EARTH CONNECTIONS 7-13-0001 Rev. 6

Page 1 of 1

PLATFORM
PLATFORM

SHUNTS

o
SEE NOTE-3
O
FLOATING ROOF TANK FIXED ROOF TANK DETAIL — P

120 x 50 x 6 THK. C.S. PLATE


80 WELDED TO STRUCTURE
17.5 [ 45 17.5 COPPER WIRE CABLE
1---1

cE
in

140 HOLES FOR M12 G.I. BOLTS COPPERATE

2-140 HOLES
SO

6 THK. COPPER PLATE


BRAZED WITH C.S. PLATE
DETAIL — K
DETAIL — E
TABLE — A
50 WIDE x 6 THK. COPPER PLATE
NO. OF EARTH CONNECTIONS 0 REQUIRED BRAZED WITH C.S. PLATE
TANK DIAMETER (D) EARTHING
(IN MTRS) CONNECTION 80

<15 2 AT 180' 45 2-140 HOLES


=
<=15 D < 25 3 AT 120' wwwwuressrsrm
<=25 D < 35 4 AT 90*
<=35 D < 45 5 AT 72' 50 WIDE x 6 THK.
C.S. PLATE
<=45 D < 55 6 AT 60' 4
I
<=55 D < 65 7 AT 51.43'
I
<=65 D < 75 8 AT 45' ROLLING LADDER TRACK
<=75 D < 85 9 AT 40'
DETAIL — R
<=85 D < 95 10 AT 36*
NOTES
ALL DIMENSIONS ARE IN mm. UNLESS OTHERWISE STATED.
ELECTRIC WIRES SHALL BE LONG ENOUGH TO COVER THE ENTIRE MOVEMENT OF THE ROLLING LADDER AND CONTINUITY
SHALL BE CHECKED AFTER INSTALLATION. QUANTITY REQUIRED PER TANK 2 SETS. TYPE OF WIRE P.V.C. INSULATED
COPPER WIRE CABLE, 50 mm 2 CROSS SECTION.
3. SPRING QUALITY STAINLESS STEEL SHUNTS OF 0.4 mm THICK x 51 mm WIDE SHALL BE PROVIDER FOR TANKS WITH
NON—METALLIC SEALS AT MAXIMUM SPACING OF 3000 mm.
P. 04' ki'ttlikA-V
30.09.2011 REVISED AND REISSUED AS STANDARD RKT A M /SC DM
5 15.11.2006 REAFFIRMED AND REISSUED AS STANDARD POREL DNN AKM VC

Rev. Prepared Checked Stds. Committee Stds. Bureau


Date Purpose by by
Convenor Chairman
No. Approved by
Format No. 8-00-0001-F4 Rev.0 Copyright EIL - All rights reserved