Professional Documents
Culture Documents
Control Panels
Two-Zone
Conventional
Fire Alarm Control Panel
Technical Manual
1. Introduction
The GSA-2B is a two-zone conventional fire detection and extinguishing control panel.
Two Initiating Device Circuits (IDC) monitor fire indication from various fire detectors and
manual push-buttons. The IDC circuit is two-wire and is compatible with all Telefire's
conventional push-buttons, detectors and / or detectors that were approved by Telefire
as compatible with the GSA-2B. All inputs and outputs (with the exception of Evacuate)
are supervised and identify open-circuits, shorts, alarm, and normal operation. Status is
indicated on the control panel.
The automatic extinguishing unit includes an adjustable extinguishing delay;
extinguishing override switch that allows the cancellation of extinguishing activation, or
preventing extinguishing activation during maintenance.
The extinguishing output allows the use of gas-release solenoid, electric matches, and
gas cartridge actuators. The low supervision current enables a large variety of
extinguishing devices.
The control panel's outputs include horn, extinguishing, trouble relay, alarm relay,
evacuation, and connector for a TFC-3 relay expansion module.
Figure 1 GSA-2B System with additional extinguishing and relays
2. Alarms
Upon detecting an alarm in one of the zones the control panel performs the following
actions:
• Turn on general ALARM LED and the specific zone's ALARM LED
• Activation of the Horn output
• Activation of the Alarm relay
• Activating relay RL3 in the TFC-3 relay expansion module (if connected)
• Turning OPERATE LED off
Pressing the SOUND OFF button will stop the alarm sounder and relay RL3 in the TFC-3
relay module, if connected.
Upon receipt of a second alarm (i.e., both zones in alarm at the same time) the control
panel performs the following:
• Turns on the second zone Alarm LED.
• Re-activates Horn output
• Activates Evacuation output
– Page 1 –
GSA-2B
Revision 1.12 July 2006
3. Automatic Extinguishing
The extinguishing process starts upon receiving an alarm from both zones, and the
extinguishing delay mechanism starts its countdown. After the delay period the
extinguishing output is activated for roughly 50 seconds. The extinguishing process is
halted if the EXTING INHIBIT button is pressed prior to extinguishing activation. After
activation of the extinguishing the EXTING indicator turns on and stays lit even after
resetting the control panel to indicate that extinguishing was activated and the gas
cylinder is empty. To reset the EXTING indication power the control panel off for about 5
seconds by disconnecting both AC and batteries. Only qualified technicians should
power the control panel off.
4. Trouble Events
During normal operation the AC POWER (meaning AC input present), and OPERATE
(meaning system OK) LEDs are on. In case of a trouble event the OPERATE LED will
turn off, the SYSTEM Trouble LED will turn on, the appropriate trouble indicator will turn
on, and the trouble relay will be activated. At the same time the integral trouble buzzer
will sound, and the relevant trouble indicating LED will be turned on. Pressing the
SOUND OFF button will silence the buzzer. An additional trouble event that occurs while
Sound Off is activated will not re-activate the trouble buzzer.
Upon loss of AC power the AC POWER and OPERATE LEDs are turned off the SYSTEM
TROUBLE LED is turned on, and the trouble buzzer sounds.
Resolving the trouble event will cancel the relevant audio-visual indication.
The GSA-2B control panel is "floating" – the positive and negative voltages are not
grounded.
The ground fault detection system enables early detection of problems in the IDC wiring,
water leakage into one of the devices or wiring, electrolyte leakage from a faulty battery,
etc. In this case the SYSTEM LED will turn on, the trouble buzzer will sound, and GF+ or
GF- LED on the (lower) power supply board will turn on, indicating whether the leak is in
the positive (GF+) or negative (GF-) wires.
5. Main Board
5.1. LEDs
LED Color Meaning of Indication
AC POWER Green Presence of mains power (230 Vac)
OPERATE Green The system is in normal operation
ALARM Red The system is in alarm
SYSTEM Yellow General trouble – see other yellow indicators for
additional information
– Page 2 –
GSA-2B
Revision 1.12 July 2006
5.2. Buttons
Button Designation Function
RESET Return the system to normal operation after alarm
TEST (SEE WARNING) Activates all LEDs and outputs except extinguishing output
SOUND OFF Silence alarm sounders and/or trouble buzzer
EXTING INHIBIT Stop extinguishing process during "countdown"
Warning
! Pressing the TEST button will activate the Alarm and Trouble relays and the
three relays in the TFC-3 expansion module, if installed.
Disconnect wire 4 (see Figure 16 on page 13) in the TFC-3 cable to prevent
relay activation while pressing the TEST button.
1 -Zone 1
2 +Zone 1
3 -Zone 2
4 +Zone 2
5 -Horn Output
6 +Horn Output – protected by fuse F1
7 -Extinguishing output
8 + Extinguishing output – protected by fuse F2
– Page 3 –
GSA-2B
Revision 1.12 July 2006
6.2. Connections
6.2.1. Battery Connections
6.3. Fuses
Fuse Value Function
MAIN 0.5A Protects 230Vac input
(ON THE CHASSIS) Warning – High Voltage
F1 0.5A Protects Horn, Evacuation, and TFC-3
outputs
F2 0.5A Protects extinguishing output
F3 1.6A Protects battery charging current
Warning
! Replace fuses with values as indicated above to prevent damage to the
system.
Replace fuses only when all power inputs are disconnected.
– Page 4 –
GSA-2B
Revision 1.12 July 2006
6.4. Batteries
The system uses two serially-connected sealed lead-acid batteries (24V total) and
capacity of 1.2 – 5 AH. Battery capacity shall be calculated according to the system's
requirements and local applicable codes and regulations.
The GSA-2B control panel can include batteries up to 13 (W) by 6 (D) by 8 (H) cm.
To measure battery voltage, connect a voltmeter to the battery terminals (see Figure 10
on page 11). The measured voltage should be 25.5 – 27V. Charging voltage is set
automatically by the power supply and is between 5 – 500 mA.
7.3. Marking
Mark on a drawing a list of protected premises and the instructions for immediate actions
that should be taken by the operator.
Write the zone names on the front panel in the space provided.
Write the name and telephone numbers of the installer company (see "GSA-2B
Instructions for Immediate Action" on the last page of this manual).
7.4. Tests
Perform a functional test every six months or as specified by local regulations.
The test should be performed only by a technician or a company approved by Telefire.
– Page 5 –
GSA-2B
Revision 1.12 July 2006
After testing and reconnecting AC power ensure that the Operate LED (green) is on and
there is no battery trouble indication. If there is a battery trouble indication – test the
batteries as per Measuring Battery Voltage and Charging Current on page 11. Replace
faulty batteries as necessary.
8. Installation
Mount the enclosure-back on a clean firm surface using 4 screws. Use the GSA-2B's
mounting screw-holes as shown by the figure below.
Connect the electric wiring through the 20 mm knockout holes to avoid contact between
the wires and the chassis.
Disconnect all power supply to the control panel when connecting IDC and NAC wiring
Figure 2 GSA-2B Chassis
– Page 6 –
GSA-2B
Revision 1.12 July 2006
9. Expansion Relays
System expansion can be achieved via the addition of the optional TFC-3 Relay Module.
This module includes three relays with a single changeover contact for each relay.
Please refer to Figure 16 on page 13.
The TFC-3 module connects to the GSA-2B's main board via a cable connected to the
AUX connector. It activates one relay (RL3) upon alarm from either of the zones, and
two relays (RL1 and RL2) when both zones are in alarm at the same time.
Warning
! Pressing the TEST button will activate the Alarm and Trouble relays and the
three relays in the TFC-3 expansion module, if installed.
Disconnect wire 4 (see Figure 16 on page 13) in the TFC-3 cable to prevent
relay activation while pressing the TEST button.
Note
i Please contact Telefire for consultation on additional activations if needed
– Page 7 –
GSA-2B
Revision 1.12 July 2006
– Page 8 –
GSA-2B
Revision 1.12 July 2006
Note
i Ensure that jumpers are soldered between pints JP4 and JP5 and JP1 and JP2
on the TLA-3K module (see figure above) before installing a TLA-3K module in a
GSA-2B system.
– Page 9 –
GSA-2B
Revision 1.12 July 2006
– Page 10 –
GSA-2B
Revision 1.12 July 2006
– Page 11 –
GSA-2B
Revision 1.12 July 2006
– Page 12 –
GSA-2B
Revision 1.12 July 2006
– Page 13 –
GSA-2B
Revision 1.12 July 2006
11. Specification
Dimensions (W / H / D).............................................290 / 280 / 112 mm
Weight (W/O batteries) .............................................4,600 gr.
Operating Temperature Range.................................-10°C – +60°C (14°F – 140°F)
Relative Humidity Range ..........................................10% – 93% non-condensing
Operating Voltage.....................................................230 +10% / -15% Vac 50 / 60 Hz
Current Consumption
Quiescence mode W/O AC input........................80 mA
Alarm mode, W/O AC input, no sounders...........180 mA
Trouble mode, W/O AC input..............................110 mA
Resistance to trigger alarm.......................................100 – 650 Ohm
Max IDC loop resistance ..........................................30 Ohm
End of Line Resistor (IDC and NAC) ........................5.1 K Ohm
Max current – Horn output........................................0.5A (common fuse for horn and
evacuation NACs) *
Max current – Evacuation output..............................0.5A (common fuse for horn and
evacuation NACs) *
As both outputs share the same fuse, current consumption is for both outputs.
Max continuous extinguishing current ......................0.5 A *
Extinguishing Delay ..................................................5 – 90 Seconds
EXTINGUISHER DELAY SHOULD NOT BE SET TO MORE THAN 60 SECONDS
Extinguishing pulse...................................................50±20 seconds
Battery charge ..........................................................Automatic, constant voltage.
Charging current monitored
automatically.
Chargeable batteries should be sealed lead-acid and capacity of 1.2 – 5 AH
The GSA-2B can contain two 12 V sealed lead-acid batteries, up to 13 (W) by 6 (D)
by 8 (H) cm each
Alarm dry contacts – max values..............................48 Vdc 1 A
Trouble dry contacts – max values...........................48 Vdc 1 A
WARNING: DUE TO SAFETY CONSIDERATIONS DO NOT CONNECT HIGH VOLTAGE TO
THESE CONTACT
12. Certification
Telefire’s GSA-2B is SI 1220 Approved.
– Page 14 –
GSA-2B Instructions for Immediate Action
NORMAL During normal operations the “OPERATE” and “AC POWER” LEDs
are on.
ALARM Silence the alarm by pressing the “SOUND OFF” button, go to the
area that is indicated by the ZONE ALARM LED, take proper
actions in accordance with the standard safety instructions at your
site, and report to your superiors.
AUTOMATIC Extinguishing is performed automatically, without human
EXTINGUISHING intervention.
If you determined that there is no need to activate extinguishing,
press EXTING INHIBIT during the countdown stage to stop the
extinguishing process.
Call the service organization listed below if the extinguishers were
activated.
RETURN TO After taking the actions detailed above, restore the system to
NORMAL OPERATION normal operation by pressing the “RESET” key.
TROUBLE The yellow TROUBLE LED turns on, the OPERATE LED turns off,
and the internal buzzer sounds.
Silence the buzzer by pressing the “SOUND OFF” key.
Identify the trouble and take actions to repair the malfunction, or if
necessary, call the service technician.
Repairing the trouble will automatically restore the system to
normal operating conditions.
Zone Description
1
2