CALCULATION FOR Class-PS CT - 1500KVA (DG)

Capacity of DG set, KVA = 1500


Voltage, KV = 0.44
Full Load Current = 1968.3
Sub Transient Reactane of DG Set, % = 14.7
Used CT Rating, PRIMARY IN AMP = 2000
Used CT Rating, SEC. IN AMP = 1
Fault current at CT Primary Side, AMP = 13389.78
Fault Current at CT Secondary Side Isc IN AMP = 6.69
Approximate Distance between DG to Panel, IN MTR. = 20
Appr. resistance of control wire (2.5SQ MM) IN Ω/KM = 7.41
Total load/wire resistance RL IN Ω = 0.2964
Resistance of CT Rct IN OHM = 5
Knee Point Voltage Vk IN VOLT = 2XIsc(Rct+RL)
= 70.92
= 70
MAGNETISING CURRENT, Ie (Imag) IN Ma <= 30mA at Vk/4
CT RATIO IN AMP = 2000/1A