Auto Recloser Function

≡ Auto Recloser is an inbuilt function of REC650 ( Bay Control Unit)

Fucntion Description IEC 61850 Identification IEC 60617 Identification ANSI/IEEE C37.2 Device Number

Auto Recloser for 3 Phase


SMBRREC O->l 79
Operation

Operation Description Value Used Logic Gate Description


Open time/ Dead Time 1 Sec And Gate (&) :- The AND gate is an electronic circuit
Reclaim Time 25 Sec that gives a high output (1) only if all its inputs are
Max Wait time for Sync check OK 30 Sec high.
Min time that CB must be Closed before new
5 Sec
sequence allows OR Gate:- The OR gate is an electronic circuit that
Max Trip Pulse Duration 0.2 Sec gives a high output (1) if one or more of its inputs are
Number of Shots 1 high

Auto Recloser Start Logic when Bay is in Normal Condition

REL 650 (Line Distance Prot. Relay)

Zone -1 Fault REC 650( Bay Control Unit)

Zone 2 Start
OR

Carrier Received

Carrier Selector &


Switch 'IN' Position

Carrier Channel
Healthy
Auto Recloser Start
&

REC 650( Bay Control Unit)

CBREADY( CB Ready for Reclosing Cycle i.e.


operating gear/mechanism charged)

CBPOS(Ensure that the CB was closed when line


fault occurred)

Blocking or Inhibit Signal shall notbe present &

Bay on Normal (NIT Switch is in Normal Position)

Synchocheck OK

Avik Bhattacharya 19/03/2019 15:20Hrs.


Auto Recloser Function
≡ Auto Recloser is an inbuilt function of REC650 ( Bay Control Unit)

Fucntion Description IEC 61850 Identification IEC 60617 Identification ANSI/IEEE C37.2 Device Number

Auto Recloser for 3 Phase


SMBRREC O->l 79
Operation

Operation Description Value Used Logic Gate Description


Open time/ Dead Time 1 Sec And Gate (&) :- The AND gate is an electronic circuit
Reclaim Time 25 Sec that gives a high output (1) only if all its inputs are
Max Wait time for Sync check OK 30 Sec high.
Min time that CB must be Closed before new
5 Sec
sequence allows OR Gate:- The OR gate is an electronic circuit that
Max Trip Pulse Duration 0.2 Sec gives a high output (1) if one or more of its inputs are
Number of Shots 1 high

Auto Recloser Start Logic when Bay is in Transfer Condition

REL 650 (Line Distance Prot. Relay)

Zone -1 Fault REC 650( Bay Control Unit)

Zone 2 Start
OR

Carrier Received

Carrier Selector &


Switch 'IN' Position

Carrier Channel
Healthy
Auto Recloser Start
&

REC 650( Bay Control Unit)

CBREADY( CB Ready for Reclosing Cycle i.e.


operating gear/mechanism charged)

CBPOS(Ensure that the CB was closed when line


fault occurred)

Blocking or Inhibit Signal shall notbe present &

Bay on Transfer (NIT Switch is in INTER/TRANSFER


position)

Synchocheck OK

Avik Bhattacharya 19/03/2019 15:20 Hrs.


Auto Recloser Blocking Logic

A/R Unsuccessful under these conditions:


REL 650 (Line Distance Prot. Relay) - Permanent fault
- During dead time faults
SOTF Trip - Out of synchronism

CB Open

Permit 3 PH Trip

Carrier Out/Fail

OC/EF Trip

GR A/B Trip relay


optd

Overvoltage Trip
OR

UndervoltageTrip

Manual CB Trip

Manual CB close

Distance Delayed Trip


(Z3,Z4)
Line REC 650
DT Received ( Bay Control Unit)

Z1,Z2,Z3,Z4
(PH-PH) Trip
Auto Recloser Block
&

Line Panel REC 650( Bay Control Unit) Bay in Normal


OR

GR A/B Trip relay


faulty

SF6 Gen Lockout

Loss of SF6 Alarm

TBC REC 650


TBC Panel ( Bay Control Unit)
REB 670
Busbar prot Trip
&
Auto Recloser Block

REC650 Bay in Transfer


OR
SF6 Gen Lockout

Loss of SF6 Alarm

Avik Bhattacharya 19/03/2019 15:20 Hrs.