Professional Documents
Culture Documents
Abstract— Double ended traveling wave fault location has been In deciding whether to monitor the voltage or current
used on transmission lines for the last decade for accurate and component for fault location it is necessary to consider the
consistent location of permanent and intermittent line faults terminating impedance at the line end. A change in
typically to the nearest tower or span. Choosing whether to impedance will result in part of the wave being reflected back
monitor the current or voltage component of the wave is into the line and part being transmitted onwards into other
discussed and practical examples of sensors given that fit to
connected lines (if they exist).
protection CTs, capacitor PTs and transformer bushings. A
variety of sensors means it is now possible to deploy the The reflection factor for the voltage and current components
traveling wave technique on sub transmission networks as well due to the impedance discontinuity at a line end is equal in
as transmission, a significant advantage to Utilities. magnitude but opposite in polarity. Reflection factor is
defined as follows (2) (3):
Index Terms—Fault Location, Overhead Lines, Traveling Waves Voltage reflection factor = Zs-Zo (2)
Zs+Zo
I. INTRODUCTION
Double ended travelling wave fault location has been used Current reflection factor = Zo-Zs (3)
on transmission lines for the last decade for accurate and Zs+Zo
consistent location of permanent and intermittent line faults (Zs is the surge impedance of the terminating busbar)
typically to the nearest tower or span. [1]
Modern travelling wave systems (TWS) use a double ended The dominant impedance contributing to Zs are other
(Type D) method for fault location that does not rely on connected lines. If the busbar has a total of n similar lines
operator intervention to determine distance to fault. Results connected to it then Zs will be (4):
are automatically calculated and immediately available for
use. The power arc at the fault site and the resulting step Zs = Zo/(n-1) (4)
change in voltage generates a travelling wave that propagates
along the line in both directions to the line ends. TWS fault The reflection factors now become (5) (6):
locators positioned at the line ends accurately tag the arrival
time of the waves using GPS as a reference. These time tags Voltage reflection factor = (2-n)/n (5)
are sent to a central location where they are used to calculate Current reflection factor = (n-2)/n (6)
distance to fault using the line length and the velocity of
propagation. Further details are given in fig 1. The voltage and current transients measured at the substation
busbar are the sum of incident and reflected waves which in
per unit terms based on the number of lines n is (7):
II. MONITORING THE TRAVELING WAVE
The fault generated traveling wave has a voltage (Vwave) Voltage = 2/n Current = (2n-2)/n (7)
and current (Iwave) component. The relationship between the
two is shown in equation (1) below: From this it can be seen that as the number of lines increases
the voltage transient tends to zero while the current transient
Iwave = Vwave / Zo (1) tends to double.
(Zo is the characteristic impedance of the line, typically 200 When two lines are connected the reflection factor is zero and
to 300ohms) either voltage or current transients can be monitored.
When one line is connected to a busbar the voltage transient
tends to double while the current transient tends to zero,
Note that it is not possible to use the CPT if power line carrier
(PLC) is present. The CPT is the line side of the wave trap
and used as an injection point for the carrier. The presence of
the high frequency carrier will continuously trigger the TWS
device rendering it useless as a fault locator.
Isolator
Current Power
Busbar A Transformer Busbar B Transformer
Circuit
Breaker
Transmission Line
REFERENCES
[1] R, Orndorf, "Evaluation of Traveling Wave Fault Locators at
Dominion" FDA Conference, Georgia Tech 2012