You are on page 1of 4

GENERAL INFORMATION

Plant Name: Date:

Brand: Safety Logic Solver Type:

Cabinet Number: Application Name:


Notes:

CONFIGURATION ITEMS
Software Version: Application Version:

Memory Type: EPROM / RAM / FLASH EPROM size CPU:

Power-on Mode: RAM size CPU:

On-line Modification: Minimum execution time:

Redundancy: Maximum execution time:


Notes:

SYSTEM INFORMATION
CPU 1 CPU 2
Battery Voltage S-Bus: VDC Battery Voltage S-Bus: VDC

Battery Voltage DBM: VDC Battery Voltage DBM: VDC

Supply Voltage VDC Supply Voltage VDC

Temperature Sensor 1: Temperature Sensor 1:

Temperature Sensor 2: Temperature Sensor 2:


Notes:
ITEMS TO BE CHECKED
Checked Action
Action Item Comments/Notes
(OK) By

Check the voltages to the


1
CPU

Check the Temperatures in


2
the CPU

Check for obstruction of air


3
flow

Check correct operation of


4
fans

Check the earth faults


5 (if earth leak detection is
available)

Check loop status of


6
signals

Check forced status of


7
signals

Check availability of spare


8
parts

Check the system


9
diagnostics

Check the backup of


10
application files

11 Check for paint damage

Check external supplied


12 DC voltages (List feeders
with voltage levels)
ITEMS TO BE CHECKED
Checked Action
Action Item Comments/Notes
(OK) By
Check DC voltages
13 generated by PSU in the
cabinet

Check fuses in power


14
distribution wiring

Check all AC voltages (List


15
feeders with voltage levels)

Check correct operation of


16
all PSU

Check fans for dust


17
concentration

18 Replace all dust filter

Check the fasteners on the


19
power distribution

20 Check all cable clamps

Check all shield


21
connections

Check all earth/ground


22
connection

23 Test all hardware I/O

Test all communication with


24
external devices
ITEMS TO BE CHECKED
Item: Comments/Notes Action By

Technician Name & Sign Approval Name & Sign

( ) ( )

Date : Date :