You are on page 1of 15

Computers and Structures 81 (2003) 239–253

www.elsevier.com/locate/compstruc

Seismic response of building structures


with dampers in shear walls
L.P.B. Madsen, D.P. Thambiratnam *, N.J. Perera
School of Civil Engineering, Physical Infrastructure Center, Queensland University of Technology, GPO Box 2434,
2 George Street, Brisbane, Qld 4001, Australia
Received 1 October 2001; accepted 1 November 2002

Abstract
When buildings are subjected to earthquakes, it is imperative to dissipate some of the input energy through pre-
determined and well designed mechanisms. This study investigates the influence of mechanical control on structural
systems through the application of strategically located component elements with reliable damping and stiffness
properties that can modulate the response. The effects of installing such damping elements at two particular locations
have been investigated. These positions are between the shear walls near the coupling beams and within cut out sections
of the wall elements in multi-storey structures. Finite element time history analysis is used in the study and results
indicate that the proposed procedure is able to achieve reasonable improvements in seismic response.
Ó 2003 Elsevier Science Ltd. All rights reserved.

Keywords: Seismic response; Building; Passive dampers; Displacements; Accelerations

1. Introduction from damage and improving the seismic response. This,


however, results in the necessity to repair the damage to
When buildings are subjected to earthquakes or the structural members after they have been subjected to
shock waves from explosions, it is essential to provide extreme load effects.
avenues for energy absorption in these buildings to Many multi-storey buildings contain shear walls
avoid the detrimental effects caused by such random and around the elevator shafts and stairwells. These walls
unpredictable loads that far exceed the elastic strength provide considerable lateral stiffness to the structure to
capacity of structural elements. During recent earth- enable it to resist horizontal loadings such as earth-
quakes it has been found that lack of energy absorption quakes and wind. There will usually be several openings
mechanisms is one of the causes of poor building per- in these shear walls and if two such openings are on
formance. It is increasingly common practice in the de- opposite sides, deep beams are used to interconnect the
sign of multi-storey buildings to detail locations that will walls. These coupling beams are generally used as a
form plastic hinges which are usually positioned in means of providing framing action to the core elements.
beams near beam column joints [12,14]. These locations In order to dissipate energy during earthquakes they
are designed to dissipate substantial energy through in- must undergo inelastic yielding, and therefore, due to
elastic deformation, thus protecting the main structure their small span to depth ratio, require highly complex
and congested reinforcing to achieve ductility. They are
difficult to construct due to the need for this diagonal
*
Corresponding author. Tel.: +61-7-3864-1467; fax: +61-7- reinforcement, as well as service penetrations.
3864-1515. In addition to using plastic hinges, the input energy
E-mail address: d.thambiratnam@qut.edu.au (D.P. Tham- can also be absorbed by the use of damping devices.
biratnam). Over the past decade there has been significant research

0045-7949/03/$ - see front matter Ó 2003 Elsevier Science Ltd. All rights reserved.
PII: S 0 0 4 5 - 7 9 4 9 ( 0 2 ) 0 0 4 4 1 - 8
240 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

conducted on the use of damping devices for dissipating system will be investigated. This will be applicable to
seismic energy [7]. These devices can be placed within the new design as well as retrofitting existing buildings to
structure to reduce the demand on the structural ele- ensure seismic safety by fitting damping devices which
ments to absorb energy, and thus, they are designed to can transform a wall panel into a damping element. A
protect the building from excessive damage. Today there highly damped lower part of a multi-storey building will,
are various types of manufactured dampers available Ôoff theoretically, modulate the dynamic excitation resulting
the shelfÕ. They use a variety of materials to obtain from strong ground motions due to a reduction in
various levels of stiffness and damping [9]. Some of them stiffness and should, therefore, produce a better overall
include viscoelastic (VE), viscous fluid, friction and seismic response of the building. The validity of this
metallic yield dampers, which have different dynamic theory will be studied by considering the effects of
characteristics and so will affect the seismic response of dampers located in various positions within the shear
structures differently [8]. These devises can enhance the wall on the acceleration and deflection response of
stiffness, damping and strength of a structure and can be buildings under seismic loading. A range of shear wall
used to retrofit old buildings to withstand natural haz- widths will be considered.
ards such as earthquakes, cyclones and shock loads. In The aim of this research will be to evaluate how the
recent years they have been used to improve the re- two aforementioned damping systems will affect the
sponse of bridges and buildings [7]. seismic response of the structure. For the purposes of
The characteristics of VE and viscous dampers are this study VE dampers will be modelled. These dampen
that they dissipate energy at all levels of deformation the excitation through shear deformation of the mate-
and over a broad range of excitation frequencies [4,5]. rial, and dissipate energy at different magnitudes and
Friction dampers on the other hand, dissipate energy patterns of deformation [3]. They were chosen for the
only when the slip force is reached and exceeded [2]. ability to conveniently approximate their behaviour
Metallic yield dampers dissipate energy through the in- under cyclic loading with reasonable accuracy. Finite
elastic deformation of the material [15]. A combination element time-history analysis under earthquake loading
of these dampers can be used within the structural sys- was carried out using the software ABAQUS Version
tem to effectively dampen out the high and low fre- 5.8.
quency content of earthquakes [11]. This is commonly
referred to as a hybrid system. These types of dampers
are categorised as passive control for they develop forces 2. Model description
in opposition to the input forces at the locations where
they are attached to the structure [7]. Other control This study examines the effects of two different
systems, classified as active or semi-active and which damping systems in improving the seismic performance
require power supply to be active during the event, are of multi-storey building structures. The dampers are
not considered in this paper. Chang et al. [6] and Aiken placed between the shear walls at the coupling beam
and Kelly [2], have shown that dampers placed within location in the first system and analysis was undertaken
relatively flexible multi-storey structures can be very on six-, and 20-storey building models to assess the ef-
effective in reducing the lateral acceleration, velocity and fectiveness of the damper placement under earthquake
deflection response under seismic loading. Structures loading. In the second system dampers were located
that have relatively high interstorey drifts or substantial within cut-out sections of shear walls. A nine and a 20-
joint rotations can enable certain types of dampers to act storey building were studied. In both these structures,
effectively to minimise damage to the buildings. there was a plane central shear wall which was con-
Using finite element time history analysis, this paper nected to columns on either side of it. These models are
investigates the seismic behaviour of multi-storey build- discussed in further detail below.
ings using damping devices strategically located within A finite element program ABAQUS Version 5.8 was
the load resisting elements. It will concentrate on two selected to obtain the response of the structures under
particular damping systems in multi-storey buildings earthquake loading. The dynamic procedure in ABA-
containing shear walls. In the first system dampers will QUS Version 5.8 [10] uses implicit time integration. The
be positioned between two shear walls, which are linked response of the structure is obtained for selected time
by coupling beams. The height of the space in which the steps of the input earthquake accelerogram. To study
dampers are to be located will be restricted, to allow the effectiveness of the damping systems in mitigating
reasonable access under these beams. A double diagonal the seismic response, the tip accelerations and displace-
damper configuration will be placed in the vicinity of ments at each floor level in the damped structure were
these beams to modulate the seismic response, which will acquired from the results of the analyses, and compared
be studied under different earthquake records. with those of the bare, undamped structure.
In the second system the effects of dampers located In this study VE dampers are used and each damper
within the shear wall in the lower stories of the building is modelled as a spring and a dashpot in parallel. The
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 241

stiffness and damping coefficients are defined by the Coupling


equations given by [1, p. 2–7]: Beam Lumped
mass
G0 A
kd ¼ ð1Þ
t Shear wall Dampers
B21 Beam
elements
G00 A Application of the time-
Cd ¼ ð2Þ history acceleration
xt

where, A is the shear area of the VE material, t is the Fig. 1. Six-storey structure with shear walls and coupling
beams––damping system 1.
thickness of the VE material, x is the loading frequency
of the VE damper, G0 is the shear storage modulus, and
G00 is the shear loss modulus. 2.1. Damping system 1––dampers between shear walls
The following expressions were used to obtain the
moduli of the VE material as defined by Abbas and 2.1.1. Six-storey structural model
Kelly [1, p. C-1]: The shear wall–coupling beam model was con-
structed using two-dimensional beam elements as shown
G0 ¼ 16:0x0:51 c0:23 eð72:46=TempÞ ð3Þ in Fig. 1. The beam element type used was a 2-node
linear beam designated B21 and consists of a two-
dimensional beam with three degrees of freedom: at each
G00 ¼ 18:5x0:51 c0:20 eð73:89=TempÞ ð4Þ node, viz; translations along and normal to the beam
axis and a rotational degree of freedom about the axis
normal to the plane. This type of element is shear de-
This model with properties determined from Eqs. (1) formable and accounts for finite axial strains and is,
and (2) will approximate the true behaviour of a VE therefore, suitable for modelling both thick and thin
damper within 10%, when subjected to vibratory loading section beams [10]. The shear wall and coupling beams
such as seismic loading. This was considered to be suf- were represented as rectangular sections; the shear wall
ficiently accurate for the purposes of this investigation. was 3 m wide by 0.5 m thick, and each coupling beam
In order to create such a computer model, it has to be was 0.6 m deep by 0.3 m wide. Lumped masses were
assumed that there is information on the frequency of placed at each node where the coupling beam intersected
loading applied to the damper; the shear strain and the the shear wall to represent the gravity loads from the
temperature of the VE material. In the present investi- floor. A lumped mass of 1:02  106 kg per floor was
gation, the ambient temperature of the VE material was designated. The distance between the shear walls was
assumed to be 21 °C, the shear strain, c, was assumed to fixed at 2.4 m, and height between each level at 3.0 m.
remain constant at 100%. This was done as it has been This corresponded to an overall height of 18.0 m for the
shown that a large decrease in the stiffness occurs in the six-storey building.
0–50% strain range, whereas in the 50–200% strain range Though several damper configurations were studied
the stiffness remains approximately constant [2]. For the [13], in this paper, results of only one configuration,
loading frequency, x, either the first or second mode of which produced the best response under earthquake
vibration of the structure was used. It was assumed in loading will be discussed. This is the double diagonal
this study that the structure will predominantly vibrate damper, which is placed throughout the height of the
in one of these modes [1]. The choice of loading fre- structure, as shown in Fig. 1 for the lowest storey. The
quency depended on which mode of vibration of the vertical distance between the end points of attachment
structure was within the predominate frequency range of of the dampers was limited to a practical value of 600
earthquakes of 0.5–3 Hz. It should be noted that in this mm so as to allow adequate clearance levels (or access)
model, only the lateral deformations are damped. Ro- under the beams. The response of this model was in-
tational deformations are not damped. vestigated under the 1940 El Centro, the 1971 San Fer-
Concrete material properties were used for the nando and the 1988 Tennant Creek earthquake records.
building (structural) models, since shear wall and cou-
pling beam structures are constructed using reinforced 2.1.2. Twenty-storey structural model
concrete. The material properties of the concrete used A 20-storey building was analysed to evaluate the
had a compressive strength, fc0 , of 32 MPa, a YoungÕs effectiveness of the method of placing dampers between
modulus, Ec , of 30,000 MPa, a Poissons ratio, t, of 0.2, the shear walls. The shear walls and coupling beams
and a density, q, of 2500 kg/m3 . were represented as rectangular sections of 1.5 by 0.5,
242 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

and 0.6 by 0.3 m, respectively. A lumped mass of of elements used for the walls were M3D4 membrane
500,000 kg was positioned at each shear wall and floor elements. These elements determine stresses in two per-
level intersection point. Dampers were placed in each pendicular directions along the horizontal x-axis and the
level of the structure. Results were obtained for the ac- vertical y-axis [10]. The columns were modelled using
celeration and deflection response of the building under Type B21 bilinear beam elements.
the 1940 El Centro earthquake. These models were ideally configured so that the
columns bore the entire gravity load. The shear wall was
then mainly used to resist the generated lateral loads.
2.2. Damping system 2––dampers within shear walls Lumped masses were located, therefore, on the columns
at each node that correlated to a floor level. At each of
2.2.1. Nine-storey shear structure the floor levels the shear wall and columns were con-
In the nine-storey model, the concrete shear wall was nected using rigid links to simulate the rigidity of the
constructed as a 6.0 m wide by 0.1 m thick rectangular floor slabs and to transfer the lateral load into the wall.
section, and the columns as 0.45 m square sections. These links were modelled in ABAQUS V5.8 [10] using
These were located on either side of the wall, as seen in mpc type beams. This type of constraint linked two
Fig. 2. The height between floor levels was set at 3.0 m, nodes, and forced the translations and rotations at the
which made the overall height of the structure to be 27.0 first node to be the same as at the second node.
m. A lumped mass of 140,000 kg was placed at each Four different damper locations, as shown in Fig. 3,
node of the columns that intersected the floor level. The were used to study the seismic response of this model. In
models studied were two-dimensional, and thus, the type Type A, dampers were placed in the lower three stories;
in Type B in the second and third stories; in Type C in
the second; third and fourth levels; and in Type D
dampers were placed in the upper two levels. Details of
L9 the damper location within the shear wall can be seen in
Shear Wall - M3D4
L8 Fig. 4, where a 4.0 m wide by 2.5 m high wall section has
Membrane elements
been cut out and replaced by two diagonal dampers. As
L7 with the six-storey frame in method 1 a time-history
Lumped analysis was used to obtain the response of the structure
L6 Mass under the same three different seismic records.
L5
L4 Column B21 beam
2.2.2. Twenty-storey shear wall structure
elements A 20-storey shear wall structure incorporating
L3
dampers within the shear wall was studied in a similar
L2 Rigid Link – manner to the nine-storey model. Three different stiff-
L1 MPC BEAM nesses of shear walls were investigated in this study.
These can be described as having relatively low (Type
L), medium (Type M), and high stiffness (Type H), with
Fig. 2. Nine-storey shear wall structure model. varying widths of 4, 6 and 8 m, respectively. The

Detail

Type A Type B Type C Type D


Fig. 3. Damper locations Types A–D, damping system 2.
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 243

3. Results

3.1. Damping system 1––dampers between shear walls at


coupling beam locations

3.1.1. Six-storey shear wall coupling beam structure


The results of the six-storey structure under the 1940
El Centro, 1971 San Fernando and 1988 Tennant Creek
earthquakes are presented below. The fundamental fre-
quency of the structure was found using the natural
frequency analysis in ABAQUS V5.8 to be x ¼ 0:552
Hz. Using this as the loading frequency of the damper
the shear storage and shear loss moduli were calculated
Fig. 4. Details of damper placement and dimensions of shear to be G0 ¼ 890,000 Pa and G00 ¼ 1,265,000 Pa, respec-
walls, damping system 2. tively. From these values and material dimensions of 400
mm by 300 mm by 11 mm for the double layered
damper, the values of the spring and dashpot were de-
amounts of shear wall cut-out in Types L, M and H were termined to be, kd ¼ 40  106 N/m and Cd ¼ 102  106
2.5 by 2, 2.5 by 4, and 2.5 by 6 m respectively. Structural N s/m.
parameters used for all three types consisted of 0.2 m Table 1 illustrates the percentage reductions in the
thick shear walls with 0.4 m square columns on either peak values of the tip acceleration, the average inter-
side of it. A lumped mass of 50,000 kg was used at each storey drift, and the tip, fourth and second storey de-
node of the floor levels. The height between the floor flections of the structure under the various earthquake
levels of the model was set at 3.0 m, which gave an records. This table demonstrates the varied effectiveness
overall height of 60.0 m. of the damper configuration under the three different
It was anticipated from the results of the nine-storey seismic records. This difference can be attributed to the
model that damper placement Type A (Fig. 3) would varying intensity and frequency content of the earth-
have the best reduction in the tip acceleration and de- quakes. In almost all cases, the greatest reductions were
flection response. In this model, it was decided to place under the El Centro earthquake.
the dampers throughout the lower one third of the shear Fig. 6 illustrates the time history responses of the tip
wall height. This corresponded to levels one to seven acceleration under the El Centro earthquake and it is
cut-out and replaced with dampers as shown in Fig. 5. In evident that the incorporation of dampers into the
all these cases, a 1 m width of shear wall was retained on structure enabled reductions of its peak acceleration.
either side of the cut out and the detail is similar to that Analogous acceleration responses were obtained under
shown in Fig. 4. These models were subjected to the first the other two earthquakes. Figs. 7 and 8 illustrate the
12 s of the 1940 S00E component of the El Centro tip deflections of the damped and undamped structure
earthquake. under the El Centro and Tennant Creek earthquakes
respectively. Analogous, but less effective, results were
obtained under the San Fernando earthquake. It can be
seen that in general, the damped and undamped re-
sponses remained in phase and that the damping was
evident after the lapse of a few seconds.

Table 1
Reduction in seismic response of six-storey structure with
damping system 1 and dampers at all levels
Response percentage Earthquake record
reduction El San Tennant
Centro Fernando Creek
Tip acceleration (%) 17.8 18.6 12.1
Tip deflection (%) 15.4 9.1 3.6
Fourth level deflection (%) 14.7 8.1 4.8
Second level deflection (%) 14.1 4.8 8.7
Av. interstorey drift (%) 16 9 5
Fig. 5. Twenty-storey shear wall model, damping system 2.
244 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

Fig. 6. Tip acceleration response of six-storey structure with damping system 1 and dampers at all levels.

Fig. 7. Tip deflection response of six-storey structure with damping system 1 and dampers at all levels.

3.1.2. Twenty-storey shear wall coupling beam structure can be seen that the incorporation of the dampers re-
The damper properties were determined as kd ¼ duced the peak value of the tip acceleration by 22.3%.
56:7  106 N/m and Cd ¼ 117  106 N s/m. These prop- Similarly the peak deflection was reduced by 20.9%.
erties were based on two double layer dampers in par- These results are similar to the results obtained for the
allel with dimensions of 470 mm by 300 mm by 10 mm six-storey building and demonstrated that dampers can
and the values G0 ¼ 994,000 Pa and G00 ¼ 1,413,000 Pa. be used to improve the mitigation of seismic forces.
These moduli were calculated using the loading fre-
quency of 0.685 Hz, which corresponded to the second 3.2. Damping system 2––dampers within shear wall
natural frequency of the structure. This frequency was
chosen, as the first natural frequency was very low and 3.2.1. Nine-storey shear wall structure
fell outside the typical range of earthquake frequencies A nine-storey shear wall structure was modelled and
of 0.5–3 Hz. analysed as described in the previous section. Results of
Fig. 9 illustrates the tip acceleration response of the the natural frequency analysis for the first and second
structure under the 1940 El Centro earthquake and it modes of the models are presented in Table 2. These
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 245

Fig. 8. Tip deflection response of six-storey structure with damping system 1 and dampers at all levels.

Fig. 9. Tip acceleration response of 20-storey structure with damping system 1 and dampers at all levels.

results show that all damper arrangement Types A–D Dynamic analysis of the structure with the various
(described in Fig. 3) reduced the natural frequencies and damper arrangements and types under the El Centro
that Type A, which has dampers positioned in the first
three stories, had the greatest changes in natural fre-
quencies compared to the bare structure. These results
Table 2
were anticipated, as reducing the stiffness at the base Natural frequencies of nine-storey structure with damping
of the structure, would increase the deformation ade- system 2 and damper placement Types A–D
quately to effectively mobilise viscous damping and
Model Natural frequency modes (Hz)
significantly reduce the natural frequency of the build-
ing. It was also shown that the dampers located in the 1 2
upper levels had little effect on the frequency of the Bare 1.088 3.830
structure. These results show that dampers located in Type A 0.565 1.846
the lower levels enable the fundamental structural fre- Type B 0.727 2.350
quency to detune from the dominant earthquake fre- Type C 0.635 2.324
Type D 1.030 2.943
quencies of 1–3 Hz.
246 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

earthquake record was conducted. For the loading fre- Time-histories of tip deflection responses of the
quency of the damper, an average of the fundamental damped and undamped structures for the damper ar-
frequencies of the damper Types A–D, x ¼ 0:739 Hz rangement Type A are shown in Fig. 10, from which it is
was used. From this, the values of the shear storage and evident that arrangement Type A noticeably reduces the
loss moduli were determined as G0 ¼ 1,033,000 Pa and deflection throughout the duration of the earthquake.
G00 ¼ 1,468,000 Pa. Assuming a double layered damper Similar results were observed for the acceleration re-
with material dimensions of 475 mm long by 325 mm sponse. The damped responses, however, did not remain
high and 10 mm thick, the damper properties were cal- in phase with that of the undamped structure responses.
culated to be kd ¼ 31:9  106 N/m and Cd ¼ 61:3  106 Fig. 11 shows the reductions in the interstorey drifts at
N s/m. the various levels for the damper locations Types A–D.
A summary of the results of the seismic response of In the above figure it can be seen that the Type A
the damped structure is presented in Table 3 which location had the greatest reductions at all levels, except
shows the percentage reductions in the maximum ac- the lowest. From the third floor up an average of 53%
celeration at the top floor and the maximum deflections reduction in the interstorey drift was achieved for this
at the top, sixth, fourth and second floors. These results placement. Again, Type D location where the dampers
indicate that the Type A damper location produced the were placed in the upper two levels seem to be the least
greatest reductions in the acceleration and deflection effective. It is anticipated that this response reduction
response of the structure and these reductions being will correspond to a decrease of the column moments
quite significant. Types B and C damper locations also and shear forces. Changes in tip deflections with the
reduced the response but not to the same level as Type percentage the changes in the fundamental frequency of
A. Type C produced a greater mitigation than Type B the structures are shown in Fig. 12 for all four damper
due to the fact that it had more dampers. Type D, where placements. This figure shows that as the change in the
the dampers are positioned in the top two stories, had natural frequency increased so did the amount of re-
little effect upon on the response of the structure. duction in the tip deflection. Type A performed best

Table 3
Percentage reductions in maximum response of the nine-storey shear wall structure with damping system 2 and damper placement
Types A–D
Damper placement Tip acceleration Tip deflection Sixth floor deflec- Fourth floor deflec- Second floor deflec-
type reduction (%) reduction (%) tion reduction (%) tion reduction (%) tion reduction (%)
A 69.40 50.67 47.47 39.97 22.35
B 38.68 30.77 30.52 27.75 22.50
C 41.88 39.30 38.55 34.38 34.93
D 3.34 3.07 4.92 4.67 4.46

Fig. 10. Tip deflection response of nine-storey shear wall structure with damping system 2 and damper Type A.
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 247

Fig. 11. Interstorey drift reductions in nine-storey shear wall structure with damping system 2 for damper placements Types A–D.

Fig. 12. Variation of tip deflection with natural frequency in nine-storey shear wall structure with damping system 2 and damper
placement Types A–D.

with a 48.1% change in the frequency and a 50.7% de- of the seismic energy can be dissipated by the strategic
crease in deflection. This indicates that the stiffness of placement of the dampers.
the buildings was sufficiently reduced to allow for the The effect of Type A damper placement was further
effective utilisation of the dampers. It is anticipated, studied under the 1971 San Fernando earthquake and
however, that if the stiffness is too low and deformations the 1988 Tennant Creek earthquake records. In these
are too high other secondary effects would endanger the case, the masses and structural properties were kept the
stability and strength of the structural system. As a re- same, as with the damper properties of kd ¼ 31:9  106
sult there needs to be a balance between stiffness, de- N/m and Cd ¼ 61:3  106 N s/m. Tip deflection re-
formation and damping within the structural system for sponses of the structure under the San Fernando
optimum results. It is shown that a considerable amount earthquake is shown in Fig. 13. It can be seen that a
248 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

Fig. 13. Tip deflection response of nine-storey shear wall structure with damping system 2 for damper Type A.

significant reduction has been achieved and this dem- Tables 5 and 6 summarise of the results of the seis-
onstrates that for this severe earthquake record with a mic response of the models with the two types of
peak acceleration of 11.48 m/s2 , the damping system is dampers under the 1940 El Centro earthquake record.
able to modulate the seismic response. Analogous results The maximum acceleration at the tip and the maximum
were obtained under the relatively moderate Tennant deflection at the tip, 15th, 10th and 5th floors were re-
Creek earthquake (with a peak acceleration of 4.09 m/ corded. The results in Table 6 indicate that optimum
s2 ). Similar results were obtained fro the acceleration reductions in the response (except at level 5) are ob-
response. tained with model M. Such reductions would lessen the
magnitude of the lateral forces on the building. Though
3.2.2. Twenty-storey shear wall structure fifth level deflections increased in the damped structures
Table 4 shows the results of the natural frequency (Table 6), they would not have a substantial adverse
analysis of (shear wall) models L, M, and H for the first effect on the structure as the deflections are small. These
and second modes of vibration. All models suffered a tables also show that reductions in deflection continued
reduction in natural frequencies due to the insertion of to increase further up the structure in model M and that
dampers. This was expected, since a reduction in the there were significant reductions in tip acceleration and
stiffness of the structure can be expected to increase the deflections in the damped structures for both damper
ductility, and thus, reduce the natural frequencies It can types. These values demonstrate the reductions in the
be seen that the influence on the natural frequencies response achieved by this damping system, assuming
increased with increasing stiffness of the shear wall. that the structure vibrates predominantly in the first
The damper properties kd and Cd for each model were and second modes and show that the damping sys-
obtained assuming a double layer VE damper with tem can enhance the ability to mitigate the seismic
material dimensions of 475 mm by 300 mm by 10 mm. forces.
Two different dampers Types 1 and 2 were treated and The tip acceleration and deflection time-history re-
their properties were obtained assuming that the loading sponses for shear wall model M with damper property
frequency corresponded to the first and second natural Types 1 and 2 are presented in Figs. 14 and 15 and show
frequencies of the damped structure, respectively. that the damping system reduces the various peak ac-

Table 4
Natural frequencies of 20-storey shear wall models L, M, and H with damping system 2
Models Natural frequency mode 1 Natural frequency mode 2
Bare Damped % change Bare Damped % change
L 0.262 (0.249) 4.73 1.422 (1.141) 19.71
M 0.383 (0.329) 14.07 2.062 (1.256) 39.06
H 0.517 (0.387) 25.16 2.722 (1.341) 50.73
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 249

Table 5
Maximum response of 20-storey shear wall models L, M and H with damping system 2
Model type Placement kd ðN=mÞ Cd ðN s=mÞ Maximum Maximum Maximum Maximum Maximum
 106  106 acceleration tip deflection 15th floor 10th floor fifth floor
deflection deflection deflection
Model L Bare – – – 4.47 305.2 196.3 99.8 41.4
Model L (1) 1–7 17 100 3.86 295.3 188.8 98.5 42.4
Model L (2) 1–7 38.7 46.7 3.51 295.8 189.2 99.8 43.2
Model M Bare – – – 4.96 461.6 301.4 157.0 47.7
Model M (1) 1–7 19.3 86.1 3.83 368.6 243.3 146.3 56.1
Model M (2) 1–7 38.7 45 3.41 344.9 247.5 152.8 62.9
Model H Bare – – – 3.720 262.25 174.25 91.71 27.83
Model H (1) 1–7 21.2 77.8 3.614 322.84 218.05 119.28 39.05
Model H (2) 1–7 38.7 42.2 3.227 310.35 216.20 127.20 50.83

Table 6
Percentage reductions in maximum response of 20-storey shear wall models L, M and H with damping system 2
Models Tip acceleration Tip deflection 15th floor deflection 10th floor deflection Fifth floor deflection
reduction (%) reduction (%) reduction (%) reduction (%) reduction (%)
Model L (1) 13.65 3.26 3.79 1.24 )2.18
Model L (2) 21.52 3.08 3.57 )0.06 )4.21
Model M (1) 22.93 20.15 19.28 6.82 )17.54
Model M (2) 31.27 25.29 17.90 2.69 )31.88
Model H (1) 2.84 )23.10 )25.14 )30.07 )40.33
Model H (2) 13.23 )18.34 )24.08 )38.69 )82.64

Fig. 14. Tip acceleration response of 20-storey shear wall model M with damping system 2.

celerations while remaining generally in phase with the seen to have a similar, but greater effect on the response
bare structure response. Fig. 16 displays the results of of the structure, with an average decrease of 31% in the
the reductions in the interstorey drifts for model M with interstorey drifts at all levels above the seventh floor.
damper property Types 1 and 2. With Type 1 dampers The increases in interstorey drifts of the damped struc-
there was a 21% average reduction in the interstorey ture in the lower levels (up to the sixth floor) are small
drift beyond the seventh floor. This has the effect of and these small values of deflection will not increase the
reducing the column moments. Damper Type 2 can be moments and shear forces significantly.
250 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

Fig. 15. Tip deflection response of 20-storey shear wall model M with damping system 2.

Fig. 16. Interstorey drift reductions in 20-storey shear wall model M for damping system 2 and damper property Types 1 and 2.

Fig. 17 compares the percentage reductions in the tip the amount of reduction in both acceleration and de-
acceleration for the three shear wall models, with respect flection increased up to a maximum point, beyond which
to the change in the natural frequency from the bare the trend reverses. In all cases, model L had the least
structure to the damped structure, for both damper change in the natural frequency with a marginal to
(property) Types 1 and 2. Similar results were obtained moderate reduction in the responses. Model M had the
for the change in tip deflection. These results demon- best reduction in both the acceleration and deflection
strate consistent and similar trends in the responses of responses for both damper property Types 1 and 2.
the various shear walls with changes in the natural fre- Model H, conversely, had the least amount of reduction
quency. As the change in natural frequency increased, in the responses of the structure. This case (H) also
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 251

Fig. 17. Variation of tip acceleration reduction with natural frequency in 20-storey shear wall models L, M and H under El Centro
earthquake.

corresponded to the largest change in the natural fre- Finite element methods were used to analyse the effects
quency, but there was an increase in the tip deflection for of dampers in these structural systems under different
both damper Types 1 and 2. earthquakes records.
In general, the structure with damper property Type The first method examined various damper configu-
2, which was associated with the second mode, had a rations and locations within a shear wall–coupling beam
greater reduction in both acceleration and deflection structure. The results of the study showed that this
responses than those with Type 1. From this it can be method had some, but limited potential for mitigation of
surmised that a decrease in the rigidity of the structure the seismic response of multi-storey structures. This is
by too much, as in model H, or too little, as in model L, believed to be due to the small difference in displacement
will have either an adverse effect or only a moderate to between the end points of attachment of the damper, and
little effect on the seismic response. This suggests that to the restriction on the depth of placement within the
there is an optimum level of rigidity that needed to be cavity between floor levels, and the high stiffness of the
taken out of the structure, or that sections needed to be shear wall against lateral loads. The dampersÕ potential
cut out of the shear wall, and replaced with a certain for energy dissipation were, therefore, not fully realised.
level of damper properties kd and Cd , in order to obtain The investigation of the six-storey structure showed that
the maximum reduction in the seismic response. It is also the effectiveness of the dampers varied under the different
possible that a higher mode could be closer to the earthquake records. This can be attributed to the varying
dominant mode in the seismic excitation. Under the intensity and frequency content of the earthquake. The
earthquake loading the structure could be acting largely results of the analysis of the 20-storey structure with
in its second or third mode of vibration and so the po- dampers in all levels, illustrated that dampers can be used
sitioning of the dampers in the lower half of the struc- to improve the mitigation of seismic forces and this
ture could be less effective. The placement of dampers supported the results obtained for the six-storey building.
within the shear wall could, therefore, be more effective Limitations of this placement application indicate the
in the regions of higher curvature. This, however, needs need for damping mechanisms that are sensitive to small
further investigation for validation. displacements or non displacement dependent damping
systems to derive a significant and practical benefit when
located at coupling beams.
4. Discussion and conclusion The second damping system, which had the dam-
ping devices located within cut-out sections of the shear
Two different VE damping systems within a struc- wall, showed that substantial reductions could be
tural system which contains shear walls (and coupling achieved in the seismic response of the building. Re-
beams), has been explored. The first system involved sults from this study indicated that by reducing the
dampers placed between the shear walls at the coupling stiffness at the base of a shear wall, and by inserting
beam locations, while the second system used damping dampers into the lower levels, it was possible to reduce
devices placed within windows cut in the shear wall. the acceleration and deflection response of the structure.
252 L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253

Dampers placed in the upper levels had little to no existing building with minor structural modifications.
effect on the structural response. The responses of the The second method was more complex with modifica-
structure were compared under different earthquake tions required to the shear wall in order to incorporate
records. There was significant reductions in deflection the damping devices.
and acceleration response under all earthquake records. The results of the investigations of the two damping
The reduction in acceleration will lead to lesser inertia systems have nevertheless demonstrated an ability to
forces and so increases the ability of the building to reduce the seismic response of buildings by strategic
cope with seismic events. The response however, varied placement of mechanical damping devices within the
with the earthquake record indicating its dependence conventional shear wall systems.
on the intensity and frequency content of the earth-
quake.
The effects of the width of the shear wall and the size of References
the cut-out on the seismic response were studied, with the
dampers were located in the lower levels of the shear wall. [1] Abbas H, Kelly JM. A methodology for design of
The results showed that there was a correlation between viscoelastic dampers in earthquake-resistant structures.
the amount of rigidity cut out of the system and the Technical Report UCB/EERC-93/09, Earthquake Engi-
stiffness and damping coefficients of the damper replacing neering Research Center, University of California, Berke-
this. This suggests that there is a need to balance these ley, 1993.
parameters in order to obtain the optimum improvement [2] Aiken ID, Kelly JM. Experimental and analytical studies
in seismic performance. It was also possible that the of two energy-absorbing systems for multistorey structures.
In: Proc 11th Inter Conf on Structural Mechanics in
modal response of the structure could influence the ef-
Reactor Technology, Tokyo, Japan, vol. K, 1991. p. 145–
fectiveness on the placement of dampers within the shear 50.
wall. This second damping system showed that, overall, [3] Aiken ID, Nims DK, Kelly JM. Comparative study of four
the dampers were most effectively positioned at the base passive energy dissipation systems. Bull New Zealand Nat
of a stiff structure which is the region nearest to the energy Soc Earthquake Eng 1992;25(3):175–92.
input source. Placement of the dampers within the shear [4] Chang KC, Chen SJ, Lai ML. Inelastic behaviour of steel
walls reduces the stiffness of the structure and this is ad- frames with added viscoelastic dampers. J Struct Eng
vantageous to the point of effectively mobilising the 1993a;122(10):1178–86.
dampers. Thereafter the energy input is modulated by a [5] Chang KC, Lai ML, Soong TT, Hao DS, Yeh YC. Seismic
combination of deformation and damping with the re- behaviour and design guidelines for steel frame struc-
tures with added viscoelastic dampers. Technical Report
maining stiffness of the structure helping to dissipate the
NCEER-93-0009, State University of New York, Buffalo,
energy while maintaining stability and resistance. The NY, 1993.
resulting advantage is the reduction of strength demand [6] Chang KC, Soong TT, Oh ST, Lai ML. Seismic response
and ductility from traditional construction materials. The of a 2/5 scale steel structure with added viscoelastic
investigations showed that significant reduction in struc- dampers. Technical Report NCEER-91-0012, State Uni-
ture acceleration, deformation and consequent strength versity of New York, Buffalo, NY, 1991.
demand can be achieved by strategically placing the [7] Constantinou MC, Soong TT, Dargush GF. Passive
dampers within the core walls and controlling the reduc- energy dissipation systems for structural design and
tion of stiffness within a reasonable range. It also showed retrofit. Monograph No. 1. Multidisciplinary Center for
an ability to de-tune the natural frequency of the structure Earthquake Engineering Research, State University of
New York, Buffalo, NY, 1998.
from the spectrum of the earthquake frequencies, in
[8] Fukumoto S, Inoue Y. Effect of characteristics of various
order to avoid resonance. The seismic response of a inter-storey dampers on response control for vibration of
20-storey shear wall structure with three different wall building structures. In: Proc 11th World Conf on Earth-
widths showed that there is an optimum stiffness of the quake Eng, Paper No. 552, 1996.
wall beyond which there was an adverse effect on the [9] Hart GC, Wong K. Structural dynamics for structural
response. engineers. New York: John Wiley & Sons; 2000.
The first damping system had very small values of [10] Hibbitt, Karlsson, Sorensen. ABAQUS User Manuals
interstorey deflections at the lower levels, but these in- Version 5.8, USA, 1998.
creased along the structure height, enabling reasonable [11] Hisano K, Kuribayashi H, Saitou K, Nakano T. The
amounts of response reductions. The second damping application example of the hybrid damping system com-
bined the hysteretic damper with viscous damper to high-
system which effectively changed the structural proper-
rise building. In: Proc 5th Inter Conf on Motion and
ties (at the lower levels) and increased the deflections, Vibration Control, Sydney, Australia, vol. 1, 2000. p. 451–
enabled the dampers to provide large reactionary forces 6.
to the input forces and hence larger response reductions. [12] Krawinkler H. A few basic concepts for performance based
The advantages of the first system simply lay in the ease seismic design. In: Proc 11th World Conf on Earthquake
of construction with the dampers being attached to the Eng, Paper No. 1133, 1996.
L.P.B. Madsen et al. / Computers and Structures 81 (2003) 239–253 253

[13] Madsen LPB. Improving the seismic response of structures [14] Park R. Reinforced concrete structures. New York: John
by the use of dampers in shear walls. ME thesis, School of Wiley & Sons; 1975.
Civil Engineering, Queensland University of Technology, [15] Tsai CS, Tsai KC. TPEA device as seismic damper for
Brisbane, Australia, 2001. high-rise buildings. J Eng Mech 1992;121(10):1075–81.

You might also like