damping network are equipment or HVDC links). Harmonic voltage measurements
considered for 6 locations in the TenneT 380 kV and 220 kV were carried out at six 380 kV substations where the planned
networks, totaling 1500 Mvar of capacitor banks. Based on these capacitor banks will be connected. Additionally a similar
studies the design and specifications of ten banks were finalized.
measurement was carried out at the 380 kV substation
This paper summarizes the results of this evaluation, design and
analysis studies. Maasvlakte, near Rotterdam, since a planned HVDC
connection is expected to be landed at this sub-station. The
Index Terms- Harmonic Analysis; Power Filters; Power purpose of these measurements was to quantify the harmonic
System Harmonics; Reactive Power Control; Voltage voltage distortion in the 220/380 kV network of TenneT over
Transformers. a period of 5 consecutive days. The individual harmonics
were recorded up to the 40th harmonic.
I. INTRODUCTION To measure the harmonic voltage distortion of the network
R-C-R Divider 2
Rp
Divider ratio 4000:1
400 MΩ
Attenuation at 2 kHz 0 dB
3x 575 pF 1.5
Attenuation at 3 kHz -0,46 dB
Capacitors
Attenuation at 5 kHz -1,1 dB
Data-logger
0.5
LV-arm U1THD % avG
U1H5 % avG
U1H7 % avG
0
25-02-02 26-02-02 27-02-02 28-02-02 01-03-02 02-03-02 03-03-02 04-03-02 05-03-02
00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00
Fig. 2: Measurement set-up for open-air substations
Fig. 5: Harmonic measurement result in a 380 kV substation
The measurements performed at the Maasvlakte substation
were carried out on a GIS installation. For this purpose the The results of these harmonic measurements indicated that
capacitive voltage indicator in the installation was used. The some of the characteristic voltage harmonics were
indicator itself was removed and its plug was connected to a approaching the planning harmonic levels on the 380 kV
termination capacitor. In this way a capacitive voltage divider network. It was concluded that with the planned HVDC links
was realized. Before starting measurements, the bandwidth of and MSCs directly connected onto the 380 kV network, the
this set-up was checked at a spare GIS section at the planning harmonic levels might be exceeded if no measures
substation. A schematic diagram and photograph of the GIS are taken. Care should therefore be taken when capacitive
measurement set-up are given in Fig. 3 and Fig. 4. reactive power compensation equipment is connected to the
GIS Tube 380 kV network, in order to avoid possible resonance points
near characteristic harmonic frequencies.
Busbar 400 kV
III. REACTIVE POWER COMPENSATION
C1 1500 Mvar reactive power compensation equipment are
currently installed for the TenneT 220 kV and 380 kV
Datalogger network at 6 different sub-stations. All individual banks were
configured as 150 Mvar banks and at some of the substations
C2 two parallel banks will be implemented. Due to the low
number of expected switching operations per day (1 – 4) it
was decided to use mechanically switched capacitor banks for
Fig. 3: Measurement set-up for GIS substation
this purpose. Point-on-Wave synchronized switching would
be implemented in the breaker designs. These banks will
however dramatically impact the 380 kV network impedance
and these harmonic impedance results are also required to
perform a good HVDC filter design. The designs of both
capacitor with turn-on reactors (MSC) [4] and C-Type
capacitor bank with damping network (MSCDN) [2], [5],
were evaluated. The harmonic impedance of the network and
the transients at some of the 380 kV substations were
evaluated, using regular capacitor only banks and a C-Type
damped capacitive filter bank.
-500.
Harmonic order no. Amplification
0.0 600. 1200. 1800. 2400. [Hz] 300
2 ≤ 1,3
Fig. 9: Result of harmonic impedance Z (Ω) calculations with simple
capacitor MSCs (Effect shown on Harmonic Impedance with a single 150 3 ≤ 1,2
Mvar MSC switching) 4 to 31 ≤1
2000.
The harmonic amplification can be plotted in terms of the
calculated network impedance Znet, and the impedance of the
1500. C-Bank, Zc. These amplification factors are compared
between a MSC and a MSCDN design at Diemen. These
results are plotted in Fig. 13:
1000.
6
0.0
4
-500.
0.0 600. 1200. 1800. 2400. [Hz] 30
3
Fig. 10: Result of harmonic impedance Z (Ω) with C-Type damped
MSCDN design (Effect shown on Harmonic Impedance with a single 150 2
Mvar MSCDN switching) 1
0
For the next result all the ten capacitor banks (1500 Mvar) 0 500 1000 1500 2000 2500 3000
in the network are switched on, and the harmonic impedance frequency [Hz]
at one substation is generated.
The results are compared between the simple MSC design Fig. 13: The harmonic amplification plotted in terms of the network
and a C-Type MSCDN design for all banks. The polar R-X impedance and the impedance of the C-Bank.
results are plotted in Fig. 11 and Fig. 12 respectively for the
MSC and MSCDN designs. It is clear that the MSC design does not comply to the
indicated voltage amplification levels. The MSCDN design on
Harmonic impedance the other hand complies fully with this requirement.
500
0
evaluated for both MSC and MSCDN designs. Although
Point-on-Wave synchronized circuit breakers are considered
in the MSC designs, the transient calculations were based on
−500
the fact that these breakers did not operate on the zero voltage
0 500 1000 crossings. As a worst case it is assumed that two phases of the
Resistance [Ω]
bank are turned on at the peak voltage of one phase and the
Fig. 11: R-X Polar plot of harmonic Fig. 12: R-X Polar plot of harmonic other phase 3,3 ms later. Firstly the regular MSC with a turn-
impedance with simple MSC design impedance with MSCDN Design on reactor of some 30 mH (Maximum practical value) and the
minimum short circuit impedance was considered. The inrush
current for the bank is shown in Fig. 14.
3.0
DI SILEN
400.
1.8 240.
1 80.0
-0.6 -80.0
-1.8 -240.
-3.0 -400.
0.00 0.01 0.02 0.03 0.04 [s] 0.05 0.00 0.01 0.02 0.03 0.04 [s] 0.05
R 2: Phase Current A/Terminal i in kA DIM\-: Phase Voltage A in kV
R 2: Phase Current B/Terminal i in kA DIM\-: Phase Voltage B in kV
R 2: Phase Current C/Terminal i in kA DIM\-: Phase Voltage C in kV
Fig. 14: Result of turn-on current transient at peak voltage, using regular Fig. 17: Result of Turn-on Voltage Transient with 380 kV 150 Mvar C-
380 kV, 150 Mvar capacitor bank and a turn-on reactor of 30 mH (Turn-on Type damped MSC design (Two phases switch at time 0 and the other
of two phases at time 0 and the other phase 3,3 ms later) phase 3,3 ms later)
A peak of more than 2 kA at 380 kV is calculated. The From these transient calculations it is clear that the C-Type
nominal rms-current is around 220 A. The voltage transients MSCDN capacitor banks are also the preferred choice.
at the 380 kV bus bar are shown in Fig. 15. These are no
acceptable transients for such a high voltage substation. VII. C-TYPE MSCDN DESIGN AND SPECIFICATION
CONSIDERATIONS
500.
1.00
0.2
0.6
0.1
0.2
-0.08
-0.20
-0.24
-0.60
-0.40
0.00 0.01 0.02 0.03 0.04 [s] 0.05
-1.00 RL 2: Phase Current A/Terminal i in kA
0.00 0.01 0.02 0.03 0.04 [s] 0.05 RL 2: Phase Current B/Terminal i in kA
CL 2: Phase Current A/Terminal i in kA RL 2: Phase Current C/Terminal i in kA
CL 2: Phase Current B/Terminal i in kA
CL 2: Phase Current C/Terminal i in kA Fig. 18: Result of turn-on current (voltage[x900]) transient through the
Fig. 16: Result of Turn-on Current Transient with 380 kV, 150 Mvar C- damping resitor R1, at peak voltage, using the regular 380 kV, 150 Mvar
Type MSCDN design (Two phases at time 0 and the other 3,3 ms later) capacitor bank (Turn-on of two phases at time 0 and the other 3,3 ms later)
Since the turn-on current of the damping resistor R1 is [7] J.H.R. Enslin, J. Knijp, C.P.J. Jansen, P. Bauer, “Integrated approach to
network stability and wind energy technology for on-shore and offshore
taken, the voltage transient is the same scaled by the resistor applications”, in Proc. 24th PCIM Conference (PCIM-03), Nuremberg,
value of 900 Ω. 20-22 May 2003.
A surge arrester is designed across this resistor to handle
these transients when the Point-on-Wave synchronization XI. BIOGRAPHIES
breaker switch is not operating.
Johan HR Enslin (M'85, SM'92) received the B.Eng,
VIII. CONCLUSIONS M.Eng and D.Eng. degrees in Electrical and Electronic
Engineering from the Rand Afrikaans University (RAU),
From the harmonic voltage measurements, the zero base South Africa, in 1981, 1993 and 1988 respectively.
harmonic voltage values are obtained for reference and Through 1982 to 1985 he was with SPOORNET in South
specification purposes of future MSC and HVDC Africa. He joined the Department of Electrical
Engineering at the University of Pretoria in 1986 and
installations. When comparing the characteristics of the served as Professor and Head of Department until 1991.
network model obtained from implementing the C-Type Through 1991 - 1999 he held the Chair of Energy Systems
MSCDN with that of a simple capacitor MSC, the network in the Department of Electrical and Electronic Engineering at the University
of Stellenbosch, and was also the SAPSSI Technical Director at ESKOM.
resonances are much better damped with the C-Type MSCDN Since 2000 he holds a senior consulting position with KEMA in Arnhem, The
design. Furthermore the C-Type MSCDN is not affecting the Netherlands. He is involved in consulting and research work in the fields of
harmonic resonance frequencies and has an excellent wide- reactive power compensation, renewable energy, power quality and power
electronics.
band damping effect of the network resonances. The
transients are kept well under control. Some design Johan Knijp graduated from the Groningen (The
considerations are however important in this design. These Netherlands) College of Advanced Technology in
include the rating and transients of the damping resistor, as Electrical Engineering in 1991, and Groningen College of
Business Administration in 1992. He joined KEMA in
well as the series reactor losses, noise production and
1994 as a researcher in Power Quality and is since 1998 a
electromagnetic induction. consultant in power quality, design and utilization of power
The design of the 1500 Mvar MSCs has now been finalized systems. He is presently responsible for the Risk analyses,
on a C-Type MSCDN design. The harmonic resonance Economics en Power Quality Group of KEMA T&D
Consulting, Arnhem, the Netherlands.
characteristics are calculated for the Dutch 380 and 220 kV
network, taking into account future network upgrades and the Cees P.J. Jansen received the M.Eng degree in Electrical
1500 Mvar capacitive reactive power compensation Engineering from the Technical University Eindhoven
equipment. It was found that the network damping is the (TUE), The Netherlands, in 1982. Through 1983 to 1986
he was with ASEA in Sweden. Since 1986 he holds a
worst when the capacitors are out of operation. senior consulting position with KEMA in Arnhem, The
Netherlands. He is involved in system studies and network
IX. ACKNOWLEDGMENT calculations for public networks and industrial
installations.
The authors gratefully acknowledge the contributions of
Ali Atmadji and Erwin Hoeksma for some simulation studies Johan H. Schuld received the M.Eng degree in Electrical
and Jeremy Price from NGC, for good technical discussions Engineering from the Technical University Eindhoven in
the Netherlands. From 1982 to 2000 he was with KEMA
during this project.
at different departments. He started in a research
department in the field of power electronics and dispersed
X. REFERENCES power generation and in particular in combination with
wind turbines. From 1986 he worked at the engineering
Periodicals: department in power system analysis. As consultant he
[1] A. Robert, T. Deflandre, CIGRé Working Group CC02, "Guide for carried out numerous studies on network development and
assessing the network harmonic impedance", Cigré Electra, no. 167, on the integration of power generation in industrial and public networks.
August 1996. Since 2000 he holds a senior position at the Dutch TSO TenneT in the
department of Network Strategy and System Development where he is among
Books: others responsible for the development of the 220-kV and 380-kV network
[2] J. Arrillaga, D.A. Bradley and P.S. Bodger: “Power system harmonics”, including the connections to the regional networks (110-kV and 150-kV) and
John Wiley & Sons, Norwich, 1985. the interconnections with Belgium and Germany.
[3] N. Mohan; T.M. Undeland; W.P. Robbins: "Power electronics:
Converters, applications and design, 2nd Edition" New York, Wiley &
Sons, 1995.
[4] T.J.E. Miller: "Reactive power control in electric systems," New York,
John Wiley & Sons, 1982.